27BA001_Plans.pdf
PDF 12 MB Posted
- Attached to
- Dworshak Powerhouse Roof Replacement
- Solicitation number
- W912EF27BA001
About this file
ROOF REPLACEMENT PROJECT - DESIGN DOCUMENTS
Dworshak Dam and Reservoir Powerhouse
This file package contains the complete design and construction documents for a roof replacement project at the Dworshak Dam Powerhouse located on the North Fork Clearwater River in Idaho. The solicitation number is W912EF27BA001, issued in November 2026 by the U.S. Army Corps of Engineers, Walla Walla District.
The project involves comprehensive roof replacement across five distinct roof sections (A, B, C, D, and E) with varying elevations ranging from 1,036 to 1,074 feet. The scope includes demolition of existing roofing assemblies, structural modifications, installation of new steel and stair systems, mechanical systems (heat pump and air handling equipment), and electrical infrastructure. The design incorporates fully-adhered EPDM membrane roofing with rigid polyiso insulation over existing metal and concrete decks. New steel stairs with FRP guardrails provide access between roof levels. Mechanical work includes removal of existing HVAC equipment and installation of new 5-ton heat pump systems with ductwork. The project requires coordination with high-voltage transmission lines (500 kV and 115 kV), microwave transmission equipment, and telecommunications infrastructure. The design documents include structural calculations per UFC criteria and industry standards including ACI 318-19, AISC 16th Edition, and ASCE 7-22, with specific attention to wind loading (110 mph design wind speed) and seismic design requirements. All exterior steel is hot-dipped galvanized, and concrete work conforms to exposure categories for freezing/thawing and water contact conditions. The documents provide detailed plans, sections, schedules, and specifications for general, structural, architectural, mechanical, and electrical disciplines with over 40 drawing sheets addressing demolition, installation, and coordination requirements across multiple elevation levels.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D7
NORTH NORTH
NORTH
G13
SITE MAP
SCALE: NTS
D1
VICINITY MAP
SCALE: NTS D7
LOCATION MAP
SCALE: NTS
G13
POWERHOUSE
LOG BOOM
STILLING BASIN
SPILLWAY
DWORSHAK DAM
TO AHSAHKA
TO OROFINO
VIEWPOINT RD
NORTHFORK DR
W
AS
H
IN
G
TO
N
ID
AH
O
LEWISTON
SNAKE RIVER
OROFINO
KAMIAH
NOTE: CONSTRUCTION BASE LINE TO GRID NORTH ROTATION IS 39°09'0.00"
IDAHO
WASHINGTON
OREGON
NEVADA UTAH
WYOMING
MONTANA
500 KV TRANSMISSION LINE
115 KV TRANSMISSION LINE
NORTH FORK CLEARWATER RIVER
NORTH FORK CLEARWATER RIVER
(DWORSHAK RESERVOIR)
FLOW
US Army Corps of Engineers ®
SHEET ID
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E
US Army Corps of Engineers ®
SOLICITATION NO.:
CONTRACT NO.:
ISSUE DATE:
M
AR
K D
ES
C
R
IP
TI
O
N
D S:
D
IR
O O
TS
PD
: A D
O
BE
P R
IN
T
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N U
M
BE
R
R :\d
6\
D W
A5
6_
SA
M
E_ N
EW
R
O O
F_
.rv t 9/
/2
1:
:1
PM
G-001
W
AL
LA
W
AL
LA
D
IS
TR
IC
T
N
R
D A
VE
W
AL
LA
W
AL
LA
, W
A
M .F
LA
N
AG
AN
M .F
LA
N
AG
AN
JO
SH
U A
K.
T
AP
P, R .A
M .Z
AN
G
ER
N O
VE
M
BE
R
W
2E F2
7B A0
FI
N
AL
WALLA WALLA DISTRICT
W912EF27BA001
NOVEMBER 2026
D W
G -1
-0 -1
/5
C O
VE
R
S H
EE
T
AN
D
L O
C
AT
IO
N
M
AP
S
D W
O R
SH
AK
D
AM
A N
D R
ES
ER
VO
IR
R O
O F
R
EP
LA
C
EM
EN
T
N O
R
TH
F O
R K
C
LE
AR
W
AT
ER
R
IV
ER
, I
D
AH
O
PO
W
ER
H O
U
SE
DWORSHAK DAM AND RESERVOIR
NORTH FORK CLEARWATER RIVER, IDAHO
ROOF REPLACEMENT
POWERHOUSE
SUBMITTED BY:
SUBMITTED BY:
SUBMITTED BY:
SUBMITTED BY:
SUBMITTED BY:
APPROVED BY:
MARCUS PALMER, P.E.
CHIEF OF DESIGN BRANCH
WALLA WALLA DISTRICT
KEVIN RENSHAW, P.E.
CHIEF OF MECHANICAL DESIGN SECTION
WALLA WALLA DISTRICT
LEVI VAN STEDUM, P.E.
CHIEF OF ELECTRICAL DESIGN SECTION
WALLA WALLA DISTRICT
DWAYNE WESTON, P.E.
CHIEF OF ENGINEERING & CONSTRUCTION DIVISION
WALLA WALLA DISTRICT
JOSHUA K. TAPP, R.A.
SUPERVISORY ARCHITECT
WALLA WALLA DISTRICT
This project was designed by the Walla Walla District of the U.S. Army Corps of Engineers.
The initials or signatures and registration designations of individuals appear on these project documents within the scope of their employment as required by ER 1110-1-8152.
JULIO MORELOS, P.E.
CHIEF OF STRUCTURAL DESIGN SECTION
WALLA WALLA DISTRICT
US Army Corps of Engineers ®
SHEET ID
U .S . A
R M Y C O R
PS
O F
EN
G
IN
EE
R S
D R
AW
N B Y:
D
ES
IG
N
ED
B Y:
SU
BM
IT
TE
D B Y:
SI
ZE
C H
EC
KE
D B Y:
AN
SI
D
IS
SU
E D
AT
E:
C O N
TR
AC
T N O
SO
LI
C
IT
AT
IO
N N O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K D
ES
C R
IP
TI
O N
D S:
D
IR
O O
TS
PD
: A
D O
BE
P R
IN
T
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N U M
BE
R
C :\U se rs \g 4e ch ga i\D oc um en ts \D W A5
6_
SA
M E_
N
EW
R O O F_ _g ui do .a .ig le si as .rv t
/1 7/ 0:
:4
AM
G-002
W
AL
LA
W
AL
LA
D
IS
TR
IC
T
N R D A
VE
W
AL
LA
W
AL
LA
, W A
M . F
LA
N
AG
AN
M . F
LA
N
AG
AN
JO
SH
U A K.
T
AP
P, R .A
M . Z
AN
G
ER
N O
VE
M
BE
R
W 2E
F2 7B
A0
FI
N
AL
D W G -1 -0 -1 /5
SH
EE
T
IN
D
EX
D W O R
SH
AK
D
AM
A N D R
ES
ER
VO
IR
R O O F R
EP
LA
C
EM
EN
T
N O R
TH
F O R K C
LE
AR
W
AT
ER
R
IV
ER
, I D
AH
O
PO
W
ER
H O U
SE
G-001 COVER SHEET AND LOCATION MAPS DWG-1-0-1/505 DWA515646_SAME_NEWROOF_2023.rvt G-002 SHEET INDEX DWG-1-0-1/506 DWA515646_SAME_NEWROOF_2023.rvt G-003 GENERAL NOTES, ABBREVIATIONS DWG-1-0-1/507 DWA515646_SAME_NEWROOF_2023.rvt G-101 SITE PLAN DWG-1-0-1/508 DWA515646_SAME_NEWROOF_2023.rvt G-401 HAZARDOUS AREAS EQUIPMENT PLAN DWG-1-0-1/509 DWA515646_SAME_NEWROOF_2023.rvt G-901 SITE PHOTO DWG-1-0-1/510 DWA515646_SAME_NEWROOF_2023.rvt
S-001 STRUCTURAL GENERAL NOTES DWP-1-5-1/9 DWA515646_SAME_NEWROOF_2023.rvt S-002 STRUCTURAL LOADING DIAGRAMS DWP-1-5-1/10 DWA515646_SAME_NEWROOF_2023.rvt SD101 STRUCTURAL DEMOLITION DWP-1-5-1/11 DWA515646_SAME_NEWROOF_2023.rvt S-101 ROOF PLAN DWP-1-5-1/12 DWA515646_SAME_NEWROOF_2023.rvt S-110 PLAN - ROOF A DWP-1-5-1/13 DWA515646_SAME_NEWROOF_2023.rvt S-111 PLAN - ROOFS B, C & D DWP-1-5-1/14 DWA515646_SAME_NEWROOF_2023.rvt S-112 PLAN - ROOFS D & E DWP-1-5-1/15 DWA515646_SAME_NEWROOF_2023.rvt S-301 SECTIONS DWP-1-5-1/16 DWA515646_SAME_NEWROOF_2023.rvt S-511 STRUCTURAL DETAILS DWP-1-5-1/17 DWA515646_SAME_NEWROOF_2023.rvt S-512 STRUCTURAL DETAILS DWP-1-5-1/18 DWA515646_SAME_NEWROOF_2023.rvt S-513 STRUCTURAL DETAILS DWP-1-5-1/19 DWA515646_SAME_NEWROOF_2023.rvt S-514 STRUCTURAL DETAILS DWP-1-5-1/20 DWA515646_SAME_NEWROOF_2023.rvt S-515 STRUCTURAL DETAILS DWP-1-5-1/21 DWA515646_SAME_NEWROOF_2023.rvt
A-001 ARCHITECTURAL NOTES, LEGENDS, ABBREVIATIONS DWP-1-2-1/26 DWA515646_SAME_NEWROOF_2023.rvt AD101 ROOF DEMOLITION PLAN DWP-1-2-1/27 DWA515646_SAME_NEWROOF_2023.rvt A-101 ROOF PLAN DWP-1-2-1/28 DWA515646_SAME_NEWROOF_2023.rvt A-401 ENLARGED ROOF PLAN - ROOF A DWP-1-2-1/29 DWA515646_SAME_NEWROOF_2023.rvt A-402 ENLARGED ROOF PLAN - ROOFS B, C, & D DWP-1-2-1/30 DWA515646_SAME_NEWROOF_2023.rvt A-403 ENLARGED ROOF PLAN - ROOF E DWP-1-2-1/31 DWA515646_SAME_NEWROOF_2023.rvt A-404 ENLARGED STAIR PLANS & SECTIONS DWP-1-2-1/32 DWA515646_SAME_NEWROOF_2023.rvt A-405 ENLARGED STAIR SECTIONS & DETAILS DWP-1-2-1/33 DWA515646_SAME_NEWROOF_2023.rvt A-501 TYPICAL ROOFING DETAILS DWP-1-2-1/34 DWA515646_SAME_NEWROOF_2023.rvt A-502 ROOFING DETAILS DWP-1-2-1/35 DWA515646_SAME_NEWROOF_2023.rvt A-503 ROOFING DETAILS DWP-1-2-1/36 DWA515646_SAME_NEWROOF_2023.rvt A-504 ROOFING DETAILS DWP-1-2-1/37 DWA515646_SAME_NEWROOF_2023.rvt A-505 ROOFING DETAILS DWP-1-2-1/38 DWA515646_SAME_NEWROOF_2023.rvt
MD101 DEMOLITION - MECHANICAL ROOF PLAN DWP-1-3-1/16 DWA515646_SAME_NEWROOF_2023.rvt MD102 DEMOLITION - MECHANICAL FLOOR PLAN - EL 1045.43 DWP-1-3-1/17 DWA515646_SAME_NEWROOF_2023.rvt MD301 DEMOLITION - SECTION - MECHANICAL DWP-1-3-1/18 DWA515646_SAME_NEWROOF_2023.rvt MD901 DEMOLITION - EXISTING PHOTOGRAPHS DWP-1-3-1/19 DWA515646_SAME_NEWROOF_2023.rvt M-101 INSTALLATION - MECHANICAL FLOOR PLAN DWP-1-3-1/20 DWA515646_SAME_NEWROOF_2023.rvt M-301 INSTALLATION - SECTION - MECHANICAL ROOM DWP-1-3-1/21 DWA515646_SAME_NEWROOF_2023.rvt M-302 INSTALLATION - SECTION - MECHANICAL ROOM EXTERIOR DWP-1-3-1/22 DWA515646_SAME_NEWROOF_2023.rvt M-601 MECHANICAL SCHEDULES DWP-1-3-1/23 DWA515646_SAME_NEWROOF_2023.rvt M-901 INSTALLATION - HVAC PIPING ISOMETRIC DWP-1-3-1/24 DWA515646_SAME_NEWROOF_2023.rvt
ED101 ELECTRICAL DEMO PLAN - EL.1065 DWP-1-6-1/18 DWA515646_SAME_NEWROOF_2023.rvt ED201 ELECTRICAL DEMO ELEVATION - EL. 1038.79 DWP-1-6-1/19 DWA515646_SAME_NEWROOF_2023.rvt ED401 EL. 1045 ELEVATOR ROOM ELECTRICAL DEMO DWP-1-6-1/20 DWA515646_SAME_NEWROOF_2023.rvt E-101 ELECTRICAL INSTALL PLAN DWP-1-6-1/21 DWA515646_SAME_NEWROOF_2023.rvt E-201 ELECTRICAL INSTALL ELEVATION - EL. 1038.79 DWP-1-6-1/22 DWA515646_SAME_NEWROOF_2023.rvt E-401 EL. 1045 ELEVATOR ROOM ELECTRICAL INSTALL DWP-1-6-1/23 DWA515646_SAME_NEWROOF_2023.rvt
SHEET INDEX
SHEET ID DESCRIPTION FILE NO. SOURCE
GENERAL
STRUCTURAL
ARCHITECTURAL
MECHANICAL
ELECTRICAL
DRAWING ABBREVIATIONS INDEX OF DRAWINGS
NUMBERING SYSTEM:
XX100
DISCIPLINE:
C - CIVIL
L - LANDSCAPE
A - ARCHITECTURE
M - MECHANICAL
E - ELECTRICAL
P - PLUMBING
S - STRUCTURAL
K - FOOD SERVICE
DISCIPLINE MODIFIER
SHEET NUMBER WITHIN
SERIES
ANNOTATION CALLOUTS/DRAWING
SYMBOLS
A ---------------------
A/C AIR CONDITION
A/C UNIT AIR CONDITIONING UNIT
AB ANCHOR BOLT
ABA ARCHITECTURAL BARRIERS
ACT
ACC ACCESSIBLE
ACS AUTOMATIC CONTROL SYSTEM
ACS DR ACCESS DOOR
ACS PNL ACCESS PANEL
ADMIN ADMINISTRATION
AFS ABOVE FINISHED SLAB
AGGR AGGREGATE
AHU AIR HANDLING UNIT
AIB AIR INFILTRATION BARRIER
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZE
APPROX APPROXIMATE
AR AS REQUIRED
ARCH ARCHITECT
ASSY ASSEMBLY
AVG AVERAGE
B ---------------------
BD BOARD
BDRY BOUNDARY
BLDG BUILDING
BLKG BLOCKING
BLT IN BUILT-IN
BN BULLNOSE
BOS BOTTOM OF STEEL
BOT BOTTOM
BPA BONNEVILLE POWER
ADMINISTRATION
BRKT BRACKET
BTWN BETWEEN
C ---------------------
C CONC CAST CONCRETE
CAV CAVITY
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR
FURNISHED/CONTRACTOR
INSTALLED
CFE CONTRACTOR FURNISHED
EQUIPMENT
CFLG COUNTERFLASHING
CFM CUBIC FEET PER MINUTE
CFMF COLD-FORMED METAL
FRAMING
CFS CUBIC FEET PER SECOND
CI CAST IRON
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLL COLUMN LINE
CLR COLOR
CNDS CONDENSATE
CO CLEANOUT
COL COLUMN
COMM COMMUNICATION
CONC CONCRETE
CONC FLR CONCRETE FLOOR
CONT CONTINUE
COORD COORDINATE
CTR CENTER
CU FT CUBIC FEET
D ---------------------
D DEPTH
DBL DOUBLE
DEMO DEMOLITION
DET DETAIL
DIA DIAMETER
DIMS DIMENSIONS
DIR DIRECTION
DIST DISTANCE
DOC DOCUMENT
E ---------------------
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
ES EACH SIDE
EL ELEVATION
ELEV ELEVATOR
ENTR ENTRANCE
EPDM ETHYLENE PROPYLENE
DIENE MONOMER
EQ EQUAL
EWC ELECTRIC WATER COOLER
EXP EXPOSED
EXT EXTERIOR
F ---------------------
FED FEDERAL
FLEX FLEXIBLE
FLR FLOOR
FM FACTORY MUTUAL
FOC FACE OF CONCRETE
FRMG FRAMING
FRP FIBERGLASS REINFORCED
PLASTIC
FS FAR SIDE
FSTNR FASTENER
FT FEET
G --------------------
GALV GALVANIZED
GFCI GOVERNMENT FURNISHED
CONTRACTOR INSTALLED
GFGI GOVERNMENT FURNISHED
INSTALLED BY GOVERNMENT
GYP BD GYPSUM BOARD
H ---------------------
HORIZ HORIZONTAL
HT HEIGHT
I ---------------------
IBC INTERNATIONAL BUILDING
CODE
INSUL INSULATION
INT INTERIOR
L ---------------------
LBS POUND
LDG LANDING
LF LINEAR FEET (FOOT)
LIN LINEAR
LVR LOUVER
M ---------------------
MACH RM MACHINE ROOM
MATL MATERIAL
MAX MAXIMUM
MC MOISTURE CONTENT
MD METAL DECK
MECH MECHANICAL
MECH RM MECHANICAL ROOM
MEMB MEMBRANE
MFR MANUFACTURER
MID MIDDLE
MIN MINIMUM
MISC MISCELLANEOUS
MOD MODIFY
MTG MOUNTING
MTL METAL
N ---------------------
N NORTH
NA NOT APPLICABLE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
O -------------------
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OPNG OPENING
OPP OPPOSITE
OWSJ OPEN WEB STEEL JOIST
ORD OVERFLOW ROOF DRAIN
ORIG ORIGINAL
P --------------------
PA PUBLIC ADDRESS
PAR PARAPET
PAT PATTERN
PCF POUNDS PER CUBIC FOOT
PCT PERCENT
PERIM PERIMETER
PH PHASE
PLBG PLUMBING
PNL PANEL
POLYISO POLYISOCYANURATE
INSULATION
PR PAIR
PRCST PRECAST
PS CONC PRESTRESSED
CONCRETE
Q --------------------
QTY QUANTITY
R --------------------
RC REINFORCED CONCRETE
RD ROOF DRAIN
RDG INSRIGID INSULATION, SOLID
REC RECESSED
REF REFERENCE
REM REMOVABLE
REP REPAIR
REPL REPLACE
REQ REQUIRE
REQD REQUIRED
RFG ROOFING
RLG RAILING
RO ROUGH OPENING
S --------------------
SCHED SCHEDULE
SF SQUARE FOOT (FEET)
SGL SINGLE
SHT MTL FLASH SHEET METAL
(FLASHING)
SIM SIMILAR
SLNT SEALANT
SP EL SPOT ELEVATION
SPEC SPECIFICATION
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SST STAINLESS STEEL
ST STAIRS
STD STANDARD
STL JST STEEL JOIST
STL RF DK STEEL ROOF DECK
STR STRINGERS
T --------------------
T TREAD
TEMP TEMPORARY
THK THICKNESS
TN TRUE NORTH
TOP TOP OF PARAPET
TOPO TOPOGRAPHY
TYP TYPICAL
V --------------------
VFY VERIFY
REFER TO AEC CAD
STANDARDS FOR PROPER
SHEET NUMBERING
REVISION
TAG
NORTH ARROW w/
TRUE NORTH
INDICATION
ELEVATION NUMBER
SECTION
EXTERIOR ELEVATION
ENLARGEMENT,
DETAIL
SPOT ELEVATION
LEVEL NAME
SHEET NUMBER
SHEET NUMBER
SHEET NUMBER
A SHEET KEYNOTE
INTERIOR ELEVATION
SHEET NUMBER
Name Elevation
PLAN NORTH
A101
SIM
A101
A101
SIM
A101
1 Ref
R ef
1Ref
R ef
METAL DECK STRONG
AXIS SPAN INDICATOR
SLOPE ARROW
AND DIRECTION
CONSTRUCTION/
COLD JOINT
STRUCTURE STEP
US Army Corps of Engineers ®
SHEET ID
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
D S:
D
IR
O O
TS
PD
: A D
O
BE
P R
IN
T
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N U
M
BE
R
R :\d
6\
D W
A5
6_
SA
M
E_ N
EW
R
O O
F_
.rv t 9/
/2
1:
:1
PM
G-003
W
AL
LA
W
AL
LA
D
IS
TR
IC
T
N
R
D A
VE
W
AL
LA
W
AL
LA
, W
A
M . F
LA
N
AG
AN
M . F
LA
N
AG
AN
JO
SH
U A
K.
T
AP
P, R .A
M . Z
AN
G
ER
N O
VE
M
BE
R
W
2E F2
7B A0
FI
N
AL
D W
G -1
-0 -1
/5
G
EN
ER
AL
N O
TE
S, A
BB
R
EV
IA
TI
O N
S
D W
O R
SH
AK
D
AM
A N
D R
ES
ER
VO
IR
R O
O F
R
EP
LA
C
EM
EN
T
N O
R
TH
F O
R K
C
LE
AR
W
AT
ER
R
IV
ER
, I
D
AH
O
PO
W
ER
H O
U
SE
G-401 A1
C
LE
AR
ROOF ACCESS DOOR
POTENTIAL
CONTRACTOR
SCAFFOLDING
ACCESS POINT
TO ROOF E
DURING 500 KV
OUTAGE
BALCONY
GOVERNMENT HAZARDOUS
WASTE STORAGE
POWERHOUSE
LOBBY ENTRANCE
ERECTION BAY BAY #1 BAY #2 BAY #3
POWERHOUSE
CONTRACTOR
LAYDOWN
AREA
CONTRACTOR TRAILER
GUARD
SHACK
SECURITY
GATE
CONTRACTOR PERSONAL
VEHICLE PARKING
20' - 0"
SHOP
BUILDINGS
OPEN TO BELOW
CLEARWATER RIVER
EMERGENCY DIESEL
GENERATOR AREASPARE TRANSFORMER
SHED
US Army Corps of Engineers ®
SHEET ID
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
D S:
D
IR
O O
TS
PD
: A D
O
BE
P R
IN
T
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N U
M
BE
R
R :\d
6\
D W
A5
6_
SA
M
E_ N
EW
R
O O
F_
.rv t 9/
/2
1:
:2
PM
G-101
W
AL
LA
W
AL
LA
D
IS
TR
IC
T
N
R
D A
VE
W
AL
LA
W
AL
LA
, W
A
M . F
LA
N
AG
AN
M . F
LA
N
AG
AN
JO
SH
U A
K.
T
AP
P, R .A
M . Z
AN
G
ER
N O
VE
M
BE
R
W
2E F2
7B A0
FI
N
AL
D W
G -1
-0 -1
/5
SI
TE
P
LA
N
D W
O R
SH
AK
D
AM
A N
D R
ES
ER
VO
IR
R O
O F
R
EP
LA
C
EM
EN
T
N O
R
TH
F O
R K
C
LE
AR
W
AT
ER
R
IV
ER
, I
D
AH
O
PO
W
ER
H O
U
SE
0 25' 50' 100'SCALE: 1" = 50'-0"A1 POWERHOUSE SITE PLAN
GENERAL NOTES
1. SEE SECTION 01 55 10.00 28 FOR CONTRACTOR WORK, ACCESS AND STORAGE
AREAS.
2. THE PROJECT SITE HAS HIGH VOLTAGE ELECTRICAL EQUIPMENT AND HIGH
FREQUENCY TELECOMMUNICATIONS EQUIPMENT. SEE SHEET G-401 FOR AREAS
THAT REQUIRE A SCHEDULED CLEARANCE TO ACCESS.
3. HIGH VOLTAGE OVERHEAD POWERLINES PASS OVER THE POWERHOUSE.
CONTRACTOR MUST ACCOUNT FOR THESE IN THE CRANE PLAN SUBMITTAL.
NORTH
19' - 9 1/2"
50' - 0"
R = 27' - 0" R = 27' - 0"
R = 27' - 0"
100' - 0"
6' - 0"
6' - 0"
3 5
R = 12' - 4" R = 12' - 4"
R = 12' - 4"
ROOF A
ROOF B
ROOF C
ROOF
D
ROOF E
LEGEND
500 KV ELECTRICAL HAZARD AREA
115 KV ELECTRICAL HAZARD AREA
500 KV & 115 KV ELECTRICAL HAZARD OVERLAP AREA
TELECOMMUNICATION ANTENNA HAZARD AREA
MICROWAVE RADIO 1 TRANSMISSION AREA
MICROWAVE RADIO 2 TRANSMISSION AREA
US Army Corps of Engineers ®
SHEET ID
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
D S:
D
IR
O O
TS
PD
: A D
O
BE
P R
IN
T
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N U
M
BE
R
R :\d
6\
D W
A5
6_
SA
M
E_ N
EW
R
O O
F_
.rv t 9/
/2
1:
:2
PM
G-401
W
AL
LA
W
AL
LA
D
IS
TR
IC
T
N
R
D A
VE
W
AL
LA
W
AL
LA
, W
A
M . F
LA
N
AG
AN
M . F
LA
N
AG
AN
JO
SH
U A
K.
T
AP
P, R .A
M . Z
AN
G
ER
N O
VE
M
BE
R
W
2E F2
7B A0
FI
N
AL
D W
G -1
-0 -1
/5
H
AZ
AR
D
O U
S
AR
EA
S
EQ
U
IP
M
EN
T
PL
AN
D W
O R
SH
AK
D
AM
A N
D R
ES
ER
VO
IR
R O
O F
R
EP
LA
C
EM
EN
T
N O
R
TH
F O
R K
C
LE
AR
W
AT
ER
R
IV
ER
, I
D
AH
O
PO
W
ER
H O
U
SE
SCALE: 3/32" = 1'-0"G-101
A1 A1 HAZARDOUS EQUIPMENT AREA PLAN
0 4' 8' 16' 24'
NORTH
GENERAL NOTES
1. COORDINATE ALL OUTAGE REQUESTS WITH THE CONTRACTING OFFICER
REPRESENTATIVE.
2. SEE ADDITIONAL INFORMATION IN SECTION 01 14 00.10 28.
3. EM 385-1-1 REQUIRED ELECTRICAL HAZARD CLEARANCE RADII SHOWN ARE
APPROXIMATE.
KEYNOTES
1. MICROWAVE RADIO HAZARD ZONE. NO OUTAGE IS REQUIRED TO ENTER THIS
AREA.
2. ROOF A 115 KV HAZARD ZONE. AN OUTAGE IS REQUIRED TO ENTER THIS AREA.
3. ROOF E 115 KV HAZARD ZONE. AN OUTAGE IS REQUIRED TO ENTER THIS AREA.
4. ROOF A 500 KV HAZARD ZONE. AN OUTAGE IS REQUIRED TO ENTER THIS AREA.
5. ROOF E 500 KV HAZARD ZONE. AN OUTAGE IS REQUIRED TO ENTER THIS AREA.
6. ROOF A HIGH FREQUENCY TELECOMMUNICATION ANTENNA HAZARD ZONE. AN
OUTAGE IS REQUIRED TO ENTER THIS AREA.
BALCONY
KEYNOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
GUARD SHACK AND SECURITY GATE
OVERHEAD POWERLINES
MICROWAVE DISHES
SPARE TRANSFORMER AND CONCRETE CURB
POWERHOUSE LOBBY ENTRANCE
ROOF A
ROOF B
ROOF C
ROOF D
ROOF E
BALCONY
SKELETON BAYS
TAILRACE DECK
ROOF ACCESS DOOR
LIVE TRANSFORMERS AND CONTAINMENT
US Army Corps of Engineers ®
SHEET ID
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
D S:
D
IR
O O
TS
PD
: A D
O
BE
P R
IN
T
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N U
M
BE
R
R :\d
6\
D W
A5
6_
SA
M
E_ N
EW
R
O O
F_
.rv t 9/
/2
1:
:2
PM
G-901
W
AL
LA
W
AL
LA
D
IS
TR
IC
T
N
R
D A
VE
W
AL
LA
W
AL
LA
, W
A
M . F
LA
N
AG
AN
M . F
LA
N
AG
AN
JO
SH
U A
K.
T
AP
P, R .A
M . Z
AN
G
ER
N O
VE
M
BE
R
W
2E F2
7B A0
FI
N
AL
D W
G -1
-0 -1
/5
SI
TE
P H
O
TO
D W
O R
SH
AK
D
AM
A N
D R
ES
ER
VO
IR
R O
O F
R
EP
LA
C
EM
EN
T
N O
R
TH
F O
R K
C
LE
AR
W
AT
ER
R
IV
ER
, I
D
AH
O
PO
W
ER
H O
U
NTSSCALE:A1 PHOTO - DWORSHAK ROOF SITE
1.
A.
B.
C.
D.
2.
A.
B.
1.
2.
C.
1.
2.
D.
1.
2.
E.
1.
2.
3.
A.
4.
3.
A.
1.
2.
B.
1.
C.
D.
E.
THE PROJECT SHALL BE DESIGNED PRIMARILY UNDER UFC CRITERIA AND
INDUSTRY STANDARDS AS MODIFIED BY THE UFC. STRUCTURAL DESIGN,
FABRICATION, AND CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE
GOVERNING CODE EDITIONS PER UFC 1-200-01, INCLUDING BUT NOT LIMITED TO:
ACI 318-19 BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE
AISC MANUAL OF STEEL CONSTRUCTION (16th EDITION)
ASCE 7-22 AMERICAN SOCIETY OF CIVIL ENGINEERS MINIMUM DESIGN
LOADS AND ASSOCIATED CRITERIA FOR BUILDINGS AND OTHER
STRUCTURES
INTERNATIONAL BUILDING CODE (IBC) 2024
DESIGN LOADS:
RISK CATEGORY = III
DEAD LOADS:
STAIR STEEL: SELF WEIGHT OF MEMBERS
STAIR GRATING SYSTEM: 14 PSF
LIVE LOADS:
STAIRS & EXITS = 100 PSF
ROOF LIVE LOAD = 20 PSF, 300 LB CONCENTRATED LOAD
NONCONCURRENT WITH UNIFORM LIVE LOAD
SNOW LOAD:
GROUND SNOW LOAD = 63 PSF
FLAT ROOF SNOW LOAD = 50 PSF
WIND LOAD:
DESIGN WIND SPEED = 110 MPH 3-SECOND GUST
EXPOSURE CATEGORY = C
BUILDING CONDITION = ENCLOSED
GCpi = +/-0.18 TOPOGRAPHIC FACTOR, Kzt = 1.22
SEISMIC LOAD:
MAXIMUM CONSIDERED EARTHQUAKE SPECTRAL RESPONSE
ACCELERATIONS:
Ss = 0.31g S1 = 0.09g
DESIGN EARTHQUAKE SPECTRAL RESPONSE ACCELERATIONS:
SDS = 0.3g
SITE CLASS = D
SEISMIC DESIGN CATEGORY = C
IMPORTANCE FACTOR = 1.25
DESIGN STANDARDS & LOADS
1.
2.
3.
4.
5.
6.
7.
8.
THESE NOTES, AND OTHER DRAWING DETAILS AND NOTES, CONTAINED WITHIN,
ARE PROVIDED TO MEET SPECIFIC REQUIREMENTS AND TO SUPPLEMENT THE
CONTRACT SPECIFICATIONS. THESE DRAWINGS NEITHER REPLACE NOR
OVERRIDE THE PROVISIONS AND REQUIREMENTS OF THE CONTRACT
SPECIFICATIONS.
COORDINATE ALL STRUCTURAL WORK WITH WORK SHOWN ON ALL OTHER
DISCIPLINE DRAWINGS. NOTIFY CONTRACTING OFFICER OF DISCREPANCIES.
CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED
STRUCTURE. CONTRACTOR IS RESPONSIBLE FOR ALL MEANS AND METHODS
OF CONSTRUCTION INCLUDING, BUT NOT LIMITED TO, SHORING, TEMPORARY
CONSTRUCTION LOADS, AND TEMPORARY BRACING. UNDERTAKE ALL
NECESSARY MEASURES TO ENSURE SAFETY OF ALL PERSONS AND
STRUCTURES AT THE SITE AND ADJACENT TO THE SITE. VISITS TO THE SITE BY
THE CONTRACTING OFFICER'S REPRESENTATIVE SHALL NOT RELIEVE THE
CONTRACTOR OF SUCH RESPONSIBILITY.
ALL PRODUCTS SHALL BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURERS' WRITTEN INSTRUCTIONS AND RECOMMENDATIONS, UNLESS
NOTED OTHERWISE.
ELEVATION DATUM PER SUPPLEMENTARY DRAWINGS. NOTIFY THE
CONTRACTING OFFICER OF ANY DISCREPANCIES BETWEEN THE STRUCTURAL
DRAWINGS AND OTHER DISCIPLINE DRAWING ELEVATIONS.
USE STRUCTURAL DRAWINGS IN CONJUNCTION WITH ALL DRAWINGS OF OTHER
DISCIPLINES, COORDINATE WORK OF ALL TRADES. THE CONTRACTOR IS
RESPONSIBLE FOR DETERMINING SUCH REQUIREMENTS PRIOR TO
FABRICATION OR ERECTION OF THE STRUCTURE. PENETRATIONS THROUGH
THE STRUCTURE ARE NOT PERMITTED WITHOUT WRITTEN APPROVAL BY THE
CONTRACTING OFFICER.
THE STRUCTURAL DRAWINGS GOVERN THE WORK FOR STRUCTURAL
FEATURES, UNLESS OTHERWISE NOTED, DIMENSIONS SHOWN ON PLANS,
SECTIONS, AND DETAILS ARE TO GOVERN THE STRUCTURAL WORK.
REPRODUCTION OF CONTRACT DRAWINGS SHALL NOT BE USED AS SHOP
DRAWINGS UNDER ANY CIRCUMSTANCE.
GENERAL NOTES
1.
2.
A.
B.
C.
D.
WORK IS SUBJECT TO SPECIAL INSPECTIONS AND TESTING AS DESCRIBED IN
CHAPTER 17 OF THE INTERNATIONAL BUILDING CODE AND FOUND IN THE
SPECIFICATIONS.
MECHANICAL AND ELECTRICAL COMPONENTS:
PERIODIC SPECIAL INSPECTION DURING ANCHORING OF ELECTRICAL
EQUIPMENT FOR EMERGENCY OR STANDBY POWER SYSTEMS
PERIODIC SPECIAL INSPECTION DURING INSTALLATION OF PIPING
SYSTEMS CARRYING FLAMMABLE, COMBUSTIBLE OR HIGHLY TOXIC
CONTENTS AND THEIR ASSOCIATED MECHANICAL UNITS
PERIODIC SPECIAL INSPECTION DURING INSTALLATION OF VIBRATON
ISOLATION SYSTEMS WHERE CONSTUCTION DOCUMENTS REQUIRE A
NOMINAL CLEARANCE OF 1/4 INCH OR LESS BETWEEN THE EQUIPMENT
SUPPORT FRAME AND RESTRAINT
MECHANICAL AND ELECTRICAL EQUIPMENT MANUFACTURER SHALL
TEST OR ANALYZE THE COMPONENT AND ITS MOUNTING SYSTEM OR
ANCHORAGE AND SUBMIT CERTIFICATE OF COMPLIANCE PER IBC
SPECIAL INSPECTION & TESTING
STRUCTURAL STEEL
1.
2.
3.
4.
A.
5.
A.
6.
A.
7.
A.
8.
A.
9.
A.
10.
A.
1.
11.
12.
A.
B.
13.
A.
B.
C.
D.
1.
2.
3.
14.
15.
A.
B.
16.
17.
18.
19.
20.
A.
B.
C.
D.
E.
STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED IN ACCORDANCE
WITH AISC STEEL CONSTRUCTION MANUAL.
TEMPORARY ERECTION BRACING SHALL BE DESIGNED AND PROVIDED BY THE
CONTRACTOR AS REQUIRED AND SHALL NOT BE REMOVED UNTIL ALL
PERMANENT LATERAL-LOAD-RESISTING ELEMENTS AND CONNECTIONS ARE
COMPLETELY INSTALLED.
ALL STRUCTURAL STEEL SHALL BE HOT-DIPPED GALVANIZED.
WIDE FLANGE SHAPES AND TEES:
ASTM A992, Fy = 50 KSI
PLATES AND ANGLES:
ASTM A572, GR. 50, Fy = 50 KSI
OTHER SHAPES AND THREADED RODS:
ASTM A572, GR. 50, Fy = 50 KSI, UNLESS NOTED OTHERWISE
SQUARE AND RECTANGULAR HOLLOW STRUCTURAL SECTIONS:
ASTM A500 GRADE C, Fy = 50 KSI
ROUND HOLLOW STRUCTURAL SECTIONS:
ASTM A500 GRADE C, Fy = 46 KSI
PIPE:
ASTM A53 TYPE E OR S, GRADE B, Fy = 35 KSI
BOLTS:
3/4"Ø ASTM F3125, TYPE N, TYPICAL UNLESS NOTED OTHERWISE
FRAMING CONNECTIONS:
PRETENSIONED JOINTS WITH STANDARD HOLES, UNLESS NOTED
OTHERWISE
WELD IN ACCORDANCE WITH AWS D1.1 USING E70 ELECTRODE WITH LOW
HYDROGEN.
ALL DOUBLE ANGLE MEMBERS SHALL HAVE SPACER PLATES TO COMPLY WITH
AISC 360 PARAGRAPH E6.2:
THICKNESS TO MATCH END GUSSET PLATES
CONNECT TO BACK-TO-BACK LEGS OF ANGLES USING ONE 3/4"Ø BOLT,
MIN
ANCHOR BOLTS:
ASTM F1554 GRADE 55 UNLESS SPECIFICALLY NOTED AS GRADE 105
LOCATE ANCHOR BOLTS ACCURATELY, SET WITH TEMPLATES, AND
SECURELY HOLD IN POSITION WHILE PLACING CONCRETE
PROTECT IN-PLACE ANCHOR BOLTS FROM CONSTRUCTION ACTIVITY
THE FOLLOWING ARE PROHIBITED WITHOUT THE EXPLICIT PRIOR
APPROVAL IN WRITING OF THE CONTRACTING OFFICER:
INSERTING ANCHOR BOLTS INTO FRESH OR PARTIALLY
HARDENED CONCRETE
SUBSTITUTING POST-INSTALLED ANCHORS WHERE EMBEDDED
ANCHOR BOLTS ARE INDICATED
REPAIRING, REPLACING, OR MODIFYING INSTALLED ANCHOR
BOLTS
NONSHRINK GROUT MINIMUM COMPRESSIVE STRENGTH = 5,000 PSI
STEEL USING COMPLETE JOINT PENETRATION GROOVE WELDS THAT FUSE
THROUGH THE THICKNESS OF THE FLANGE OR WEB SHALL HAVE A MINIMUM
CHARPY V-NOTCH IMPACT TESTING VALUE AS FOLLOWS:
HOT-ROLLED SHAPES WITH A FLANGE THICKNESS EXCEEDING 2 INCHES
20 FT-LB @ 70 DEGREE FARHENHEIT
TESTING TO BE IN ACCORDANCE WITH ASTM A6, SUPPLEMENTARY
REQUIREMENT S30, CHARPY V-NOTCH IMPACT TEST FOR STRUCTURAL
SHAPES - ALTERNATE CORE LOCATION
REFER TO ARCHITECTURAL DRAWINGS FOR MISCELLANEOUS STEEL NOT
INCLUDED IN STRUCTURAL DRAWINGS.
INCLUDE MISCELLANEOUS STEELS IN SHOP DRAWINGS FOR REVIEW AND
APPROVAL.
PROTECT ROOF DURING ALL FIELD WELDING.
ALL EXTERIOR STEEL SHALL BE GALVANIZED.
OPENINGS AND SEALING:
FABRICATOR SHALL PROVIDE VENT AND DRAIN HOLES IN HOLLOW AND
ENCLOSED MEMBERS AS REQUIRED FOR HOT-DIP GALVANIZING PER
ASTM A385. LOCATE AT CONCEALED OR INCONSPICUOUS LOCATIONS
WHERE PRACTICABLE. DRILL OR REAM HOLES TO A UNIFORM DIAMETER.
AFTER GALVANIZING, SEAL ALL EXPOSED OPENINGS INTO HOLLOW
MEMBERS — INCLUDING GALVANIZING VENT AND DRAIN HOLES, UNUSED
BOLT HOLES, AND HOLES MADE DURING FABRICATION, MODIFICATION,
OR ERECTION — WITH TAPERED SOLID ZINC DRIVE-IN PLUGS, DRIVEN
TIGHT AND FILED FLUSH.
CLOSE ALL OPEN ENDS OF PIPE AND HOLLOW STRUCTURAL SECTIONS
WITH CAPS WELDED PRIOR TO GALVANIZING OR WITH GALVANIZED END
CAPS.
REPAIR GALVANIZED COATING AT PLUGS, CAPS, AND FIELD
MODIFICATIONS PER ASTM A780.
ALL OPENINGS INTO HOLLOW STEEL MEMBERS SHALL BE SEALED TO
PREVENT INSECT INTRUSION AND NESTING.
1.
2.
A.
B.
C.
D.
E.
F.
G.
3.
A.
1.
2.
3.
4.
5.
4.
A.
1.
2.
3.
4.
B.
1.
2.
3.
4.
C.
INSTALLATION SHALL BE IN CONFORMANCE WITH MANUFACTURER'S PRINTED
LITERATURE, AND AS INDICATED IN THE DRAWINGS.
ADHESIVE ANCHORS:
ADHESIVE SHALL CONSIST OF A TWO COMPONENT STRUCTURAL GRADE
INJECTION MATERIAL CONFORMING TO ASTM C881
DOWELS SHALL CONFORM TO ASTM A615, GRADE 60, DEFORMED, TYP UNO
THREADED ROD ANCHORS SHALL CONFORM TO GALVANIZED ASTM F1554,
GR. 55, TYP UNO
ALL ANCHORS SHALL BE APPROVED FOR USE WITH THE GOVERNING
EDITION OF THE IBC
DRILL HOLES WITH A PERCUSSION-TYPE DRILL AND REMOVE ALL
CUTTINGS FROM THE HOLES
DO NOT CORE DRILL, DO NOT CUT REINFORCING
DRILL HOLES STRAIGHT AND TRUE AT RIGHT ANGLES TO THE FACE, UNO
MECHANICAL ANCHORS:
MECHANICAL ANCHORS CALLED OUT SHALL BE A TORQUE-CONTROLLED
MECHANICAL EXPANSION ANCHOR SHALL CONSIST OF A STUD (ANCHOR
BODY) WITH A WEDGE EXPANSION ELEMENT:
MINIMUM ANCHOR YIELD STRENGTH = 92,000 PSI
MINIMUM ANCHOR ULTIMATE STRENGTH = 115,000 PSI
MINIMUM DIAMETER AND LENGTH ARE PER PLAN, SCHEDULE OR
DETAILS
REQUIRED INSTALLATION TORQUE IS PER SELECTED
MANUFACTURER'S EVALUATION REPORT
ALL OTHER INSTALLATION PROCEDURES SHALL BE
MANUFACTURER REQUIREMENTS
POWER ACTUATED FASTENERS:
PAF TO CONCRETE:
MINIMUM DIAMETER = 0.157"
MINIMUM EMBEDMENT LENGTH = 1 1/4"
MINIMUM EDGE DISTANCE = 3"
MINIMUM SPACING = 4"
PAF TO STEEL:
MINIMUM DIAMETER = 0.157"
MINIMUM EMBEDMENT LENGTH = VARIES, FASTENER SHALL
PENETRATE THROUGH THE STEEL BASE MATERIAL
MINIMUM EDGE DISTANCE = 1/2"
MINIMUM SPACING = 1"
SUBMIT SUBSTITUTION REQUEST FOR THE USE OF POWER ACTUATED
FASTENERS OR SCREWS WITH MANUFACTURER LITERATURE OR
INTERNATIONAL CODE COUNCIL EVALUATION SERVICE REPORTS
SHOWING A LARGER CAPACITY THAN WHAT IS SHOWN IN THE CONTRACT
DOCUMENTS FOR EACH CONDITION THE SUBSTITUTION REQUESTED
POST INSTALLED ANCHORS
CONCRETE REHABILITATION
1.
2.
3.
4.
A.
5.
A.
B.
C.
D.
E.
F.
CHIP OUT ALL SPALLED, CRACKED, OR DELMINATED CONCRETE IDENTIFIED IN
THE DEMOLITION DRAWINGS OR WHERE NEW FEATURES OF WORK ARE
DETAILED.
SAND BLAST AND CLEAN ALL EXPOSED REINFORCING
FIELD PRIME ALL REINFORCING AND STEEL EXPOSED TO WEATHER
FIELD GALVANIZE WITH GALVANIZED COATING ALL STEEL THAT IS GALVANIZED
OR PERMANENTLY EXPOSED TO WEATHER
COATING SHALL BE ASTM A780 ZINC RICH PAINT
FIELD VERFICATION OF DAMAGED OR SPALLED CONCRETE SHALL INCLUDE AT
MINIMUM THE FOLLOWING STEPS:
REMOVAL OF DAMAGED/SPALLED CONCRETE
CLEAN AREA, INCLUDING STEEL AND CONCRETE FEATURES
INSPECT STEEL FOR ANY SURFACE RUST OR DETERIORATION, SAND
BLAST AND CLEAN AS REQUIRED PER SPECIFICATIONS
SAW CUT SMOOTH AND STRAIGHT EDGES AROUND DAMAGED
CONCRETE AREA
SET ALL POST-INSTALLED ANCHORS, REBAR WITH ADHESIVE INTO
SOUND CONCRETE, FIELD PRIME OR GALVANIZE STEEL COMPONENTS
FORM AREA AND POUR CONCRETE OR GROUT REPAIR AS SPECIFIED OR
DETAILED IN DRAWINGS
CAST-IN-PLACE CONCRETE
1.
2.
3.
4.
5.
6.
7.
8.
A.
B.
C.
D.
9.
A.
B.
C.
D.
10.
A.
11.
A.
B.
C.
12.
A.
13.
A.
1.
B.
1.
2.
3.
C.
1.
2.
3.
REINFORCED CONCRETE WORK IS TO BE IN ACCORDANCE WITH THE AMERICAN
CONCRETE INSTITUTE 318 BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE.
MIXING, TRANSPORTING, PLACING, AND TESTING OF CONCRETE IS TO BE DONE
IN ACCORDANCE WITH ACI 301, UNO.
DETAIL AND PLACE ALL REINFORCEMENT IN ACCORDANCE WITH ACI SP-66, ACI
301, ACI 318, AND CRSI MANUAL OF STANDARD PRACTICE.
REINFORCEMENT IS TO BE SECURELY HELD IN PLACE WHILE PLACING
CONCRETE. IF REQUIRED, ADDITIONAL BARS, STIRRUPS, OR CHAIRS SHALL BE
PROVIDED BY THE CONTRACTOR TO FURNISH SUPPORT TO KEEP
REINFORCEMENT IN PLACE PER DESIGN.
CONTINUOUS REINFORCING BARS TO BE BENT AND LAPPED AT CORNERS AND
INTERSECTIONS. LAP SPLICES TO BE PER SCHEDULE OR DETAILS. HOOKED
BARS TO HAVE STANDARD ACI HOOKS, UNO.
CONCRETE TO BE CURED BY METHOD COMPATIBLE WITH FINAL FINISH.
EXPANSION JOINT FILLER SHALL BE PER SPECIFICATIONS. EXPANSION AND
CONTRACTION JOINT SEALANT SHALL BE APPLIED AS RECOMMENDED BY THE
MANUFACTURER OF THE SEALANT.
FORMWORK:
CONTRACTOR IS RESPONSIBLE FOR DESIGN, ENGINEERING,
STRUCTURAL ADEQUACY, AND CONSTRUCTION OF ALL CONCRETE
FORMWORK IN ACCORDANCE WITH THE CONTRACT SPECIFICATIONS
COORDINATE ALL CONCRETE WORK WITH THE PLACEMENT OF PIPING,
INSERTS, FLOOR DRAINS, AND OTHER EMBEDDED ITEMS INDICATED ON
THE CONTRACT DRAWINGS OR IN THE CONTRACT SPECIFICATIONS
ALL NEW OR EXISTING PIPING OR UTILITIES PASSING THROUGH NEW
CONCRETE SHALL BE SLEEVED 1/2" CLEAR ALL AROUND, UNLESS
NOTED OTHERWISE. SEE OTHER DISCIPLINE DRAWINGS FOR SLEEVE
DETAILS. PROVIDE MEASURES TO ENSURE THAT SLEEVES REMAIN
FREE OF DEBRIS AND WATER DURING CONSTRUCTION
PROVIDE 3/4" CHAMFER STRIPS ON ALL EDGES OF EXPOSED
CONCRETE, UNLESS NOTED OTHERWISE
CONCRETE EXPOSURE CATEGORIES AND CLASSES PER ACI 318:
FREEZING AND THAWING = F2
SULFATE = S1
CONTACT WITH WATER = W1
CORROSION PROTECTION OF REINFORCEMENT = C1
CAST-IN-PLACE CONCRETE:
MINIMUM COMPRESSIVE STRENGTH f'c = 4,500 PSI, NORMALWEIGHT
DEFORMED REINFORCEMENT:
CONFORM TO ASTM A615, GRADE 60 UNO
CONFORM TO ASTM A706, GRADE 60 (WELDABLE)
ALL CONCRETE SHALL BE REINFORCED UNLESS SPECIFICALLY MARKED
"NOT REINFORCED" OR "UNREINFORCED"
WELDED WIRE FABRIC:
CONFORM TO ASTM A185, WELDABLE STEEL WIRE FABRIC SHEET TYPE
MINIMUM CONCRETE CLEAR COVER OVER REINFORCEMENT SHALL BE AS
FOLLOWS, UNO:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH:
ALL REINFORCING = 3"
CONCRETE EXPOSED TO EARTH OR WEATHER:
#6 THROUGH #11 BARS = 2"
#5 AND SMALLER BARS = 1 1/2"
WELDED WIRE FABRIC = 1 1/2"
CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH THE
GROUND:
SLABS AND WALLS (#14 AND #18 BARS) = 1 1/2"
SLABS AND WALLS (ALL OTHER BARS) = 3/4"
BEAMS AND COLUMNS, PRIMARY REINFORCEMENT, TIES,
STIRRUPS, SPIRALS = 1 1/2"
#3
LAP SPLICE SCHEDULE
REBAR
SIZE
LOCATION
OR TYPE
F'c = 3,000PSI
LENGTH (IN)
F'c = 4,000PSI
LENGTH (IN)
F'c = 5,000PSI
LENGTH (IN)
TOP
OTHER
HOOKED
#4
TOP
OTHER
HOOKED
#5
TOP
OTHER
HOOKED
#6
TOP
OTHER
HOOKED
#7
TOP
OTHER
HOOKED
#8
TOP
OTHER
HOOKED
#9
TOP
OTHER
HOOKED
#10
TOP
OTHER
HOOKED
#11
TOP
OTHER
HOOKED
1.
2.
3.
4.
NOTES:
TOP BAR CONDITION OCCURS WHERE THERE IS MORE THAN 12 INCHES OF
FRESH CONCRTE PLACED BELOW THE SPLICE.
FOR F'c VALUES BETWEEN TABLULATED VALUES SHOWN ABOVE, USE THE LOWER F'c SPLICE LENGTH.
FOR LIGHTWEIGHT CONCRETE, MULTIPLY VALUE SHOWN BY 1.3.
TABLE ASSUMES NON-STAGGERED SPLICES OF REBAR. SPLICE LENGTHS
MAY BE REDUCED BY 30% AND ROUNDED UP TO THE NEAREST INCH
PROVIDED AT LEAST 50% OF SPLICES AT ANY SECTION ARE STAGGERED
BY AT LEAST THE DEVELOPMENT LENGTH VALUE BETWEEN EVERY OTHER
REBAR PER ACI 314 T10.7.5.2.2. STAGGERING MUST BE CLEARLY SHOWN
AND ANNOTATED IN THE REBAR SHOP DRAWINGS.
F'c = 6,000PSI
LENGTH (IN)
FRP GUARDRAIL SYSTEM
1.
2.
A.
B.
C.
D.
3.
A.
B.
C.
D.
E.
F.
G.
4.
A.
B.
C.
D.
E.
F.
G.
1.
2.
H.
1.
2.
3.
5.
A.
B.
C.
D.
ALL FRP GUARDRAIL WORK SHALL CONFORM TO UFGS-06 82 14, IBC 2024, ASCE
7-22, OSHA 29 CFR 1910.29, AND USACE EM 385-1-1.
GUARDRAIL AND ALL CONNECTIONS TO METAL STRINGERS SHALL BE DESIGNED
FOR THE FOLLOWING MINIMUM LOADS PER IBC 2024 §1607.9 AND ASCE 7-22 §4.5.
CONCENTRATED AND UNIFORM LOADS NEED NOT BE APPLIED
SIMULTANEOUSLY.
TOP RAIL - CONCENTRATED: 200 LBF IN ANY DIRECTION AT ANY POINT
TOP RAIL - UNIFORM: 50 LBF/LFT IN ANY DIRECTION
MID-RAIL: 50 LBF CONCENTRATED, APPLIED HORIZONTALLY
POST BASE: DESIGNED FOR FULL LOAD TRANSFER TO STEEL STRINGER
INCLUDING PRYING ACTION AND ECCENTRICITY
GEOMETRY AND DIMENSIONS
TOP RAIL HEIGHT: 42 IN. MIN ABOVE STAIR NOSING OR WALKING
SURFACE PER OSHA 29 CFR 1910.29
MID-RAIL HEIGHT: 21 IN. MIN ABOVE STAIR NOSING OR WALKING
SURFACE PER OSHA 29 CFR 1910.29
TOP RAIL DIAMETER: 1-1/4" MIN TO 2" MAX (OD) PER IBC 2024 §1014.3
MAX POST SPACING: 8 FT O.C. UNLESS JUSTIFIED BY MFR'S STAMPED
CALCULATIONS
MAX OPENING: NO OPENING BETWEEN INTERMEDIATE MEMBERS SHALL
EXCEED 19 INCHES PER OSHA 29 CFR 1910.29(b)
KICKPLATE: 4 IN. MINIMUM HEIGHT AT ALL STAIR LANDINGS PER OSHA 29
CFR 1910.23
EXPANSION JOINTS: MAX 20 FT OR PER MFR'S CERTIFIED ASTM D696
TEST DATA, WHICHEVER IS MORE STRINGENT.
FRP CONNECTION TO STEEL
ALL FASTENERS AND ANCHORS AT FRP-TO-SUBSTRATE INTERFACE
SHALL BE TYPE 316 STAINLESS STEEL. CARBON STEEL AND GALVANIZED
STEEL FASTENERS ARE NOT PERMITTED AT THIS INTERFACE.
MINIMUM TWO (2) BOLTS PER POST BASE, 1/2-IN. DIAMETER MINIMUM
PROVIDE 2-IN. O.D. MINIMUM FENDER WASHERS UNDER ALL BOLT HEADS
AND NUTS BEARING ON FRP SURFACES.
PROVIDE 1/8-IN. THICK, 60-DUROMETER NEOPRENE ISOLATION PAD
BETWEEN FRP POST BASE AND SUBSTRATE INTERFACE.
MAXIMUM FASTENER TORQUE PER MFR'S WRITTEN INSTRUCTIONS.
POWDER-ACTUATED FASTENERS SHALL NOT BE USED IN FRP MEMBERS.
FRP CONNECTION TO STEEL
FASTENERS SHALL BE TYPE 316 SS BOLTS WITH NUTS AND
DISSIMILAR METAL ISOLATION KITS.
CONNECTION SHALL BE DESIGNED FOR FULL LOAD TRANSFER
INCLUDING PRYING ACTION AND ECCENTRICITY.
FRP CONNECTION TO CONCRETE
POST-INSTALLED ANCHORS SHALL BE TYPE 316 SS WEDGE OR
ADHESIVE ANCHORS
ANCHOR EMBEDMENT DEPTH, EDGE DISTANCE, AND SPACING
SHALL SATISFY ACI 318-19
EXISTING CONCRETE COMPRESSIVE STRENGTH SHALL BE
VERIFIED PRIOR TO ANCHOR DESIGN. ASSUME f'c = 3,000 PSI
MINIMUM
OPENINGS AND SEALING:
SEAL ALL CUT ENDS AND DRILLED HOLES IN FRP MEMBERS WITH THE
RAILING MANUFACTURER'S RECOMMENDED RESIN SEALANT.
CLOSE ALL OPEN ENDS OF HOLLOW FRP RAILS AND POSTS WITH THE
MANUFACTURER'S MOLDED, UV-STABILIZED END CAPS OR POST CAPS,
BONDED OR FASTENED PER THE MANUFACTURER.
PLUG ALL UNUSED OR ABANDONED HOLES IN HOLLOW FRP MEMBERS
WITH MANUFACTURER-SUPPLIED UV-STABILIZED PLUGS, OR FILL WITH
COMPATIBLE EPOXY RESIN FINISHED FLUSH. DO NOT USE METAL DRIVE-
IN PLUGS IN FRP MEMBERS.
ALL OPENINGS INTO HOLLOW FRP MEMBERS SHALL BE SEALED TO
PREVENT INSECT INTRUSION AND NESTING.
US Army Corps of Engineers ®
SHEET ID
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
D S:
D
IR
O O
TS
PD
: A D
O
BE
P R
IN
T
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N U
M
BE
R
C :\U se rs
\g 4e ch ga i\D oc um en ts \D
W A5
6_
SA
M E_
N
EW
R O
O F_
_g ui do .a
.ig le si as
.rv t
/1
7/
1:
:4
AM
S-001
W
AL
LA
W
AL
LA
D
IS
TR
IC
T
N
R
D A
VE
W
AL
LA
W
AL
LA
, W
A
S.
O
LS
O
N
G . I
G
LE
SI
AS
JU
LI
O M
O R
EL
O
S, P
.E
J.
M
O R
EL
O
S
N O
VE
M
BE
R
W
2E F2
7B A0
FI
N
AL
D W
P- 1-
5- 1/
ST
R
U C
TU
R
AL
G
EN
ER
AL
N
O
TE
S
D W
O R
SH
AK
D
AM
A N
D R
ES
ER
VO
IR
R O
O F
R
EP
LA
C
EM
EN
T
N O
R
TH
F O
R K
C
LE
AR
W
AT
ER
R
IV
ER
, I
D
AH
O
PO
W
ER
H O
U
ROOF B
ROOF C
ROOF A
ROOF E
ROOF D
ROOF PRESSURES (PLAN)
WIND PRESSURE ZONE, TYP
R O
O F
A, T
YP
"A
/8
R O
O F
A, T
YP
A"
8'
8"
3 3
0.2 * "hs2" = 6' - 10 3/4"
0.
hs
2"
6'
/4
0.
hs
2"
/8
0.6 * "hs2" = 20' - 8 3/8"
0.
hs
2"
5'
/4
0.
hs
2"
/8
0.2 * "hs2" = 5' - 10 3/4"
0.6 * "hs2" = 17' - 8 3/8"
WALL PRESSURES (ELEVATION)
5 4 5
"A" TYP
"A" VALUES
ROOF A = 9'-4"
ROOF B = 6'-0"
ROOF C = 3'-0"
ROOF D = 3'-0"
ROOF E = 10'-5"
COMPONENT AND CLADDING PRESSURES UNFACTORED (PSF)
ROOF AREA ALL ZONE 1 ZONE 2 ZONE 3 WALL AREA ALL ZONE 4 ZONE 5
10 SF 20.11 -52.58 -86.38 -120.18 10 SF 33.80 -33.80 -67.60
20 SF 33.80 -33.80 -67.60
50 SF 30.59 -31.66 -59.05
500 SF 22.53 -26.29 -37.56
NOTES:
ROOF A IS GREATER THAN 60' TALL; ASCE 7-22 FIGURE 30.4-1 APPLIES.
ROOFS B, C, D & E ARE LESS THAN OR EQUAL TO 60' TALL; ASCE 7-22 FIGURE 30.3-3 (STEPPED ROOFS) APPLIES.
SEE STRUCTURAL CALCULATIONS FOR MORE DETAILS.
HIGH ROOF A, C, OR D
LOW ROOF B OR E
FLAT ROOF SNOW
LOAD = 50.0 PSF
DRIFT WIDTH
D R
IF
T
IN
TE
N
SI
TY
PARAPET - NO SNOW DRIFT
ROOF A, C, OR D WALL, DRIFT
APPLIES TO ALL EDGES
ROOF B = 20.5 FT
ROOF C = 24.5 FT
ROOF E = 11.0 FT
R O
O F
B
PS
F
R O
O F
C
P
SF
R O
O F
E
P
SF
NOTES:
SNOW DRIFT PROFILES AND PRESSURES SHOWN ARE
PROVIDED SOLELY FOR THE DESIGN OF THE NEW
STAIRCASE. EXISTING ROOF SNOW DRIFT LOADS AND
CAPACITIES REMAIN UNALTERED BY THIS SCOPE OF WORK.
A
B
C D
E
US Army Corps of Engineers ®
SHEET ID
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
D S:
D
IR
O O
TS
PD
: A D
O
BE
P R
IN
T
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N U
M
BE
R
C :\U se rs
\g 4e ch ga i\D oc um en ts \D
W A5
6_
SA
M E_
N
EW
R O
O F_
_g ui do .a
.ig le si as
.rv t
/1
7/
1:
:4
AM
S-002
W
AL
LA
W
AL
LA
D
IS
TR
IC
T
N
R
D A
VE
W
AL
LA
W
AL
LA
, W
A
S.
O
LS
O
N
G . I
G
LE
SI
AS
JU
LI
O M
O R
EL
O
S, P
.E
J.
M
O R
EL
O
S
N O
VE
M
BE
R
W
2E F2
7B A0
FI
N
AL
D W
P- 1-
5- 1/
ST
R
U C
TU
R
AL
L
O
AD
IN
G
D
IA
G R
AM
S
D W
O R
SH
AK
D
AM
A N
D R
ES
ER
VO
IR
R O
O F
R
EP
LA
C
EM
EN
T
N O
R
TH
F O
R K
C
LE
AR
W
AT
ER
R
IV
ER
, I
D
AH
O
PO
W
ER
H O
U
SE
SCALE: 3/32" = 1'-0"A1 WIND LOADING - C&C
GENERAL NOTES
1. WIND LOADING IS UNFACTORED COMPONENTS AND CLADDING FOR THE AREAS
LISTED
2. BUILDING STEPS SHOWN, SEE ARCH AND ELEVATIONS FOR MORE INFORMATION
3. SNOW DRIFT LOAD APPLIES ONLY TO UNBALANCED FLAT ROOF SNOW LOAD
CONDITIONS
4. CANOPY AROUND ROOF B NOT SHOWN
0 4' 8' 16'
NTSSCALE:L1 SNOW DRIFT
= DEMO GUARD RAIL FEATURE, SEE DIMENSIONS
FOR LENGTHS, ALL OTHER EXISTING FIXTURES AND
CONC PILLARS TO REMAIN
ROOF B
ROOF C
ROOF A
ROOF E
ROOF D
DEMO ROOF LADDERS
231' - 4 1/4" ROOF A - DEMO GUARD RAIL ALL SIDES
R
O O
F C
B O
TH
E
N D
S
" D
EM
O G
U
AR
D R
AI
L
DEMO GUARD RAIL
25' - 6 1/4" ROOF C
39' - 11 3/8" ROOF E - DEMO GUARD RAIL
D
EM
O G
U
AR
D R
AI
L
/4 " R
O O
F E
D
EM
O G
U
AR
D R
AI
L
/8 " R
O O
F D
/8 " R
O O
F A
- D
EM
O G
U
AR
D R
AI
L
AL
L
SI
D
ES
G16
SD101
GROUT ABANDONED REFRIGERANT
LINE PENETRATIONS FULL DEPTH
WITH NON-SHRINK GROUT AT
REMOVED HVAC CONDENSER UNIT.
A16
SD101
1'
2"
1' - 6"
2'
7"
17' - 0"
CORE DRILL OR SAW CUT EXIST
CONC ROOF DECK FOR NEW DUCT
OPENING. CONTRACTOR TO VFY IN
FIELD EXACT DIMS WITH MECH
AND ARCHITECTURAL DRAWINGS
PRIOR TO DEMOLITION.
EL 1060.25
1060' - 3"
EL 1074.33
1074' - 4"
DEMO LADDER
DEMO GUARDRAIL
DEMO 8" OF
PARAPET AT STAIR
TOP LANDING
ROOF C
ROOF A
EL 1060.25
1060' - 3"
EL 1039
1039' - 0"
EL 1045.43
1045' - 5 5/32"
DEMO GUARDRAIL
DEMO 8" OF PARAPET
AT STAIR TOP LANDING
ROOF C
ROOF B
3' - 0" 6"
8"
ROOF A
WALL
A
B
C D
E
US Army Corps of Engineers ®
SHEET ID
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
D S:
D
IR
O O
TS
PD
: A D
O
BE
P R
IN
T
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N U
M
BE
R
C :\U se rs
\g 4e ch ga i\D oc um en ts \D
W A5
6_
SA
M E_
N
EW
R O
O F_
_g ui do .a
.ig le si as
.rv t
/1
7/
1:
:4
AM
SD101
W
AL
LA
W
AL
LA
D
IS
TR
IC
T
N
R
D A
VE
W
AL
LA
W
AL
LA
, W
A
S.
O
LS
O
N
G . I
G
LE
SI
AS
JU
LI
O M
O R
EL
O
S, P
.E
J.
M
O R
EL
O
S
N O
VE
M
BE
R
W
2E F2
7B A0
FI
N
AL
D W
P- 1-
5- 1/
ST
R
U C
TU
R
AL
D
EM
O
LI
TI
O N
D W
O R
SH
AK
D
AM
A N
D R
ES
ER
VO
IR
R O
O F
R
EP
LA
C
EM
EN
T
N O
R
TH
F O
R K
C
LE
AR
W
AT
ER
R
IV
ER
, I
D
AH
O
PO
W
ER
H O
U
SE
SCALE: 3/32" = 1'-0"A1 STRUCTURAL DEMOLITION PLAN
GENERAL NOTES
1. SEE ARCH FOR INFORMATION NOT SHOWN IN THE DEMO PLAN
2. CONTRACTOR TO PATCH ALL REMOVED CONCRETE ANCHOR LOCATIONS
3. CONTRACTOR TO REMOVE/REPAIR SPALLED CONC
NORTH
0 4' 8' 16' 24'
SCALE: 1/4" = 1'-0"SD101
A1 G16 ROOF A WALL DEMO
0 2' 4' 8'SCALE: 1/4" = 1'-0"SD101
A1 A16 ROOF C WALL DEMO
0 2' 4' 8'
NEW STAIR FROM
ROOF B TO ROOF C
NEW STAIR FROM
ROOF C TO ROOF A
ROOF A
DAM EQUIPMENT NOT SHOWN ON ROOF PLAN, TYP
HVAC FAN
ROOF B
ROOF C
ROOF E
ROOF D
S-112 A5
S-110 A1
S-111 A1
A
B
C D
E
US Army Corps of Engineers ®
SHEET ID
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
D S:
D
IR
O O
TS
PD
: A D
O
BE
P R
IN
T
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N U
M
BE
R
C :\U se rs
\g 4e ch ga i\D oc um en ts \D
W A5
6_
SA
M E_
N
EW
R O
O F_
_g ui do .a
.ig le si as
.rv t
/1
7/
1:
:4
AM
S-101
W
AL
LA
W
AL
LA
D
IS
TR
IC
T
N
R
D A
VE
W
AL
LA
W
AL
LA
, W
A
S.
O
LS
O
N
G . I
G
LE
SI
AS
JU
LI
O M
O R
EL
O
S, P
.E
J.
M
O R
EL
O
S
N O
VE
M
BE
R
W
2E F2
7B A0
FI
N
AL
D W
P- 1-
5- 1/
R O
O F
PL
AN
D W
O R
SH
AK
D
AM
A N
D R
ES
ER
VO
IR
R O
O F
R
EP
LA
C
EM
EN
T
N O
R
TH
F O
R K
C
LE
AR
W
AT
ER
R
IV
ER
, I
D
AH
O
PO
W
ER
H O
U
SE
SCALE: 3/32" = 1'-0"A1 OVERALL ROOF PLAN
0 4' 8' 16' 24'
NEW ROOF A TO C STAIR
ROOF A
FACE MOUNTED FRP GUARD RAIL
ALONG ROOF A, CONTINUOUS
ALONG SIDE, TYP
NO FACE MOUNTED FRP GUARDRAIL IN THIS AREA, SEE ARCH
33' - 5 1/8"
STOP FRP GUARD RAIL AT CONCRETE COLUMN FEATURE,
TYP WHERE OCCURS. MAX 4" CLEAR OPENING BETWEEN
END OF RAILING AND ADJACENT SURFACE, TYP.
ROOF C
A1
S-513
TYP
A5 S-513
A1 S-513
A9 S-513
EPDM WALKWAY
PAD, TYP
S-110 L1
A
B
C D
E
54+51
E43+92.5
A6 S-511
_____________________________________________________________ A13 S-511
A1 S-301
G
AL
V
ST
EE
L
G R
AT
IN
G
C12X20.7 STRINGER
DIAGONAL BRACE
BELOW STRINGER
(REF. K6/S-512) (TYP)
C12X20.7 STRINGER
W 6X
W 6X
C
X2 0.
C
X2 0.
C12X20.7
L6X4X3/8
C12X20.7
3' - 6"
3' - 11 1/8"
2' - 0"
H1 S-514
3'
0" 1'
1/ 2"
SHEAR TAB
(SIMILAR TO
DETAIL A7/S-512)
STAIR TO TOP LANDING
CONNECTION (SEE
DETAIL A7/S-512)3' - 0 7/8" US Army Corps of Engineers ®
SHEET ID
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
D S:
D
IR
O O
TS
PD
: A D
O
BE
P R
IN
T
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N U
M
BE
R
C :\U se rs
\g 4e ch ga i\D oc um en ts \D
W A5
6_
SA
M E_
N
EW
R O
O F_
_g ui do .a
.ig le si as
.rv t
/1
7/
1:
:4
AM
S-110
W
AL
LA
W
AL
LA
D
IS
TR
IC
T
N
R
D A
VE
W
AL
LA
W
AL
LA
, W
A
S.
O
LS
O
N
G . I
G
LE
SI
AS
JU
LI
O M
O R
EL
O
S, P
.E
J.
M
O R
EL
O
S
N O
VE
M
BE
R
W
2E F2
7B A0
FI
N
AL
D W
P- 1-
5- 1/
PL
AN
R
O O
F A
D W
O R
SH
AK
D
AM
A N
D R
ES
ER
VO
IR
R O
O F
R
EP
LA
C
EM
EN
T
N O
R
TH
F O
R K
C
LE
AR
W
AT
ER
R
IV
ER
, I
D
AH
O
PO
W
ER
H O
U
SE
GENERAL NOTES
1. SEE ARCH FOR ROOF ELEVATIONS AND STAIR INFORMATION NOT SHOWN OR
DETAILED IN STRUCTURAL DRAWINGS
2. SEE MEP DRAWINGS FOR EQUIPMENT INFORMATION NOT SHOWN OR HIDDEN IN
PLAN
SCALE: 1/8" = 1'-0"S-101
A1 A1 ENLARGED ROOF PLAN: ROOF A
0 4' 8' 16'
NORTH
SCALE: 1/2" = 1'-0"S-110
A1 L1 ENLARGED STAIR PLAN: ROOF A TO C
0 1' 2' 4'
H13 S-511
J6 S-511
H1 S-511
NEW STAIR
ROOF C
NEW FACE MOUNTED FRP GUARD
RAIL AROUND ROOF C, TYP
NEW ROOF A TO C STAIR
STAIR (REF. L1/S-110)
J1 S-513
J1 S-513
J1 S-513
A11 S-301
ROOF B
ROOF D
A1 S-514
TYP
POST-INSTALLED FALL PROTECTION
SWIVEL ANCHOR AT CONCRETE
WALL TYP, SEE SPECS AND DTLS
12' - 5 7/8" 20' - 0" 12' - 11 7/8"
13' - 0"
WALL-MOUNTED FALL
PROTECTION ANCHOR
UNDER STAIRS
A17 S-513
NEW FACE MOUNTED
FRP GUARDRAIL
AROUND ROOF D, TYP
A13 S-513
A7 S-514
A14 S-514
J7 S-515
J1 S-515
17' - 0"
2'
7"
1'
2"
1' - 6"
S-512 K6
DIAGONAL BRACE
BLW STRINGER TYP
HVAC UNIT AND STRUCTURAL
SUPPORT BRACKET
A
B
C D
E
US Army Corps of Engineers ®
SHEET ID
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
D S:
D
IR
O O
TS
PD
: A D
O
BE
P R
IN
T
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N U
M
BE
R
C :\U se rs
\g 4e ch ga i\D oc um en ts \D
W A5
6_
SA
M E_
N
EW
R O
O F_
_g ui do .a
.ig le si as
.rv t
/1
7/
1:
:4
AM
S-111
W
AL
LA
W
AL
LA
D
IS
TR
IC
T
N
R
D A
VE
W
AL
LA
W
AL
LA
, W
A
S.
O
LS
O
N
G . I
G
LE
SI
AS
JU
LI
O M
O R
EL
O
S, P
.E
J.
M
O R
EL
O
S
N O
VE
M
BE
R
W
2E F2
7B A0
FI
N
AL
D W
P- 1-
5- 1/
PL
AN
R
O O
FS
B
, C
D
D W
O R
SH
AK
D
AM
A N
D R
ES
ER
VO
IR
R O
O F
R
EP
LA
C
EM
EN
T
N O
R
TH
F O
R K
C
LE
AR
W
AT
ER
R
IV
ER
, I
D
AH
O
PO
W
ER
H O
U
SE
GENERAL NOTES
1. SEE ARCH FOR ROOF ELEVATIONS AND STAIR INFORMATION NOT SHOWN OR
DETAILED IN STRUCTURAL DRAWINGS
2. SEE MEP DRAWINGS FOR EQUIPMENT INFORMATION NOT SHOWN OR HIDDEN IN
PLAN
SCALE: 1/4" = 1'-0"S-101
A1 A1 ENLARGED ROOF PLAN: ROOFS B, C, & D
0 2' 4' 8'
4 PLAN: DWORSHAK POWERHOUSE EL. 1022
(SNAPPING ON ANY POINT WILL TELL YOU THE FOLLOWING: (DISTANCE FROM CBL, STATIONING)
NOTE: THIS VIEW IS ROTATED
ELEVATOR
STAIRWELL
UP
DOWN
UP
EL. 1030.26
EL. 1021.87
EL. 1022
LOBBY
WOMENS TOILET
MENS TOILET
PIPE SPACEJANITOR
HALL
HALL
CONFERENCE ROOM
MANAGER
GENERAL OFFICE
CLOSETSTORAGE ROOM
MICROWAVE ROOM
CENTRAL AIR CONDITIONING ROOM
MECH.
SHAFT
CONSTRUCTION BASE LINECONSTRUCTION BASE LINE
ERECTION BAY BAY 1 BAY 2 BAY 3 BAY 4 BAY 5 BAY 6
ERECTION BAY UPPER LEVEL
ST
AT
IO
N
CONSTRUCTION BASE LINEN
128'64'0'
NEW FACE MOUNTED
FRP GUARDRAIL WITH
GATE ALONG ROOF D
EXISTING LADDER
APPROXIMATE GATE
LOCATION, SEE ARCH
A13 S-513
NEW FRP GUARD
RAIL ON ROOF E
J5 S-513
J10 S-513
APPROX GATE
LOC, SEE ARCH
+/- 8'-6"
A1 S-514
POST-INSTALLED FALL PROTECTION SWIVEL ANCHOR AT CONCRETE WALL TYP, SEE SPECS AND DTLS
5 ANCHORS @ 20'
A17 S-513
TYP
±18'-0" 20' - 0"
POST-INSTALLED FALL PROTECTION
SWIVEL ANCHOR AT CONCRETE
WALL TYP, SEE SPECS AND DTLS
A
B
C D
E
US Army Corps of Engineers ®
SHEET ID
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
D S:
D
IR
O O
TS
PD
: A D
O
BE
P R
IN
T
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N U
M
BE
R
C :\U se rs
\g 4e ch ga i\D oc um en ts \D
W A5
6_
SA
M E_
N
EW
R O
O F_
_g ui do .a
.ig le si as
.rv t
/1
7/
1:
:4
AM
S-112
W
AL
LA
W
AL
LA
D
IS
TR
IC
T
N
R
D A
VE
W
AL
LA
W
AL
LA
, W
A
S.
O
LS
O
N
G . I
G
LE
SI
AS
JU
LI
O M
O R
EL
O
S, P
.E
J.
M
O R
EL
O
S
N O
VE
M
BE
R
W
2E F2
7B A0
FI
N
AL
D W
P- 1-
5- 1/
PL
AN
R
O O
FS
D
E
D W
O R
SH
AK
D
AM
A N
D R
ES
ER
VO
IR
R O
O F
R
EP
LA
C
EM
EN
T
N O
R
TH
F O
R K
C
LE
AR
W
AT
ER
R
IV
ER
, I
D
AH
O
PO
W
ER
H O
U
SE
SCALE: 1/8" = 1'-0"S-101
A1 A5 ENLARGED ROOF PLAN: ROOF D & E
GENERAL NOTES
1. SEE ARCH FOR ROOF ELEVATIONS AND STAIR INFORMATION NOT SHOWN OR
DETAILED IN STRUCTURAL DRAWINGS
2. SEE MEP DRAWINGS FOR EQUIPMENT INFORMATION NOT SHOWN OR HIDDEN IN
PLAN
0 4' 8' 16'
EL 1058.25
1058' - 3"
A6 S-511
A13 S-511
FRP GUARD RAIL
STEEL STAIR
HANDRAIL PER DTL
C12X20.7 STAIR STRINGER
BAR GRATING TREADS PER DTLS
AND SPECS.
ROOF C
ROOF A
FRP GUARD RAIL
1073.05
TO LANDING
WELDED GUSSET TO PLATE WITH
ANCHORS TO CONC TYP
STAIR BRACING, SEE /K6 S-512
STRINGER MAY BE FIELD SPLICED AS
NEEDED FOR CONSTRUCTABILITY,
CONTRACTOR TO PROVIDE SPLICE
LOCATIONS AND DETAILS FOR GOV'T
APPROVAL.
TO LANDING
ATTACHMENT TO IRREGULAR CONCRETE:
FIELD VERIFY EXISTING WALL PROFILE AT
ALL STAIR ATTACHMENT LOCATIONS.
NOSING WP
3'
6"
2'
1'
9"
NOSING WP
1069.72
INCLUDE CAST ABRASIVE NOSING AT LANDINGS (TYP)
NOSING WP
1/2
1/2
R
IS
ES
0'
8"
R
IS
ES
16 RUN @ 10" = 13' - 4"2' - 4"5 RUN @ 10" = 4' - 2"
5 7/8"
1'
9"2'
3'
6"
3"3 1/4"
3' - 9"
9 7/8"
1"
(TYP)
10"
(T
YP
8"STRINGER CONNECTION
(SEE DETAIL A7/S-512)
S-514 H7
H1 S-514
S-515 C1
C8 S-515
4' - 5 1/2"
EL 1039.42
1039' - 5"
H13 S-511
J6 S-511
H1 S-511
3'
1/
4"
FRP GUARD RAIL
TYP ANGLE
BRACKET TO
WALL, SEE
SECTION
STEEL HANDRAIL PER DTL
C12X20.7 STAIR STRINGER
BAR GRATING TREADS PER DTLS AND SPECS,
ATTACHED TO STAIR STRINGERS
ROOF B
ROOF C
NEOPRENE
BEARING PAD AT
STAIR LANDING
TO ROOF
TO LANDING
TO LANDING
STAIR BRACING, SEE /K6 S-512
FALL PROTECTION
ANCHOR
4'
6"
13' - 0 1/8"
H1 S-511
HVAC
A7 S-514
A1 S-514
TYP
R
IS
ES
/4
/4
13 RUN @ 10" = 10' - 10"2' - 2"14 RUN @ 10" = 11' - 8"
(TYP)
10"
(T
YP
3/
4"
3/4
3/4
NOSING WP
NOSING WP
NOSING WP
3'
2"
3'
2"
4 7/8" 9 1/4"
EDGE OF BUILDING
5' - 2 1/2"
1048.91
INCLUDE CAST ABRASIVE
NOSINGS AT LANDINGS
(TYP)
4' - 10 3/4"
3'
2"
3"2' - 8 5/8"
3' - 2 1/2"3 1/2"
1059.12
R
IS
ES
/4
0'
/2
STRINGER
CONNECTION (SEE
DETAIL A7/S-512)
US Army Corps of Engineers ®
SHEET ID
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
D S:
D
IR
O O
TS
PD
: A D
O
BE
P R
IN
T
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N U
M
BE
R
C :\U se rs
\g 4e ch ga i\D oc um en ts \D
W A5
6_
SA
M E_
N
EW
R O
O F_
_g ui do .a
.ig le si as
.rv t
/1
7/
1:
:4
AM
S-301
W
AL
LA
W
AL
LA
D
IS
TR
IC
T
N
R
D A
VE
W
AL
LA
W
AL
LA
, W
A
S.
O
LS
O
N
G . I
G
LE
SI
AS
JU
LI
O M
O R
EL
O
S, P
.E
J.
M
O R
EL
O
S
N O
VE
M
BE
R
W
2E F2
7B A0
FI
N
AL
D W
P- 1-
5- 1/
SE
C
TI
O
N S
D W
O R
SH
AK
D
AM
A N
D R
ES
ER
VO
IR
R O
O F
R
EP
LA
C
EM
EN
T
N O
R
TH
F O
R K
C
LE
AR
W
AT
ER
R
IV
ER
, I
D
AH
O
PO
W
ER
H O
U
SE
SCALE: 1/2" = 1'-0"S-110
L1 A1 SECTION - ROOF C TO A STAIRS (UPPER)
0 1' 2' 4' SCALE: 3/8" = 1'-0"S-111
A1 A11 SECTION - ROOF B TO C STAIRS (LOWER)
0 1' 2' 4' 6'
NOTES
1. GUARDRAIL AND HANDRAIL SHALL MEET ALL DIMENSIONAL REQUIREMENTS OF
OSHA (29 CFR 1910, SUBPART D), LIFE SAFETY CODE (NFPA 101-27), AND EM 385-1-1.
WHERE GUARDRAILING OR HANDRAIL DETAILS ARE OMITTED, THE DETAILS ON THE
CONTRACTOR DEVELOPED SHOP DRAWINGS SHALL COMPLY WITH THOSE
REGULATIONS AND STANDARDS.
2. ALL GRATING SHALL BE GALVANIZED AND WELDED 2" SERRATED BAR GRATING
WITH 3/16" BEARING BARS SPACED AT 1 3/16" AND CROSS BARS SPACED AT 4". STAIR
TREADS SHALL BE OF SIMILAR CONSTRUCTION AND INCLUDE CAST-ABRASIVE
NOSINGS AND CARRIER PLATES.
3) EACH GRATING PANEL SHALL BE ATTACHED IN ACCORDANCE WITH THE
MANUFACTURER'S REQUIREMENTS IN AT LEAST 4 LOCATIONS.
3/8" GUSSET PLATE
W/ (2) 13/16" HOLES
FOR (2) 3/4" BOLTS
ON GAGE
STAIR SYSTEM PER DTL
FRP GUARDRAIL
STAIR GUARDRAIL
PER DETAIL, TYP
ATTACHMENT TO IRREGULAR CONCRETE:
CHIP OUT 2" FROM THE RUSTICATIONS TO
INSTALL ANCHORS AND MISS EXISTING
WALL REBAR. CONTRACTOR SHALL FIELD
VERIFY RUSTICATIONS.
W6X12
3/8" GUSSET PLATE W/
(2) 13/16" HOLES FOR (2)
3/4" BOLTS ON GAGE
1/4
1/4 1"
(2) 11/16" HOLES FOR
(2) 5/8" BOLTS ON GAGE
9"
11/16" HOLES FOR
3/4" EPOXY ANCHORS
3' - 0"
3/4" BOTTOM CONNECTION PLATE
3/4" EPOXY ANCHORS
WITH 12" EMBEDMENT
A1 S-511
TOP CONNECTION PLATE
1/2"1/2 " M
IN
(T
YP)
1 1/2" (TYP)
1 1/2" (TYP)
3" (TYP)
1 1 /8"
45.00°
1/ 2"
1 1/4" 1' - 4 1/2"
WP
L4X4X3/8
ROOF A
ROOF A PARAPET STEP,
FLASH PER ARCH
TYPICAL WT TO
WALL, SEE /G7 S-512
STAIR GUARDRAIL
PER DTL, TYP
CHANNEL,
SEE PLAN
TYPICAL ANGLE
BRACE, SEE /A1 S-512
GALV STEEL
GRATING,
SEE PLAN
WT4X20X0'-9" W/ (3) 3/4"
DIA A325 BOLTS (SIMILAR
TO G7/S-512)
LEDGER ANGLE, SEE
PLAN
45.00°
3" T
YP
1' - 4 1/2"
4' - 7 3/4"
C12X20.7
SHEAR TAB CONNECTION (SEE
DETAIL A7/S-512)
3' - 0"
1/
2" 6"
1/
2"
H14 S-514
1/ 2"
1/2"
3' - 9 1/2"
ROOF B INTERMEDIATE LANDING
TYPICAL ANGLE
BRACKET, SEE
TYPICAL WT TO
WALL, SEE /G7 S-512
/A1 S-512
EXISTING
CONCRETE WALL
TYPICAL ANGLE,
SEE /A1 S-512
STAIR GUARDRAIL
PER DTL, TYP
7 3/4" 2' - 11 3/8"
TYPICAL ANGLE ,
SEE /A1 S-512
3' - 0"
7/8"
ROOF B
STEEL
STAIR
TYPICAL ANGLE
BRACKET, SEE
PLATE TO ANGLE AND
STRINGER, SEE DETAIL
(TYP)
TYPICAL WT TO
WALL, SEE /G7 S-512
/A1 S-512EXISTING
CONCRETE WALL
/K1 S-512
TYPICAL ANGLE,
SEE /A1 S-512
STAIR GUARDRAIL
PER DTL, TYP
3' - 6 7/8"
STAIR SYSTEM PER DTL
45.00°
3' - 0"
1 1/8"
1/
8"
TYPICAL ANGLE
BRACKET, SEE
TYPICAL WT TO
WALL, SEE /G7 S-512
/A1 S-512
EXISTING
CONCRETE WALL
ROOF LANDING
ROOF PARAPET STEP,
FLASH PER ARCH
STAIR GUARDRAIL
PER DTL, TYP
C12X20.7
6"
1/
2" C
LR
GALV STEEL GRATING,
SEE PLAN
1/
2" 6"
1/
2"
L6X4X3/8 LEDGER ANGLE
(SIMILAR TO H14/S-514)
WT4X20X0'-9" W/ (3) 3/4"
DIA A325 BOLTS (SIMILAR
TO G7/S-512)
3" 7" 2' - 9 1/8"
1/ 2"
1/2"
45.00°
2" 6"
2"
SHEAR TAB CONNECTION (SEE
DETAIL A7/S-512)
L14 S-514
2"8"2"
3/ 4"
(T
YP
2" 6"
2"
3/4" (TYP)
W6X12 1" PLATE
3/4" PLATE
5/16 3/16
TOP CONNECTION
PLATE
2" 6"
2"
1 3/4"1' - 2 1/2"1 3/4"
3/4" PLATE
L4X4X3/8
3/8" GUSSET PLATE
BOTTOM
CONNECTION
PLATE
1/4
1/4
3/4" BOLTS
1/ 2"
1/ 2"
US Army Corps of Engineers ®
SHEET ID
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
D S:
D
IR
O O
TS
PD
: A D
O
BE
P R
IN
T
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N U
M
BE
R
C :\U se rs
\g 4e ch ga i\D oc um en ts \D
W A5
6_
SA
M E_
N
EW
R O
O F_
_g ui do .a
.ig le si as
.rv t
/1
7/
1:
:4
AM
S-511
W
AL
LA
W
AL
LA
D
IS
TR
IC
T
N
R
D A
VE
W
AL
LA
W
AL
LA
, W
A
S.
O
LS
O
N
G . I
G
LE
SI
AS
JU
LI
O M
O R
EL
O
S, P
.E
J.
M
O R
EL
O
S
N O
VE
M
BE
R
W
2E F2
7B A0
FI
N
AL
D W
P- 1-
5- 1/
ST
R
U C
TU
R
AL
D
ET
AI
LS
D W
O R
SH
AK
D
AM
A N
D R
ES
ER
VO
IR
R O
O F
R
EP
LA
C
EM
EN
T
N O
R
TH
F O
R K
C
LE
AR
W
AT
ER
R
IV
ER
, I
D
AH
O
PO
W
ER
H O
U
SE
SCALE: 1" = 1'-0"S-111
A1 H13 DETAIL - ROOF B UPPER LANDING
SCALE: 1" = 1'-0"S-111
A1 J6 DETAIL - ROOF B INTERMEDIATE LANDING
SCALE: 1" = 1'-0"S-111
A1 H1 DETAIL - ROOF B LOWER LANDING
SCALE: 1" = 1'-0"S-110
L1 A6 DETAIL - ROOF C INTERMEDIATE LANDING
SCALE: 1" = 1'-0"S-110
L1 A13 DETAIL - ROOF A LANDING
0 1.5" 3" 6" 9" 0 0.5' 1' 2'
0 0.5' 1' 2'
0 0.5' 1' 2'
0 0.5' 1' 2'
SCALE: 3" = 1'-0"S-511
A6 A1 DETAIL - CONNECTION PLATE
NOTE: CONTRACTOR SHALL ADJUST DIMENSIONS BASED ON FIELD VERIFIED RUSTICATION
LOCATIONS. RUSTICATION SHALL SHALL BE CHIPPED OUT AND ANCHOR PLATE DIMENSIONS
ADJUSTED SUCH THAT THE SHANK OF THE ANCHOR ROD IS NOT EXPOSED BETWEEN THE
CONNECTION PLATE AND THE CONCRETE WALL. DIMENSIONS ACCOUNTING FOR
RUSTICATIONS SHALL BE SHOWN ON THE SHOP DRAWINGS.
0 0.5' 1' 2'
SEE DETAIL
VARIES
SEE DETAILS 1/2"
45.00°
L6X4X3/8, LLV
L4X4X3/8
2"
3/16
ALL EDGES,
TYP AT ENDS
3/16
NS & FS
1/2"
3/
8"
2"
1 1/2"
1/2" WT6X26.5x0'-8", TYP
OFFSET PER DETAILS
FRAME SECTION
ANGLE CONNECTING
FRAMES, FRONT AND
BACK, TYP AT FRAMES
L6X4X3/8, LLV
4" 2 3/8" 2"
8"
5/
8"
1"
3/16
NS & FS,
ALL EDGES
L6X4X3/8, TYP
(2) 3/4"Ø TENSIONED
BOLT, TYP
SEE ELEVATION
ANGLE CONNECTING FRAMES
FOR WT ANCHORS
TO CONCRETE,
SEE /G7 S-512
3"
(2) 3/4"Ø BOLT ES ALIGN W/ STAIR
STRINGER
3/16
ALL EDGES
NS AND FS
2" 6" 2"
2"6"
2"
(4) 3/4"Ø X 4" EMBED
ADHESIVE ANCHORS
4"
WT6x26.5
O R
J O
IN
T
1/
2" C
LR
T
O E
D G
E
CONCRETE
EDGE OR JOINT
STRINGER
SIDE VIEW SECTION
PL 1/2", WELDED TO
STRINGER AND ANGLE, ALIGN
TO FACE OF CHANNEL
CJP
3/16
ANGLE PER /A1 S-512
C12X20.7, TYP
CHANNEL SPLICES
CJP FLANGES
& WEB
CHANNEL TO ANGLE
TREAD SUPPORT
3/4"Ø SNUG TIGHT
BOLT, CENTER ON
ANGLE FLANGE
STAIR TREAD PER DTLS & MFR
CARRIER PL PER MFR
DIAPHRAGM BRACE
L4X4X1/4 DIAGONAL BRACE AT
BOTTOM FLANGE WITH 3/4" BOLT, TYP
EA END, CONFIGURE TO DISTRIBUTE
EVENLY ON VERTICAL RISES
BRACE CONNECTION
45.00°
C12 STAIR STRINGER
C12 STAIR STRINGER
4"
2"
TY
P 1"
C
LR
NOTE: START BRACING AT TOP OF RISE,
CONTINUE DOWN, TERMINATE IF WITHIN
3'-0" OF LANDINGS (MID OR BOTTOM)
STRINGER PER SECTION
PE
R
M
FR
D
EP
TH
SLOTTED HOLE PER MFR
WELDED GALVANIZED STEEL BAR
GRATING W/ SERRATED SURFACE
CAST ABBRASIVE NOSING
WELD END PL TO GRATING PER MFR. PLACE
T/O END PL TO FLUSH /W T/O GRATING
BOLT HOLE PER MFR
CARRIER PL
STRINGER PER SECTION AND DTLS
ARCH AND MFR
TREAD WIDTH PER
NOTE: CONTRACTOR MAY FIELD WELD CARRIER PLATE TO STRINGER
IN ACCORDANCE WITH MANUFACTURER REQUIREMENTS WHERE
BOLTING IS NOT POSSIBLE.
3/16
3/16
3-…