W68SBV02894718

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

The purpose of this amendment is to revise the Technical Specif ications by adding information in response to questions from industry.

Revisions are in red text. The quote date is extended until December 7, 2020.

1. CONTRACT ID CODE PAGE OF PAGES

J 1 11

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY 23-Nov-2020

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street , County, State and Zip Code) X W912EF21Q0007

X 9B. DATED (SEE ITEM 11)

09-Nov-2020

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN

REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

23-Nov-2020

CODE

USAED, WALLA WALLA - CONTRACTING DIV.

RUTH A. JOHNSON

201 N. THIRD AVENUE

WALLA WALLA WA 99362-1976

W912EF 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

W912EF21Q0007

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

SECTION SF 1449 - CONTINUATION SHEET

SOLICITATION/CONTRACT FORM

The required response date/time has changed from 23-Nov-2020 04:00 PM to 07-Dec-2020 04:00 PM.

The following have been modified:

TECHNICAL SPECIFICATIONS

REVISIONS IN RED

1.0 SCOPE OF WORK

The successful offeror shall supply the design, fabrication, assembly, wiring, testing, and delivery of a 125 VDC switchboard as specified herein.

2.0 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL(ASTM)

ASTM A123/A123M (2015) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products

ASTM A153/A153M (2016) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware

ASTM A240/A240M (2015b) Standard Specification for Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications

ASTM A653/A653M (2015; E 2016) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process

ASTM B187/B187M (2016) Standard Specification for Copper, Bus Bar, Rod and Shapes and General Purpose Rod, Bar and Shapes

ASTM D1535 (2014) Specifying Color by the Munsell System

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

NEMA ICS 6 (1993; R 2016) Industrial Control and Systems: Enclosures

NEMA PB 2 (2011) Deadfront Distribution Switchboards

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 70 (2017) National Electrical Code

UNDERWRITERS LABORATORIES (UL)

UL 44 (2014; Reprint Feb 2015) Thermoset-Insulated Wires and Cables

UL 489 (2016) Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures

UL 891 (2005; Reprint Oct 2012) Switchboards

AMERICAN CONCRETE INSTITUTE INTERNATIONAL (ACI)

ACI 318 (2014; Errata 1-2 2014; Errata 3-5 2015;

Errata 6 2016; Errata 7-9 2017) Building Code Requirements for Structural Concrete (ACI 318-

14) and Commentary (ACI 318R-14)

AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)

ASCE 7 (2010; Errata 2011; Supp 1 2013) Minimum Design Loads for Buildings and Other Structures

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE 693 (2018) Recommended Practice for Seismic Design of Substations

3.0 SUBMITTALS

Approval of the material submitted shall in no way relieve the Contractor from the responsibility of complying with the requirements of the specifications as to the suitability and quality of materials and workmanship.

Government approval is required for submittals. Submit the following as specified herein:

a. Switchboard Shop Contract drawings

i. Submit within 30 calendar days after Notice of Award.

Assembly and Detail drawings and data to demonstrate that all parts of the equipment will conform to the requirements and intent of these specifications. The drawings and data shall include sectional views of switchboard unit, description of removable elements, all relays and other devices, equipment lists, and nameplate schedule.

Outline drawings for coordination of equipment and physical location. Outline drawings shall include the overall dimensions and weights of the equipment; the size and location of conduit and cable entrances; details of provisions for bolting equipment to the floor, walls, and ceilings, and the equipment crate sizes.

Schematic and Wiring Diagrams shall show the one line diagrams of the switchboard assembly and a complete assembly full line wiring diagram showing that the equipment will function in a way to meet the requirements and intent of these specifications. All controls and external connections indicated by the contract drawings shall be accounted for. Point-to-point connection or wiring diagrams shall show all terminal blocks and connections between the blocks and switchboard equipment and shall provide a space at least three (3) inches below and adjacent to the terminal blocks in which external circuits, conduits or connections may be shown. The wiring diagrams shall be made as seen by an observer of the actual wiring and space on the drawings shall be provided for the addition of devices where actual mounting space exists on the structure. Drawings shall also show the proposed arrangement of terminal blocks and supports for incoming cables.

Seismic Restraint Detail Drawings. Submit detail drawings together with Structural Design Calculations for Seismic Restraints.

b. Product Data

i. Submit within 30 calendar days after Notice of Award.

Switchboards Nameplates Molded Case Circuit Breakers Terminal Blocks Relays Indicating Instruments Spare Parts List Seismic Equipment Certification

c. Factory Test Procedures

i. Submit within 30 calendar days prior to the proposed date of factory tests.

d. Certification of Seismic Requirement

i. Submit within 60 calendar days after Notice of Award.

e. Factory Test Reports

i. Submit within 30 days after completion of factory tests.

f. Operation and Maintenance Manuals

i. Submit with delivery of switchboard.

g. Design Data

i. Structural Design Calculations for Seismic Restraints

4.0 SWITCHBOARD FEATURES

a. Compliance with Standards

i. Equipment shall meet NEMA and UL standards and rating requirements as specified. No equivalent will be acceptable. Immediately notify the Contracting Officer of any requirements of the specifications or contractor proposed materials or assemblies that do not comply with NEMA or UL. International Electrotechnical Commission (IEC) rated equipment will not be considered an acceptable alternative to specified NEMA ratings.

b. Coordination

i. The general arrangement of the switchboard is shown on the contract drawings. Any modifications of the equipment arrangement or device requirements as indicated will be subject to the approval of the Contracting Officer. If any conflicts occur necessitating departures from the contract drawings, details of and reasons for departures shall be submitted and approved prior to implementing any change. Completely assemble all equipment at the factory. The switchboard may be disassembled into sections, if necessary, for convenience of handling and shipping.

c. Standard Products

i. Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship, and have been in satisfactory industrial use for 5 years prior to bid opening including applications of equipment and materials under similar circumstances and of similar size.

d. Switchboard

i. The switchboard shall be manufactured by EATON, type PRLC and shall not be taller than 78 inches in height, 36 inches in width and 18 inches in depth. The switchboard shall be a dead-front type switchboard conforming to NEMA PB 2 and labeled under UL 891. The switchboard shall be a completely enclosed self-supporting metal structures with the required number of vertical panel sections, buses, molded-case circuit breakers, and other devices as shown on the contract drawings.

ii. Switchboard: consisting of one vertical section, front and rear aligned.

iii. All circuit breakers: front accessible.

iv. Front and rear aligned switchboard: front accessible.

v. Where indicated, "space for future" or "space" means to include a vertical bus provided behind a blank front cover. Where indicated, "provision for future" means full hardware provided to mount a breaker suitable for the location.

vi. Completely factory engineered and assembled, including protective devices and equipment indicated with necessary interconnections, instrumentation, and control wiring.

e. Switchboard Ratings

i. Voltage rating: 125 volts DC ungrounded

ii. Continuous current rating of the main bus: 800 A

iii. Short-circuit current withstand rating: 65,000 A rms symmetrical

iv. UL listed and labeled

f. Enclosure

i. NEMA ICS 6 Type 1 fabricated entirely of 12 gauge steel.

ii. Bolted together with removable bolt-on side.

iii. Front doors: provide with stainless steel pad-lockable vault handles with a three (3) -point latch.

iv. Bases, frames and channels of enclosure: corrosion resistant and fabricated of ASTM

A240/A240M type 304 or 304L stainless steel.

v. Galvanized steel: ASTM A123/A123M, ASTM A653/A653M G90 coating, and ASTM

A153/A153M, as applicable. Galvanize after fabrication where practicable.

vi. Paint color: ASTM D1535 light gray No. 61.

vii. Paint coating system: comply with IEEE C57.12.28 for galvanized steel.

g. Bus

i. All buses shall be of copper and shall be tin or silver-plated throughout. Copper bars and shapes for bus conductors shall conform to the applicable requirements of ASTM B187/B187M.

The buses shall be insulated for not less than 600 volts. Tap connections shall be brazed, pressure-welded or bolted. All splices for field assembly shall be bolted. The buses shall be mounted on insulating supports of wet process porcelain, glass polyester, or suitable molded material, and shall be braced to withstand not less than 65,000 symmetrical amperes DC.

h. Ground Bus

i. A continuous copper ground bus shall be provided and secured to each vertical section along the entire length of the switchboard. A full clamp-type solderless copper or copper alloy lug for No. 2/0 AWG stranded copper cable shall be provided at each end of the bus for connection to the station grounding system.

i. Components

i. Switchboard shall be equipped with molded-case circuit breakers conforming to item MOLDED CASE CIRCUIT BREAKERS herein, and with frame sizes, trip ratings, and terminal connectors for attachment of outgoing power cables as shown on the contract drawings. The circuit breakers shall be of a type designed for bolted connection to buses.

j. Indicating Instruments

i. Switchboard type ammeter and voltmeter shall be both analog and digital and shall be provided where indicated on the contract drawings. The ammeter and voltmeter shall be Yokogawa Dual-Vue model or approved equal. The instrument shall be designed for back-connected, semi-flush mounting. Meters shall be 4-1/2 inch minimum rectangular type. Devices shall be provided for local indications of the 125VDC system. Meters shall have red LED digital display. The digital display shall be of 3-1/2 digit, 7 segment display, and 0.56 inches high display. The display shall have the following features and characteristics:

ii. Ammeter

Power Supply: 125VDC Input signal of 4-20mA and scale display range of 400-0-400 A 600A shunt shall be provided. Shunt shall be rated 0-50mV.

An identical ammeter shall be provided per paragraph SPARE PARTS herein. The local switchboard ammeter shall be able to handle remote meter, which will be installed by others.

iii. Voltmeter

Power Supply: 125VDC

b. DC Voltmeter: meter shall have input signal of 0-150V with a display range of 0-150 V.

k. Wiring

i. All control wire shall be stranded tinned copper switchboard wire with 600V flame-retardant insulation Type SIS meeting UL 44 and shall pass the VW-1 flame tests included in those standards. Hinge wire shall have Class K stranding. Current transformer secondary leads shall not be smaller than No. 10 AWG. The minimum size of control wire shall be No. 14 AWG.

Power wiring for 480V circuits and below shall be of the same type as control wiring and the minimum size shall be No. 12 AWG. Special attention shall be given to wiring and terminal arrangement on the terminal blocks to permit the individual conductors of each external cable to be terminated on adjacent terminal points. Indented ring tongue terminals shall be used for all control wiring terminated at terminal blocks.

ii. The switchboard shall have terminal blocks and all local switchboard devices shall be pre-wired prior to shipment. Wiring provision shall be provided inside the switchboard for remote meter wiring.

iii. Terminal Blocks

Control circuit terminal blocks for control wiring shall be molded or fabricated type with barriers, rated not less than 600V. The terminals shall be removable binding, fillister or washer head screw type, or of the stud type with contact and locking nuts. The terminals shall be not less than No. 10 in size and shall have sufficient length and space for connecting at least two indented terminals for 10 AWG conductors to each terminal. If space is a constraint, modular, pull apart terminal blocks may be proposed provided they are of the channel or rail-mounted type. The Contractor shall submit data showing that the proposed alternative will accommodate the specified number of wires, are of adequate current-carrying capacity, and are constructed to assure positive contact between current-carrying parts. Not less than four

(4) spare terminals or 15 percent shall be provided at each block or group of blocks, whichever is greater.

Marking Strips: White or other light-colored plastic marking strips fastened by screws to the molded sections at each control terminal block shall be provided for circuit designation.

Each connected terminal of each block shall have the circuit designation or wire number neatly printed on the marking strip with durable marking fluid. Wire numbers shall be taken from the contract drawings if shown, otherwise from approved Contractor shop contract drawings. Terminals for use with grounding conductors shall be green or yellow/green in color and of the same type and size per above. One reversible or two marking strips shall be furnished with each block.

l. Molded Case Circuit Breakers

i. Molded case circuit breakers shall conform to the applicable requirements of UL 489. The circuit breakers shall be Eaton, be manually-operated, quick-make/quick-break, common trip type, and shall be of automatic-trip type, unless otherwise specified. All poles of each breaker shall be operated simultaneously by means of a common handle. The operating handles shall clearly indicate whether the breakers are in "On," "Off," or "Tripped" position and shall have provisions for padlocking in the "Off" position. Personnel safety line terminal shields shall be provided for each breaker. The circuit breakers shall be products of only one manufacturer and shall be interchangeable when of the same frame size. The breaker shall include a bell alarm that indicates when the breaker has tripped. The contacts shall be suitable for 125 VDC and shall reset when the breaker is reset.

ii. Trip Units

Except as otherwise noted, the circuit breakers, of frame sizes and the trip unit ratings as shown on the contract drawings, shall be provided with combination thermal and instantaneous magnetic or solid-state trip units. The Government reserves the right to change the indicated trip ratings, within frame limits, of the trip devices at the time the Contractor’s shop drawings are submitted for approval. The breaker trip units shall be interchangeable and the instantaneous magnetic trip units shall be adjustable on frame sizes larger than 150 amperes. Non-adjustable instantaneous magnetic trip units shall be set at approximately 10 times the continuous current ratings of the circuit breakers.

iii. 125VDC Circuit Breakers

Circuit breakers for 125VDC circuits shall be two-pole, rated 125/250VDC or 125VDC, and shall have a UL listed minimum interrupting capacity of 42,000 symmetrical amperes at

250VDC.

m. Nameplates

i. Provide nameplates made of melamine plastic, 0.125" thick, black with white center core.

Corners shall be square. Accurately align lettering and engrave into the core. Minimum size of nameplates shall be 1 inch high by 2.5 inches wide. lettering shall be a minimum of 0.25 inches high. Nameplate designations shall be in accordance with lists on the contract drawings, and as a minimum shall be provided for the following equipment:

Switchboard Individually mounted circuit breakers in switchboard

n. Spare Parts

i. Furnish spare parts as specified below. All spare parts shall be of the same material and workmanship, shall meet the same requirements, and shall be interchangeable with the corresponding original parts furnished. Parts shall be listed on the Spare Parts List.

One - complete spare breaker of each type and size provided

Six - Fuses of each type and size

One - Ammeter for remote use in Control Room

One - Voltmeter for remote use in Control Room

o. Seismic Restraint

i. General Requirements

Apply the requirements for seismic protection measures described in this section to the equipment below. Accomplish resistance to lateral forces induced by earthquakes without consideration of friction resulting from gravity loads. Existing concrete strength is taken as f'c = 3,000 pounds per square inch (psi).

For detail drawings, include catalog cuts, templates, anchorage system including mechanical specifications of anchor bolts, erection and installation details for the items listed. Provide submittals complete in detail; indicate thickness, type, grade, class of metal, and dimensions;

and show construction details, anchorage, and installation. Stamp all drawings with the Professional Engineer (PE) stamp who performs and stamps the calculations required above.

ii. Code Requirements for Equipment Restraint

Complete seismic design for all equipment restraint in accordance with Chapter 13, "Seismic Design Requirements for Nonstructural Components," of ASCE 7 with the seismic design force computed as per Section 13.3 "Seismic Demands on Nonstructural Components" at a minimum.

For electrical equipment restraint, design in accordance with the applicable provisions in IEEE 693, or Section 13.3 of ASCE 7 whichever produces the more adverse seismic effects. For ASCE 7, use a spectral acceleration SDS = 0.247, IP = 1.50, and z/h=1. For IEEE 693, use a seismic qualification level of high.

iii. Requirements for Equipment Certification

Design, construct, and assemble the 125 VDC switchboard to be provided under this contract to withstand the seismic forces specified in paragraph "Code Requirements for Equipment Restraint." Provide Seismic Equipment Certification supported by testing or analysis stating the seismic capability of the equipment.

iv. Definitions

Undercut anchor. Undercut concrete anchors are bearing-type anchors designed to be installed in cured concrete in a hole with a conical undercut near its blind end.

Expansive anchor. Expansive concrete anchors are designed to be installed in cured concrete in a straight hole. Anchorage relies on an torque-controlled expansion wedge and the friction developed between the drilled hole and the expanded wedge.

Adhesive anchor. Adhesive concrete anchors are designed to be installed in cured concrete in a straight hole drilled with a roto-impact drill, consistent with the manufacturers printed installation instructions and the applicable ESR report. Anchorage relies on a chemical adhesive bond to the threaded rod and to the concrete.

v. Concrete Anchors

Furnish all concrete anchors details and other materials and accessories required for seismic restraint of equipment.

General Requirements for Fasteners to Concrete

Compute anchor capacity as per Chapter 17 of ACI 318 and reduce the anchor capacity to account for the effect of spacing between the anchor bolts and the distance between anchor bolt and the nearest concrete edge. Provide anchor test data in accordance with ICC ES Evaluation Services Reports (ESR) for each type and class of concrete anchor verifying the suitability of an anchor for the intended application. For all post-installed anchors, select anchors suitable for use in cracked concrete and under seismic loading.

Floor Mounted Equipment

Provide anchor detail for floor mounted equipment to concrete that is reinforced and integrally connected to the reinforced concrete structure. Intermittent tension developed due to laterally applied seismic force of 1000 pounds (lbs) or less may be resisted with expansive concrete anchors capable of resisting dynamic loading in cracked and un-cracked concrete. Resist intermittent tension developed due to laterally applied seismic force greater than 1000 lbs with undercut concrete anchors.

5.0 FACTORY TESTS

Each item of equipment supplied under this contract shall be given the manufacturer's routine factory tests and tests as specified below, to ensure successful operation of all parts of the assemblies.

a. Submit manufacturer's routine factory test procedures and production line tests within a minimum of 30 days prior to the proposed date of tests.

b. The factory test equipment and the test methods used shall conform to the applicable NEMA standards and shall be subject to the approval of the Contracting Officer. Submit factory test reports documenting all results, including all plotted data curves, all test conditions, a listing of test equipment complete with calibration certifications, and all measurements taken.

c. Report shall be signed and dated by a representative of the manufacturer. The cost of performing all tests shall be borne by the Contractor.

d. Switchboard Tests

i. Production Tests

Switchboard shall be completely assembled and given applicable production tests for assembled switchboard as specified in NEMA PB 2.

ii. Short Circuit Tests

If the unit is not UL labeled for the specified short circuit current requirement, design tests may be submitted demonstrating that satisfactory short-circuit tests have been made on a switchboard of similar type of construction and having the same available short circuit rating as the switchboard specified to be furnished under these specifications.

6.0 WARRANTY

Each component of the switchboard shall be covered by the manufacturer’s standard warranty on all parts, labor, and workmanship from factory defects.

7.0 OPERATION AND MAINTENANCE MANUALS

Submit an electronic copy of the Operation and Maintenance (O&M) Manual in high resolution.PDF format for the switchboard provided. The following information shall be included:

i. Bill of material and spare parts list

ii. Product cut sheets

iii. Procedures for equipment installation and maintenance.

iv. Procedures for trouble shooting equipment

v. Shop drawings

Any information pertaining to models or components not supplied under this contract shall be crossed out.

The O&M Manuals shall also include a sheet at the front of the manual listing the name, phone number, contact information for the manufacturer, and a distributor where spare parts can be purchased. The complete contract award number (as found on the contract Award document) shall also be included.

8.0 SHIPMENT AND DELIVERY

The switchboard shall be shipped as completely assembled and wired as feasible. The switchboard, spare parts and any other equipment shall be wrapped suitably or otherwise protected from damage during shipment.

The Government will assist with unloading the items at the site. Verify the condition and quantity of the items upon delivery by the Contracting Officer and acknowledge receipt and condition thereof in writing.

If delivered items are damaged or a shortage is determined, notify the Contracting Officer of such in writing within 24 hours after delivery.

All items shall be delivered FOB to Ice Harbor Lock and Dam within 24 weeks of contract award. The Contractor shall be responsible for packing and shipping the items in a manner that will ensure undamaged and complete arrival to the Project site. No shipments are allowed other than normal business hours of Monday through Thursday 7:00 a.m. to 4:00 p.m., excluding federal holidays.

All shipments shall be delivered to:

Ice Harbor Lock and Dam 2763 Monument Drive Burbank, WA 99323

(End of Summary of Changes)