Post Office Box 1446 • Auburn, Washington 98071-1446 • PHONE (253) 351-0677 • FAX (253) 351-0688 • E-mail: fullertona@medtoxnw.com Website: www.medtoxnw.com

May 2, 2017

Mr. Greg Nespor, AIA WJA Design Collaborative 119 South Main Street, Suite 400 Seattle, Washington 98104 Subject: CLIN 0001 Repair Sanitary Sewer System

MTEF Facility, Yakima Training Center (YTC) Joint Base Lewis-McChord, Washington Med-Tox Northwest Project No. A-8321.9

Dear Mr. Nespor:

On March 13, 14 and 15, 2017 Anthony Fullerton and Ingrid Holznagel of Med-Tox Northwest (MTNW) conducted an asbestos survey of the underground water and sewer lines associated with CLIN 0001 Repair Sanitary Sewer System MTEF Facility YTC –Joint Base Lewis McChord, Washington. The existing water and sewer lines associated with the YRS compound were included in this survey. This survey was conducted to identify whether the pipes associated with both systems were suspect asbestos-containing materials.

MTNW employs inspectors certified by an Environmental Protection Agency (EPA)-approved training provider to provide Asbestos Hazard Emergency Response Act (AHERA) building surveys, including renovation and demolition surveys. A copy of Mr. Fullerton’s and Ms. Holznagel’s AHERA certificates are attached.

Applied Professional Services, Inc. (APS) provided potholing which included using water and air suction to excavate dirt to locate underground water and sewer lines. APS was contracted to locate several utilities while on site (water, sewer, electrical). MTNW sampled materials associated with the water and sewer pothole locations. Subsurface pipes were approximately four to ten feet underground. All potholing locations were identified by APS and shown on the attached site figure. Due to the destructive nature of the testing and to the risk of breaking a pipe, most sewer pipe samples were collected from manholes directly adjacent to identified potholing locations. The water pipe that was sampled came from an exposed pipe located next to the SCIF building. Conversations with the base water department representative indicated that the exposed pipe is typical of the buried pipe. Pothole locations and findings are as follows in Table 1:

CLIN 0001 Repair Sanitary Sewer System MTEF Facility, Yakima Training Center (YTC)

May 2017 WJA Design Collaborative

Table 1. Summary of Potholing Locations

Number Test Location Findings Pothole 1 Northwest side of

SCIF

ACM water pipe buried in pea gravel in-fill approximately 42-inches below the surface.

No access due to collapsing hole. Exposed water pipe next to the SCIF building directly adjacent to potholes 1 and 2 was sampled.

Exposed pipe is approximately +/- 6-inches.

Pothole 2 Northwest side of

SCIF

Assumed ACM water pipe buried in pea gravel in-fill approximately 48-inches below the surface. No access due to collapsing hole.

Pothole 3 Northwest side of

SCIF

Assumed ACM water pipe buried in pea gravel in-fill approximately 73-inches below the surface. No access due to collapsing hole.

Pothole 4 Northwest side of

SCIF

Assumed ACM water pipe buried in pea gravel in-fill approximately 73-inches below the surface. No access due to collapsing hole.

Pothole 15 Inside fence of SCIF- northwest corner of building.

Water pipe- Dug to 8-foot depth and no pipes located.

Pothole 19 Inside fence of SCIF, northwest side of building, directly west of pothole location 3 and 4.

ACM cement sewer pipe approximately 50-inches down. Pipe is +/- 8-inches in diameter.

Sample was collected from manhole located 12-feet to the southwest of pothole location.

Pothole 20 North end of fenced in area, along gravel road leading to retention ponds.

ACM cement sewer pipe approximately 40-inches down. Pipe is +/- 8-inches in diameter.

Sample was collected from manhole located right next to pothole location.

Sewer manhole access 200116

North of pothole 20 on gravel road leading to retention pond. Identifying number painted on manhole cover.

ACM cement sewer pipe approximately 60-inches down. Pipe is +/- 8-inches in diameter.

Sample was collected from manhole.

Sewer manhole access 200117

North of pothole 200116 on gravel road leading to retention pond.

Identifying number painted on manhole

ACM cement sewer pipe approximately 40-inches down. Pipe is +/- 8-inches in diameter.

Sample was collected from manhole.

Number Test Location Findings cover.

Sewer manhole access 200118

North of pothole 200117 on gravel road inside retention pond fencing.

Identifying number painted on manhole cover.

ACM cement sewer pipe approximately 46-inches down. Pipe is +/- 8-inches in diameter.

Sample was collected from manhole.

Sewer manhole access 200118

North of pothole 20017 on gravel road inside retention pond fencing.

Identifying number painted on manhole cover.

ACM cement sewer pipe approximately 44-inches down. Pipe is approximately +/- 8-inches in diameter. Sample was collected from manhole.

Note: All sewer and water pipe sampled was determined to be asbestos-containing.

Table 2 lists materials that were identified as asbestos-containing:

Table 2. Summary of Asbestos-Containing Materials

Material Location Friable

CLIN 0001-POTHOLING

Gray cementitious pipe Sewer pipe locations No Gray cementitious transite water pipe Water pipe locations (sample collected from exposed pipe) No

Note: This table is not to be used without the complete survey document for additional information.

Table 3 lists all materials sampled during the survey, including locations of potholing:

Table 3. Summary of Materials Sampled for Asbestos

Sample Material Location AHERA Type HM Result 8321.9-AF-01 6-inch cementitious water pipe

SE of pothole location #19- Exposed water pipe located next to building

Misc. 01 18% CHR

8321.9-AF-02 6-inch cementitious water pipe collar/cap

SE of pothole location #19- Exposed water pipe located next to building

Misc. 02 13% CHR 3% Crocidolite

8321.9-AF-03 8-inch cementitious sewer pipe

Manhole located SW of pothole location #19

Misc. 03 16% CHR 4% Crocidolite

Sample Material Location AHERA Type HM Result 8321.9-AF-04 8-inch cementitious sewer pipe

Manhole-pothole location #20

Misc. 03 14% CHR 2% Crocidolite

8321.9-AF-05 8-inch cementitious sewer pipe

Manhole- location 200116, down line from #20

Misc. 03 17% CHR 3% Crocidolite

8321.9-AF-06 8-inch cementitious sewer pipe

Manhole- location 200117, down line from #200116

Misc. 03 15% CHR 3% Crocidolite

8321.9-AF-07 8-inch cementitious sewer pipe

Manhole- location 200118, down line from #200117

Misc. 03 19% CHR 6% Crocidolite

CHR = Chrysotile asbestos, HM = homogeneous material, Misc = miscellaneous.

The seven bulk samples collected in Table 3 were analyzed by Polarized Light Microscopy (PLM) dispersion staining EPA Method 600/R-93/116 by Seattle Asbestos Test, LLC (SAT). SAT is accredited through the National Voluntary Laboratory Accreditation Program (NVLAP) of the U. S. Department of Commerce. This accreditation does not constitute endorsement, but rather a finding of laboratory competence. The NVLAP participant number for SAT is 200768-0 laboratory competence. Their NVLAP participant number is 102021 (certification is attached). A copy of the laboratory analytical report is also attached.

Med-Tox Northwest recommends, and state law requires, that all asbestos materials identified in Table 1 be removed prior to renovation or demolition activities that may impact them. MTNW recommends that this survey report be placed on-site during site activities and copies provided to the contractor(s) bidding and performing work. Washington Industrial Safety and Health Act (WISHA), Occupational Safety and Health Administration (OSHA) require that the report be on-site and available for review during the entire project duration.

Sampling was performed consistent with the level of care and skill ordinarily exercised by professionals currently practicing under similar conditions in the area. No other warranty, expressed or implied, is made.

This report has been prepared for the exclusive use of WJA Design Collaborative and its’ designates for this project only. The analyses, conclusions, and recommendations presented in this report are based on conditions encountered at the time of our study and our experience and judgment. MTNW cannot be held responsible for interpretation by others of the data contained in this report; any use of this report shall include the entire document. This survey is not intended for use as abatement plans and/or specifications.

If you have any questions or require additional information, please call me at (253) 351- 0677.

Sincerely, Anthony Fullerton Project Manager Med-Tox Northwest Attachments

Hazardous Building Materials Survey—Repair Sanitary Sewer System YSR Compound- Yakima Training Center

WJA Design Collaborative Appendix C-1

Table-Summary of Materials Sampled for Asbestos Sample Material Location AHERA Type HM Result

8321.9-AF-01 6-inch cementitious water pipe

SE of pothole location #19- Exposed water pipe located next to building

Misc. 01 18% CHR

8321.9-AF-02 6-inch cementitious water pipe collar/cap

SE of pothole location #19- Exposed water pipe located next to building

Misc. 02 13% CHR 3% Crocidolite

8321.9-AF-03 8-inch cementitious sewer pipe

Manhole located SW of pothole location #19

Misc. 03 16% CHR 4% Crocidolite

8321.9-AF-04 8-inch cementitious sewer pipe

Manhole-pothole location #20

Misc. 03 14% CHR 2% Crocidolite

8321.9-AF-05 8-inch cementitious sewer pipe

Manhole- location 200116, down line from #20

Misc. 03 17% CHR 3% Crocidolite

8321.9-AF-06 8-inch cementitious sewer pipe

Manhole- location 200117, down line from #200116

Misc. 03 15% CHR 3% Crocidolite

8321.9-AF-08 8-inch cementitious sewer pipe

Manhole- location 200118, down line from #200117

Misc. 03 19% CHR 6% Crocidolite

CHR = Chrysotile asbestos, HM = homogeneous material, NA= not analyzed, ND = none detected

8321.9 Repair Sanitary Sewer System MTEF Facility YTC Rpt AF 050117revi...
Table 3. Summary of Materials Sampled for Asbestos
Asbestos Table YRS Compound Repair Sanitary Sewer System YTC MTNW Project 8321.9
Table-Summary of Materials Sampled for Asbestos
201710459
Potholing Location Drawing
AF BI Exp 090717