Lean-To Drawing.docx
DOCX document 2 MB Posted
- Attached to
- DWA Building Lean-to Federal contract opportunity
- Solicitation number
- W912EF24Q0084
About this file
The document provided is a detailed technical drawing for a Lean-To Shed structure, including a list of materials, general notes, and various elevations and details. The drawing is part of a federal contract opportunity issued by the U.S. Army Corps of Engineers, Walla Walla District, for the construction of a Lean-To Shed facility. The solicitation number is W912EF24Q0084, and the contract opportunity is named "DWA Building Lean-to". The key details provided in the drawing include the structural steel members, dimensions, panel materials, hardware, and installation requirements. The drawing provides sufficient information to construct two Lean-To Shed structures, with dimensions of approximately 19'10" x 13'6" and 19'10" x 13'8". The document also includes general notes regarding material specifications, welding, and dimensional tolerances.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Solicitation amendment DWA Building Lean-To W912EF-24-Q-0084 mod.pdf | ||
| Lean-To Drawing.pdf | ||
| Solicitation DWA Building Lean-To W912EF-24-Q-0084.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
LIST OF MATERIALS:
P DWORSHAK GARCO LEAN TO SHEDQTY
Description Length Material Location Approximate Weight HSS 4x4x3/16 (North Lean-to) 13'-6"
ASTM A500
Grid A HSS 4x4x3/16 (North Lean-to) 10'-5 3/4"
ASTM A500
Grid B HSS 4x4x3/16 (South Lean-to) 13'-8"
ASTM A500
Grid A HSS 4x4x3/16 (South Lean-to) 10'-7 7/8"
ASTM A500
Grid B W10x12 12.25
ASTM A992
Girders W8x10
ASTM A992
Joists 26GA Tuff-Rib Panel, Grade 50 yield 762 sq. ft.
ASTM A792
Roof Panels 26GA Tuff-Rib Panel, Grade 50 yield 301 sq. ft.
ASTM A792
Wall Panels 1/2" Thick Plate N/A
ASTM A572
Typ Base Plates 1/2" Thick Plate N/A
ASTM A572
Gusseted Base Plates Galvanized 6" DP x 2-1/2" FL x 12 GA Z-GIRT, Unpunched, 50 Ksi
ASTM A1003
End Wall Z-Girts L4x4x1/4
ASTM A36
End Wall Base Angle L3x3x1/4
ASTM A36
End Wall Roof Angle Galvanized 5/8" Thick Shackle with Safety Pin, 10,000 lb capacity N/A
STEEL
Shackle Galvanized Clevis to Clevis Turnbuckle, 10,000 lb capacity N/A
STEEL
Turnbuckle Galvanized 5/8" ø wire rope x 50 ft
STEEL
Wire Rope PL 3/8" x 4" x 6" N/A
ASTM A572
Shear Tabs for Girders L6x4x3/8 x 6" LG
ASTM A36
Shear Tabs for Joists 3/4" Thick Plate N/A
ASTM A572
Lower Gusset Plates 3/4" Thick Plate N/A
ASTM A572
Upper Gusset Plates PL 3/8" x 3" x 9" N/A
ASTM A572
Upper Gusset Conn Plates PL 3/16" x 3" x 3" N/A
ASTM A572
Z-Girt Tabs HSS 3x3x1/8
ASTM A500
Roof Slope HSS 3/4" ø Bolts x 2" LG N/A
ASTM F3125
Bolts 20.5 3/4" ø Washers N/A
ASTM F436
Washers 3/4" ø Nuts N/A
ASTM A563
Nuts #12 x 1" Screws N/A
STEEL
Screws Galvanized, 16 GA
ASTM A1003
Roof to Roof Flashing Galvanized, 16 GA
ASTM A1003
Roof to End Wall Flashing Galvanized, 16 GA
ASTM A1003
Wall to Wall Flashing #4 x 21" LG, GR 60 N/A
ASTM A615
Reinforcing
GENERAL NOTES:
N 1. STRUCTURAL STEEL
A. WF - ASTM A992/A992M, GRADE 50
| B. HSS - ASTM A500/A500M, GRADE C (50KSI MIN YIELD STRENGTH) | ||
| C. ANGLE - ASTM A36 | ||
| M | D. PLATE - ASTM A572/A572M, GRADE 50 | |
| E. SHEET METAL / FLASHING - 16 GA, GALVANIZED | ||
| F. COLD FORMED STEEL - ASTM A1003 |
G. CAP ALL OPEN HSS MEMBER ENDS WITH 3/16" PL, SEAL WELD ALL AROUND
L 2. CONNECTIONS
A. BOLTS - ASTM F3125/F3125M GRADE A325, TYPE 1
| B. NUTS - ASTM A563, GRADE A | ||
| C. WASHERS - ASTM F436, TYPE 1 | ||
| K | D. EXPANSION ANCHORS | |
| E. SCREWS - #12-14 X 1" |
F. BOLT ASSEMBLIES TO BE WRENCH TIGHT
3. WELDING - WELD PER AWS D1.1/D1.1MJ
4. ROOF PANELS. TUFF RIB PANEL, 26 GA, 50 KSI YIELD STRENGTH. COLOR = COPPER GALVALUME
5. WALL PANELS. TUFF RIB PANEL, 26 GA, 50 KSI YIELD STRENGTH. COLOR = SANDSTONE #22 MIRAMAC METALS
6. ALL STRUCTURAL STEEL SHALL BE HOT-DIPPED GALVANIZED (H.D.G.) IN ACCORDANCE WITH ASTM A123/A123M. TOUCH UP REPAIR OF GALVANIZING SHALL BE DONE BY THE "HOT STICK" METHOD AS DESCRIBED INH
ASTM A780/A780M. ADD ZINC PLUGS TO FILL HOT DIP GALVANIZING VENT HOLES.
7. FOR DIMENSIONS LESS THAN 2 FEET, DIMENSIONS SHALL BE WITHIN +/- 1/16 INCH OF DIMENSIONS SHOWN ON THE DRAWING. FOR DIMENSIONS GREATER THAN OR EQUAL TO TWO FEET AND UP TO 8 FEET, DIMENSIONS SHALL G BE WITHIN +/- 1/8 INCH OF DIMENSIONS SHOWN ON THE DRAWING. FOR DIMENSIONS GREATER THAN OR EQUAL TO 8 FEET, DIMENSIONS SHALL BE WITHIN +/- 1/4 INCH OF DIMENSIONS SHOWN ON THE DRAWING.
ADDL NOTES:
F THIS DRAWING IS SET UP TO BUILD (1) LEAN-TO SHED. (2) ARE REQUIRED. LIST OF MATERIALS MUST BE DOUBLED EXCEPT FOR HSS COLUMN MEMBERS WHICH HAVE ALL COLUMN MEMBERS IN THE LIST OF MATERIALS FOR BOTH THE NORTH AND SOUTH LEAN-TO SHEDS.
E
D
C
B
ISOMETRIC VIEW OF LEAN-TO 1
A SCALE:
US Army Corps of Engineers ®
SHEET IDDESIGNED BY:
B. MEACHAM DRAWN BY:
B. MEACHAM CHECKED BY:
Checker SUBMITTED BY:
Approver
SIZE: FILE NO: ANSI D
ISSUE DATE: 10/31/23 SOLICITATION NO:
Enter address here
U.S. ARMY CORPS OF ENGINEERS WALLA WALLA DISTRICT
201 N 3RD AVE WALLA WALLA, WA 99362
CONTRACT NO.:
MARK
DESCRIPTION
DATE
S.1V:\Operations_and_Maintenance\Engineering Tech Support\Dworshak\FY24 SC- Garco shed shelter AFU Update\Docs\Drawings\Lean To.rvt Project Status
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Project Status V:\Operations_and_Maintenance\Engineering Tech Support\Dworshak\FY24 SC- Garco shed shelter AFU Update\Docs\Drawings\Lean To.rvt
A B A BP
12' - 0" 12' - 0"
A B US Army Corps of Engineers ®12' - 0"
HSS4X4X3/16 HSS4X4X3/16DATE
N
B1 S.3
M
L
K
B2 S.5
NEW FOOTING REQUIRED 24" X 24" X 12" DP MIN W/
(4) #4 EW BOT 3" CLR
HSS4X4X3/16
HSS4X4X3/1619' - 10"
B2 S.5W8X10 W8X10 W8X10 W8X10
19' - 10"
W10X12
E8 S.4
E8 S.419' - 10"
MARK
DESCRIPTION
| 3 | 3 | 3 |
| - | - | |
| --- | --- |
JISSUE DATE: 11/06/23 SOLICITATION NO:
CONTRACT NO.:
BRACED BAY PER ELEVATION
H59' - 11 1/2" 19' - 10" W8X10 W8X10 W8X10 W8X10 W8X10 19' - 10" 19' - 10"
DESIGNED BY:
Designer DRAWN BY:
Author CHECKED BY:
Checker SUBMITTED BY:
Approver
SIZE: FILE NO: ANSI D
G J14 S.4
J14 S.4
F B9
HSS4X4X3/16 HSS4X4X3/16
A8 A2
N 13' - 6" S 13' - 8"S 13' - 8"
B9
N 10' - 5 3/4" S 10' - 7 7/8"10' - 8"
2 2 B9
S.3
S.4
S.4
S.3
G16 S.5
G16 S.5
E19' - 10"
W8X10 W8X10 W8X10 W8X10 19' - 10" 19' - 10"
U.S. ARMY CORPS OF ENGINEERS WALLA WALLA DISTRICT
201 N 3RD AVE WALLA WALLA, WA 99362
B16 S.5
HSS4X4X3/16 HSS4X4X3/16
2' - 11"
3' - 0"
3' - 0"
3' - 1"
METAL ROOF WITH #12 SCREWS. ATTACHMENT PATTERN PER A14/S.4
B10 S.5
A GroundA1
SCALE: 1/4" = 1'-0"
NOTE: IF CONCRETE IS MISSING UNDER SIDE WALLS, PROVIDE 12" W X 12" DP FOOTING W/ (3) #4 CONTINUOUS BOT 3" CLR
NEW FOOTING REQUIRED 24" X 24" X 12" DP MIN W/
(4) #4 EW BOT 3" CLRA8
ATTACH COLUMN TO EXISTING CONCRETE, TYP (6) PLACES
B10 S.5Enter address here
Level 2
B10 S.51
Level 2 - Roof Deck ExtentsA14
SHEET ID
S.2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P
NDATE
A B 2 3DESCRIPTION
A
Project Status V:\Operations_and_Maintenance\Engineering Tech Support\Dworshak\FY24 SC- Garco shed shelter AFU Update\Docs\Drawings\Lean To.rvt
J
GIRDER PER PLAN
JOIST PER PLAN, TYP
Level 2
N/S VARIES13' - 8"
J2 S.4
1' - 3"L3X3X1/4
ALIGN WITH BASE GUSSET PL ON GRID 3
ALIGN WITH BASE GUSSET PL ON GRID 2ISSUE DATE: 11/06/23 SOLICITATION NO:
H 6" DP X 2-1/2" FLANGE X 12GA Z-GIRTDESIGNED BY:
Designer DRAWN BY:
Author CHECKED BY:
Checker SUBMITTED BY:
SIZE: FILE NO: ANSI D
G 6" DP X 2-1/2" FLANGE X 12GA Z-GIRT2' - 0"
HSS4X4X3/16
F 6" DP X 2-1/2" FLANGE X 12GA Z-GIRTHSS4X4X3/16
2' - 0"
E 6" DP X 2-1/2" FLANGE X 12GA Z-GIRT2' - 0"
F6 S.510' - 8"
GALVANIZED CLEVIS TO CLEVIS TURNBUCKLE, 10,000 LB CAPACITY
GALVANIZED WIRE ROPE 5/8"ø, 8,000 LB MIN CAPACITY2' - 0"
D 6" DP X 2-1/2" FLANGE X 12GA Z-GIRT
GALVANIZED SHACKLE EA END. 5/8"ø WITH SAFETY PIN, 10,000 LB CAPACITY1' - 9" Enter address here
L4X4X1/4
Ground 0' - 0"
E2 S.4
Ground 0' - 0"
B EXT WALL ELEVATION B1
SCALE: 3/4" = 1'-0"
BRACED FRAME ELEVATION
SCALE: 3/4" = 1'-0"B9
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
CAP PL
N
M0' - 3"
MTL ROOF NOT SHOWN FOR CLARITY GIRDER NOT SHOWN FOR CLARITY
BEAM PER PLAN (CONNECTIONS NOT SHOWN FOR CLARITY)
1' - 1" 0' - 1 1/2" 0' - 3" 0' - 3" 0' - 1 1/2"
(3) 3/4" ø A325 BOLTS
PL 3/8 X AS SHOWN, LOCATE SO GUSSET PL ALIGNS WITH GUSSET PL ON SAME CABLE
0' - 0 1/2" TYP
MTL ROOF PER PLAN
PL 3/8 X 4" X 6", TYP
3/16 PL TO COL,
1/8 2-12
MTL ROOF PER PLAN0' - 1 1/2"
0' - 2"
#12 SCREW PER A14/S.4, TYPDATE
HSS 3X3X1/8 CUT TO SLOPE OR L3X2X3/16
RUN.1 1/4"
0' - 0 1/2" 0' - 4"
3/16
TYP
1/8 2-12
BEAM PER PLAN
L0' - 1 1/2" 0' - 7" 1 1/4" ø 0' - 1"
PL TO BEAM
(2) 3/4"ø A325 BOLTS
SHACKLE PER ELEVATIONDESCRIPTION
0' - 1 1/4"
0' - 2 3/4"
BEAM PER PLAN, TYP
COL PER PLAN
0' - 11"
PL 3/4" X AS SHOWN, ALIGN WITH GUSSET PL ON SAME CABLE RUN. SEE B9/S.3 AND A8/S.4 FOR ADDL INFO.
HSS COL PER PLAN
UPPER GUSSET PLATE MARK
J2
SCALE: 3" = 1'-0"
ROOF CONNECTION TO COLUMN
SCALE: 3" = 1'-0"J8
ROOF DECK TO BEAM CONN
SCALE: 3" = 1'-0"J14
JISSUE DATE: 11/06/23 SOLICITATION NO:
COL PER PLAN
0' - 6" 0' - 0 1/2"
L 6 X 4 X 3/8 X AS SHOWN
(2) 3/4" ø A325 BOLTS
H
Gø 0' - 1"
SHACKLE PER ELEVATION0' - 6"
0' - 3"
PL 3/4" X AS SHOWN
0' - 3 7/8"DESIGNED BY:
Author CHECKED BY:
Checker SUBMITTED BY:
Approver
SIZE: FILE NO: ANSI D
BEAM PER PLAN 0' - 1 1/2"0' - 7"
0' - 3 1/2" 0' - 1 1/2"
F
0' - 8"
Ground
GIRDER PER PLAN
NOTE: TOP OF BEAM IS FLUSH WITH GIRDER. DUE TO ROOF SLOPE CONNECTIONS WILL BE ANGLED.
3/16
BASE PL PER PLAN
E LOWER GUSSET PLATE E2
SCALE: 3" = 1'-0"
BEAM TO GIRDER CONNECTION
SCALE: 3" = 1'-0"E8
D 0' - 1"
GUSSET PL 3/4"
OFFSET 1" FROM CENTERLINE T&B OPPOSITE SIDES FOR EACH CABLE RUN SO THEY DON'T OVERLAP.Enter address here
0' - 6" 0' - 6"
1" ø HOLE FOR 3/4" X 4" LG EXPANSION ANCHOR
1" ø HOLE FOR 3/4" X 4" LG EXPANSION ANCHOR
PL 1/2 X AS SHOWN0' - 6"
C 2
PL 1/2 X AS SHOWN0' - 8"
21' - 6"
0' - 4" 0' - 2"
TYP0' - 6"
3/16 3/162"
2" TYP
2" 1' - 0"
TYP BASEPLATE A2
SCALE: 1 1/2" = 1'-0"
BASEPLATE WITH GUSSET
SCALE: 1 1/2" = 1'-0"A8
SCREW PATTERN
SCALE: 1 1/2" = 1'-0"A14
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
P 4
ROOF PER PLAN
US Army Corps of Engineers ®
RAKE FLASHING AND ATTACHMENT PER A1/S.6
N
EXISTING BUILDING ROOF
ADATE
ROOF FLASHING PER G16 / S.5A
Level 2 M13' - 8"
N/S VARIES
BEAM PER PLAN
K 0' - 2"
K6 S.50' - 1 1/2"
WALL PER PLAN
#12 SCREW PER A14/S.4, TYP
| 1/8 | 2-12 |
| 1/8 | 2-12 |
ROOF TO WALL FLASHING
BENT ANGLE FLASHING PER K6 / S.5
EXISTING WALLK6
EXISTING ROOF13' - 8"
Level
EXISTING FLASHING
#12 SCREW @ 12" O.C. MAX
0' - 2"
NEW 16GA FLASHING (NO ATTACHMENT TO NEW ROOF)
14' - 2"
Level 213' - 8" Level 4
DESCRIPTION
J WALL PANEL2' - 0"
ISSUE DATE: 12/07/23 SOLICITATION NO:
F6 S.5
H2' - 0"
G
WALL PANEL
6" DP X 2-1/2" FL X 12 GA Z-GIRT
0' - 0 1/2" GAP
Z-GIRT PER PLAN
1/8 1/8
16 GA FLASHING. ATTACH TO EXISTING BUILDING CORNER FLASHING WITH #12 SCREW @ 6" O.C. OVERLAP 4" MIN WITH NEW BUILDING WALL PANELS.
0' - 6"DESIGNED BY:
Author CHECKED BY:
Checker SUBMITTED BY:
SIZE: FILE NO: ANSI D
ROOF FLASHING MAIN TO LEAN-TO G16
SCALE: 3" = 1'-0"U.S. ARMY CORPS OF ENGINEERS WALLA WALLA DISTRICT
PL 3" X 3" X 1/8"F6
F2' - 0"
#12 SCREW PER A14/S.4, TYP
(4) #12 SCREWS EA END
Z-GIRT TO HSS COL CONN
SCALE: 1 1/2" = 1'-0"
EXISTING BUILDING CORNER FLASHING
EXISTING BUILDING EXTENTS
EXISTING CORNER FLASHING2' - 0"
B6 S.51' - 9"
C Ground
L X 4" X 4" X 1/4"
WALL PANEL PER GENERAL NOTES 26GA TUFF-RIB PANEL
ATTACH WALL PANEL TO ANGLE WITH #12 SCREW PER A14/S.4, TYP
B16 S.5G16
COL PER PLAN
0' - 6" WALL SUPPORT ANGLE PER B6 / S.5
1Enter address here
WALL PANEL PER PLAN
16 GA FLASHING, BEND AS REQ'D, NO ATTACHMENT TO NEW STRUCTURE
#12 SCREW @ 6" O.C.
B WALL LAYOUT AT END OF LEAN-TO B2
SCALE: 1" = 1'-0"
ATTACH TO CONC WITH 1/2"ø x 3" MIN EMBEDMENT EXPANSION ANCHOR @ 24" O.C.
WALL TO GROUND CONNECTION B6
WALL FLASHING MAIN TO LEAN-TO
SCALE: 1" = 1'-0"B10
CORNER FLASHING
SCALE: 1 1/2" = 1'-0"B16
V:\Operations_and_Maintenance\Engineering Tech Support\Dworshak\FY24 SC- Garco shed shelter AFU Update\Docs\Drawings\Lean To.rvt Project Status
S.5
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
NDATE
LDESCRIPTION
KMARK
JISSUE DATE: 01/24/24 SOLICITATION NO:
HDESIGNED BY:
Author CHECKED BY:
Checker SUBMITTED BY:
SIZE: FILE NO: ANSI D
GU.S. ARMY CORPS OF ENGINEERS WALLA WALLA DISTRICT
F
DEnter address here
A RAKEA1
SCALE: 1 1/2" = 1'-0"V:\Operations_and_Maintenance\Engineering Tech Support\Dworshak\FY24 SC- Garco shed shelter AFU Update\Docs\Drawings\Lean To.rvt Project Status
END WALL
SCALE: 1 1/2" = 1'-0"SHEET ID
S.6 A8 image6.png image94.png image95.png image96.png image97.png image98.png image99.png image100.png image101.png image102.png image7.png image103.png image104.png image105.png image106.png image107.png image108.png image109.png image110.png image111.png image112.png image113.png image114.png image115.png image116.png image117.png image118.png image119.png image120.png image121.png image8.png image122.png image9.png image10.png image11.png image12.png image13.png image14.png image15.png image16.png image17.png image18.png image19.png image20.png image21.png image22.png image23.png image24.png image25.png image26.png image27.png image28.png image29.png image30.png image31.png image32.png image33.png image34.png image35.png image36.png image37.png image38.png image39.png image40.png image41.png image42.png image43.png image1.png image44.png image45.png image46.png image47.png image48.png image49.png image50.png image51.png image52.png image53.png image2.png image54.png image55.png image56.png image57.png image58.png image59.png image60.png image61.png image62.png image63.png image3.png image64.png image65.png image66.png image67.png image68.png image69.png image70.png image71.png image72.png image73.png image4.png image74.png image75.png image76.png image77.png image78.png image79.png image80.png image81.png image82.png image83.png image5.png image84.png image85.png image86.png image87.png image88.png image89.png image90.png image91.png image92.png image93.png
File details come from the government source that posted it. Updated .