W912EF22Q0189 Amendment 0001.pdf

PDF 538 KB Posted

Attached to
Dworshak Motor Control Centers & Switchboard Upgrade Federal contract opportunity
Solicitation number
W912EF22Q0189
Issued by
Department of the Army Corps of Engineers Engineering District Walla Walla

View the file

Other files for this federal contract opportunity

Other files attached to Dworshak Motor Control Centers & Switchboard Upgrade, newest first.
File Type Posted
W912EF22Q0189 Amendment 0004.pdf PDF
W912EF22Q0189 as of Amendment 0003.pdf PDF
W912EF22Q0189 Amendment 0003.pdf PDF
W912EF22Q0189 Amendment 0002.pdf PDF
Brand Name Determination - MCC and Switchboard Upgrade - Redacted.pdf PDF
Attachment 2 - Technical Specifications GCQ2.pdf PDF
W912EF22Q0189.pdf PDF
Attachment 3 - Technical Specifications GCQ3.pdf PDF
Attachment 1 - Technical Specifications ESQ1.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

The purpose of this amendment is to extend the delivery deadline to 22 March 2023. All other terms and conditions remain unchanged.

1. CONTRACT ID CODE PAGE OF PAGES

J 1 8

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY 31-Aug-2022

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street , County, State and Zip Code) X W912EF22Q0189

X 9B. DATED (SEE ITEM 11)

25-Aug-2022

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN

REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

31-Aug-2022

CODE

USAED, WALLA WALLA - CONTRACTING DIV.

PRESTON E JONES

201 N. THIRD AVENUE

WALLA WALLA WA 99362-1876

W912EF 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

W912EF22Q0189

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

SECTION SF 1449 - CONTINUATION SHEET

DELIVERIES AND PERFORMANCE

The following Delivery Schedule item for CLIN 0001 has been changed from:

DELIVERY DATE QUANTITY SHIP TO ADDRESS DODAAC /

CAGE

22-DEC-2022 1 ARMY CORPS OF ENGINEERS

PERFORMANCE SPECIALIST

DWORSHAK PROJECT OFFICE

1428 NORTHFORK DRIVE

AHSAHKA ID 83520-0048

FOB: Destination

960201

To:

DELIVERY DATE QUANTITY SHIP TO ADDRESS DODAAC /

CAGE

22-MAR-2023 1 ARMY CORPS OF ENGINEERS

PERFORMANCE SPECIALIST

DWORSHAK PROJECT OFFICE

1428 NORTHFORK DRIVE

AHSAHKA ID 83520-0048

The following Delivery Schedule item for CLIN 0002 has been changed from:

CAGE

22-DEC-2022 1 ARMY CORPS OF ENGINEERS

PERFORMANCE SPECIALIST

DWORSHAK PROJECT OFFICE

1428 NORTHFORK DRIVE

AHSAHKA ID 83520-0048

CAGE

22-MAR-2023 1 ARMY CORPS OF ENGINEERS

PERFORMANCE SPECIALIST

DWORSHAK PROJECT OFFICE

1428 NORTHFORK DRIVE

AHSAHKA ID 83520-0048

The following Delivery Schedule item for CLIN 0003 has been changed from:

CAGE

22-DEC-2022 1 ARMY CORPS OF ENGINEERS

PERFORMANCE SPECIALIST

DWORSHAK PROJECT OFFICE

1428 NORTHFORK DRIVE

AHSAHKA ID 83520-0048

CAGE

22-MAR-2023 1 ARMY CORPS OF ENGINEERS

PERFORMANCE SPECIALIST

DWORSHAK PROJECT OFFICE

1428 NORTHFORK DRIVE

AHSAHKA ID 83520-0048

The following have been modified:

TECHNICAL SPECIFICATIONS

DWORSHAK NATIONAL FISH HATCHERY

MOTOR CONTROL CENTER & SWITCHBOARD UPGRADE

TECHNICAL SPECIFICATION

1.0 SCOPE

This specification pertains to the purchase of two new merchandized Square D Model 6 Motor Control Centers (MCCs) and one new merchandized QED-2 Switchboard for Dworshak Project located near Ahsahka, Idaho. The Contractor shall supply, package, and deliver the new Motor Control Centers and Switchboard; he Motor Control Centers and Switchboard will be installed by the Government.

2.0 EQUIPMENT REQUIREMENTS

The Motor Control Centers shall be a Square D (by Schneider Electric) Model 6 Motor Control Center and the Switchboard shall be a Square D (by Schneider Electric) QED-2 Low Voltage Switchboard, per the design specifications. The Contractor shall supply MCCs and Switchboard that match, to the greatest extent possible, the existing MCC and Switchboard footprints and circuit breaker lineup to avoid having to splice existing conductors to extend their length and to include any upgrades or modifications as noted in these specifications (See attached reference drawings for existing lineups). Contractor shall also supply a Square D Circuit Breaker Test Set for testing circuit breakers located in QED-2 Low Voltage Switchboard and Circuit Breaker Picking Device Attachment as specified in section 2.1.3 Circuit Breaker Requirements.

2.1 GENERAL REQUIREMENTS

Equipment provided under this contract shall meet the following salient requirements:

2.1.1 Model 6 Motor Control Center ESQ1

Physical Requirements o Unused vertical space within the MCC lineup shall utilize 6” Blank Covers. In circumstances where a

6” Blank Cover cannot be utilized a 3” Blank Cover or combination of a 6” and 3” blank cover shall be used in conjunction.

o Enclosure shall be a NEMA Type 1A, Top-fed, 20” Deep General Purpose o All components, including Buckets, Circuit Breakers, Transformers, Control Power Transformers, Distribution Panelboards, and Motor Starters shall be new and unused and shall be manufactured by Square D for use in Model 6 MCCs o All Buckets, including Circuit Breakers, Contactors, and Motor Starters shall be draw-out style.

o Shall include any necessary hardware and special tools for performing installation.

o Shall include Wire Tie Retainers in vertical wireway and Rodent Barriers.

o Shall include engraved Master Nameplate for MCC and engraved Nameplates for each individual bucket. Nameplates shall be black surface, white letters, and stainless-steel nameplate screws. Once the submitted design package is approved by the government, the government will provide designations for each nameplate.

o Shall be suitable for the Seismic Category of Clearwater County, Idaho, which is category B.

o Shall meet the requirements of UL, where UL standards are established for those items.

Electrical Requirements o System voltage is 480 VAC, 3 Phase, 3 Wire, 60 Hz o 800A minimum rated Horizontal Bus constructed of copper o Shall include an appropriately rated Vertical Bus constructed of copper o Shall include an appropriately rated continuous-ground bus of tin-plated copper at the bottom of all

MCC sections.

o All Electrical Components: Designed for a Max Available Fault Current (RMS) of 65 kA o Wiring shall be NEMA Type 1B o All Control and Annunciation Circuits shall be designed for 125VDC o Shall meet the requirements of NFPA 70, where NFPA 70 standards are established for those items.

Circuit Breaker Requirements o Shall include a minimum of one alarm contact for remote annunciation for when breaker trips o Shall include a means for locking out the device for Hazardous Energy Control o Where ratings allow, circuit breakers shall occupy a 6-inch vertical section of MCC o Shall be provided with draw-out bucket o Circuit breakers shall include means of being locked out for Hazardous Energy control o This MCC includes two Main Feeder Circuit Breakers with one circuit breaker rated at 600A and the other rated at 150A. The following additional requirements apply for those circuit breakers:

These circuit breakers shall be electrically interlocked to prevent them from being closed simultaneously.

The main circuit breakers shall be capable of being electronically operated for open/close functionality.

Circuit Breakers shall include Micrologic 6.0P Trip Unit with LSIG overcurrent protection Circuit Breakers shall include auxiliary A/B contacts for control wiring

Circuit Breakers shall have capabilities of being shunt tripped Circuit breakers shall be supplied lugs shall be capable of accepting a minimum of two parallel

350MCM cables per phase and neutral on the line side of the circuit breaker.

Lineup o 600A, 480VAC, 3 Pole Main Feeder Circuit Breaker from Powerhouse Diesel o 150A, 480VAC, 3 Pole Main Feeder Circuit Breaker from Dam Diesel o 50A, 480VAC, 3 Pole Branch Circuit Breaker - CQ05 (Existing Bucket 1A) o 100A, 480VAC, 3 Pole Branch Circuit Breaker - CQ01 (Existing Bucket 2A) o 30A, 480VAC, 3 Pole Branch Circuit Breaker - Governor Air Compressor #3 (Existing Bucket 1B) o 100A, 480VAC, 3 Pole Branch Circuit Breaker - SU1 (Existing Bucket 2B) o 50A, 480VAC, 3 Pole Branch Circuit Breaker - SU2 (Existing Spare Bucket 1C, this is a new breaker in this lineup) o 250A, 480VAC, 3 Pole Branch Circuit Breaker - SU3 (Existing Bucket 2C, this breaker has been upsized from the original lineup) o 150A, 480VAC, 3 Pole Branch Circuit Breaker - Batter Charger #1 (Existing Bucket 1D) o 175A, 480VAC, 3 Pole Branch Circuit Breaker - Skeleton Bay Pump #4 (Existing Bucket 1E)

2.1.2 Model 6 Motor Control Center GCQ2

System Information o This Motor Control Center operates as a manual transfer switch for multiple loads.

o It is comprised of circuit breaker pairs, one used to supply power to a load from a normal source, and one used to supply power from the emergency source.

The Emergency Source supply breaker is fed from the vertical bus work of the MCC.

The Normal Source supply breaker does not stab into the vertical bus, rather both the line and load sides of the breaker are equipped with lugs. The line side of the breaker is fed via cable from another source.

The Normal and Emergency source supply breakers (and disconnecting means, in the case of motor starters) shall be mechanically interlocked to prevent both from being closed in at the same time.

o Footprint: Existing MCC is 48" W x 90" H x 30" D; new MCC shall be similar in size as the original MCC because of space restrictions.

o Unused vertical space within the MCC lineup shall utilize 6” Blank Covers. In circumstances where a 6” Blank Cover cannot be utilized a 3” Blank Cover or combination of a 6” and 3” blank covers shall be used.

o Enclosure shall be a NEMA Type 1A, Top-fed, 20” Deep General Purpose o All components, including Buckets, Circuit Breakers, Transformers, Control Power Transformers, Distribution panelboards, and Motor Starters shall be new and unused and shall be manufactured by Square D for use in Model 6 MCCs o All buckets, including circuit breakers, contactors, and motor starters shall be draw-out style.

o Shall include any necessary hardware and special tools for performing installation.

o Shall include wire tie retainers in vertical wireway and rodent barriers.

o Shall include engraved master nameplate for MCC and engraved nameplates for each individual bucket. Nameplates shall be black surface, white letters, and stainless-steel nameplate screws. Once the submitted design package is approved by the government, the government will provide designations for each nameplate.

o System voltage is 480VAC, 3 Phase, 3 Wire, 60 Hz o Shall be 800A minimum rated Horizontal Bus constructed of copper o Shall be equipped with an appropriately rated Vertical Bus constructed of copper o Shall include an appropriately rated continuous-ground bus of tin-plated copper at the bottom of all

MCC sections.

o All Electrical Components: Designed for a Max Available Fault Current (RMS) of 65 kA o Wiring shall be NEMA Type 1B o All Control and Annunciation Circuits shall be designed for 120VAC power o Shall include a minimum of one alarm contact for remote annunciation for when breaker trips o Shall include a means for locking out the device for Hazardous Energy Control

Motor Starter Package Requirements o Shall include an appropriately rated circuit breaker o 480:120VAC control power transformer with a minimum 150VA rating o Appropriately sized fuses for the control power transformer and any other current-limited devices o Motor overload protection device o Hand-Off-Auto (HOA) selector switch o “Motor Off” green LED pilot light with push-to-test feature o “Motor On” red LED pilot light with push-to-test feature o Minimum two additional “normally open” and two “normally closed” auxiliary contacts for control wiring o Additional four terminal blocks for field wiring

Lineup (See attached drawing for suggested lineup configuration of this MCC.)

o Emergency Loads (All stab into vertical bus):

800A, 480VAC, 3 Pole Circuit Breaker (HCQ6 Feeder) - Emergency Generator Feed NEMA Size 2 FVNR Motor Starter with motor circuit protector disconnects for 15 HP motor -

Incubation Pump #1 Emergency Feed NEMA Size 1 FVNR Motor Starter with motor circuit protector disconnects for 5 HP motor -

Generator Remote Radiator Fan Emergency Feed NEMA Size 2 FVNR Motor Starter with motor circuit protector disconnects for 15 HP motor -

Reuse Water Pump #5 Emergency Feed NEMA Size 2 FVNR Motor Starter with motor circuit protector disconnects for 15 HP motor -

Exhaust Fan Emergency Feed 5kVA Transformer, 480:120/240VAC, 1 Phase o Normal Loads (All compartments shall be isolated from vertical bus and breakers shall be equipped with lugs on the line and load side):

800A, 480VAC, 3 Pole Circuit Breaker - HCQ6 Normal Feed 150A, 480VAC, 3 Pole Circuit Breaker - Incubation Pump #1 Normal Feed 150A, 480VAC, 3 Pole Circuit Breaker - Generator Remote Radiator Fan Normal Feed 150A, 480VAC, 3 Pole Circuit Breaker - Reuse Water Pump #5 Normal Feed 150A, 480VAC, 3 Pole Circuit Breaker - Exhaust Fan Normal Feed o 100A, 120/240VAC, 1 Phase, 65kA AIC, 18 Circuit Panelboard, Copper Ground Bus and Copper 100% Rated Neutral Bus Main Circuit Breaker - 100A, 2 Pole, 65kA AIC, Bolt-on Style, rated to accept copper or aluminum conductors, Equipped with Padlocking device for hazardous energy control – Qty 1 Branch Circuit Breakers – 15A, 1 pole, 65kA AIC, Bolt-on Style, Rated to accept copper or aluminum conductors, Equipped with padlocking device for hazardous energy control – Qty 6 Branch Circuit Breakers – 20A, 1 pole, 65kA AIC, Bolt-on Style, Rated to accept copper or aluminum conductors, Equipped with padlocking device for hazardous energy control – Qty 6 Branch Circuit Breakers – 30A, 2 pole, 65kA AIC, Bolt-on Style, Rated to accept copper or aluminum conductors, Equipped with padlocking device for hazardous energy control – Qty 2

2.1.3 QED-2 Switchboard GCQ3

o Footprint: Existing Switchboard is 52" W x 90" H x 40" D; new switchboard shall match the footprint of the original switchboard to cover cable trough below unit and to mate to adjacent equipment.

o Enclosure shall be NEMA Type 1A, bottom-fed o All components used in the construction of this switchboard shall be new and unused.

o Shall include any necessary hardware and special tools for performing installation.

o Shall include wire tie retainers in vertical wireway.

o Shall include engraved master nameplate for MCC and engraved nameplates for each individual bucket. Nameplates shall be black surface, white letters, and stainless-steel nameplate screws. Once the submitted design package is approved by the government, the government will provide designations for each nameplate.

o System voltage is 480/277 VAC, 3 Phase, 4 Wire, 60 Hz o Shall include appropriately rated copper bus o Shall include 100% rated neutral bus constructed of copper o Shall include an appropriately rated continuous-ground bus of tin-plated copper at the bottom of section of switchboard o All Electrical Components: Designed for a Max Available Fault Current (RMS) of 65 kA o Shall include wiring NEMA Type 1B o All Control and Annunciation Circuits shall be designed for 120VAC power o Circuit Breakers shall be Square D Masterpact NW Draw Out Style Circuit Breakers to match existing inventory of Square D style breakers.

o Circuit Breaker shall be equipped with Micrologic 6.0P Trip Units.

o Circuit Breakers shall be sized appropriately to include appropriately sized frame and rating Plug o Circuit breaker shall be equipped with the following features:

Auxiliary switches 4A-4B Ready-to-Close 1A/1B from C Contact (PF) Undervoltage relay with adjustable Time Delay 120VAC Spring charging Motor Control wiring shall be designed for 120VAC Electronically controlled for Open/Close Overcurrent trip annunciation contacts Means of being locked out for Hazardous Energy control o Accessories:

Shall include a Circuit Breaker Test Set with Product Number: LV485500 for testing Masterpact

NW Style Circuit Breakers. Test Set shall include all accessories to allow for full functionality of Test Set to include Software, Licenses, Service Interface Kit/Case, Service Interface Module, Power Supplies, Communication Cables, and auxiliary connectors.

Shall include a picking device attachment for draw out style Masterpact NW Circuit Breakers.

Note, to be used with government’s pre-existing hoist equipment.

Lineup o 1200AF/700AT, 480VAC, 3 Pole Masterpact NW Style Circuit Breaker – GCQ3 Dire Emergency Feeder Breaker – Quantity 1 o 1200AF/1000AT, 480VAC, 3 Pole Masterpact NW Style Circuit Breaker – HCQ10 Emergency & Subfeed Breaker – Quantity 1 o 800AF/600AT, 480VAC, 3 Pole Masterpact NW Style Circuit Breaker - HSQ2-GCQ3 Tie Breaker – Quantity 1

3.0 SUBMITTALS

3.1 PRE-AWARD SUBMITTALS

Sufficient product information (i.e., brochures, cut sheets, options available and offered, etc.) for the Government to determine whether the offered product meets the salient requirements. Items in the documentation not related to the offer should be crossed or blackened out. A checklist of this specification alone will not be considered a sufficient offer.

3.2 POST-AWARD SUBMITTALS

Within 14 calendar days from contract award, the Contractor shall provide a design package to include design drawings and product data of the MCC, Switchboard, and auxiliary equipment/devices for government review to verify it meets the salient requirements prior to submitting order of equipment to the factory.

3.3 FINAL DELIVERY SUBMITTALS

At or before delivery, the Contractor shall provide the following for each product provided:

Operations & Maintenance Manual (Electronic version preferred) Final Manufacture’s Drawings Installation Guide Product Data Complete Warranty Information

4.0 SHIPMENT AND DELIVERY

Deliveries shall be coordinated with the Government at least fourteen calendar days in advance. All items shall be delivered FOB Destination to Dworshak Powerhouse no later than December 22, 2022 March 22, 2023. The Contractor shall be responsible for packing and shipping the components in a manner that will ensure undamaged and complete arrival to Dworshak Project. Delivery shall be made during Dworshak Project Normal Operating Hours, Monday through Thursday, 7:30 a.m. – 4:30 p.m. (Pacific), excluding federal holidays.

Delivery shall be to:

USACE Dworshak Powerhouse Attn: Contract Performance Specialist 1428 Northfork Drive Ahsahka, ID 83520

(End of Summary of Changes)