A22 - Pump Info and Nameplate Data.pdf

PDF 9 MB Posted

Attached to
SE Des Moines Pump Station Rehab
Solicitation number
W912EK22R0022
Issued by

About this file

This document contains technical specifications and nameplate data for pumps and a liquid level controller for the Southeast Des Moines Pump Station rehabilitation project. The project involves rehabilitating the pump station located on the Des Moines River in Des Moines, Iowa. The pump station contains three pumps that will be replaced. Pump specifications include manufacturer, model, horsepower, flow rates, and other technical details. The document also provides installation and operation instructions for a Model 407 liquid level controller that will automatically control the three new pumps based on sensed water levels. The related federal contract opportunity is a solicitation from the U.S. Army Corps of Engineers seeking bids for the pump station rehabilitation project. The project is estimated to cost between $5-10 million and take 360 days to complete. Bids will be evaluated using lowest price technically acceptable criteria.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MODEL 407

Liquid Level Controller

Three pump operation

Three run-time meters

Selectable lead or automatic alternation

Five sensing levels

Alarm outputs

Hand-off-auto controls

DESCRIPTION

The Model 407 Liquid Level Controller provides central control of triplex pumping systems. The Model 407 includes pump alternating, visual run-time meters, hand-off-auto (HOA) controls and alarm outputs.

Five level-sense inputs interface with float switches, pressure switches, or other level sensing devices which can provide a contact closure.

A SPST, normally-closed internal power-fail contact opens when AC power 120VAC is connected to the controller, and closes if power is lost or removed. Connections for external remote alarm contacts, which must remain closed for normal operation (or jumpered if not required), are supplied for each pump.

If either circuit opens, the corresponding pump will be locked out until the problem is corrected and the ‘Alarm reset’ switch is pressed.

DIMENSIONS

SPECIFICATIONS

MODEL 407

Input voltage 105-130VAC

Input frequency 60Hz

Power consumption 10W max.

Contacts SPST relay

Contact rating 10A at 240VAC resistive

Float Switch Potential 12VDC at 1mA

Transient protection 2500 V for 10ms

Operating temperature - 20º to +140º F

Display to 99,999.9 non-resettable

Humidity tolerance 0-97% without condensation

Expected relay life Mechanical: 10 million operations Electrical: 100,000 operations at rated load

Case material 20 gauge Steel

Termination Removable terminal strip

Weight 6.1 lbs

12.0”

11.5” 3.25”

7.1”

7.6” 6.7”

.187” dia

TIME MARK is a division of

Telephone: Main - (918) 438-1220 Sales - (800) 862-2875

Fax: (918) 437-7584

E-mail: sales@time-mark.com Internet: http://www.time-mark.com

Page 1 of 4 11/2011

© 2011 TIME MARK CORPORATION

11440 East Pine Stree t Tulsa, Oklahoma 74116

MODEL 407 Liquid Level Controller

READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.

KEEP THIS DATA SHEET FOR FUTURE REFERENCE.

GENERAL SAFETY

POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 407.

ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.

DO NOT EXCEED THE OUTPUT OR INPUT RATINGS, AS STATED IN THE SPECIFICATIONS.

PROTECT THE UNIT WITH PROPERLY RATED FUSES.

DO NOT INSTALL IN DAMP OR MOIST AREAS.

THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.

Installation Instructions

INSTALLATION

Mount the controller in a suitable enclosure. Unplug the terminal connectors from the controller.

Referring to the terminal block decal on the controller and the illustration on this page, make the following connections.

1. Connect a chassis ground to the terminals marked

AC GND.

2. Connect 115VAC operating power to the terminals marked 115VAC.

3. Connect the LOW float switch to the LOW terminals. Polarity is not critical.

4. Repeat step 3 for LEAD, LAG, LAG-LAG, and HIGH terminals.

5. The SIGNAL GROUND connection is a common between the controller and a Liquid Level Sensor, no connection is necessary if the sensor is not used.

6. The PUMP 1, 2, & 3 REMOTE ALARM terminals should be connected to normally closed (NC) alarm contacts in the motors. If none exist it is st i l l necessary to install a jumper connection between Pump 1, PUMP 2, & PUMP 3 REMOTE ALARM terminals.

7. The POWER FAIL, ALARM BELL, & ALARM LIGHT are not required for proper operation, but are provided for your convenience. If used, connect an audible/visual alarm across the terminals. The POWER FAIL contact is open while power is applied and closes on loss of power. Connect audible and visual a l a r m s across the ALARM BELL and ALARM Light terminals respectively. These contacts are normally open and will close on a fault (high or remote alarm) condition.

8. Connect the PUMP 1, PUMP 2, & PUMP 3 contacts to the appropriate motor control circuits.

These contacts start and stop the pump motors during operation.

Set the HOA (Hand-off-Auto) switches and the LEAD PUMP selector switch as required. Apply operating power. Test alarm LEDs and bells by pressing the ALARM TEST switch.

TIME MARK is a division of

Telephone: Main - (918) 438-1220 Sales - (800) 862-2875

Fax: (918) 437-7584

E-mail: sales@time-mark.com Internet: http://www.time-mark.com

Page 2 of 4 11/2011

© 2011 TIME MARK CORPORATION

11440 East Pine Stree t Tulsa, Oklahoma 74116

These contacts are external

If motor contacts not used, install a jumper connection

OUTPUT CONTACTS

10 AMPS MAX

INPUT SWITCHES

12VDC

Model 407 Panel

Panel Layout

A. Pump running time meter to 99,999.9 hours, non-resettable.

B. Indicator LEDs illuminate when pumps are running.

C. Indicator LEDs illuminate when pump is stopped because the remote alarm circuit is open.

D. Hand-off-Auto switch to manually or automatically control the pumps.

E. Lead pump selector switch alternates lead pump selection or a fixed lead pump operation of pump 1, 2, or 3.

F. Momentary switch tests remote alarm bell, light, and illuminates alarm light I.

G. Momentary switch silences alarm bell until problem is corrected.

H. Momentary switch resets all alarm indicators to return to normal operation.

I. Alarm light stays lit until alarm reset switch is pressed.

J. Indicator LEDs show which level switches are closed.

K. Indicator LED illuminates when primary power is applied.

WARRANTY

This product is warranted to be free from defects in materials and workmanship for one year. Should this device fail to operate, we will repair it for one year from the date of manufacture. For complete warranty details, see the Terms and Conditions of Sales page in the front section of the Time Mark catalog or contact Time Mark at 1-800-862-2875.

Which pump actually starts is determined by the LEAD PUMP selector switch. The third and fourth switch (LAG and LAG-LAG) starts the second and third pumps. The final level switch (HIGH) illuminates the alarm indicator and closes the alarm bell and alarm light outputs.

As the level switches are opened (in reverse order) all operating pumps remain on until the LOW switch is opened. All pumps are then turned off and the internal alternator is triggered. On the next operating cycle the next pump depending which was on before (either 1, 2, or 3) will become the lead pump.

If the HIGH level is triggered an alarm light and alarm bell circuit are activated, plus an LED on the controller illuminates to warn of the problem.

Should this occur, an ‘Alarm Silence’ switch on the controller breaks the alarm bell contacts, but leaves the LED alarm indicator on.

When the alarm condition is corrected, an alarm reset switch returns the controller to its normal operating mode.

TROUBLESHOOTING

Problem: Remote alarm LEDs will not extinguish Causes: 1. Remote alarm inputs not jumpered closed

2. Motor circuit to close jumpers is open Solutions: 1. Install jumpers

2. Close circuit

Problem: Remote alarm LEDs come on for no apparent reason and inputs are jumpered closed.

Causes: Externally generated noise. Noise can be generated from faulty circuit breakers, contacts and motors. It can also be induced from the source being too close to the controller with little or no shielding.

Solutions: Replace faulty components; install noise suppression devices; shield wiring.

Note: This device is not a field repairable unit. Should the unit not operate properly during installation or testing, insure that all electrical, ground, and physical connections are correct. Verify that the proper voltage is applied and check all fuses. Check all motor control circuits, and insure that, if the REMOTE ALARM contacts are not used, they are jumpered. If everything is correct and the device still fails to operate, contact the factory. Should the controller fail during use, contact the factory for instructions on returning the device for repair.

MODEL 407 Liquid Level Controller

OPERATION

The Liquid Level controller can be used in either pump-down applications (with sump pumps) or in pump-up applications (to fill water tanks or reservoirs). The type of application is determined by the type of level switch used, normally-open or normally-closed.

In typical application, as shown on page 4, pumps are used to remove water from wet well when the water level activates the float switches. Activating the first switch (LOW) prepares the controller for operation. No pump is started. The second level switch (LEAD) starts the first pump.

TIME MARK is a division of

Telephone: Main - (918) 438-1220 Sales - (800) 862-2875

Fax: (918) 437-7584

E-mail: sales@time-mark.com Internet: http://www.time-mark.com

Page 3 of 4 11/2011

© 2011 TIME MARK CORPORATION

Note:

1. Remote alarm contacts are normally closed contacts located at the motor controllers. Jumper closed if not used.

2. Power fail contacts close on power failure.

3. Alarm Bell and Alarm Light contacts close on alarm condition.

TYPICAL APPLICATION

MODEL 407 Liquid Level Controller

TIME MARK is a division of

Telephone: Main - (918) 438-1220 Sales - (800) 862-2875

Fax: (918) 437-7584

E-mail: sales@time-mark.com Internet: http://www.time-mark.com

Page 4 of 4 11/2011

© 2011 TIME MARK CORPORATION

SOUTHEAST DES MOINES PUMP STATION

PUMP INFORMATION

PUMP #1

STAGE 1 SIZE 24 FIGURE 6310

FRAME (blank) MODEL (blank) TOTAL HD 900 (should be 29) SERIES K2P2057338-1 RPM 29 (should be 900) GPM 14000

IMP DIA. A357

SIZE 24 INCH FIGURE 6310 STAGE 1

GPM 17300 TOTAL HD 18 FT. RPM 888

FRAME (blank) MODEL A357 IMP. DIA. G3.66

SERIAL K4G2-502948-1 MTR SN 502415R3

PUMP #2

STAGE 1 SIZE 24 FIGURE 6310

FRAME (blank) MODEL (blank) TOTAL HD 900 (should be 29) SERIES K2P2057338-2 RPM 29 (should be 900) GPM 14000

IMP DIA. A357

SIZE 24 INCH FIGURE 6310 STAGE 1

GPM 15900 TOTAL HD 18 FT. RPM 888

FRAME (blank) MODEL A357 IMP. DIA. G3.25

SERIAL K4G2-502948-2 MTR SN 502415R1

PUMP #3

STAGE 1 SIZE 24 FIGURE 6310

FRAME (blank) MODEL (blank) TOTAL HD 900 (should be 29) SERIES K2P2057338 RPM 29 (should be 900) GPM 14000

IMP DIA. A357

SIZE 24 INCH FIGURE 6310 STAGE 1

GPM 16940 TOTAL HD 18 FT. RPM 888

FRAME 3.5 MODEL A357 IMP. DIA. G3.5

SERIAL K4G2-502948-3 MTR SN 502415R2

June 2010