AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

W912DW-16-R-0004 FY14 AUC Fire Station (PN 76776) Joint Base Lew is-McChord, WA

(see continuation page)

1. CONTRACT ID CODE PAGE OF PAGES

1 2

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY 25-Nov-2015

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912DW-16-R-0004

X 9B. DATED (SEE ITEM 11)

03-Nov-2015

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN

REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

25-Nov-2015

CODE

USA ENGINEER DISTRICT, SEATTLE

ATTN: CECT-NWS

4735 EAST MARGINAL WAY SOUTH, BLDG. 1202

SEATTLE WA 98134-2388

W912DW 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

W912DW-16-R-0004

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

SECTION SF 30 - BLOCK 14 CONTINUATION PAGE

The following have been added by full text:

R0002

1. This amendment one (0002) provides for the following changes:

a. Revision to the following drawings: ES001, ES002, ES502, and TS001.

2. The proposal submittal time and date of December 3, 2015 at 2:00:00 p.m. LOCAL TIME remains the same.

3. The attached revised sections are to be replaced in their entirety. Specifications changes are generally identified, for convenience, either by strikeout for deletions, and double underlining of text for additions or a single dark line in the margin. All portions of the revised sections shall apply whether or not changes have been indicated.

4. NOTICE TO OFFERORS: Offerors must acknowledge receipt of this amendment by number and date on offer.

Encl:

Drawings as stated (revised)

(End of Summary of Changes)

L

C

T

A M

B L Y

N

E N

D

E

1 2 3 4 5

D

C

B

A

D R

A W

N

B

Y

D E

S I G

N

B

Y

S B

M T

B

Y

S I Z

E

F I L

E

N

A M

E

D A

T E

C O

N T

R A

C

N

O

S O

L I C

I T

A T

I O

N

N

O

U S

A

R M

Y

C

O R

P

F

E

N G

I N

E E

R S

M A

R K

D E

S C

R I P

T I O

N D

A T

E A

P P

R

C K

D

B

Y

SEATTLE DISTRICT

US ARMY CORPS OF

ENGINEERS ®

X

S E

A T

T

E

D

I S

T R

I C

T

S E

A T

T

W

S

H I N

G T

O N

F I L

E

N

U M

B E

R

P L

A

L E

P L

T

E

T S

A N

G

L E G E N D

EXISTING UNDERGROUND POWEREUP

EOP

EXISTING OVERHEAD POWER

EXISTING UNDERGROUND POWER TO BE REMOVED

R

R0002

BLDG 3096

G

E

N

E

R

A

T

O

R

C

O

N

D

U

I T

S

V

L

S

V

G

H

T

I

G

N

E

L

A

T

I O

N

C

O

N

D

U

I T

L

C

T

A M

B L Y

N

E N

D

E

N

SCALE:

40' 80'40

1"=40'

SCALE:

1' = 40'

ELECTRICAL SITE PLAN

1 2 3 4 5

D

C

B

A

D R

A W

N

B

Y

D E

S I G

N

B

Y

S B

S I Z

E

F I L

E

N

A M

E

D A

T E

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

M

Y

C

O R

E

N G

I N

E E

R S

M A

R K

D E

S C

R I P

T I O

N D

A T

E A

P P

R

C K

D

B

Y

SEATTLE DISTRICT

US ARMY CORPS OF

ENGINEERS ®

S E

A T

T

S

T R

I C

T

S E

A T

T

S

H I N

G T

O N

F I L

E

N

U M

B E

R

P L

A

L E

P L

T

E

T S

A N

G

R0002

POWER RISER

NOTE: ALL MEDIUM-VOLTAGE CONDUCTORS SHALL BE 15kV, EPR, CU, 133 PERCENT INSULATION, WITH INSULATION SHIELDING.

SOUTH 18TH ST AIRPORT WAY (SOUTH)

VAULT

JUNCTION

EXISTING

PROVIDED IN RSU CONTRACT.

EXISTING 2-5", SCHEDULE 40 PVC. ONE DUCT IS A

SPARE WITH PULL WIRE. THE OTHER DUCT CONTAINS

EXISTING 3#4/0, 15kV CU, EPR CONDUCTORS WITH

BARE #2/0 CONDUCTOR IN ENCASEMENT.

3 TYPICAL DETAIL

GENERAL NOTES

TYPICAL DETAIL 4

1. COORDINATE UNDERGROUND DISTRIBUTION SYSTEM INSTALLATION WITH JOINT BASE LEWIS-McCHORD

PUBLIC WORKS, EXTERIOR ELECTRIC.

2. DEPTH AS REQUIRED TO AVOID EXISTING UTILITIES, MEET CODE REQUIREMENTS, AND ENTER VAULTS AT

THE LOWEST POINT POSSIBLE.

3. MEET ALL OSHA/WISHA SAFETY STANDARDS FOR STABLE SLOPE AND/OR SHORING REQUIREMENTS.

4. ALL DUCTS SHALL ENTER VAULTS AT THE LOWEST KNOCKOUT. COORDINATE WITH CONTRACTING OFFICER

PRIOR TO PLACEMENT.

5. PROVIDE A PULLWIRE IN ALL DUCTS.

6. ALL DUCTBANKS SHALL BE CONSTRUCTED WITH FORMWORK. OVER EXCAVATE TRENCH AS NECESSARY TO

CONSTRUCT FORMWORK.

7. DUCT LINES SHALL BE LAID WITH A MINIMUM SLOPE OF 4 INCHES PER 100 FEET SHORT-RADIUS

MANUFACTURED 90-DEGREE DUCT BENDS MAY BE USED ONLY FOR POLE OR EQUIPMENT RISERS. THE

MINIMUM MANUFACTURED BEND RADIUS SHALL BE 18 INCHES FOR DUCTS OF LESS THAN 3 INCH DIAMETER

AND 36 INCHES FOR DUCTS 3 INCHES OR GREATER IN DIAMETER. OTHERWISE, LONG SWEEP BENDS HAVING

A MINIMUM RADIUS OF 25 FEET SHALL BE USED FOR A CHANGE OF DIRECTION OF MORE THAN 5 DEGREES, EITHER HORIZONTALLY OR VERTICALLY BOTH CURVED AND STRAIGHT SECTIONS MAY BE USED TO FORM

LONG SWEEP BENDS, BUT THE MAXIMUM CURVE USED SHALL BE 30 DEGREES AND MANUFACTURED BENDS

SHALL BE USED. DUCTS SHALL BE PROVIDED WITH END BELLS WHENEVER DUCT LINES TERMINATE IN

MANHOLES OR HANDHOLES.

8. DUCTS SHALL BE KEPT CLEAN OF CONCRETE, DIRT, OR FOREIGN SUBSTANCES DURING CONSTRUCTION.

DUCTS SHALL BE SUFFICIENTLY PLUGGED TO PREVENT ENTRY OF ANY WATER OR SOLID SUBSTANCES.

9. ALL POWER DUCTBANKS SHALL BE ENCASED IN 2000 PSI CONTROLLED DENSITY FILL (CDF), EXCEPT 3000 PSI

REINFORCED CONCRETE SHALL BE USED UNDER ROADS OR PAVED AREAS SUBJECT TO VEHICULAR

TRAFFIC.

10. IN ALL DUCTBANKS, PROVIDE METALLIC WARNING TAPE ABOVE THE DUCTS AND LOCATE 12 INCH BELOW

FINISHED GRADE.

11. DUCT LINE ENCASEMENTS SHALL BE MONOLITHIC CONSTRUCTION. WHERE A CONNECTION IS MADE TO A

PREVIOUSLY POURED ENCASEMENT, THE NEW ENCASEMENT SHALL BE WELL BONDED OR DOWELED TO THE

EXISTING ENCASEMENT.

12. AT ANY POINT, TOPS OF CONCRETE ENCASEMENTS SHALL BE NOT LESS THAN THE COVER REQUIREMENTS

LISTED IN NFPA 70.

13. WHERE DUCTS ARE JACKED UNDER EXISTING PAVEMENT, RIGID STEEL CONDUIT WILL BE INSTALLED

BECAUSE OF ITS STRENGTH. TO PROTECT THE CORROSION-RESISTANT CONDUIT COATING, PREDRILLING

OR INSTALLING CONDUIT INSIDE A LARGER IRON PIPE SLEEVE (JACK-AND-SLEEVE) IS REQUIRED.

14. SEPARATORS OR SPACING BLOCKS SHALL BE MADE OF STEEL, CONCRETE, PLASTIC OR A COMBINATION OF

THESE MATERIALS PLACED NOT FARTHER APART THAN 4 FEET ON CENTERS. DUCTS SHALL BE SECURELY

ANCHORED TO PREVENT MOVEMENT DURING THE PLACEMENT OF CONCRETE AND JOINTS SHALL BE

STAGGERED AT LEAST 6 INCHES VERTICALLY.

LOCATED AT AIRPORT WAY AND FIRE STATION.

STUBBED OUT 5 FEET FROM PAD WITH

PULL WIRE, ONE FOR REGIONAL FLIGHT

CENTER, ONE FOR SPARE

TO JUNCTION BOX ON

SOUTH 18TH STREET

NEW

PUMP HOUSE

VAULT

EXISTING

PAD MTD

TRANS

NEW

75 kVA

NEW

FIRE STATION

IN FRONT

OF FIRE

STATION

EXISTING 2-WAY 4" POWER DUCTBANK WITH

ONE BARE #2 COPPER WIRE IN ENCASEMENT.

PROVIDE NEW WIRE - 3#2, 15 kV, CU, EPR

CONDUCTORS IN ONE POWER DUCT AND LEAVE

ONE SPARE POWER DUCT WITH PULL WIRE.

PRIMARY

VAULT

JUNCTION

EXISTING

PRIMARY

VAULT

EXISTING

PAD MTD

TRANS

NEW

500 kVA

STUBBED OUT 5 FEET FROM PAD

WITH PULL WIRE, ONE FOR SPARE

NOTE: NEW 75 kVA (PUMP HOUSE)

TRANSFORMER IS LOOP FED FROM 500 kVA

(FIRE STATION) TRANSFORMER

TERMINATE CABLE ON

PRIMARY LUGS OF

TRANSFORMER WITH

200A, 15kV LOAD

BREAK ELBOW.

L

C

T

A M

B L Y

N

E N

D

E

1 2 3 4 5

D

C

B

A

D R

A W

N

B

Y

D E

S I G

N

B

Y

S B

S I Z

E

F I L

E

N

A M

E

D A

T E

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

M

Y

C

O R

E

N G

I N

E E

R S

M A

R K

D E

S C

R I P

T I O

N D

A T

E A

P P

R

C K

D

B

Y

SEATTLE DISTRICT

US ARMY CORPS OF

ENGINEERS ®

S E

A T

T

S

T R

I C

T

S E

A T

T

S

H I N

G T

O N

F I L

E

N

U M

B E

R

P L

A

L E

P L

T

E

T S

A N

G

R0002

BLDG 3096

CONTRACTOR SHALL INSTALL

6-4" CONDUITS TO COMM ROOM

75 PAIR COPPER, 24 STRANDS

FIBER. SEE DETAIL TS501.

EXISTING FROM RSU CONTRACT

75 PAIR COPPER, 24 SMFOC

COILED IN EXISTING MANHOLE.

EXISTING FROM RSU CONTRACT

25 PAIR COPPER, 12 SMFOC

COILED IN EXISTING MANHOLE.

EXISTING FROM RSU CONTRACT

200 PAIR COPPER, 48 SMFOC IN

EXISTING CONDUIT.

SEE DETAIL TS501.

EXISTING FROM RSU CONTRACT

75 PAIR COPPER, 24 SMFOC IN

EXISTING CONDUIT.

SEE DETAIL TS501.

EXISTING FROM RSU CONTRACT

100 PAIR COPPER, 12 SMFOC

COILED IN EXISTING MANHOLE.

EXISTING FROM RSU CONTRACT

100 PAIR COPPER, 36 SMFOC IN

EXISTING CONDUIT.

SEE DETAIL TS501.

COMMUNICATIONS MANHOLE

AND SPLICE CASE PROVIED

IN RSU-SITE CONTRACT.

TYPICAL THIS SHEET.

L

C

T

A M

B L Y

N

E N

D

E D

C

O L L I E

R

1 2 3 4 5

D

C

B

A

D R

A W

N

B

Y

D E

S I G

N

B

Y

S B

S I Z

E

F I L

E

N

A M

E

D A

T E

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

M

Y

C

O R

E

N G

I N

E E

R S

M A

R K

D E

S C

R I P

T I O

N D

A T

E A

P P

R

C K

D

B

Y

SEATTLE DISTRICT

US ARMY CORPS OF

ENGINEERS ®

S E

A T

T

S

T R

I C

T

S E

A T

T

S

H I N

G T

O N

F I L

E

N

U M

B E

R

P L

A

L E

P L

T

E

T S

A N

G

N

SCALE:

40' 80'40

1"=40'

SCALE:

1' = 40'

COMMUNICATIONS SITE PLAN

R0002

SF30_R0002
ES001YN80-22x34-AmendR0002-Nov2015
ES002YN80-22x34-AmendR0002-Nov2015
ES502YN80-22x34-AmendR0002-Nov2015
TS001YN80-22x34-AmendR0002-Nov2015