ROOF REPLACEMENT PROJECT - DESIGN DOCUMENTS

Dworshak Dam and Reservoir Powerhouse

This file package contains the complete design and construction documents for a roof replacement project at the Dworshak Dam Powerhouse located on the North Fork Clearwater River in Idaho. The solicitation number is W912EF27BA001, issued in November 2026 by the U.S. Army Corps of Engineers, Walla Walla District.

The project involves comprehensive roof replacement across five distinct roof sections (A, B, C, D, and E) with varying elevations ranging from 1,036 to 1,074 feet. The scope includes demolition of existing roofing assemblies, structural modifications, installation of new steel and stair systems, mechanical systems (heat pump and air handling equipment), and electrical infrastructure. The design incorporates fully-adhered EPDM membrane roofing with rigid polyiso insulation over existing metal and concrete decks. New steel stairs with FRP guardrails provide access between roof levels. Mechanical work includes removal of existing HVAC equipment and installation of new 5-ton heat pump systems with ductwork. The project requires coordination with high-voltage transmission lines (500 kV and 115 kV), microwave transmission equipment, and telecommunications infrastructure. The design documents include structural calculations per UFC criteria and industry standards including ACI 318-19, AISC 16th Edition, and ASCE 7-22, with specific attention to wind loading (110 mph design wind speed) and seismic design requirements. All exterior steel is hot-dipped galvanized, and concrete work conforms to exposure categories for freezing/thawing and water contact conditions. The documents provide detailed plans, sections, schedules, and specifications for general, structural, architectural, mechanical, and electrical disciplines with over 40 drawing sheets addressing demolition, installation, and coordination requirements across multiple elevation levels.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

D7

NORTH NORTH

NORTH

G13

SITE MAP

SCALE: NTS

D1

VICINITY MAP

SCALE: NTS D7

LOCATION MAP

SCALE: NTS

G13

POWERHOUSE

LOG BOOM

STILLING BASIN

SPILLWAY

DWORSHAK DAM

TO AHSAHKA

TO OROFINO

VIEWPOINT RD

NORTHFORK DR

W

AS

H

IN

G

TO

N

ID

AH

O

LEWISTON

SNAKE RIVER

OROFINO

KAMIAH

NOTE: CONSTRUCTION BASE LINE TO GRID NORTH ROTATION IS 39°09'0.00"

IDAHO

WASHINGTON

OREGON

NEVADA UTAH

WYOMING

MONTANA

500 KV TRANSMISSION LINE

115 KV TRANSMISSION LINE

NORTH FORK CLEARWATER RIVER

NORTH FORK CLEARWATER RIVER

(DWORSHAK RESERVOIR)

FLOW

US Army Corps of Engineers ®

SHEET ID

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E

US Army Corps of Engineers ®

SOLICITATION NO.:

CONTRACT NO.:

ISSUE DATE:

M

AR

K D

ES

C

R

IP

TI

O

N

D S:

D

IR

O O

TS

PD

: A D

O

BE

P R

IN

T

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

FI

LE

N U

M

BE

R

R :\d

6\

D W

A5

6_

SA

M

E_ N

EW

R

O O

F_

.rv t 9/

/2

1:

:1

PM

G-001

W

AL

LA

W

AL

LA

D

IS

TR

IC

T

N

R

D A

VE

W

AL

LA

W

AL

LA

, W

A

M .F

LA

N

AG

AN

M .F

LA

N

AG

AN

JO

SH

U A

K.

T

AP

P, R .A

M .Z

AN

G

ER

N O

VE

M

BE

R

W

2E F2

7B A0

FI

N

AL

WALLA WALLA DISTRICT

W912EF27BA001

NOVEMBER 2026

D W

G -1

-0 -1

/5

C O

VE

R

S H

EE

T

AN

D

L O

C

AT

IO

N

M

AP

S

D W

O R

SH

AK

D

AM

A N

D R

ES

ER

VO

IR

R O

O F

R

EP

LA

C

EM

EN

T

N O

R

TH

F O

R K

C

LE

AR

W

AT

ER

R

IV

ER

, I

D

AH

O

PO

W

ER

H O

U

SE

DWORSHAK DAM AND RESERVOIR

NORTH FORK CLEARWATER RIVER, IDAHO

ROOF REPLACEMENT

POWERHOUSE

SUBMITTED BY:

SUBMITTED BY:

SUBMITTED BY:

SUBMITTED BY:

SUBMITTED BY:

APPROVED BY:

MARCUS PALMER, P.E.

CHIEF OF DESIGN BRANCH

WALLA WALLA DISTRICT

KEVIN RENSHAW, P.E.

CHIEF OF MECHANICAL DESIGN SECTION

WALLA WALLA DISTRICT

LEVI VAN STEDUM, P.E.

CHIEF OF ELECTRICAL DESIGN SECTION

WALLA WALLA DISTRICT

DWAYNE WESTON, P.E.

CHIEF OF ENGINEERING & CONSTRUCTION DIVISION

WALLA WALLA DISTRICT

JOSHUA K. TAPP, R.A.

SUPERVISORY ARCHITECT

WALLA WALLA DISTRICT

This project was designed by the Walla Walla District of the U.S. Army Corps of Engineers.

The initials or signatures and registration designations of individuals appear on these project documents within the scope of their employment as required by ER 1110-1-8152.

JULIO MORELOS, P.E.

CHIEF OF STRUCTURAL DESIGN SECTION

WALLA WALLA DISTRICT

US Army Corps of Engineers ®

SHEET ID

U .S . A

R M Y C O R

PS

O F

EN

G

IN

EE

R S

D R

AW

N B Y:

D

ES

IG

N

ED

B Y:

SU

BM

IT

TE

D B Y:

SI

ZE

C H

EC

KE

D B Y:

AN

SI

D

IS

SU

E D

AT

E:

C O N

TR

AC

T N O

SO

LI

C

IT

AT

IO

N N O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K D

ES

C R

IP

TI

O N

D S:

D

IR

O O

TS

PD

: A

D O

BE

P R

IN

T

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

FI

LE

N U M

BE

R

C :\U se rs \g 4e ch ga i\D oc um en ts \D W A5

6_

SA

M E_

N

EW

R O O F_ _g ui do .a .ig le si as .rv t

/1 7/ 0:

:4

AM

G-002

W

AL

LA

W

AL

LA

D

IS

TR

IC

T

N R D A

VE

W

AL

LA

W

AL

LA

, W A

M . F

LA

N

AG

AN

M . F

LA

N

AG

AN

JO

SH

U A K.

T

AP

P, R .A

M . Z

AN

G

ER

N O

VE

M

BE

R

W 2E

F2 7B

A0

FI

N

AL

D W G -1 -0 -1 /5

SH

EE

T

IN

D

EX

D W O R

SH

AK

D

AM

A N D R

ES

ER

VO

IR

R O O F R

EP

LA

C

EM

EN

T

N O R

TH

F O R K C

LE

AR

W

AT

ER

R

IV

ER

, I D

AH

O

PO

W

ER

H O U

SE

G-001 COVER SHEET AND LOCATION MAPS DWG-1-0-1/505 DWA515646_SAME_NEWROOF_2023.rvt G-002 SHEET INDEX DWG-1-0-1/506 DWA515646_SAME_NEWROOF_2023.rvt G-003 GENERAL NOTES, ABBREVIATIONS DWG-1-0-1/507 DWA515646_SAME_NEWROOF_2023.rvt G-101 SITE PLAN DWG-1-0-1/508 DWA515646_SAME_NEWROOF_2023.rvt G-401 HAZARDOUS AREAS EQUIPMENT PLAN DWG-1-0-1/509 DWA515646_SAME_NEWROOF_2023.rvt G-901 SITE PHOTO DWG-1-0-1/510 DWA515646_SAME_NEWROOF_2023.rvt

S-001 STRUCTURAL GENERAL NOTES DWP-1-5-1/9 DWA515646_SAME_NEWROOF_2023.rvt S-002 STRUCTURAL LOADING DIAGRAMS DWP-1-5-1/10 DWA515646_SAME_NEWROOF_2023.rvt SD101 STRUCTURAL DEMOLITION DWP-1-5-1/11 DWA515646_SAME_NEWROOF_2023.rvt S-101 ROOF PLAN DWP-1-5-1/12 DWA515646_SAME_NEWROOF_2023.rvt S-110 PLAN - ROOF A DWP-1-5-1/13 DWA515646_SAME_NEWROOF_2023.rvt S-111 PLAN - ROOFS B, C & D DWP-1-5-1/14 DWA515646_SAME_NEWROOF_2023.rvt S-112 PLAN - ROOFS D & E DWP-1-5-1/15 DWA515646_SAME_NEWROOF_2023.rvt S-301 SECTIONS DWP-1-5-1/16 DWA515646_SAME_NEWROOF_2023.rvt S-511 STRUCTURAL DETAILS DWP-1-5-1/17 DWA515646_SAME_NEWROOF_2023.rvt S-512 STRUCTURAL DETAILS DWP-1-5-1/18 DWA515646_SAME_NEWROOF_2023.rvt S-513 STRUCTURAL DETAILS DWP-1-5-1/19 DWA515646_SAME_NEWROOF_2023.rvt S-514 STRUCTURAL DETAILS DWP-1-5-1/20 DWA515646_SAME_NEWROOF_2023.rvt S-515 STRUCTURAL DETAILS DWP-1-5-1/21 DWA515646_SAME_NEWROOF_2023.rvt

A-001 ARCHITECTURAL NOTES, LEGENDS, ABBREVIATIONS DWP-1-2-1/26 DWA515646_SAME_NEWROOF_2023.rvt AD101 ROOF DEMOLITION PLAN DWP-1-2-1/27 DWA515646_SAME_NEWROOF_2023.rvt A-101 ROOF PLAN DWP-1-2-1/28 DWA515646_SAME_NEWROOF_2023.rvt A-401 ENLARGED ROOF PLAN - ROOF A DWP-1-2-1/29 DWA515646_SAME_NEWROOF_2023.rvt A-402 ENLARGED ROOF PLAN - ROOFS B, C, & D DWP-1-2-1/30 DWA515646_SAME_NEWROOF_2023.rvt A-403 ENLARGED ROOF PLAN - ROOF E DWP-1-2-1/31 DWA515646_SAME_NEWROOF_2023.rvt A-404 ENLARGED STAIR PLANS & SECTIONS DWP-1-2-1/32 DWA515646_SAME_NEWROOF_2023.rvt A-405 ENLARGED STAIR SECTIONS & DETAILS DWP-1-2-1/33 DWA515646_SAME_NEWROOF_2023.rvt A-501 TYPICAL ROOFING DETAILS DWP-1-2-1/34 DWA515646_SAME_NEWROOF_2023.rvt A-502 ROOFING DETAILS DWP-1-2-1/35 DWA515646_SAME_NEWROOF_2023.rvt A-503 ROOFING DETAILS DWP-1-2-1/36 DWA515646_SAME_NEWROOF_2023.rvt A-504 ROOFING DETAILS DWP-1-2-1/37 DWA515646_SAME_NEWROOF_2023.rvt A-505 ROOFING DETAILS DWP-1-2-1/38 DWA515646_SAME_NEWROOF_2023.rvt

MD101 DEMOLITION - MECHANICAL ROOF PLAN DWP-1-3-1/16 DWA515646_SAME_NEWROOF_2023.rvt MD102 DEMOLITION - MECHANICAL FLOOR PLAN - EL 1045.43 DWP-1-3-1/17 DWA515646_SAME_NEWROOF_2023.rvt MD301 DEMOLITION - SECTION - MECHANICAL DWP-1-3-1/18 DWA515646_SAME_NEWROOF_2023.rvt MD901 DEMOLITION - EXISTING PHOTOGRAPHS DWP-1-3-1/19 DWA515646_SAME_NEWROOF_2023.rvt M-101 INSTALLATION - MECHANICAL FLOOR PLAN DWP-1-3-1/20 DWA515646_SAME_NEWROOF_2023.rvt M-301 INSTALLATION - SECTION - MECHANICAL ROOM DWP-1-3-1/21 DWA515646_SAME_NEWROOF_2023.rvt M-302 INSTALLATION - SECTION - MECHANICAL ROOM EXTERIOR DWP-1-3-1/22 DWA515646_SAME_NEWROOF_2023.rvt M-601 MECHANICAL SCHEDULES DWP-1-3-1/23 DWA515646_SAME_NEWROOF_2023.rvt M-901 INSTALLATION - HVAC PIPING ISOMETRIC DWP-1-3-1/24 DWA515646_SAME_NEWROOF_2023.rvt

ED101 ELECTRICAL DEMO PLAN - EL.1065 DWP-1-6-1/18 DWA515646_SAME_NEWROOF_2023.rvt ED201 ELECTRICAL DEMO ELEVATION - EL. 1038.79 DWP-1-6-1/19 DWA515646_SAME_NEWROOF_2023.rvt ED401 EL. 1045 ELEVATOR ROOM ELECTRICAL DEMO DWP-1-6-1/20 DWA515646_SAME_NEWROOF_2023.rvt E-101 ELECTRICAL INSTALL PLAN DWP-1-6-1/21 DWA515646_SAME_NEWROOF_2023.rvt E-201 ELECTRICAL INSTALL ELEVATION - EL. 1038.79 DWP-1-6-1/22 DWA515646_SAME_NEWROOF_2023.rvt E-401 EL. 1045 ELEVATOR ROOM ELECTRICAL INSTALL DWP-1-6-1/23 DWA515646_SAME_NEWROOF_2023.rvt

SHEET INDEX

SHEET ID DESCRIPTION FILE NO. SOURCE

GENERAL

STRUCTURAL

ARCHITECTURAL

MECHANICAL

ELECTRICAL

DRAWING ABBREVIATIONS INDEX OF DRAWINGS

NUMBERING SYSTEM:

XX100

DISCIPLINE:

C - CIVIL

L - LANDSCAPE

A - ARCHITECTURE

M - MECHANICAL

E - ELECTRICAL

P - PLUMBING

S - STRUCTURAL

K - FOOD SERVICE

DISCIPLINE MODIFIER

SHEET NUMBER WITHIN

SERIES

ANNOTATION CALLOUTS/DRAWING

SYMBOLS

A ---------------------

A/C AIR CONDITION

A/C UNIT AIR CONDITIONING UNIT

AB ANCHOR BOLT

ABA ARCHITECTURAL BARRIERS

ACT

ACC ACCESSIBLE

ACS AUTOMATIC CONTROL SYSTEM

ACS DR ACCESS DOOR

ACS PNL ACCESS PANEL

ADMIN ADMINISTRATION

AFS ABOVE FINISHED SLAB

AGGR AGGREGATE

AHU AIR HANDLING UNIT

AIB AIR INFILTRATION BARRIER

ALT ALTERNATE

ALUM ALUMINUM

ANOD ANODIZE

APPROX APPROXIMATE

AR AS REQUIRED

ARCH ARCHITECT

ASSY ASSEMBLY

AVG AVERAGE

B ---------------------

BD BOARD

BDRY BOUNDARY

BLDG BUILDING

BLKG BLOCKING

BLT IN BUILT-IN

BN BULLNOSE

BOS BOTTOM OF STEEL

BOT BOTTOM

BPA BONNEVILLE POWER

ADMINISTRATION

BRKT BRACKET

BTWN BETWEEN

C ---------------------

C CONC CAST CONCRETE

CAV CAVITY

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR

FURNISHED/CONTRACTOR

INSTALLED

CFE CONTRACTOR FURNISHED

EQUIPMENT

CFLG COUNTERFLASHING

CFM CUBIC FEET PER MINUTE

CFMF COLD-FORMED METAL

FRAMING

CFS CUBIC FEET PER SECOND

CI CAST IRON

CIP CAST-IN-PLACE

CJ CONTROL JOINT

CL CENTER LINE

CLG CEILING

CLL COLUMN LINE

CLR COLOR

CNDS CONDENSATE

CO CLEANOUT

COL COLUMN

COMM COMMUNICATION

CONC CONCRETE

CONC FLR CONCRETE FLOOR

CONT CONTINUE

COORD COORDINATE

CTR CENTER

CU FT CUBIC FEET

D ---------------------

D DEPTH

DBL DOUBLE

DEMO DEMOLITION

DET DETAIL

DIA DIAMETER

DIMS DIMENSIONS

DIR DIRECTION

DIST DISTANCE

DOC DOCUMENT

E ---------------------

EA EACH

EF EACH FACE

EJ EXPANSION JOINT

ES EACH SIDE

EL ELEVATION

ELEV ELEVATOR

ENTR ENTRANCE

EPDM ETHYLENE PROPYLENE

DIENE MONOMER

EQ EQUAL

EWC ELECTRIC WATER COOLER

EXP EXPOSED

EXT EXTERIOR

F ---------------------

FED FEDERAL

FLEX FLEXIBLE

FLR FLOOR

FM FACTORY MUTUAL

FOC FACE OF CONCRETE

FRMG FRAMING

FRP FIBERGLASS REINFORCED

PLASTIC

FS FAR SIDE

FSTNR FASTENER

FT FEET

G --------------------

GALV GALVANIZED

GFCI GOVERNMENT FURNISHED

CONTRACTOR INSTALLED

GFGI GOVERNMENT FURNISHED

INSTALLED BY GOVERNMENT

GYP BD GYPSUM BOARD

H ---------------------

HORIZ HORIZONTAL

HT HEIGHT

I ---------------------

IBC INTERNATIONAL BUILDING

CODE

INSUL INSULATION

INT INTERIOR

L ---------------------

LBS POUND

LDG LANDING

LF LINEAR FEET (FOOT)

LIN LINEAR

LVR LOUVER

M ---------------------

MACH RM MACHINE ROOM

MATL MATERIAL

MAX MAXIMUM

MC MOISTURE CONTENT

MD METAL DECK

MECH MECHANICAL

MECH RM MECHANICAL ROOM

MEMB MEMBRANE

MFR MANUFACTURER

MID MIDDLE

MIN MINIMUM

MISC MISCELLANEOUS

MOD MODIFY

MTG MOUNTING

MTL METAL

N ---------------------

N NORTH

NA NOT APPLICABLE

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NS NEAR SIDE

NTS NOT TO SCALE

O -------------------

OA OVERALL

OC ON CENTER

OD OUTSIDE DIAMETER

OFD OVERFLOW DRAIN

OPNG OPENING

OPP OPPOSITE

OWSJ OPEN WEB STEEL JOIST

ORD OVERFLOW ROOF DRAIN

ORIG ORIGINAL

P --------------------

PA PUBLIC ADDRESS

PAR PARAPET

PAT PATTERN

PCF POUNDS PER CUBIC FOOT

PCT PERCENT

PERIM PERIMETER

PH PHASE

PLBG PLUMBING

PNL PANEL

POLYISO POLYISOCYANURATE

INSULATION

PR PAIR

PRCST PRECAST

PS CONC PRESTRESSED

CONCRETE

Q --------------------

QTY QUANTITY

R --------------------

RC REINFORCED CONCRETE

RD ROOF DRAIN

RDG INSRIGID INSULATION, SOLID

REC RECESSED

REF REFERENCE

REM REMOVABLE

REP REPAIR

REPL REPLACE

REQ REQUIRE

REQD REQUIRED

RFG ROOFING

RLG RAILING

RO ROUGH OPENING

S --------------------

SCHED SCHEDULE

SF SQUARE FOOT (FEET)

SGL SINGLE

SHT MTL FLASH SHEET METAL

(FLASHING)

SIM SIMILAR

SLNT SEALANT

SP EL SPOT ELEVATION

SPEC SPECIFICATION

SQ SQUARE

SQ IN SQUARE INCH

SQ YD SQUARE YARD

SST STAINLESS STEEL

ST STAIRS

STD STANDARD

STL JST STEEL JOIST

STL RF DK STEEL ROOF DECK

STR STRINGERS

T --------------------

T TREAD

TEMP TEMPORARY

THK THICKNESS

TN TRUE NORTH

TOP TOP OF PARAPET

TOPO TOPOGRAPHY

TYP TYPICAL

V --------------------

VFY VERIFY

REFER TO AEC CAD

STANDARDS FOR PROPER

SHEET NUMBERING

REVISION

TAG

NORTH ARROW w/

TRUE NORTH

INDICATION

ELEVATION NUMBER

SECTION

EXTERIOR ELEVATION

ENLARGEMENT,

DETAIL

SPOT ELEVATION

LEVEL NAME

SHEET NUMBER

SHEET NUMBER

SHEET NUMBER

A SHEET KEYNOTE

INTERIOR ELEVATION

SHEET NUMBER

Name Elevation

PLAN NORTH

A101

SIM

A101

A101

SIM

A101

1 Ref

R ef

1Ref

R ef

METAL DECK STRONG

AXIS SPAN INDICATOR

SLOPE ARROW

AND DIRECTION

CONSTRUCTION/

COLD JOINT

STRUCTURE STEP

US Army Corps of Engineers ®

SHEET ID

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

D S:

D

IR

O O

TS

PD

: A D

O

BE

P R

IN

T

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

FI

LE

N U

M

BE

R

R :\d

6\

D W

A5

6_

SA

M

E_ N

EW

R

O O

F_

.rv t 9/

/2

1:

:1

PM

G-003

W

AL

LA

W

AL

LA

D

IS

TR

IC

T

N

R

D A

VE

W

AL

LA

W

AL

LA

, W

A

M . F

LA

N

AG

AN

M . F

LA

N

AG

AN

JO

SH

U A

K.

T

AP

P, R .A

M . Z

AN

G

ER

N O

VE

M

BE

R

W

2E F2

7B A0

FI

N

AL

D W

G -1

-0 -1

/5

G

EN

ER

AL

N O

TE

S, A

BB

R

EV

IA

TI

O N

S

D W

O R

SH

AK

D

AM

A N

D R

ES

ER

VO

IR

R O

O F

R

EP

LA

C

EM

EN

T

N O

R

TH

F O

R K

C

LE

AR

W

AT

ER

R

IV

ER

, I

D

AH

O

PO

W

ER

H O

U

SE

G-401 A1

C

LE

AR

ROOF ACCESS DOOR

POTENTIAL

CONTRACTOR

SCAFFOLDING

ACCESS POINT

TO ROOF E

DURING 500 KV

OUTAGE

BALCONY

GOVERNMENT HAZARDOUS

WASTE STORAGE

POWERHOUSE

LOBBY ENTRANCE

ERECTION BAY BAY #1 BAY #2 BAY #3

POWERHOUSE

CONTRACTOR

LAYDOWN

AREA

CONTRACTOR TRAILER

GUARD

SHACK

SECURITY

GATE

CONTRACTOR PERSONAL

VEHICLE PARKING

20' - 0"

SHOP

BUILDINGS

OPEN TO BELOW

CLEARWATER RIVER

EMERGENCY DIESEL

GENERATOR AREASPARE TRANSFORMER

SHED

US Army Corps of Engineers ®

SHEET ID

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

D S:

D

IR

O O

TS

PD

: A D

O

BE

P R

IN

T

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

FI

LE

N U

M

BE

R

R :\d

6\

D W

A5

6_

SA

M

E_ N

EW

R

O O

F_

.rv t 9/

/2

1:

:2

PM

G-101

W

AL

LA

W

AL

LA

D

IS

TR

IC

T

N

R

D A

VE

W

AL

LA

W

AL

LA

, W

A

M . F

LA

N

AG

AN

M . F

LA

N

AG

AN

JO

SH

U A

K.

T

AP

P, R .A

M . Z

AN

G

ER

N O

VE

M

BE

R

W

2E F2

7B A0

FI

N

AL

D W

G -1

-0 -1

/5

SI

TE

P

LA

N

D W

O R

SH

AK

D

AM

A N

D R

ES

ER

VO

IR

R O

O F

R

EP

LA

C

EM

EN

T

N O

R

TH

F O

R K

C

LE

AR

W

AT

ER

R

IV

ER

, I

D

AH

O

PO

W

ER

H O

U

SE

0 25' 50' 100'SCALE: 1" = 50'-0"A1 POWERHOUSE SITE PLAN

GENERAL NOTES

1. SEE SECTION 01 55 10.00 28 FOR CONTRACTOR WORK, ACCESS AND STORAGE

AREAS.

2. THE PROJECT SITE HAS HIGH VOLTAGE ELECTRICAL EQUIPMENT AND HIGH

FREQUENCY TELECOMMUNICATIONS EQUIPMENT. SEE SHEET G-401 FOR AREAS

THAT REQUIRE A SCHEDULED CLEARANCE TO ACCESS.

3. HIGH VOLTAGE OVERHEAD POWERLINES PASS OVER THE POWERHOUSE.

CONTRACTOR MUST ACCOUNT FOR THESE IN THE CRANE PLAN SUBMITTAL.

NORTH

19' - 9 1/2"

50' - 0"

R = 27' - 0" R = 27' - 0"

R = 27' - 0"

100' - 0"

6' - 0"

6' - 0"

3 5

R = 12' - 4" R = 12' - 4"

R = 12' - 4"

ROOF A

ROOF B

ROOF C

ROOF

D

ROOF E

LEGEND

500 KV ELECTRICAL HAZARD AREA

115 KV ELECTRICAL HAZARD AREA

500 KV & 115 KV ELECTRICAL HAZARD OVERLAP AREA

TELECOMMUNICATION ANTENNA HAZARD AREA

MICROWAVE RADIO 1 TRANSMISSION AREA

MICROWAVE RADIO 2 TRANSMISSION AREA

US Army Corps of Engineers ®

SHEET ID

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

D S:

D

IR

O O

TS

PD

: A D

O

BE

P R

IN

T

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

FI

LE

N U

M

BE

R

R :\d

6\

D W

A5

6_

SA

M

E_ N

EW

R

O O

F_

.rv t 9/

/2

1:

:2

PM

G-401

W

AL

LA

W

AL

LA

D

IS

TR

IC

T

N

R

D A

VE

W

AL

LA

W

AL

LA

, W

A

M . F

LA

N

AG

AN

M . F

LA

N

AG

AN

JO

SH

U A

K.

T

AP

P, R .A

M . Z

AN

G

ER

N O

VE

M

BE

R

W

2E F2

7B A0

FI

N

AL

D W

G -1

-0 -1

/5

H

AZ

AR

D

O U

S

AR

EA

S

EQ

U

IP

M

EN

T

PL

AN

D W

O R

SH

AK

D

AM

A N

D R

ES

ER

VO

IR

R O

O F

R

EP

LA

C

EM

EN

T

N O

R

TH

F O

R K

C

LE

AR

W

AT

ER

R

IV

ER

, I

D

AH

O

PO

W

ER

H O

U

SE

SCALE: 3/32" = 1'-0"G-101

A1 A1 HAZARDOUS EQUIPMENT AREA PLAN

0 4' 8' 16' 24'

NORTH

GENERAL NOTES

1. COORDINATE ALL OUTAGE REQUESTS WITH THE CONTRACTING OFFICER

REPRESENTATIVE.

2. SEE ADDITIONAL INFORMATION IN SECTION 01 14 00.10 28.

3. EM 385-1-1 REQUIRED ELECTRICAL HAZARD CLEARANCE RADII SHOWN ARE

APPROXIMATE.

KEYNOTES

1. MICROWAVE RADIO HAZARD ZONE. NO OUTAGE IS REQUIRED TO ENTER THIS

AREA.

2. ROOF A 115 KV HAZARD ZONE. AN OUTAGE IS REQUIRED TO ENTER THIS AREA.

3. ROOF E 115 KV HAZARD ZONE. AN OUTAGE IS REQUIRED TO ENTER THIS AREA.

4. ROOF A 500 KV HAZARD ZONE. AN OUTAGE IS REQUIRED TO ENTER THIS AREA.

5. ROOF E 500 KV HAZARD ZONE. AN OUTAGE IS REQUIRED TO ENTER THIS AREA.

6. ROOF A HIGH FREQUENCY TELECOMMUNICATION ANTENNA HAZARD ZONE. AN

OUTAGE IS REQUIRED TO ENTER THIS AREA.

BALCONY

KEYNOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

GUARD SHACK AND SECURITY GATE

OVERHEAD POWERLINES

MICROWAVE DISHES

SPARE TRANSFORMER AND CONCRETE CURB

POWERHOUSE LOBBY ENTRANCE

ROOF A

ROOF B

ROOF C

ROOF D

ROOF E

BALCONY

SKELETON BAYS

TAILRACE DECK

ROOF ACCESS DOOR

LIVE TRANSFORMERS AND CONTAINMENT

US Army Corps of Engineers ®

SHEET ID

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

D S:

D

IR

O O

TS

PD

: A D

O

BE

P R

IN

T

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

FI

LE

N U

M

BE

R

R :\d

6\

D W

A5

6_

SA

M

E_ N

EW

R

O O

F_

.rv t 9/

/2

1:

:2

PM

G-901

W

AL

LA

W

AL

LA

D

IS

TR

IC

T

N

R

D A

VE

W

AL

LA

W

AL

LA

, W

A

M . F

LA

N

AG

AN

M . F

LA

N

AG

AN

JO

SH

U A

K.

T

AP

P, R .A

M . Z

AN

G

ER

N O

VE

M

BE

R

W

2E F2

7B A0

FI

N

AL

D W

G -1

-0 -1

/5

SI

TE

P H

O

TO

D W

O R

SH

AK

D

AM

A N

D R

ES

ER

VO

IR

R O

O F

R

EP

LA

C

EM

EN

T

N O

R

TH

F O

R K

C

LE

AR

W

AT

ER

R

IV

ER

, I

D

AH

O

PO

W

ER

H O

U

NTSSCALE:A1 PHOTO - DWORSHAK ROOF SITE

1.

A.

B.

C.

D.

2.

A.

B.

1.

2.

C.

1.

2.

D.

1.

2.

E.

1.

2.

3.

A.

4.

3.

A.

1.

2.

B.

1.

C.

D.

E.

THE PROJECT SHALL BE DESIGNED PRIMARILY UNDER UFC CRITERIA AND

INDUSTRY STANDARDS AS MODIFIED BY THE UFC. STRUCTURAL DESIGN,

FABRICATION, AND CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE

GOVERNING CODE EDITIONS PER UFC 1-200-01, INCLUDING BUT NOT LIMITED TO:

ACI 318-19 BUILDING CODE REQUIREMENTS FOR STRUCTURAL

CONCRETE

AISC MANUAL OF STEEL CONSTRUCTION (16th EDITION)

ASCE 7-22 AMERICAN SOCIETY OF CIVIL ENGINEERS MINIMUM DESIGN

LOADS AND ASSOCIATED CRITERIA FOR BUILDINGS AND OTHER

STRUCTURES

INTERNATIONAL BUILDING CODE (IBC) 2024

DESIGN LOADS:

RISK CATEGORY = III

DEAD LOADS:

STAIR STEEL: SELF WEIGHT OF MEMBERS

STAIR GRATING SYSTEM: 14 PSF

LIVE LOADS:

STAIRS & EXITS = 100 PSF

ROOF LIVE LOAD = 20 PSF, 300 LB CONCENTRATED LOAD

NONCONCURRENT WITH UNIFORM LIVE LOAD

SNOW LOAD:

GROUND SNOW LOAD = 63 PSF

FLAT ROOF SNOW LOAD = 50 PSF

WIND LOAD:

DESIGN WIND SPEED = 110 MPH 3-SECOND GUST

EXPOSURE CATEGORY = C

BUILDING CONDITION = ENCLOSED

GCpi = +/-0.18 TOPOGRAPHIC FACTOR, Kzt = 1.22

SEISMIC LOAD:

MAXIMUM CONSIDERED EARTHQUAKE SPECTRAL RESPONSE

ACCELERATIONS:

Ss = 0.31g S1 = 0.09g

DESIGN EARTHQUAKE SPECTRAL RESPONSE ACCELERATIONS:

SDS = 0.3g

SITE CLASS = D

SEISMIC DESIGN CATEGORY = C

IMPORTANCE FACTOR = 1.25

DESIGN STANDARDS & LOADS

1.

2.

3.

4.

5.

6.

7.

8.

THESE NOTES, AND OTHER DRAWING DETAILS AND NOTES, CONTAINED WITHIN,

ARE PROVIDED TO MEET SPECIFIC REQUIREMENTS AND TO SUPPLEMENT THE

CONTRACT SPECIFICATIONS. THESE DRAWINGS NEITHER REPLACE NOR

OVERRIDE THE PROVISIONS AND REQUIREMENTS OF THE CONTRACT

SPECIFICATIONS.

COORDINATE ALL STRUCTURAL WORK WITH WORK SHOWN ON ALL OTHER

DISCIPLINE DRAWINGS. NOTIFY CONTRACTING OFFICER OF DISCREPANCIES.

CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED

STRUCTURE. CONTRACTOR IS RESPONSIBLE FOR ALL MEANS AND METHODS

OF CONSTRUCTION INCLUDING, BUT NOT LIMITED TO, SHORING, TEMPORARY

CONSTRUCTION LOADS, AND TEMPORARY BRACING. UNDERTAKE ALL

NECESSARY MEASURES TO ENSURE SAFETY OF ALL PERSONS AND

STRUCTURES AT THE SITE AND ADJACENT TO THE SITE. VISITS TO THE SITE BY

THE CONTRACTING OFFICER'S REPRESENTATIVE SHALL NOT RELIEVE THE

CONTRACTOR OF SUCH RESPONSIBILITY.

ALL PRODUCTS SHALL BE INSTALLED IN ACCORDANCE WITH THE

MANUFACTURERS' WRITTEN INSTRUCTIONS AND RECOMMENDATIONS, UNLESS

NOTED OTHERWISE.

ELEVATION DATUM PER SUPPLEMENTARY DRAWINGS. NOTIFY THE

CONTRACTING OFFICER OF ANY DISCREPANCIES BETWEEN THE STRUCTURAL

DRAWINGS AND OTHER DISCIPLINE DRAWING ELEVATIONS.

USE STRUCTURAL DRAWINGS IN CONJUNCTION WITH ALL DRAWINGS OF OTHER

DISCIPLINES, COORDINATE WORK OF ALL TRADES. THE CONTRACTOR IS

RESPONSIBLE FOR DETERMINING SUCH REQUIREMENTS PRIOR TO

FABRICATION OR ERECTION OF THE STRUCTURE. PENETRATIONS THROUGH

THE STRUCTURE ARE NOT PERMITTED WITHOUT WRITTEN APPROVAL BY THE

CONTRACTING OFFICER.

THE STRUCTURAL DRAWINGS GOVERN THE WORK FOR STRUCTURAL

FEATURES, UNLESS OTHERWISE NOTED, DIMENSIONS SHOWN ON PLANS,

SECTIONS, AND DETAILS ARE TO GOVERN THE STRUCTURAL WORK.

REPRODUCTION OF CONTRACT DRAWINGS SHALL NOT BE USED AS SHOP

DRAWINGS UNDER ANY CIRCUMSTANCE.

GENERAL NOTES

1.

2.

A.

B.

C.

D.

WORK IS SUBJECT TO SPECIAL INSPECTIONS AND TESTING AS DESCRIBED IN

CHAPTER 17 OF THE INTERNATIONAL BUILDING CODE AND FOUND IN THE

SPECIFICATIONS.

MECHANICAL AND ELECTRICAL COMPONENTS:

PERIODIC SPECIAL INSPECTION DURING ANCHORING OF ELECTRICAL

EQUIPMENT FOR EMERGENCY OR STANDBY POWER SYSTEMS

PERIODIC SPECIAL INSPECTION DURING INSTALLATION OF PIPING

SYSTEMS CARRYING FLAMMABLE, COMBUSTIBLE OR HIGHLY TOXIC

CONTENTS AND THEIR ASSOCIATED MECHANICAL UNITS

PERIODIC SPECIAL INSPECTION DURING INSTALLATION OF VIBRATON

ISOLATION SYSTEMS WHERE CONSTUCTION DOCUMENTS REQUIRE A

NOMINAL CLEARANCE OF 1/4 INCH OR LESS BETWEEN THE EQUIPMENT

SUPPORT FRAME AND RESTRAINT

MECHANICAL AND ELECTRICAL EQUIPMENT MANUFACTURER SHALL

TEST OR ANALYZE THE COMPONENT AND ITS MOUNTING SYSTEM OR

ANCHORAGE AND SUBMIT CERTIFICATE OF COMPLIANCE PER IBC

SPECIAL INSPECTION & TESTING

STRUCTURAL STEEL

1.

2.

3.

4.

A.

5.

A.

6.

A.

7.

A.

8.

A.

9.

A.

10.

A.

1.

11.

12.

A.

B.

13.

A.

B.

C.

D.

1.

2.

3.

14.

15.

A.

B.

16.

17.

18.

19.

20.

A.

B.

C.

D.

E.

STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED IN ACCORDANCE

WITH AISC STEEL CONSTRUCTION MANUAL.

TEMPORARY ERECTION BRACING SHALL BE DESIGNED AND PROVIDED BY THE

CONTRACTOR AS REQUIRED AND SHALL NOT BE REMOVED UNTIL ALL

PERMANENT LATERAL-LOAD-RESISTING ELEMENTS AND CONNECTIONS ARE

COMPLETELY INSTALLED.

ALL STRUCTURAL STEEL SHALL BE HOT-DIPPED GALVANIZED.

WIDE FLANGE SHAPES AND TEES:

ASTM A992, Fy = 50 KSI

PLATES AND ANGLES:

ASTM A572, GR. 50, Fy = 50 KSI

OTHER SHAPES AND THREADED RODS:

ASTM A572, GR. 50, Fy = 50 KSI, UNLESS NOTED OTHERWISE

SQUARE AND RECTANGULAR HOLLOW STRUCTURAL SECTIONS:

ASTM A500 GRADE C, Fy = 50 KSI

ROUND HOLLOW STRUCTURAL SECTIONS:

ASTM A500 GRADE C, Fy = 46 KSI

PIPE:

ASTM A53 TYPE E OR S, GRADE B, Fy = 35 KSI

BOLTS:

3/4"Ø ASTM F3125, TYPE N, TYPICAL UNLESS NOTED OTHERWISE

FRAMING CONNECTIONS:

PRETENSIONED JOINTS WITH STANDARD HOLES, UNLESS NOTED

OTHERWISE

WELD IN ACCORDANCE WITH AWS D1.1 USING E70 ELECTRODE WITH LOW

HYDROGEN.

ALL DOUBLE ANGLE MEMBERS SHALL HAVE SPACER PLATES TO COMPLY WITH

AISC 360 PARAGRAPH E6.2:

THICKNESS TO MATCH END GUSSET PLATES

CONNECT TO BACK-TO-BACK LEGS OF ANGLES USING ONE 3/4"Ø BOLT,

MIN

ANCHOR BOLTS:

ASTM F1554 GRADE 55 UNLESS SPECIFICALLY NOTED AS GRADE 105

LOCATE ANCHOR BOLTS ACCURATELY, SET WITH TEMPLATES, AND

SECURELY HOLD IN POSITION WHILE PLACING CONCRETE

PROTECT IN-PLACE ANCHOR BOLTS FROM CONSTRUCTION ACTIVITY

THE FOLLOWING ARE PROHIBITED WITHOUT THE EXPLICIT PRIOR

APPROVAL IN WRITING OF THE CONTRACTING OFFICER:

INSERTING ANCHOR BOLTS INTO FRESH OR PARTIALLY

HARDENED CONCRETE

SUBSTITUTING POST-INSTALLED ANCHORS WHERE EMBEDDED

ANCHOR BOLTS ARE INDICATED

REPAIRING, REPLACING, OR MODIFYING INSTALLED ANCHOR

BOLTS

NONSHRINK GROUT MINIMUM COMPRESSIVE STRENGTH = 5,000 PSI

STEEL USING COMPLETE JOINT PENETRATION GROOVE WELDS THAT FUSE

THROUGH THE THICKNESS OF THE FLANGE OR WEB SHALL HAVE A MINIMUM

CHARPY V-NOTCH IMPACT TESTING VALUE AS FOLLOWS:

HOT-ROLLED SHAPES WITH A FLANGE THICKNESS EXCEEDING 2 INCHES

20 FT-LB @ 70 DEGREE FARHENHEIT

TESTING TO BE IN ACCORDANCE WITH ASTM A6, SUPPLEMENTARY

REQUIREMENT S30, CHARPY V-NOTCH IMPACT TEST FOR STRUCTURAL

SHAPES - ALTERNATE CORE LOCATION

REFER TO ARCHITECTURAL DRAWINGS FOR MISCELLANEOUS STEEL NOT

INCLUDED IN STRUCTURAL DRAWINGS.

INCLUDE MISCELLANEOUS STEELS IN SHOP DRAWINGS FOR REVIEW AND

APPROVAL.

PROTECT ROOF DURING ALL FIELD WELDING.

ALL EXTERIOR STEEL SHALL BE GALVANIZED.

OPENINGS AND SEALING:

FABRICATOR SHALL PROVIDE VENT AND DRAIN HOLES IN HOLLOW AND

ENCLOSED MEMBERS AS REQUIRED FOR HOT-DIP GALVANIZING PER

ASTM A385. LOCATE AT CONCEALED OR INCONSPICUOUS LOCATIONS

WHERE PRACTICABLE. DRILL OR REAM HOLES TO A UNIFORM DIAMETER.

AFTER GALVANIZING, SEAL ALL EXPOSED OPENINGS INTO HOLLOW

MEMBERS — INCLUDING GALVANIZING VENT AND DRAIN HOLES, UNUSED

BOLT HOLES, AND HOLES MADE DURING FABRICATION, MODIFICATION,

OR ERECTION — WITH TAPERED SOLID ZINC DRIVE-IN PLUGS, DRIVEN

TIGHT AND FILED FLUSH.

CLOSE ALL OPEN ENDS OF PIPE AND HOLLOW STRUCTURAL SECTIONS

WITH CAPS WELDED PRIOR TO GALVANIZING OR WITH GALVANIZED END

CAPS.

REPAIR GALVANIZED COATING AT PLUGS, CAPS, AND FIELD

MODIFICATIONS PER ASTM A780.

ALL OPENINGS INTO HOLLOW STEEL MEMBERS SHALL BE SEALED TO

PREVENT INSECT INTRUSION AND NESTING.

1.

2.

A.

B.

C.

D.

E.

F.

G.

3.

A.

1.

2.

3.

4.

5.

4.

A.

1.

2.

3.

4.

B.

1.

2.

3.

4.

C.

INSTALLATION SHALL BE IN CONFORMANCE WITH MANUFACTURER'S PRINTED

LITERATURE, AND AS INDICATED IN THE DRAWINGS.

ADHESIVE ANCHORS:

ADHESIVE SHALL CONSIST OF A TWO COMPONENT STRUCTURAL GRADE

INJECTION MATERIAL CONFORMING TO ASTM C881

DOWELS SHALL CONFORM TO ASTM A615, GRADE 60, DEFORMED, TYP UNO

THREADED ROD ANCHORS SHALL CONFORM TO GALVANIZED ASTM F1554,

GR. 55, TYP UNO

ALL ANCHORS SHALL BE APPROVED FOR USE WITH THE GOVERNING

EDITION OF THE IBC

DRILL HOLES WITH A PERCUSSION-TYPE DRILL AND REMOVE ALL

CUTTINGS FROM THE HOLES

DO NOT CORE DRILL, DO NOT CUT REINFORCING

DRILL HOLES STRAIGHT AND TRUE AT RIGHT ANGLES TO THE FACE, UNO

MECHANICAL ANCHORS:

MECHANICAL ANCHORS CALLED OUT SHALL BE A TORQUE-CONTROLLED

MECHANICAL EXPANSION ANCHOR SHALL CONSIST OF A STUD (ANCHOR

BODY) WITH A WEDGE EXPANSION ELEMENT:

MINIMUM ANCHOR YIELD STRENGTH = 92,000 PSI

MINIMUM ANCHOR ULTIMATE STRENGTH = 115,000 PSI

MINIMUM DIAMETER AND LENGTH ARE PER PLAN, SCHEDULE OR

DETAILS

REQUIRED INSTALLATION TORQUE IS PER SELECTED

MANUFACTURER'S EVALUATION REPORT

ALL OTHER INSTALLATION PROCEDURES SHALL BE

MANUFACTURER REQUIREMENTS

POWER ACTUATED FASTENERS:

PAF TO CONCRETE:

MINIMUM DIAMETER = 0.157"

MINIMUM EMBEDMENT LENGTH = 1 1/4"

MINIMUM EDGE DISTANCE = 3"

MINIMUM SPACING = 4"

PAF TO STEEL:

MINIMUM DIAMETER = 0.157"

MINIMUM EMBEDMENT LENGTH = VARIES, FASTENER SHALL

PENETRATE THROUGH THE STEEL BASE MATERIAL

MINIMUM EDGE DISTANCE = 1/2"

MINIMUM SPACING = 1"

SUBMIT SUBSTITUTION REQUEST FOR THE USE OF POWER ACTUATED

FASTENERS OR SCREWS WITH MANUFACTURER LITERATURE OR

INTERNATIONAL CODE COUNCIL EVALUATION SERVICE REPORTS

SHOWING A LARGER CAPACITY THAN WHAT IS SHOWN IN THE CONTRACT

DOCUMENTS FOR EACH CONDITION THE SUBSTITUTION REQUESTED

POST INSTALLED ANCHORS

CONCRETE REHABILITATION

1.

2.

3.

4.

A.

5.

A.

B.

C.

D.

E.

F.

CHIP OUT ALL SPALLED, CRACKED, OR DELMINATED CONCRETE IDENTIFIED IN

THE DEMOLITION DRAWINGS OR WHERE NEW FEATURES OF WORK ARE

DETAILED.

SAND BLAST AND CLEAN ALL EXPOSED REINFORCING

FIELD PRIME ALL REINFORCING AND STEEL EXPOSED TO WEATHER

FIELD GALVANIZE WITH GALVANIZED COATING ALL STEEL THAT IS GALVANIZED

OR PERMANENTLY EXPOSED TO WEATHER

COATING SHALL BE ASTM A780 ZINC RICH PAINT

FIELD VERFICATION OF DAMAGED OR SPALLED CONCRETE SHALL INCLUDE AT

MINIMUM THE FOLLOWING STEPS:

REMOVAL OF DAMAGED/SPALLED CONCRETE

CLEAN AREA, INCLUDING STEEL AND CONCRETE FEATURES

INSPECT STEEL FOR ANY SURFACE RUST OR DETERIORATION, SAND

BLAST AND CLEAN AS REQUIRED PER SPECIFICATIONS

SAW CUT SMOOTH AND STRAIGHT EDGES AROUND DAMAGED

CONCRETE AREA

SET ALL POST-INSTALLED ANCHORS, REBAR WITH ADHESIVE INTO

SOUND CONCRETE, FIELD PRIME OR GALVANIZE STEEL COMPONENTS

FORM AREA AND POUR CONCRETE OR GROUT REPAIR AS SPECIFIED OR

DETAILED IN DRAWINGS

CAST-IN-PLACE CONCRETE

1.

2.

3.

4.

5.

6.

7.

8.

A.

B.

C.

D.

9.

A.

B.

C.

D.

10.

A.

11.

A.

B.

C.

12.

A.

13.

A.

1.

B.

1.

2.

3.

C.

1.

2.

3.

REINFORCED CONCRETE WORK IS TO BE IN ACCORDANCE WITH THE AMERICAN

CONCRETE INSTITUTE 318 BUILDING CODE REQUIREMENTS FOR STRUCTURAL

CONCRETE.

MIXING, TRANSPORTING, PLACING, AND TESTING OF CONCRETE IS TO BE DONE

IN ACCORDANCE WITH ACI 301, UNO.

DETAIL AND PLACE ALL REINFORCEMENT IN ACCORDANCE WITH ACI SP-66, ACI

301, ACI 318, AND CRSI MANUAL OF STANDARD PRACTICE.

REINFORCEMENT IS TO BE SECURELY HELD IN PLACE WHILE PLACING

CONCRETE. IF REQUIRED, ADDITIONAL BARS, STIRRUPS, OR CHAIRS SHALL BE

PROVIDED BY THE CONTRACTOR TO FURNISH SUPPORT TO KEEP

REINFORCEMENT IN PLACE PER DESIGN.

CONTINUOUS REINFORCING BARS TO BE BENT AND LAPPED AT CORNERS AND

INTERSECTIONS. LAP SPLICES TO BE PER SCHEDULE OR DETAILS. HOOKED

BARS TO HAVE STANDARD ACI HOOKS, UNO.

CONCRETE TO BE CURED BY METHOD COMPATIBLE WITH FINAL FINISH.

EXPANSION JOINT FILLER SHALL BE PER SPECIFICATIONS. EXPANSION AND

CONTRACTION JOINT SEALANT SHALL BE APPLIED AS RECOMMENDED BY THE

MANUFACTURER OF THE SEALANT.

FORMWORK:

CONTRACTOR IS RESPONSIBLE FOR DESIGN, ENGINEERING,

STRUCTURAL ADEQUACY, AND CONSTRUCTION OF ALL CONCRETE

FORMWORK IN ACCORDANCE WITH THE CONTRACT SPECIFICATIONS

COORDINATE ALL CONCRETE WORK WITH THE PLACEMENT OF PIPING,

INSERTS, FLOOR DRAINS, AND OTHER EMBEDDED ITEMS INDICATED ON

THE CONTRACT DRAWINGS OR IN THE CONTRACT SPECIFICATIONS

ALL NEW OR EXISTING PIPING OR UTILITIES PASSING THROUGH NEW

CONCRETE SHALL BE SLEEVED 1/2" CLEAR ALL AROUND, UNLESS

NOTED OTHERWISE. SEE OTHER DISCIPLINE DRAWINGS FOR SLEEVE

DETAILS. PROVIDE MEASURES TO ENSURE THAT SLEEVES REMAIN

FREE OF DEBRIS AND WATER DURING CONSTRUCTION

PROVIDE 3/4" CHAMFER STRIPS ON ALL EDGES OF EXPOSED

CONCRETE, UNLESS NOTED OTHERWISE

CONCRETE EXPOSURE CATEGORIES AND CLASSES PER ACI 318:

FREEZING AND THAWING = F2

SULFATE = S1

CONTACT WITH WATER = W1

CORROSION PROTECTION OF REINFORCEMENT = C1

CAST-IN-PLACE CONCRETE:

MINIMUM COMPRESSIVE STRENGTH f'c = 4,500 PSI, NORMALWEIGHT

DEFORMED REINFORCEMENT:

CONFORM TO ASTM A615, GRADE 60 UNO

CONFORM TO ASTM A706, GRADE 60 (WELDABLE)

ALL CONCRETE SHALL BE REINFORCED UNLESS SPECIFICALLY MARKED

"NOT REINFORCED" OR "UNREINFORCED"

WELDED WIRE FABRIC:

CONFORM TO ASTM A185, WELDABLE STEEL WIRE FABRIC SHEET TYPE

MINIMUM CONCRETE CLEAR COVER OVER REINFORCEMENT SHALL BE AS

FOLLOWS, UNO:

CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH:

ALL REINFORCING = 3"

CONCRETE EXPOSED TO EARTH OR WEATHER:

#6 THROUGH #11 BARS = 2"

#5 AND SMALLER BARS = 1 1/2"

WELDED WIRE FABRIC = 1 1/2"

CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH THE

GROUND:

SLABS AND WALLS (#14 AND #18 BARS) = 1 1/2"

SLABS AND WALLS (ALL OTHER BARS) = 3/4"

BEAMS AND COLUMNS, PRIMARY REINFORCEMENT, TIES,

STIRRUPS, SPIRALS = 1 1/2"

#3

LAP SPLICE SCHEDULE

REBAR

SIZE

LOCATION

OR TYPE

F'c = 3,000PSI

LENGTH (IN)

F'c = 4,000PSI

LENGTH (IN)

F'c = 5,000PSI

LENGTH (IN)

TOP

OTHER

HOOKED

#4

TOP

OTHER

HOOKED

#5

TOP

OTHER

HOOKED

#6

TOP

OTHER

HOOKED

#7

TOP

OTHER

HOOKED

#8

TOP

OTHER

HOOKED

#9

TOP

OTHER

HOOKED

#10

TOP

OTHER

HOOKED

#11

TOP

OTHER

HOOKED

1.

2.

3.

4.

NOTES:

TOP BAR CONDITION OCCURS WHERE THERE IS MORE THAN 12 INCHES OF

FRESH CONCRTE PLACED BELOW THE SPLICE.

FOR F'c VALUES BETWEEN TABLULATED VALUES SHOWN ABOVE, USE THE LOWER F'c SPLICE LENGTH.

FOR LIGHTWEIGHT CONCRETE, MULTIPLY VALUE SHOWN BY 1.3.

TABLE ASSUMES NON-STAGGERED SPLICES OF REBAR. SPLICE LENGTHS

MAY BE REDUCED BY 30% AND ROUNDED UP TO THE NEAREST INCH

PROVIDED AT LEAST 50% OF SPLICES AT ANY SECTION ARE STAGGERED

BY AT LEAST THE DEVELOPMENT LENGTH VALUE BETWEEN EVERY OTHER

REBAR PER ACI 314 T10.7.5.2.2. STAGGERING MUST BE CLEARLY SHOWN

AND ANNOTATED IN THE REBAR SHOP DRAWINGS.

F'c = 6,000PSI

LENGTH (IN)

FRP GUARDRAIL SYSTEM

1.

2.

A.

B.

C.

D.

3.

A.

B.

C.

D.

E.

F.

G.

4.

A.

B.

C.

D.

E.

F.

G.

1.

2.

H.

1.

2.

3.

5.

A.

B.

C.

D.

ALL FRP GUARDRAIL WORK SHALL CONFORM TO UFGS-06 82 14, IBC 2024, ASCE

7-22, OSHA 29 CFR 1910.29, AND USACE EM 385-1-1.

GUARDRAIL AND ALL CONNECTIONS TO METAL STRINGERS SHALL BE DESIGNED

FOR THE FOLLOWING MINIMUM LOADS PER IBC 2024 §1607.9 AND ASCE 7-22 §4.5.

CONCENTRATED AND UNIFORM LOADS NEED NOT BE APPLIED

SIMULTANEOUSLY.

TOP RAIL - CONCENTRATED: 200 LBF IN ANY DIRECTION AT ANY POINT

TOP RAIL - UNIFORM: 50 LBF/LFT IN ANY DIRECTION

MID-RAIL: 50 LBF CONCENTRATED, APPLIED HORIZONTALLY

POST BASE: DESIGNED FOR FULL LOAD TRANSFER TO STEEL STRINGER

INCLUDING PRYING ACTION AND ECCENTRICITY

GEOMETRY AND DIMENSIONS

TOP RAIL HEIGHT: 42 IN. MIN ABOVE STAIR NOSING OR WALKING

SURFACE PER OSHA 29 CFR 1910.29

MID-RAIL HEIGHT: 21 IN. MIN ABOVE STAIR NOSING OR WALKING

SURFACE PER OSHA 29 CFR 1910.29

TOP RAIL DIAMETER: 1-1/4" MIN TO 2" MAX (OD) PER IBC 2024 §1014.3

MAX POST SPACING: 8 FT O.C. UNLESS JUSTIFIED BY MFR'S STAMPED

CALCULATIONS

MAX OPENING: NO OPENING BETWEEN INTERMEDIATE MEMBERS SHALL

EXCEED 19 INCHES PER OSHA 29 CFR 1910.29(b)

KICKPLATE: 4 IN. MINIMUM HEIGHT AT ALL STAIR LANDINGS PER OSHA 29

CFR 1910.23

EXPANSION JOINTS: MAX 20 FT OR PER MFR'S CERTIFIED ASTM D696

TEST DATA, WHICHEVER IS MORE STRINGENT.

FRP CONNECTION TO STEEL

ALL FASTENERS AND ANCHORS AT FRP-TO-SUBSTRATE INTERFACE

SHALL BE TYPE 316 STAINLESS STEEL. CARBON STEEL AND GALVANIZED

STEEL FASTENERS ARE NOT PERMITTED AT THIS INTERFACE.

MINIMUM TWO (2) BOLTS PER POST BASE, 1/2-IN. DIAMETER MINIMUM

PROVIDE 2-IN. O.D. MINIMUM FENDER WASHERS UNDER ALL BOLT HEADS

AND NUTS BEARING ON FRP SURFACES.

PROVIDE 1/8-IN. THICK, 60-DUROMETER NEOPRENE ISOLATION PAD

BETWEEN FRP POST BASE AND SUBSTRATE INTERFACE.

MAXIMUM FASTENER TORQUE PER MFR'S WRITTEN INSTRUCTIONS.

POWDER-ACTUATED FASTENERS SHALL NOT BE USED IN FRP MEMBERS.

FRP CONNECTION TO STEEL

FASTENERS SHALL BE TYPE 316 SS BOLTS WITH NUTS AND

DISSIMILAR METAL ISOLATION KITS.

CONNECTION SHALL BE DESIGNED FOR FULL LOAD TRANSFER

INCLUDING PRYING ACTION AND ECCENTRICITY.

FRP CONNECTION TO CONCRETE

POST-INSTALLED ANCHORS SHALL BE TYPE 316 SS WEDGE OR

ADHESIVE ANCHORS

ANCHOR EMBEDMENT DEPTH, EDGE DISTANCE, AND SPACING

SHALL SATISFY ACI 318-19

EXISTING CONCRETE COMPRESSIVE STRENGTH SHALL BE

VERIFIED PRIOR TO ANCHOR DESIGN. ASSUME f'c = 3,000 PSI

MINIMUM

OPENINGS AND SEALING:

SEAL ALL CUT ENDS AND DRILLED HOLES IN FRP MEMBERS WITH THE

RAILING MANUFACTURER'S RECOMMENDED RESIN SEALANT.

CLOSE ALL OPEN ENDS OF HOLLOW FRP RAILS AND POSTS WITH THE

MANUFACTURER'S MOLDED, UV-STABILIZED END CAPS OR POST CAPS,

BONDED OR FASTENED PER THE MANUFACTURER.

PLUG ALL UNUSED OR ABANDONED HOLES IN HOLLOW FRP MEMBERS

WITH MANUFACTURER-SUPPLIED UV-STABILIZED PLUGS, OR FILL WITH

COMPATIBLE EPOXY RESIN FINISHED FLUSH. DO NOT USE METAL DRIVE-

IN PLUGS IN FRP MEMBERS.

ALL OPENINGS INTO HOLLOW FRP MEMBERS SHALL BE SEALED TO

PREVENT INSECT INTRUSION AND NESTING.

US Army Corps of Engineers ®

SHEET ID

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

D S:

D

IR

O O

TS

PD

: A D

O

BE

P R

IN

T

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

FI

LE

N U

M

BE

R

C :\U se rs

\g 4e ch ga i\D oc um en ts \D

W A5

6_

SA

M E_

N

EW

R O

O F_

_g ui do .a

.ig le si as

.rv t

/1

7/

1:

:4

AM

S-001

W

AL

LA

W

AL

LA

D

IS

TR

IC

T

N

R

D A

VE

W

AL

LA

W

AL

LA

, W

A

S.

O

LS

O

N

G . I

G

LE

SI

AS

JU

LI

O M

O R

EL

O

S, P

.E

J.

M

O R

EL

O

S

N O

VE

M

BE

R

W

2E F2

7B A0

FI

N

AL

D W

P- 1-

5- 1/

ST

R

U C

TU

R

AL

G

EN

ER

AL

N

O

TE

S

D W

O R

SH

AK

D

AM

A N

D R

ES

ER

VO

IR

R O

O F

R

EP

LA

C

EM

EN

T

N O

R

TH

F O

R K

C

LE

AR

W

AT

ER

R

IV

ER

, I

D

AH

O

PO

W

ER

H O

U

ROOF B

ROOF C

ROOF A

ROOF E

ROOF D

ROOF PRESSURES (PLAN)

WIND PRESSURE ZONE, TYP

R O

O F

A, T

YP

"A

/8

R O

O F

A, T

YP

A"

8'

8"

3 3

0.2 * "hs2" = 6' - 10 3/4"

0.

hs

2"

6'

/4

0.

hs

2"

/8

0.6 * "hs2" = 20' - 8 3/8"

0.

hs

2"

5'

/4

0.

hs

2"

/8

0.2 * "hs2" = 5' - 10 3/4"

0.6 * "hs2" = 17' - 8 3/8"

WALL PRESSURES (ELEVATION)

5 4 5

"A" TYP

"A" VALUES

ROOF A = 9'-4"

ROOF B = 6'-0"

ROOF C = 3'-0"

ROOF D = 3'-0"

ROOF E = 10'-5"

COMPONENT AND CLADDING PRESSURES UNFACTORED (PSF)

ROOF AREA ALL ZONE 1 ZONE 2 ZONE 3 WALL AREA ALL ZONE 4 ZONE 5

10 SF 20.11 -52.58 -86.38 -120.18 10 SF 33.80 -33.80 -67.60

20 SF 33.80 -33.80 -67.60

50 SF 30.59 -31.66 -59.05

500 SF 22.53 -26.29 -37.56

NOTES:

ROOF A IS GREATER THAN 60' TALL; ASCE 7-22 FIGURE 30.4-1 APPLIES.

ROOFS B, C, D & E ARE LESS THAN OR EQUAL TO 60' TALL; ASCE 7-22 FIGURE 30.3-3 (STEPPED ROOFS) APPLIES.

SEE STRUCTURAL CALCULATIONS FOR MORE DETAILS.

HIGH ROOF A, C, OR D

LOW ROOF B OR E

FLAT ROOF SNOW

LOAD = 50.0 PSF

DRIFT WIDTH

D R

IF

T

IN

TE

N

SI

TY

PARAPET - NO SNOW DRIFT

ROOF A, C, OR D WALL, DRIFT

APPLIES TO ALL EDGES

ROOF B = 20.5 FT

ROOF C = 24.5 FT

ROOF E = 11.0 FT

R O

O F

B

PS

F

R O

O F

C

P

SF

R O

O F

E

P

SF

NOTES:

SNOW DRIFT PROFILES AND PRESSURES SHOWN ARE

PROVIDED SOLELY FOR THE DESIGN OF THE NEW

STAIRCASE. EXISTING ROOF SNOW DRIFT LOADS AND

CAPACITIES REMAIN UNALTERED BY THIS SCOPE OF WORK.

A

B

C D

E

US Army Corps of Engineers ®

SHEET ID

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

D S:

D

IR

O O

TS

PD

: A D

O

BE

P R

IN

T

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

FI

LE

N U

M

BE

R

C :\U se rs

\g 4e ch ga i\D oc um en ts \D

W A5

6_

SA

M E_

N

EW

R O

O F_

_g ui do .a

.ig le si as

.rv t

/1

7/

1:

:4

AM

S-002

W

AL

LA

W

AL

LA

D

IS

TR

IC

T

N

R

D A

VE

W

AL

LA

W

AL

LA

, W

A

S.

O

LS

O

N

G . I

G

LE

SI

AS

JU

LI

O M

O R

EL

O

S, P

.E

J.

M

O R

EL

O

S

N O

VE

M

BE

R

W

2E F2

7B A0

FI

N

AL

D W

P- 1-

5- 1/

ST

R

U C

TU

R

AL

L

O

AD

IN

G

D

IA

G R

AM

S

D W

O R

SH

AK

D

AM

A N

D R

ES

ER

VO

IR

R O

O F

R

EP

LA

C

EM

EN

T

N O

R

TH

F O

R K

C

LE

AR

W

AT

ER

R

IV

ER

, I

D

AH

O

PO

W

ER

H O

U

SE

SCALE: 3/32" = 1'-0"A1 WIND LOADING - C&C

GENERAL NOTES

1. WIND LOADING IS UNFACTORED COMPONENTS AND CLADDING FOR THE AREAS

LISTED

2. BUILDING STEPS SHOWN, SEE ARCH AND ELEVATIONS FOR MORE INFORMATION

3. SNOW DRIFT LOAD APPLIES ONLY TO UNBALANCED FLAT ROOF SNOW LOAD

CONDITIONS

4. CANOPY AROUND ROOF B NOT SHOWN

0 4' 8' 16'

NTSSCALE:L1 SNOW DRIFT

= DEMO GUARD RAIL FEATURE, SEE DIMENSIONS

FOR LENGTHS, ALL OTHER EXISTING FIXTURES AND

CONC PILLARS TO REMAIN

ROOF B

ROOF C

ROOF A

ROOF E

ROOF D

DEMO ROOF LADDERS

231' - 4 1/4" ROOF A - DEMO GUARD RAIL ALL SIDES

R

O O

F C

B O

TH

E

N D

S

" D

EM

O G

U

AR

D R

AI

L

DEMO GUARD RAIL

25' - 6 1/4" ROOF C

39' - 11 3/8" ROOF E - DEMO GUARD RAIL

D

EM

O G

U

AR

D R

AI

L

/4 " R

O O

F E

D

EM

O G

U

AR

D R

AI

L

/8 " R

O O

F D

/8 " R

O O

F A

- D

EM

O G

U

AR

D R

AI

L

AL

L

SI

D

ES

G16

SD101

GROUT ABANDONED REFRIGERANT

LINE PENETRATIONS FULL DEPTH

WITH NON-SHRINK GROUT AT

REMOVED HVAC CONDENSER UNIT.

A16

SD101

1'

2"

1' - 6"

2'

7"

17' - 0"

CORE DRILL OR SAW CUT EXIST

CONC ROOF DECK FOR NEW DUCT

OPENING. CONTRACTOR TO VFY IN

FIELD EXACT DIMS WITH MECH

AND ARCHITECTURAL DRAWINGS

PRIOR TO DEMOLITION.

EL 1060.25

1060' - 3"

EL 1074.33

1074' - 4"

DEMO LADDER

DEMO GUARDRAIL

DEMO 8" OF

PARAPET AT STAIR

TOP LANDING

ROOF C

ROOF A

EL 1060.25

1060' - 3"

EL 1039

1039' - 0"

EL 1045.43

1045' - 5 5/32"

DEMO GUARDRAIL

DEMO 8" OF PARAPET

AT STAIR TOP LANDING

ROOF C

ROOF B

3' - 0" 6"

8"

ROOF A

WALL

A

B

C D

E

US Army Corps of Engineers ®

SHEET ID

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

D S:

D

IR

O O

TS

PD

: A D

O

BE

P R

IN

T

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

FI

LE

N U

M

BE

R

C :\U se rs

\g 4e ch ga i\D oc um en ts \D

W A5

6_

SA

M E_

N

EW

R O

O F_

_g ui do .a

.ig le si as

.rv t

/1

7/

1:

:4

AM

SD101

W

AL

LA

W

AL

LA

D

IS

TR

IC

T

N

R

D A

VE

W

AL

LA

W

AL

LA

, W

A

S.

O

LS

O

N

G . I

G

LE

SI

AS

JU

LI

O M

O R

EL

O

S, P

.E

J.

M

O R

EL

O

S

N O

VE

M

BE

R

W

2E F2

7B A0

FI

N

AL

D W

P- 1-

5- 1/

ST

R

U C

TU

R

AL

D

EM

O

LI

TI

O N

D W

O R

SH

AK

D

AM

A N

D R

ES

ER

VO

IR

R O

O F

R

EP

LA

C

EM

EN

T

N O

R

TH

F O

R K

C

LE

AR

W

AT

ER

R

IV

ER

, I

D

AH

O

PO

W

ER

H O

U

SE

SCALE: 3/32" = 1'-0"A1 STRUCTURAL DEMOLITION PLAN

GENERAL NOTES

1. SEE ARCH FOR INFORMATION NOT SHOWN IN THE DEMO PLAN

2. CONTRACTOR TO PATCH ALL REMOVED CONCRETE ANCHOR LOCATIONS

3. CONTRACTOR TO REMOVE/REPAIR SPALLED CONC

NORTH

0 4' 8' 16' 24'

SCALE: 1/4" = 1'-0"SD101

A1 G16 ROOF A WALL DEMO

0 2' 4' 8'SCALE: 1/4" = 1'-0"SD101

A1 A16 ROOF C WALL DEMO

0 2' 4' 8'

NEW STAIR FROM

ROOF B TO ROOF C

NEW STAIR FROM

ROOF C TO ROOF A

ROOF A

DAM EQUIPMENT NOT SHOWN ON ROOF PLAN, TYP

HVAC FAN

ROOF B

ROOF C

ROOF E

ROOF D

S-112 A5

S-110 A1

S-111 A1

A

B

C D

E

US Army Corps of Engineers ®

SHEET ID

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

D S:

D

IR

O O

TS

PD

: A D

O

BE

P R

IN

T

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

FI

LE

N U

M

BE

R

C :\U se rs

\g 4e ch ga i\D oc um en ts \D

W A5

6_

SA

M E_

N

EW

R O

O F_

_g ui do .a

.ig le si as

.rv t

/1

7/

1:

:4

AM

S-101

W

AL

LA

W

AL

LA

D

IS

TR

IC

T

N

R

D A

VE

W

AL

LA

W

AL

LA

, W

A

S.

O

LS

O

N

G . I

G

LE

SI

AS

JU

LI

O M

O R

EL

O

S, P

.E

J.

M

O R

EL

O

S

N O

VE

M

BE

R

W

2E F2

7B A0

FI

N

AL

D W

P- 1-

5- 1/

R O

O F

PL

AN

D W

O R

SH

AK

D

AM

A N

D R

ES

ER

VO

IR

R O

O F

R

EP

LA

C

EM

EN

T

N O

R

TH

F O

R K

C

LE

AR

W

AT

ER

R

IV

ER

, I

D

AH

O

PO

W

ER

H O

U

SE

SCALE: 3/32" = 1'-0"A1 OVERALL ROOF PLAN

0 4' 8' 16' 24'

NEW ROOF A TO C STAIR

ROOF A

FACE MOUNTED FRP GUARD RAIL

ALONG ROOF A, CONTINUOUS

ALONG SIDE, TYP

NO FACE MOUNTED FRP GUARDRAIL IN THIS AREA, SEE ARCH

33' - 5 1/8"

STOP FRP GUARD RAIL AT CONCRETE COLUMN FEATURE,

TYP WHERE OCCURS. MAX 4" CLEAR OPENING BETWEEN

END OF RAILING AND ADJACENT SURFACE, TYP.

ROOF C

A1

S-513

TYP

A5 S-513

A1 S-513

A9 S-513

EPDM WALKWAY

PAD, TYP

S-110 L1

A

B

C D

E

54+51

E43+92.5

A6 S-511

_____________________________________________________________ A13 S-511

A1 S-301

G

AL

V

ST

EE

L

G R

AT

IN

G

C12X20.7 STRINGER

DIAGONAL BRACE

BELOW STRINGER

(REF. K6/S-512) (TYP)

C12X20.7 STRINGER

W 6X

W 6X

C

X2 0.

C

X2 0.

C12X20.7

L6X4X3/8

C12X20.7

3' - 6"

3' - 11 1/8"

2' - 0"

H1 S-514

3'

0" 1'

1/ 2"

SHEAR TAB

(SIMILAR TO

DETAIL A7/S-512)

STAIR TO TOP LANDING

CONNECTION (SEE

DETAIL A7/S-512)3' - 0 7/8" US Army Corps of Engineers ®

SHEET ID

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

D S:

D

IR

O O

TS

PD

: A D

O

BE

P R

IN

T

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

FI

LE

N U

M

BE

R

C :\U se rs

\g 4e ch ga i\D oc um en ts \D

W A5

6_

SA

M E_

N

EW

R O

O F_

_g ui do .a

.ig le si as

.rv t

/1

7/

1:

:4

AM

S-110

W

AL

LA

W

AL

LA

D

IS

TR

IC

T

N

R

D A

VE

W

AL

LA

W

AL

LA

, W

A

S.

O

LS

O

N

G . I

G

LE

SI

AS

JU

LI

O M

O R

EL

O

S, P

.E

J.

M

O R

EL

O

S

N O

VE

M

BE

R

W

2E F2

7B A0

FI

N

AL

D W

P- 1-

5- 1/

PL

AN

R

O O

F A

D W

O R

SH

AK

D

AM

A N

D R

ES

ER

VO

IR

R O

O F

R

EP

LA

C

EM

EN

T

N O

R

TH

F O

R K

C

LE

AR

W

AT

ER

R

IV

ER

, I

D

AH

O

PO

W

ER

H O

U

SE

GENERAL NOTES

1. SEE ARCH FOR ROOF ELEVATIONS AND STAIR INFORMATION NOT SHOWN OR

DETAILED IN STRUCTURAL DRAWINGS

2. SEE MEP DRAWINGS FOR EQUIPMENT INFORMATION NOT SHOWN OR HIDDEN IN

PLAN

SCALE: 1/8" = 1'-0"S-101

A1 A1 ENLARGED ROOF PLAN: ROOF A

0 4' 8' 16'

NORTH

SCALE: 1/2" = 1'-0"S-110

A1 L1 ENLARGED STAIR PLAN: ROOF A TO C

0 1' 2' 4'

H13 S-511

J6 S-511

H1 S-511

NEW STAIR

ROOF C

NEW FACE MOUNTED FRP GUARD

RAIL AROUND ROOF C, TYP

NEW ROOF A TO C STAIR

STAIR (REF. L1/S-110)

J1 S-513

J1 S-513

J1 S-513

A11 S-301

ROOF B

ROOF D

A1 S-514

TYP

POST-INSTALLED FALL PROTECTION

SWIVEL ANCHOR AT CONCRETE

WALL TYP, SEE SPECS AND DTLS

12' - 5 7/8" 20' - 0" 12' - 11 7/8"

13' - 0"

WALL-MOUNTED FALL

PROTECTION ANCHOR

UNDER STAIRS

A17 S-513

NEW FACE MOUNTED

FRP GUARDRAIL

AROUND ROOF D, TYP

A13 S-513

A7 S-514

A14 S-514

J7 S-515

J1 S-515

17' - 0"

2'

7"

1'

2"

1' - 6"

S-512 K6

DIAGONAL BRACE

BLW STRINGER TYP

HVAC UNIT AND STRUCTURAL

SUPPORT BRACKET

A

B

C D

E

US Army Corps of Engineers ®

SHEET ID

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

D S:

D

IR

O O

TS

PD

: A D

O

BE

P R

IN

T

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

FI

LE

N U

M

BE

R

C :\U se rs

\g 4e ch ga i\D oc um en ts \D

W A5

6_

SA

M E_

N

EW

R O

O F_

_g ui do .a

.ig le si as

.rv t

/1

7/

1:

:4

AM

S-111

W

AL

LA

W

AL

LA

D

IS

TR

IC

T

N

R

D A

VE

W

AL

LA

W

AL

LA

, W

A

S.

O

LS

O

N

G . I

G

LE

SI

AS

JU

LI

O M

O R

EL

O

S, P

.E

J.

M

O R

EL

O

S

N O

VE

M

BE

R

W

2E F2

7B A0

FI

N

AL

D W

P- 1-

5- 1/

PL

AN

R

O O

FS

B

, C

D

D W

O R

SH

AK

D

AM

A N

D R

ES

ER

VO

IR

R O

O F

R

EP

LA

C

EM

EN

T

N O

R

TH

F O

R K

C

LE

AR

W

AT

ER

R

IV

ER

, I

D

AH

O

PO

W

ER

H O

U

SE

GENERAL NOTES

1. SEE ARCH FOR ROOF ELEVATIONS AND STAIR INFORMATION NOT SHOWN OR

DETAILED IN STRUCTURAL DRAWINGS

2. SEE MEP DRAWINGS FOR EQUIPMENT INFORMATION NOT SHOWN OR HIDDEN IN

PLAN

SCALE: 1/4" = 1'-0"S-101

A1 A1 ENLARGED ROOF PLAN: ROOFS B, C, & D

0 2' 4' 8'

4 PLAN: DWORSHAK POWERHOUSE EL. 1022

(SNAPPING ON ANY POINT WILL TELL YOU THE FOLLOWING: (DISTANCE FROM CBL, STATIONING)

NOTE: THIS VIEW IS ROTATED

ELEVATOR

STAIRWELL

UP

DOWN

UP

EL. 1030.26

EL. 1021.87

EL. 1022

LOBBY

WOMENS TOILET

MENS TOILET

PIPE SPACEJANITOR

HALL

HALL

CONFERENCE ROOM

MANAGER

GENERAL OFFICE

CLOSETSTORAGE ROOM

MICROWAVE ROOM

CENTRAL AIR CONDITIONING ROOM

MECH.

SHAFT

CONSTRUCTION BASE LINECONSTRUCTION BASE LINE

ERECTION BAY BAY 1 BAY 2 BAY 3 BAY 4 BAY 5 BAY 6

ERECTION BAY UPPER LEVEL

ST

AT

IO

N

CONSTRUCTION BASE LINEN

128'64'0'

NEW FACE MOUNTED

FRP GUARDRAIL WITH

GATE ALONG ROOF D

EXISTING LADDER

APPROXIMATE GATE

LOCATION, SEE ARCH

A13 S-513

NEW FRP GUARD

RAIL ON ROOF E

J5 S-513

J10 S-513

APPROX GATE

LOC, SEE ARCH

+/- 8'-6"

A1 S-514

POST-INSTALLED FALL PROTECTION SWIVEL ANCHOR AT CONCRETE WALL TYP, SEE SPECS AND DTLS

5 ANCHORS @ 20'

A17 S-513

TYP

±18'-0" 20' - 0"

POST-INSTALLED FALL PROTECTION

SWIVEL ANCHOR AT CONCRETE

WALL TYP, SEE SPECS AND DTLS

A

B

C D

E

US Army Corps of Engineers ®

SHEET ID

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

D S:

D

IR

O O

TS

PD

: A D

O

BE

P R

IN

T

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

FI

LE

N U

M

BE

R

C :\U se rs

\g 4e ch ga i\D oc um en ts \D

W A5

6_

SA

M E_

N

EW

R O

O F_

_g ui do .a

.ig le si as

.rv t

/1

7/

1:

:4

AM

S-112

W

AL

LA

W

AL

LA

D

IS

TR

IC

T

N

R

D A

VE

W

AL

LA

W

AL

LA

, W

A

S.

O

LS

O

N

G . I

G

LE

SI

AS

JU

LI

O M

O R

EL

O

S, P

.E

J.

M

O R

EL

O

S

N O

VE

M

BE

R

W

2E F2

7B A0

FI

N

AL

D W

P- 1-

5- 1/

PL

AN

R

O O

FS

D

E

D W

O R

SH

AK

D

AM

A N

D R

ES

ER

VO

IR

R O

O F

R

EP

LA

C

EM

EN

T

N O

R

TH

F O

R K

C

LE

AR

W

AT

ER

R

IV

ER

, I

D

AH

O

PO

W

ER

H O

U

SE

SCALE: 1/8" = 1'-0"S-101

A1 A5 ENLARGED ROOF PLAN: ROOF D & E

GENERAL NOTES

1. SEE ARCH FOR ROOF ELEVATIONS AND STAIR INFORMATION NOT SHOWN OR

DETAILED IN STRUCTURAL DRAWINGS

2. SEE MEP DRAWINGS FOR EQUIPMENT INFORMATION NOT SHOWN OR HIDDEN IN

PLAN

0 4' 8' 16'

EL 1058.25

1058' - 3"

A6 S-511

A13 S-511

FRP GUARD RAIL

STEEL STAIR

HANDRAIL PER DTL

C12X20.7 STAIR STRINGER

BAR GRATING TREADS PER DTLS

AND SPECS.

ROOF C

ROOF A

FRP GUARD RAIL

1073.05

TO LANDING

WELDED GUSSET TO PLATE WITH

ANCHORS TO CONC TYP

STAIR BRACING, SEE /K6 S-512

STRINGER MAY BE FIELD SPLICED AS

NEEDED FOR CONSTRUCTABILITY,

CONTRACTOR TO PROVIDE SPLICE

LOCATIONS AND DETAILS FOR GOV'T

APPROVAL.

TO LANDING

ATTACHMENT TO IRREGULAR CONCRETE:

FIELD VERIFY EXISTING WALL PROFILE AT

ALL STAIR ATTACHMENT LOCATIONS.

NOSING WP

3'

6"

2'

1'

9"

NOSING WP

1069.72

INCLUDE CAST ABRASIVE NOSING AT LANDINGS (TYP)

NOSING WP

1/2

1/2

R

IS

ES

0'

8"

R

IS

ES

16 RUN @ 10" = 13' - 4"2' - 4"5 RUN @ 10" = 4' - 2"

5 7/8"

1'

9"2'

3'

6"

3"3 1/4"

3' - 9"

9 7/8"

1"

(TYP)

10"

(T

YP

8"STRINGER CONNECTION

(SEE DETAIL A7/S-512)

S-514 H7

H1 S-514

S-515 C1

C8 S-515

4' - 5 1/2"

EL 1039.42

1039' - 5"

H13 S-511

J6 S-511

H1 S-511

3'

1/

4"

FRP GUARD RAIL

TYP ANGLE

BRACKET TO

WALL, SEE

SECTION

STEEL HANDRAIL PER DTL

C12X20.7 STAIR STRINGER

BAR GRATING TREADS PER DTLS AND SPECS,

ATTACHED TO STAIR STRINGERS

ROOF B

ROOF C

NEOPRENE

BEARING PAD AT

STAIR LANDING

TO ROOF

TO LANDING

TO LANDING

STAIR BRACING, SEE /K6 S-512

FALL PROTECTION

ANCHOR

4'

6"

13' - 0 1/8"

H1 S-511

HVAC

A7 S-514

A1 S-514

TYP

R

IS

ES

/4

/4

13 RUN @ 10" = 10' - 10"2' - 2"14 RUN @ 10" = 11' - 8"

(TYP)

10"

(T

YP

3/

4"

3/4

3/4

NOSING WP

NOSING WP

NOSING WP

3'

2"

3'

2"

4 7/8" 9 1/4"

EDGE OF BUILDING

5' - 2 1/2"

1048.91

INCLUDE CAST ABRASIVE

NOSINGS AT LANDINGS

(TYP)

4' - 10 3/4"

3'

2"

3"2' - 8 5/8"

3' - 2 1/2"3 1/2"

1059.12

R

IS

ES

/4

0'

/2

STRINGER

CONNECTION (SEE

DETAIL A7/S-512)

US Army Corps of Engineers ®

SHEET ID

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

D S:

D

IR

O O

TS

PD

: A D

O

BE

P R

IN

T

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

FI

LE

N U

M

BE

R

C :\U se rs

\g 4e ch ga i\D oc um en ts \D

W A5

6_

SA

M E_

N

EW

R O

O F_

_g ui do .a

.ig le si as

.rv t

/1

7/

1:

:4

AM

S-301

W

AL

LA

W

AL

LA

D

IS

TR

IC

T

N

R

D A

VE

W

AL

LA

W

AL

LA

, W

A

S.

O

LS

O

N

G . I

G

LE

SI

AS

JU

LI

O M

O R

EL

O

S, P

.E

J.

M

O R

EL

O

S

N O

VE

M

BE

R

W

2E F2

7B A0

FI

N

AL

D W

P- 1-

5- 1/

SE

C

TI

O

N S

D W

O R

SH

AK

D

AM

A N

D R

ES

ER

VO

IR

R O

O F

R

EP

LA

C

EM

EN

T

N O

R

TH

F O

R K

C

LE

AR

W

AT

ER

R

IV

ER

, I

D

AH

O

PO

W

ER

H O

U

SE

SCALE: 1/2" = 1'-0"S-110

L1 A1 SECTION - ROOF C TO A STAIRS (UPPER)

0 1' 2' 4' SCALE: 3/8" = 1'-0"S-111

A1 A11 SECTION - ROOF B TO C STAIRS (LOWER)

0 1' 2' 4' 6'

NOTES

1. GUARDRAIL AND HANDRAIL SHALL MEET ALL DIMENSIONAL REQUIREMENTS OF

OSHA (29 CFR 1910, SUBPART D), LIFE SAFETY CODE (NFPA 101-27), AND EM 385-1-1.

WHERE GUARDRAILING OR HANDRAIL DETAILS ARE OMITTED, THE DETAILS ON THE

CONTRACTOR DEVELOPED SHOP DRAWINGS SHALL COMPLY WITH THOSE

REGULATIONS AND STANDARDS.

2. ALL GRATING SHALL BE GALVANIZED AND WELDED 2" SERRATED BAR GRATING

WITH 3/16" BEARING BARS SPACED AT 1 3/16" AND CROSS BARS SPACED AT 4". STAIR

TREADS SHALL BE OF SIMILAR CONSTRUCTION AND INCLUDE CAST-ABRASIVE

NOSINGS AND CARRIER PLATES.

3) EACH GRATING PANEL SHALL BE ATTACHED IN ACCORDANCE WITH THE

MANUFACTURER'S REQUIREMENTS IN AT LEAST 4 LOCATIONS.

3/8" GUSSET PLATE

W/ (2) 13/16" HOLES

FOR (2) 3/4" BOLTS

ON GAGE

STAIR SYSTEM PER DTL

FRP GUARDRAIL

STAIR GUARDRAIL

PER DETAIL, TYP

ATTACHMENT TO IRREGULAR CONCRETE:

CHIP OUT 2" FROM THE RUSTICATIONS TO

INSTALL ANCHORS AND MISS EXISTING

WALL REBAR. CONTRACTOR SHALL FIELD

VERIFY RUSTICATIONS.

W6X12

3/8" GUSSET PLATE W/

(2) 13/16" HOLES FOR (2)

3/4" BOLTS ON GAGE

1/4

1/4 1"

(2) 11/16" HOLES FOR

(2) 5/8" BOLTS ON GAGE

9"

11/16" HOLES FOR

3/4" EPOXY ANCHORS

3' - 0"

3/4" BOTTOM CONNECTION PLATE

3/4" EPOXY ANCHORS

WITH 12" EMBEDMENT

A1 S-511

TOP CONNECTION PLATE

1/2"1/2 " M

IN

(T

YP)

1 1/2" (TYP)

1 1/2" (TYP)

3" (TYP)

1 1 /8"

45.00°

1/ 2"

1 1/4" 1' - 4 1/2"

WP

L4X4X3/8

ROOF A

ROOF A PARAPET STEP,

FLASH PER ARCH

TYPICAL WT TO

WALL, SEE /G7 S-512

STAIR GUARDRAIL

PER DTL, TYP

CHANNEL,

SEE PLAN

TYPICAL ANGLE

BRACE, SEE /A1 S-512

GALV STEEL

GRATING,

SEE PLAN

WT4X20X0'-9" W/ (3) 3/4"

DIA A325 BOLTS (SIMILAR

TO G7/S-512)

LEDGER ANGLE, SEE

PLAN

45.00°

3" T

YP

1' - 4 1/2"

4' - 7 3/4"

C12X20.7

SHEAR TAB CONNECTION (SEE

DETAIL A7/S-512)

3' - 0"

1/

2" 6"

1/

2"

H14 S-514

1/ 2"

1/2"

3' - 9 1/2"

ROOF B INTERMEDIATE LANDING

TYPICAL ANGLE

BRACKET, SEE

TYPICAL WT TO

WALL, SEE /G7 S-512

/A1 S-512

EXISTING

CONCRETE WALL

TYPICAL ANGLE,

SEE /A1 S-512

STAIR GUARDRAIL

PER DTL, TYP

7 3/4" 2' - 11 3/8"

TYPICAL ANGLE ,

SEE /A1 S-512

3' - 0"

7/8"

ROOF B

STEEL

STAIR

TYPICAL ANGLE

BRACKET, SEE

PLATE TO ANGLE AND

STRINGER, SEE DETAIL

(TYP)

TYPICAL WT TO

WALL, SEE /G7 S-512

/A1 S-512EXISTING

CONCRETE WALL

/K1 S-512

TYPICAL ANGLE,

SEE /A1 S-512

STAIR GUARDRAIL

PER DTL, TYP

3' - 6 7/8"

STAIR SYSTEM PER DTL

45.00°

3' - 0"

1 1/8"

1/

8"

TYPICAL ANGLE

BRACKET, SEE

TYPICAL WT TO

WALL, SEE /G7 S-512

/A1 S-512

EXISTING

CONCRETE WALL

ROOF LANDING

ROOF PARAPET STEP,

FLASH PER ARCH

STAIR GUARDRAIL

PER DTL, TYP

C12X20.7

6"

1/

2" C

LR

GALV STEEL GRATING,

SEE PLAN

1/

2" 6"

1/

2"

L6X4X3/8 LEDGER ANGLE

(SIMILAR TO H14/S-514)

WT4X20X0'-9" W/ (3) 3/4"

DIA A325 BOLTS (SIMILAR

TO G7/S-512)

3" 7" 2' - 9 1/8"

1/ 2"

1/2"

45.00°

2" 6"

2"

SHEAR TAB CONNECTION (SEE

DETAIL A7/S-512)

L14 S-514

2"8"2"

3/ 4"

(T

YP

2" 6"

2"

3/4" (TYP)

W6X12 1" PLATE

3/4" PLATE

5/16 3/16

TOP CONNECTION

PLATE

2" 6"

2"

1 3/4"1' - 2 1/2"1 3/4"

3/4" PLATE

L4X4X3/8

3/8" GUSSET PLATE

BOTTOM

CONNECTION

PLATE

1/4

1/4

3/4" BOLTS

1/ 2"

1/ 2"

US Army Corps of Engineers ®

SHEET ID

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

D S:

D

IR

O O

TS

PD

: A D

O

BE

P R

IN

T

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

FI

LE

N U

M

BE

R

C :\U se rs

\g 4e ch ga i\D oc um en ts \D

W A5

6_

SA

M E_

N

EW

R O

O F_

_g ui do .a

.ig le si as

.rv t

/1

7/

1:

:4

AM

S-511

W

AL

LA

W

AL

LA

D

IS

TR

IC

T

N

R

D A

VE

W

AL

LA

W

AL

LA

, W

A

S.

O

LS

O

N

G . I

G

LE

SI

AS

JU

LI

O M

O R

EL

O

S, P

.E

J.

M

O R

EL

O

S

N O

VE

M

BE

R

W

2E F2

7B A0

FI

N

AL

D W

P- 1-

5- 1/

ST

R

U C

TU

R

AL

D

ET

AI

LS

D W

O R

SH

AK

D

AM

A N

D R

ES

ER

VO

IR

R O

O F

R

EP

LA

C

EM

EN

T

N O

R

TH

F O

R K

C

LE

AR

W

AT

ER

R

IV

ER

, I

D

AH

O

PO

W

ER

H O

U

SE

SCALE: 1" = 1'-0"S-111

A1 H13 DETAIL - ROOF B UPPER LANDING

SCALE: 1" = 1'-0"S-111

A1 J6 DETAIL - ROOF B INTERMEDIATE LANDING

SCALE: 1" = 1'-0"S-111

A1 H1 DETAIL - ROOF B LOWER LANDING

SCALE: 1" = 1'-0"S-110

L1 A6 DETAIL - ROOF C INTERMEDIATE LANDING

SCALE: 1" = 1'-0"S-110

L1 A13 DETAIL - ROOF A LANDING

0 1.5" 3" 6" 9" 0 0.5' 1' 2'

0 0.5' 1' 2'

0 0.5' 1' 2'

0 0.5' 1' 2'

SCALE: 3" = 1'-0"S-511

A6 A1 DETAIL - CONNECTION PLATE

NOTE: CONTRACTOR SHALL ADJUST DIMENSIONS BASED ON FIELD VERIFIED RUSTICATION

LOCATIONS. RUSTICATION SHALL SHALL BE CHIPPED OUT AND ANCHOR PLATE DIMENSIONS

ADJUSTED SUCH THAT THE SHANK OF THE ANCHOR ROD IS NOT EXPOSED BETWEEN THE

CONNECTION PLATE AND THE CONCRETE WALL. DIMENSIONS ACCOUNTING FOR

RUSTICATIONS SHALL BE SHOWN ON THE SHOP DRAWINGS.

0 0.5' 1' 2'

SEE DETAIL

VARIES

SEE DETAILS 1/2"

45.00°

L6X4X3/8, LLV

L4X4X3/8

2"

3/16

ALL EDGES,

TYP AT ENDS

3/16

NS & FS

1/2"

3/

8"

2"

1 1/2"

1/2" WT6X26.5x0'-8", TYP

OFFSET PER DETAILS

FRAME SECTION

ANGLE CONNECTING

FRAMES, FRONT AND

BACK, TYP AT FRAMES

L6X4X3/8, LLV

4" 2 3/8" 2"

8"

5/

8"

1"

3/16

NS & FS,

ALL EDGES

L6X4X3/8, TYP

(2) 3/4"Ø TENSIONED

BOLT, TYP

SEE ELEVATION

ANGLE CONNECTING FRAMES

FOR WT ANCHORS

TO CONCRETE,

SEE /G7 S-512

3"

(2) 3/4"Ø BOLT ES ALIGN W/ STAIR

STRINGER

3/16

ALL EDGES

NS AND FS

2" 6" 2"

2"6"

2"

(4) 3/4"Ø X 4" EMBED

ADHESIVE ANCHORS

4"

WT6x26.5

O R

J O

IN

T

1/

2" C

LR

T

O E

D G

E

CONCRETE

EDGE OR JOINT

STRINGER

SIDE VIEW SECTION

PL 1/2", WELDED TO

STRINGER AND ANGLE, ALIGN

TO FACE OF CHANNEL

CJP

3/16

ANGLE PER /A1 S-512

C12X20.7, TYP

CHANNEL SPLICES

CJP FLANGES

& WEB

CHANNEL TO ANGLE

TREAD SUPPORT

3/4"Ø SNUG TIGHT

BOLT, CENTER ON

ANGLE FLANGE

STAIR TREAD PER DTLS & MFR

CARRIER PL PER MFR

DIAPHRAGM BRACE

L4X4X1/4 DIAGONAL BRACE AT

BOTTOM FLANGE WITH 3/4" BOLT, TYP

EA END, CONFIGURE TO DISTRIBUTE

EVENLY ON VERTICAL RISES

BRACE CONNECTION

45.00°

C12 STAIR STRINGER

C12 STAIR STRINGER

4"

2"

TY

P 1"

C

LR

NOTE: START BRACING AT TOP OF RISE,

CONTINUE DOWN, TERMINATE IF WITHIN

3'-0" OF LANDINGS (MID OR BOTTOM)

STRINGER PER SECTION

PE

R

M

FR

D

EP

TH

SLOTTED HOLE PER MFR

WELDED GALVANIZED STEEL BAR

GRATING W/ SERRATED SURFACE

CAST ABBRASIVE NOSING

WELD END PL TO GRATING PER MFR. PLACE

T/O END PL TO FLUSH /W T/O GRATING

BOLT HOLE PER MFR

CARRIER PL

STRINGER PER SECTION AND DTLS

ARCH AND MFR

TREAD WIDTH PER

NOTE: CONTRACTOR MAY FIELD WELD CARRIER PLATE TO STRINGER

IN ACCORDANCE WITH MANUFACTURER REQUIREMENTS WHERE

BOLTING IS NOT POSSIBLE.

3/16

3/16

3-…