Design-Bid-Build

FY13 Restoration & Modernization, Fire Suppression in Alert Facility BMEWS

Thule Air Base, Greenland

W912DS-13-B-0007

Specifications

March 5, 2013

THIS PAGE IS BLANK

COVER SHEET

NEW YORK DISTRICT

CORPS OF ENGINEERS

NEW YORK, NEW YORK 10278-0090

INVITATION FOR BIDS

FOR

FY 13 RESTORATION & MODERNIZATION,

FIRE SUPPRESSION IN ALERT FACILITY BMEWS

THULE AIR BASE

GREENLAND

1. Attached is INVITATION FOR BIDS (IFB) NO. W912DS-13-B-0007 .

2. BIDS MUST BE SET FORTH full, accurate, and complete information as required by this Invitation for Bids, including attachments. The penalty for making false statements in bids is prescribed under Title 18, United States Code, Section 1001.

3. SUBMISSION OF BIDS: Complete details concerning proper submission of bids are contained in the INSTRUCTIONS, CONDITIONS, AND NOTICES TO BIDDERS (Section 00100).

4. Note the REQUIREMENT FOR AFFIRMATIVE ACTION of the EQUAL

OPPORTUNITY clause as it applies to the contract resulting from this solicitation.

(See paragraph NOTICE OF REQUIREMENT FOR AFFIRMATIVE ACTION TO ENSURE EQUAL EMPLOYMENT OPPORTUNITY in Section 00100 of this IFB).

5. REPRESENTATIONS AND CERTIFICATIONS – SECTION 00600

Bidders and Offerors are required to complete the REPRESENTATIONS AND CERTIFICATIONS and submit them with their bids.

Within Section 00600, note in particular the PROHIBITION SEGREGATED FACILITIES. Failure of a bidder or offeror to agree to the certification will render his bid or offer non-responsive to the terms of solicitations involving awards of contracts exceeding $10,000 which are not exempt from the provisions of the Equal Opportunity Clause (1984 APR).

6. Please review all bonds and accompanying documents required to be submitted.

Bonds, Powers of Attorney, statements of authenticity and continuing validity, and all related documents MUST NOT bear computer printer-generated signatures and/or seals. Documents bearing signatures and/or seals generated as part of a document, as opposed to being affixed to the document after its generation, will not be accepted.

Submission of such documents may render the bid or offer non-responsive and ineligible for award.

THIS PAGE IS BLANK

CHECKLIST - 1

US ARMY ENGINEER DISTRICT, NEW YORK

INVITATION FOR BIDS NO. W912DS-13-B-0007

CHECK LIST FOR BIDDERS

ATTACHED IS IFB NO. W912DS-13-B-0007

FY 13 RESTORATION & MODERNIZATION,

FIRE SUPPRESSION IN ALERT FACILITY BMEWS

THULE AIR BASE

GREENLAND

ALL INFORMATION REQUIRED BY THE TERMS OF THIS SOLICITATION

MUST BE FURNISHED. MISTAKES OR OMISSIONS MAY RENDER YOUR

OFFER INELIGIBLE FOR AWARD. IMPORTANT ITEMS FOR YOU TO CHECK

ARE INCLUDED IN BUT NOT LIMITED TO THOSE LISTED BELOW. THIS

INFORMATION IS FURNISHED ONLY TO ASSIST YOU IN SUBMITTING A

PROPER BID

__HAVE YOU ACKNOWLEDGED ALL AMENDMENTS?

__HAVE YOU COMPLETED THE “REPRESENTATIONS AND CERTIFICATIONS”

(SECTION 00600) PORTION OF THE SOLICITATION?

__IS YOUR DUNS NUMBER LISTED ON THE STANDARD FORM 1442?

__IS YOUR BID PROPERLY SIGNED?

__IS YOUR BID GUARANTEE PROPERLY SIGNED BY BOTH THE BIDDER AND

SURETY AND ARE ALL SEALS AFFIXED?

__DO THE BID BOND AND ACCOMPANYING DOCUMENTS BEAR

SIGNATURES AND SEALS AFFIXED AFTER THE DOCUMENT WAS

GENERATED, AS OPPOSED TO COMPUTER PRINTER-GENERATED

SIGNATURES AND/OR SEALS?

__HAVE YOU ENSURED THAT YOU HAVE NOT RESTRICTED YOUR OFFER

BY ALTERING THE PROVISIONS OF THE SOLICITATION?

__WHEN REQUIRED, HAVE YOU ENTERED A UNIT PRICE FOR EACH PRICE

ITEM? (THE SOLICITATION SPECIFICALLY STATES WHEN THIS IS

NECESSARY.)

__ARE DECIMALS IN YOUR PRICES IN THE PROPER PLACE? ARE YOUR

CHECKLIST - 2

FIGURES LEGIBLE?

__IF YOU HAVE MADE ERASURES OR CORRECTIONS ON YOUR BID, ARE

THEY INITIALED BY THE PERSON SIGNING THE BID?

__DOES THE ENVELOPE CONTAINING YOUR BID PROPERLY IDENTIFY

THAT IT ISA SEALED BID AND DOES IT CONTAIN THE CORRECT

SOLICITATION NUMBER AND BID OPENING TIME?

__WILL YOUR OFFER ARRIVE ON TIME? (SEE PARAGRAPH ENTITLED “LATE

SUBMISSIONS, MODIFICATIONS, AND WITHDRAWALS OF BIDS” IN THE

INSTRUCTIONS, CONDITIONS, AND NOTICES TO BIDDERS, SECTION 00100

OF THE SOLICITATION.)

NOTE: THERE ARE INCREASED SECURITY MEASURES AT JACOB K.

JAVITS FEDERAL BUILDING, 26 FEDERAL PLAZA THAT MAY AFFECT THE

TIME IT TAKES TO ENTER THE BUILDING. BIDDERS IS RESPONSIBLE TO

ENSURE THAT ITS BID IS SUBMITTED TIMELY.

FY13 Restoration & Modernization, Fire Suppression in Alert Facility BMEWS, TABLE OF CONTENTS - 1

MAIN TABLE OF CONTENTS

SECTION TITLE

00010 SF 1442 AND BIDDING SCHEDULE

00100 INSTRUCTIONS TO BIDDERS

00600 REPRESENTATIONS AND CERTIFICATIONS

00700 CONTRACT CLAUSES

00 80 00.00 18 SPECIAL CONTRACT REQUIREMENTS

DIVISION 00 – PROCUREMENT AND CONTRACTING REQUIREMENTS

00 31 10 METRIC MEASUREMENTS

DIVISION 01 – GENERAL REQUIREMENTS

01 02 10.00 06 PROJECT DESCRIPTION AND DESIGN REQUIREMENTS

01 12 00.00 18 DESIGN AND RECORD DRAWING REQUIREMENTS

01 32 01.00 18 PROJECT SCHEDULE

01 33 00.00 18 SUBMITTAL PROCEDURES

01 35 26 GOVERNMENT SAFETY REQUIREMENTS

01 42 00 SOURCES FOR REFERENCE PUBLICATIONS

01 45 02.00 18 QUALITY CONTROL SYSTEM (QCS)

01 45 04.00 18 CONTRACTOR QUALITY CONTROL

01 45 20.00 18 TESTING FOR MECHANICAL AND ELECTRICAL SYSTEMS

01 52 60.00 18 CONSTRUCTION INDOOR AIR QUALITY (IAQ) MANAGEMENT

01 57 20.00 10 ENVIRONMENTAL PROTECTION

01 62 35 RECYCLED/RECOVERED MATERIALS

01 74 19 CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT

01 78 00.00 18 CLOSEOUT SUBMITTALS

01 78 23.00 18 OPERATION AND MAINTENANCE DATA

DIVISION 07 – THERMAL AND MOISTURE PROTECTION

07 84 00 FIRESTOPPING

DIVISION 21 - FIRE SUPPRESSION

21 12 00 STAND PIPE SYSTEMS

21 13 17.00 10 DRY PIPE SPRINKLER SYSTEM, FIRE PROTECTION

21 13 18.00 10 REACTION AND DELUGE SPRINKLER SYSTEMS, FIRE

PROTECTION

21 30 00 FIRE PUMPS

DIVISION 28 - ELECTRONIC SAFETY AND SECURITY

28 31 64.00 10 FIRE DETECTION AND ALARM SYSTEM, ADDRESSABLE

APPENDICES

APPENDIX A SITE PHOTOS

APPENDIX B BMEWS AS-BUILTS

APPENDIX C AFFIRMATIVE PROC PLAN

APPENDIX D DBA WAIVER

APPENDIX E PACER GOOSE SHIPPING INSTRUCTIONS

FY13 Restoration & Modernization, Fire Suppression in Alert Facility BMEWS, TABLE OF CONTENTS - 2

APPENDIX F SHIPPING RATES GOV FURNISHED TRANSPORT

APPENDIX G 2013 SHIPPING RATES

-- End of Project Table of Contents --

Fire Suppression in Alert Facility BMEWS BMEWS

SECTION 00 31 10

METRIC MEASUREMENTS

04/06

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

IEEE/ASTM SI 10 (2002) American National Standard for Use of the International System of Units (SI):

The Modern Metric System

1.2 GENERAL

This project includes metric units of measurements. The metric units used are the International System of Units (SI) developed and maintained by the General Conference on Weights and Measures (CGPM); the name International System of Units and the international abbreviation SI were adopted by the 11th CGPM in 1960. A number of circumstances require that both metric SI units and English inch-pound (I-P) units be included in a section of the specifications. When both metric and I-P measurements are included, the section may contain measurements for products that are manufactured to I-P dimensions and then expressed in mathematically converted metric value (soft metric) or, it may contain measurements for products that are manufactured to an industry recognized rounded metric (hard metric) dimensions but are allowed to be substituted by I-P products to comply with the law. Dual measurements are also included to indicate industry and/or Government standards, test values or other controlling factors, such as the code requirements where I-P values are needed for clarity or to trace back to the referenced standards, test values or codes.

1.3 USE OF MEASUREMENTS IN SPECIFICATIONS

Measurements in specifications shall be either in SI or I-P units as indicated, except for soft metric measurements or as otherwise authorized.

When only SI or I-P measurements are specified for a product, the product shall be procured in the specified units (SI or I-P) unless otherwise authorized by the Contracting Officer. The Contractor is responsible for all associated labor and materials when authorized to substitute one system of units for another and for the final assembly and performance of the specified work and/or products.

1.3.1 Hard Metric

A hard metric measurement is indicated by an SI value with no expressed correlation to an I-P value. Hard metric measurements are often used for field data such as distance from one point to another or distance above the floor. Products are considered to be hard metric when they are manufactured to metric dimensions or have an industry recognized metric designation.

DOCUMENT 00 31 10 Page 1

1.3.2 Soft Metric

a. A soft metric measurement is indicated by an SI value which is a mathematical conversion of the I-P value shown in parentheses (e.g. 38.1 mm (1-1/2 inches)). Soft metric measurements are used for measurements pertaining to products, test values, and other situations where the I-P units are the standard for manufacture, verification, or other controlling factor. The I-P value shall govern while the metric measurement is provided for information.

b. A soft metric measurement is also indicated for products that are manufactured in industry designated metric dimensions but are required by law to allow substitute I-P products. These measurements are indicated by a manufacturing hard metric product dimension followed by the substitute I-P equivalent value in parentheses (e.g., 190 x 190 x 390 mm (7-5/8 x 7-5/8 x 15-5/8 inches)).

1.3.3 Neutral

A neutral measurement is indicated by an identifier which has no expressed relation to either an SI or an I-P value (e.g., American Wire Gage (AWG) which indicates thickness but in itself is neither SI nor I-P).

1.4 COORDINATION

Discrepancies, such as mismatches or product unavailability, arising from use of both metric and non-metric measurements and discrepancies between the measurements in the specifications and the measurements in the drawings shall be brought to the attention of the Contracting Officer for resolution.

1.5 RELATIONSHIP TO SUBMITTALS

Submittals for Government approval or for information only shall cover the SI or I-P products actually being furnished for the project. Submit the required drawings and calculations in the same units used in the contract documents describing the product or requirement unless otherwise instructed or approved. Use IEEE/ASTM SI 10 as the basis for establishing metric measurements required to be used in submittals.

-- End of Document --

DOCUMENT 00 31 10 Page 2

SECTION 01 02 10.00 06 Page 1

SECTION 01 02 10.00 06

PROJECT DESCRIPTION AND DESIGN REQUIREMENTS

08/10

1. GENERAL

The purpose of the fire protection survey was to determine the areas of the facility which lacked automatic sprinkler protection. The survey was also to determine whether any areas would be a candidate for non-aqueous (gaseous) fire suppression systems. The survey was subsequently expanded to include the fire alarm system and life safety.

The BMEWS (Ballistic Missile Early Warning System) facility is two buildings constructed in different eras jointed together.

The original construction dates to the early 1960s. The addition was built in the late 1980s.

The original building is approximately 34,700 square feet per floor. There are three floors; first, mezzanine and second. A first floor tunnel (above ground) connects the BMEWS to a separate satellite building. The satellite building suffered a major fire in 1980.

In the original building there is a heat dissipation area which is accessed from the second floor. The heat dissipation area is two floors; each floor is approximately 6,020 square feet. The heat dissipation equipment is in enclosed unconditioned space.

The building addition measures approximately 23,550 square feet per floor on the three lower floors (first, mezzanine and second). Above the second floor are six additional floors for radar equipment.

The first floor of the whole facility is slab-on grade. The mezzanine level is a steel open-grate floor. The second floor is poured concrete on metal pan. Most of the mezzanine level open-grate has been covered with plywood/carpet or plywood/tile.

Occupied rooms have been constructed on the (now) solid mezzanine floor.

The high-rise portion of the building addition also alternates between concrete slab and a steel open-grate floor. The high-rise floors are denoted as one through six. The high-rise first floor is not the same area as the first floor of the low-rise, refer to drawings for dimensions. The first floor of the high rise is above the second floor of the low rise. The first, third and fifth floors of the high-rise are poured concrete on metal pan. The second, fourth and sixth floors of the high-rise are steel open-grate floor. The walking surfaces of the open-grate on the second, fourth and sixth floors of the high-rise have not been covered (with plywood) and remain open.

SECTION 01 02 10.00 06 Page 2

Sleeping rooms (also known as SHELTER IN PLACE) are provided throughout the BMEWS facility. These rooms are used sporadically to house building occupants when the weather prohibits the safe transport of personnel between the BMEWS and the main Thule base.

All sleeping rooms are provided with two smoke detectors; one detector which signals the building fire alarm system and another detector (single-station) which audibly annunciates in the room of origin.

1.1 EXISTING CONDITIONS: (Also refer to Appendix A for

site photos)

FIRE SUPPRESSION:

Fire protection, where provided, is via aqueous suppression. No non-aqueous (gaseous) systems are utilized anywhere in the facility. All aqueous suppression systems are pre-action. The automatic sprinkler systems and the standpipes are pre-action.

Pre-action systems contain no water in the pipes until the deluge valve in the fire pump room is electrically activated by the fire alarm system. The sprinkler head in the affected area must also be activated from the heat of the fire for water to flow from the sprinkler head.

The original portion of the BMEWS facility is not generally provided with automatic sprinkler protection (approximately 60% of the floor area). The transformer vault and the battery room, located in the original portion of the building, are provided with sprinkler protection which is fed from the building addition. Standpipe connections (including 1 ½ inch hose and nozzles) are provided throughout the original portion of the building. The heat dissipation area is not provided with any type of fire suppression.

The building addition is provided with complete automatic sprinkler protection and standpipes (including 1 ½ inch hose and nozzles), this is approximately 40% of the floor area of the first, mezzanine and second floors. Rooms have been constructed in the sprinklered portion of the building with ceilings where the sprinkler system has not been extended into the room. These areas have sprinklers above the room ceilings but, not in the occupied space.

The sprinkler systems and the standpipe systems are interconnected throughout the facility. The standpipes, like the sprinkler system, are not charged with water until two smoke detectors are activated to trip the deluge valve in the fire pump room. Maintenance personnel have indicated that the maximum “trip time” is approximately 40 seconds. Trip time is the amount of time from the activation of the deluge valve until water flows from the most remote sprinkler head.

SECTION 01 02 10.00 06 Page 3

A fire protection water tank is housed in the new section of the BMEWS. The volume of the tank is approximately 120,000 gallons.

The tank is constructed of cast in place reinforced concrete and is formed into an octagon. A cursory calculation indicated that the volume of water in the tank corresponds to the volume of water required per the UFC 3-600-01 (DOD Fire Safety Criteria);

Table 4-1 to fight a fire.

The fire pump room is located in close proximity to the fire protection water tank. The room is provided with one-hour fire rated construction. The primary fire pump is a 1,000 GPM Aurora horizontal split-case unit with an electric motor. The secondary fire pump is a 1,000 GPM horizontal split-case with a diesel engine. A jockey pump is provided to supply small pressure boosts when required. Each fire pump is provided with a FIRETROL fire pump controller.

There is a 100-gallon day-tank (TRAMONT Brand) in the room to supply diesel fuel to the diesel fire pump. The tank is listed in accordance with UL (Underwriters Laboratories) 142 (Steel Aboveground Tanks for Flammable and Combustible Liquids).

There are four electrically-activated deluge valves to supply the four pre-action sprinkler systems throughout the building. The first three valves were installed at the time of construction of the addition. The last deluge valve was added later in conjunction with a renovation project.

The first deluge valve is a six-inch unit manufactured by RELIABLE in 1984. This valve serves the SSPAR Level 1- 6/UPS/CMOC/C2HR/TOC. The data plate indicates that the area served is 31,423 square feet. The design discharge is 0.16 GPM per square foot over a 2,000 square foot design area. This deluge valve is not provided with an emergency manual release.

The second deluge valve is a six-inch unit manufactured by RELIABLE in 1986. This valve serves the second floor and the mezzanine. The data plate indicates that the area served is 42,109 square feet. The design discharge is 0.21 GPM per square foot over a 2,000 square foot design area. This deluge valve is provided with an emergency manual release.

The third deluge valve is a four-inch unit manufactured by RELIABLE in 1986. This valve serves the first floor. The data plate indicates that the area served is 24,509 square feet. The design discharge is 0.21 GPM per square foot over a 1,950 square foot design area. This deluge valve is provided with an emergency manual release.

The fourth deluge valve is a four-inch unit manufactured by RELIABLE in 1998. This valve serves the CMOC/DCSS/ETR. The data plate indicates that the number of sprinkler heads is 79. The

SECTION 01 02 10.00 06 Page 4 design discharge is 0.15 GPM per square foot over a 1,500 square foot design area with a GPM discharge of 622 GPM at 26 psi (at base of riser). This deluge valve is not provided with an emergency manual release. The fourth deluge valve was installed in the late 1990s in conjunction with a renovation project to a small area of the original BMEWS building on the first floor.

A small cafeteria/dining facility are provided in the original portion of the building on the second level. Two hoods in the kitchen are provided with ANSUL wet-chemical suppression systems.

The suppression systems are manually activated (individually) with pull stations mounted in close proximity to the hood exhaust systems. Activation of a wet-chemical system activates the fire alarm system and shunts power (electric) to the cooking units.

A small hydraulic elevator used to transport technical material is located in the original portion of the building adjacent to the cafeteria. Signage at the elevator prohibits its use by personnel. The lift is only permitted to transport material between the first floor and the mezzanine level.

FIRE ALARM:

The fire alarm is a NOTIFIER 3030 multiplexed addressable system installed approximately 2 ½ years ago. Initiating devices consist of manual pull stations, smoke detectors and heat detectors. Alarm indicating devices consist of horn/strobe units.

The main fire alarm panel is located in the original portion of the building which is not sprinklered. The on-site fireman office is provided with a satellite panel to annunciate any fire alarm problem. A fiber optic cable provides immediate fire alarm signal annunciation to the Thule emergency control center located on the main base. The emergency operator is provided with specific point annunciation of each device and a map of the location of the device relative to the building.

All wiring is provided in EMT (electric metallic tubing) where exposed. All SLCs (Signal Line Circuits; pull stations, heat detectors and smoke detectors) and NACs (Notification Appliance Circuits; horn/strobes) are wired as Class “A” with return loops to the Notifier 3030 panel.

All areas of the facility are provided with manual pull stations and automatic detection. Audible and visual notification is provided in most areas of the facility. Secondary power is provided via battery back-up.

LIFE SAFETY:

SECTION 01 02 10.00 06 Page 5

Life safety throughout the facility does not comply with the NFPA (National Fire Protection Association) 101 Life Safety Code. Most stairwells are not fire rated. No stairwells discharge into protected corridors or directly to the exterior of the building.

Discussions with building staff indicated that frequent fire drills were executed. Building occupants congregate in an assembly area inside the building in close proximity to an exterior entrance/exit. This door is adjacent to the Notifier 3030 fire alarm control panel.

Stairwells in the original portion of the building are enclosed in sheet steel panels (no fire rating) and non-rated door assemblies. None of the stairwells have the ability to discharge directly to the exterior of the building.

The high-rise portion of the building addition is served by a single stairwell and a single elevator. The elevator is provided with a recall system via the fire alarm system. All elevator recall alarms send the elevator to the first floor of the high rise.

The single stair in the high-rise is provided with 2-hour fire-rated construction and 1 1/2 –hour rated door assemblies (as required by the Life Safety Code). After traversing the six high rise floors, a stair occupant must continue three addition floors to the bottom of the stair. These are the second, mezzanine and first floor of the low rise. This stair discharges into the general space of the first floor of the low-rise and does not discharge directly to the exterior.

An additional exit is provided from the first floor of the high-rise space to the exterior of the building. An exit door is provided on the exterior wall of the first floor of the high-rise. Egress is accomplished by traversing across the flat roof (of the second floor of the low–rise) (following the designated path) and descending a spiral staircase to grade below.

1.1.1 THULE BMEWS FIRE PROTECTION GOALS

The BMEWS Building shall be provided with fire alarm system modifications, automatic sprinkler/standpipe additions/modifications, and firestopping. The fire alarm system shall be provided in accordance with NFPA 70, NFPA 72, NFPA 101 and the UFC 3-600-01; Change 2, 1 February 2013 . The automatic sprinkler system/standpipe shall be provided in accordance with NFPA 13, NFPA 101 and the UFC 3-600-01; Change 2, 1 February 2013 . Firestopping shall be in accordance with a recognized design in accordance with the UL Fire Resistance Directory for Through- Penetration Firestop Systems.

SECTION 01 02 10.00 06 Page 6

1.1.2 Specifications

UFGS specifications shall be utilized in conjunction with this project. Firestopping shall conform to the UFGS 07 84 00.

Standpipes shall conform to UFGS 21 12 00. Automatic sprinklers shall conform to UFGS 21 13 17.00 10 and UFGS 21 13 18.00 10.

Fire pump modifications (if required) shall conform to UFGS 21 30

00. Fire alarms shall conform to UFGS 28 31 64.00 10.

1.2 Fire Protection Engineer Requirements

1.2.1 The contractor shall provide the services of a qualified registered fire protection engineer. The fire protection engineer shall be an integral part of the design team and shall be involved in all aspects of the design of the fire protection systems. As a minimum, the fire protection engineer shall design the automatic sprinkler system; the standpipe system; the fire alarm system; the through-penetration firestop system; the fire pump modifications (if required); and the nitrogen generation systems. The fire protection engineer shall promulgate a phasing plan to implement the work of this contract while minimizing outages of existing fire suppression systems. Also as a minimum the fire protection engineer shall have at least 10 years of experience in designing and commissioning of fire protection systems and carry a professional certification within his field.

1.2.2 Fire Protection and Life Safety Analysis

The fire protection engineer shall perform a fire protection design analysis of the proposed facility design. The analysis shall be submitted with the preliminary design submittal. The analysis shall include type of construction; height and area limitations; classification of occupancy; building separation or exposure protection; specific compliance with NFPA codes and the IBC; requirements for fire-rated walls, doors, fire dampers, etc.; analysis of automatic suppression systems and protected areas; water supplies; fire alarm system, including connection to the base-wide system; fire detection system; and other pertinent fire protection data. The submittal shall include a floor plan showing occupant loading, occupancy classifications and construction type, sprinklered areas, ratings of fire-resistive assemblies, and other data necessary to exhibit compliance.

1.3 BMEWS FIRE PROTECTION REQUIREMENTS, NARRATIVE

1.3.1 Sixth Floor High Rise

1.3.1.1 Extend the existing pre-action automatic sprinkler system into the landing of the stairwell. Provide upright sprinkler heads in quantity and location as appropriate.

SECTION 01 02 10.00 06 Page 7

1.3.1.2 Extend the existing pre-action automatic sprinkler

system into the elevator machine room. Provide fire alarm modifications to shunt trip the elevator in the event of a pre-action sprinkler activation of the new deluge valve serving the fifth and sixth floors. Provide wire cages for all sprinkler heads in the elevator machine room.

1.3.1.3 Extend the existing pre-action automatic sprinkler

system under the ductwork at column line 4B-5B. The ductwork in this area is greater than 48 inches in width.

1.3.1.4 Provide laser sighting of all sprinkler pipe to verify correct pitch. Re-pitch all sprinkler pipe as required to comply with NFPA 13 (2010 edition); Chapter 8.16.2.3.2. Flush all sprinkler piping in accordance with NFPA 25 (2011 edition);

Appendix D.5. Provide ultrasound scanning of Government selected sprinkler piping.

1.3.2 Fifth Floor High Rise

1.3.2.1 Replace the existing sprinkler heads under the open-

grate catwalk with INTERMEDIATE LEVEL sprinkler heads. Extend the existing upright sprigs such that the top of the deflector is within the distance required per NFPA 13. The existing sprinkler heads under the catwalk are not recognized for this type of application.

1.3.2.2 Extend the existing pre-action automatic sprinkler

system into the landing of the stairwell. Provide upright sprinkler heads in quantity and location as appropriate.

1.3.2.3 Replace the existing upright sprinkler heads between AHU- 1 and AHU-2 with INTERMEDIATE LEVEL sprinkler heads. Provide wire cages for these new sprinkler heads.

1.3.2.4 Replace the existing upright sprinkler heads between

AHU-2 and AHU-3 with INTERMEDIATE LEVEL sprinkler heads Provide wire cages for these new sprinkler heads.

1.3.2.5 Extend the existing pre-action automatic sprinkler

system under the triple fan/mixing box adjacent to AHU-1, AHU-2 and AHU-3. The ductwork in this area is greater than 48 inches in width.

1.3.2.6 Provide laser sighting of all sprinkler pipe to verify correct pitch. Re-pitch all sprinkler pipe as required to comply with NFPA 13 (2010 edition); Chapter 8.16.2.3.2. Flush all sprinkler piping in accordance with NFPA 25 (2011 edition);

Appendix D.5. Provide ultrasound scanning of Government selected sprinkler piping.

1.3.3 Fourth Floor High Rise

SECTION 01 02 10.00 06 Page 8

1.3.3.1 Extend the existing pre-action automatic sprinkler system heads in quantity and location as appropriate.

1.3.3.2 Extend the existing pre-action automatic sprinkler

system under the ductwork at column line 4C-4E. The ductwork in this area is greater than 48 inches in width.

1.3.3.3 Provide laser sighting of all sprinkler pipe to verify correct pitch. Re-pitch all sprinkler pipe as required to comply with NFPA 13 (2010 edition); Chapter 8.16.2.3.2. Flush all sprinkler piping in accordance with NFPA 25 (2011 edition);

Appendix D.5. Provide ultrasound scanning of Government selected sprinkler piping.

1.3.4 Third Floor High Rise

1.3.4.1 Extend the existing pre-action automatic sprinkler system into the landing of the stairwell. Provide upright sprinkler heads in quantity and location as appropriate.

1.3.4.2 Replace the existing sprinkler heads under the open-

grate catwalk with INTERMEDIATE LEVEL sprinkler heads. Extend the existing upright sprigs such that the top of the deflector is within the distance required per NFPA 13. The existing sprinkler heads under the catwalk are not recognized for this type of application.

1.3.4.3 Provide laser sighting of all sprinkler pipe to verify correct pitch. Re-pitch all sprinkler pipe as required to comply with NFPA 13 (2010 edition); Chapter 8.16.2.3.2. Flush all sprinkler piping in accordance with NFPA 25 (2011 edition);

Appendix D.5. Provide ultrasound scanning of Government selected

1.3.5 Second Floor High Rise

1.3.5.1 Extend the existing pre-action automatic sprinkler

system into the landing of the stairwell. Provide upright sprinkler heads in quantity and location as appropriate.

1.3.5.2 Provide laser sighting of all sprinkler pipe to

verify correct pitch. Re-pitch all sprinkler pipe as required to comply with NFPA 13 (2010 edition); Chapter 8.16.2.3.2. Flush all sprinkler piping in accordance with NFPA 25 (2011 edition);

Appendix D.5. Provide ultrasound scanning of Government selected

1.3.6 First Floor High Rise

SECTION 01 02 10.00 06 Page 9

1.3.6.1 Extend the existing pre-action automatic sprinkler system heads in quantity and location as appropriate.

1.3.6.2 Extend the existing pre-action automatic sprinkler system into the bathroom.

1.3.6.3 Extend the existing pre-action automatic sprinkler system into the alcove behind the bathroom. Provide wire cages for these new sprinkler heads.

1.3.6.4 Extend the existing pre-action automatic sprinkler

system under the ductwork at the entrance to the UEWR Compter Complex. The ductwork in this area is 48 inches in width.

1.3.6.5 Replace the existing sprinkler heads under the open-

grate catwalk with INTERMEDIATE LEVEL sprinkler heads (two areas). Extend the existing upright sprigs such that the top of the deflector is within the distance required per NFPA 13. The existing sprinkler heads under the catwalk are not recognized for this type of application.

1.3.6.6 Extend the existing fire alarm SLC (signal line circuit) to provide a smoke detector in the bathroom. Provide wire in conduit consistent with existing installation. Continue existing class “A” electrical supervision.

1.3.6.7 Extend the existing fire alarm NAC (notification

appliance circuit) to provide a horn/strobe in the bathroom.

Provide wire in conduit consistent with existing installation.

Continue existing class “A” electrical supervision. Provide an EXTENDER PANEL for additional NAC power if required.

1.3.6.8 Extend the existing fire alarm SLC (signal line circuit) to provide a manual pull station at the exterior EXIT door to the roof. Provide wire in conduit consistent with existing installation. Continue existing class “A” electrical supervision.

1.3.6.9 Provide firestopping at the penetration through the

floor beside the UEWR Compter Complex room. Fire stopping shall be rated for two-hours and shall be recognized as a UL (underwriters Laboratories) classified design in the UL Fire Resistance Directory.

1.3.6.10 Provide laser sighting of all sprinkler pipe to

verify correct pitch. Re-pitch all sprinkler pipe as required to comply with NFPA 13 (2010 edition); Chapter 8.16.2.3.2. Flush all sprinkler piping in accordance with NFPA 25 (2011 edition);

Appendix D.5. Provide ultrasound scanning of Government selected

1.3.7 Second Floor Low Rise

SECTION 01 02 10.00 06 Page 10

1.3.7.1 Provide a new single-interlock pre-action sprinkler

system for the area enclosed by column lines “A” through “N” and “11” through “22” on the second floor. Deluge valve actuation shall utilize existing smoke/heat detectors in the effected space. Hydraulic design criteria shall be HC-2 (0.2 GPM per square foot) in accordance with the UFC 3-600-01(Change 2; 1 February 2013) over the most remote 2,500 square feet. Provide three deluge valves in one area (second floor, mezzanine and first floor). Provide a new single feed main to the new fire suppression manifold serving the three deluge valves and a fourth valve (Alarm Check Valve) to feed the new wet-pipe Class I standpipes. The new single feed main to the new fire suppression manifold shall originate at the fire pumps and be constantly charged with water (wet-pipe) until the base of the deluge valves. All new control valves shall be of the OS&Y variety.

All new OS&Y valves shall be electrically supervised via a tamper switch by the fire alarm system. This group of pre-action sprinkler valves shall be provided with a single nitrogen generation supervisory gas system and manual pull station emergency activation release. The location of the new fire protection manifold shall be proposed by the contractor and agreed upon by the Government.

The fourth feed of the new fire protection manifold (alarm check valve) shall serve all Class I 2 ½ standpipe connections in the BMEWS facility (excluding the six-inch standpipe riser in the high-rise stairwell). The existing 1 ½ inch standpipe outlets shall be demolished and capped at the pre-action sprinkler system feed main.

1.3.7.2 Provide a new dry-pipe sprinkler system for the heat

dissipation area enclosed by column lines “A” through “N” and “22” through “25” on the second floor. The dry-pipe deluge valve may be fed from the new fire suppression manifold. An additional outlet would be required if the dry-pipe valve were added to this manifold. Hydraulic design criteria shall be HC-2 (0.2 GPM per square foot) in accordance with the UFC 3-600-01;(Change 2; 1 February 2013) over the most remote 3,500 square feet. The second floor heat dissipation dry-pipe sprinklered area may be combined with the first floor heat dissipation dry-pipe sprinklered area requirement into a single dry-pipe zone. Provide nitrogen generation supervisory gas system for dry-pipe valve.

1.3.7.3 Extend the existing pre-action automatic sprinkler

system under the ductwork in the corridor outside of Shelter in Place rooms 37, 38, 39, 43, 44 and 57. The ductwork in this area is at least 48 inches in width.

1.3.7.4 Extend the existing pre-action automatic sprinkler

system into the bathroom inside of the UEWR MWOC area (column A7). The remainder of the UEWR MWOC area is provided with smoke detection and pre-action sprinkler protection.

SECTION 01 02 10.00 06 Page 11

1.3.7.5 Extend the existing pre-action automatic sprinkler

system into the lounge/ Shelter in Place area occupied by Greenland Contractors (column line L-N and 1-3). Automatic sprinklers are existing atop the lounge/ Shelter in Place area.

Do not remove the existing pre-action sprinklers atop the space.

Smoke detection is provided in the lounge/ Shelter in Place area.

1.3.7.6 Extend the existing pre-action automatic sprinkler

system into the office space behind the Console Room (column L8).

The remainder of the UEWR MWOC area is provided with smoke detection and pre-action sprinkler protection.

1.3.7.7 Provide a threaded cap for the end of the sprinkler pipe at the ball-cock valve at column line L11. The ball-cock valve is not provided with an end cap.

1.3.7.8 Extend the existing fire alarm NAC (notification

appliance circuit) to provide two horn/strobe units each of the four heat dissipation cells on the upper floor(second floor).

Provide wire in conduit consistent with existing installation.

Continue existing class “A” electrical supervision. Provide an EXTENDER PANEL for additional NAC power if required.

1.3.7.9 Extend the existing fire alarm NAC (notification

appliance circuit) to provide two horn/strobe units each in the Arcade/recreation area (approximately column D20). Provide wire in conduit consistent with existing installation. Continue existing class “A” electrical supervision. Provide an EXTENDER PANEL for additional NAC power if required.

1.3.7.10 Extend the existing fire alarm SLC (signal line

circuit) to provide a smoke detector in the male kitchen employee bathroom (approximately column D16). Provide wire in conduit consistent with existing installation. Continue existing class “A” electrical supervision.

1.3.7.11 Extend the existing fire alarm SLC (signal line

circuit) to provide a smoke detector in the female kitchen employee bathroom (approximately column D16). Provide wire in conduit consistent with existing installation. Continue existing class “A” electrical supervision.

1.3.7.12 Extend the existing fire alarm NAC (notification

appliance circuit) to provide three horn/strobe units in the kitchen hallway/SPACE COMMAND hallway (approximately column D19).

Provide wire in conduit consistent with existing installation.

Continue existing class “A” electrical supervision. Provide an EXTENDER PANEL for additional NAC power if required.

1.3.7.13 Extend the existing fire alarm NAC (notification

appliance circuit) to provide one horn/strobe unit in the SPACE COMMAND Reception Area (approximately column E20). Provide wire

SECTION 01 02 10.00 06 Page 12 in conduit consistent with existing installation. Continue existing class “A” electrical supervision. Provide an EXTENDER PANEL for additional NAC power if required.

1.3.7.14 Extend the existing fire alarm SLC (signal line

circuit) to provide a smoke detector into the office space behind the Console Room (column L8). . Provide wire in conduit consistent with existing installation. Continue existing class “A” electrical supervision.

1.3.7.15 Extend the existing fire alarm NAC (notification

appliance circuit) to provide one horn/strobe unit in the female restroom (approximately column B13). Provide wire in conduit consistent with existing installation. Continue existing class “A” electrical supervision. Provide an EXTENDER PANEL for additional NAC power if required.

1.3.7.16 Extend the existing fire alarm NAC (notification

appliance circuit) to provide one horn/strobe unit in the male restroom (approximately column B13). Provide wire in conduit consistent with existing installation. Continue existing class “A” electrical supervision. Provide an EXTENDER PANEL for additional NAC power if required.

1.3.7.17 Extend the existing fire alarm NAC (notification

appliance circuit) to provide one horn/strobe unit in the male locker room (approximately column B15). Provide wire in conduit consistent with existing installation. Continue existing class “A” electrical supervision. Provide an EXTENDER PANEL for additional NAC power if required.

1.3.7.18 Extend the existing fire alarm SLC (signal line

circuit) to provide magnetic hold opens on the double doors (column J16). Provide wire in conduit consistent with existing installation. Continue existing class “A” electrical supervision.

Activate door release using existing area smoke detectors.

1.3.7.19 Provide one CLASS I standpipe connection in the

Arcade/Recreation Room within five feet of the door to access the heat dissipation units. Locate this standpipe connection such that it is easily accessible for fire fighting in the event that manual suppression is required in the heat dissipation area. No standpipe connections shall be provided in the heat dissipation area.

1.3.7.20 Provide laser sighting of all sprinkler pipe to

verify correct pitch. Re-pitch all sprinkler pipe as required to comply with NFPA 13 (2010 edition); Chapter 8.16.2.3.2. Flush all sprinkler piping in accordance with NFPA 25 (2011 edition);

SECTION 01 02 10.00 06 Page 13

1.3.8 Mezzanine Level Low Rise

1.3.8.1 Provide a new single-interlock pre-action sprinkler

system for the area enclosed by column lines “A” through “N” and “11” through “15” on the Mezzanine Level. Deluge valve actuation shall utilize existing smoke/heat detectors in the effected space. Hydraulic design criteria shall be HC-2 (0.2 GPM per square foot) in accordance with the UFC 3-600-01; (Change 2; 1 February 2013) over the most remote 2,500 square feet. Provide three deluge valves in one area (second floor, mezzanine and first floor). Provide a new single feed main to the new fire suppression manifold serving the three deluge valves and a fourth valve (Alarm Check valve) to feed the new wet-pipe Class I standpipes. The new single feed main to the new fire suppression manifold shall originate at the fire pumps and be constantly charged with water (wet-pipe) until the base of the deluge valves. All control valves shall be of the OS&Y variety. All OS&Y valves shall be electrically supervised via a tamper switch by the fire alarm system. This group of pre-action sprinkler valves shall be provided with a single nitrogen generation supervisory gas system and manual pull station emergency activation release. The location of the new fire protection manifold shall be proposed by the contractor and agreed upon by the Government.

The fourth feed of the new fire protection manifold (alarm check valve) shall serve all Class I 2 ½ inch standpipe connections in the BMEWS facility (excluding the six-inch standpipe riser in the high-rise stairwell). The existing 1 ½ inch standpipe outlets shall be demolished and capped at the pre-action sprinkler system feed main.

1.3.8.2 Extend the existing pre-action automatic sprinkler system into the restroom/shower area (column line L-N and 1-2).

Automatic sprinklers are existing atop this area. Do not remove the existing pre-action sprinklers atop the space. Smoke detection is existing in the area.

1.3.8.3 Extend the existing pre-action automatic sprinkler system into the Shielded Room (column line K2). Automatic sprinklers are existing atop this area. Do not remove the existing pre-action sprinklers atop the space.

1.3.8.4 Extend the existing pre-action automatic sprinkler system into the Janitor Break Room (approximately column line M8).

Automatic sprinklers are existing in this area. Do not remove the existing pre-action sprinklers atop the space.

1.3.8.5 Extend the existing pre-action automatic sprinkler system into the C2HR Room (approximately column line G9). Automatic sprinklers are existing in this area.

SECTION 01 02 10.00 06 Page 14

1.3.8.6 Extend the existing pre-action automatic sprinkler system under the ductwork at column line D3-D4. The ductwork in this area is at least 48 inches in width.

1.3.8.7 Extend the existing fire alarm SLC (signal line circuit) to provide electrical supervision of the unsupervised Pre-action sprinkler OS&Y valve adjacent at column E7 outside of the C2HR room. Provide wire in conduit consistent with existing installation. Continue existing class “A” electrical supervision.

1.3.8.8 Extend the existing fire alarm SLC (signal line circuit) to provide a smoke detector into the Shielded Room (column K2).

Provide wire in conduit consistent with existing installation.

Continue existing class “A” electrical supervision. Provided filters as required.

1.3.8.9 Extend the existing fire alarm NAC (notification

appliance circuit) to provide one horn/strobe unit in the Shielded Room (approximately column K2). Provide wire in conduit consistent with existing installation. Continue existing class “A” electrical supervision. Provide an EXTENDER PANEL for additional NAC power if required. Provide RFI filter for horn/strobe extension inside shielded room.

1.3.8.10 Extend the existing fire alarm SLC (signal line circuit) to provide a smoke detector into the bathroom located in the C2HR area (column D11). Provide wire in conduit consistent with existing installation. Continue existing class “A” electrical supervision.

1.3.8.11 Provide laser sighting of all sprinkler pipe to verify correct pitch. Re-pitch all sprinkler pipe as required to comply with NFPA 13 (2010 edition); Chapter 8.16.2.3.2. Flush all sprinkler piping in accordance with NFPA 25 (2011 edition);

1.3.9 First Floor Low Rise

1.3.9.1 Convert all existing standpipe connections in the BMEWS facility from pre-action operation to wet-pipe operation.

Maintain all sprinkler systems as pre-action operation. Segregate all standpipe locations to provide the 2 ½ inch to 1 ½ inch hose outlets fully-charged with water at all times.

1.3.9.2 Convert existing pre-action standpipe in the high-rise stairwell to wet-pipe. Provide four new hydraulically sized deluge valves. One deluge valve shall be provided on the sixth floor (high-rise) to serve the pre-action sprinklers on the fifth and sixth floors. The sixth floor deluge valve shall not be

SECTION 01 02 10.00 06 Page 15 located in the stairwell. The sixth floor deluge valve shall be located in close proximity to the stair. One deluge valve shall be provided on the fourth floor (high-rise) to serve the pre-action sprinklers on the third and fourth floors. The fourth floor deluge valve shall not be located in the stairwell. The fourth floor deluge valve shall be located in close proximity to the stair. One deluge valve shall be provided on the second floor (high-rise) to serve the pre-action sprinklers on the first and second floors. The second floor deluge valve shall not be located in the stairwell. The second floor deluge valve shall be located in close proximity to the stair The three pre-action sprinkler valves serving the high-rise shall be provided with a single nitrogen generation system. The remaining (fourth) deluge valve shall be provided for all other pre-action sprinklers which were previously served by the original deluge valve (UPS/CMOC/C2HR/TOC). The fourth deluge valve may be provided in the location previously occupied by the original deluge valve. If the fourth deluge valve location is reused for the low-rise pre-action sprinklers, a separate manifold connection must be provided for the high-rise standpipe which shall service the standpipe and the three deluge valves (floors six, four and two). All pre-action sprinkler valves located in the fire pump room shall be provided with a single nitrogen generation system.

1.3.9.3 Replace all existing CLASS II standpipe systems

throughout the BMEWS with a CLASS I standpipe system with 2 ½ inch fire department connections. This system is located throughout the first floor, mezzanine and second floor of the low-rise. All standpipes are currently fed from the pre-action deluge valves in the fire pump room. The new CLASS I standpipe system shall be fed from an alarm check valve.

1.3.9.4 Provide 2 ½ inch to 1 ½ inch reducers at all the 2 ½

inch valves. Add additional 2 ½ inch CLASS I standpipe connections throughout the BMEWS to comply with the spacing and location requirements of NFPA 14 and the UFC 3-600-01. Do not replace the standpipe riser in the high-rise stairwell.

1.3.9.5 Replace all existing CLASS II standpipe locations with CLASS I standpipe locations. Provide additional standpipe locations as required throughout the BMEWS to comply with the spacing and location requirements of NFPA 14 and the UFC 3-600- 01.

1.3.9.6 Provide a new single-interlock pre-action sprinkler

system for the area enclosed by column lines “A” through “N” and “11” through “22” on the first floor. Deluge valve actuation shall utilize existing smoke/heat detectors in the effected space. Hydraulic design criteria shall be HC-2 (0.2 GPM per square foot) in accordance with the UFC 3-600-01 (Change 2; 1 February 2013) over the most remote 2,500 square feet. Provide

SECTION 01 02 10.00 06 Page 16 three deluge valves in one area (second floor, mezzanine and first floor). Provide a new single feed main to the new fire suppression manifold serving the three deluge valves and a fourth valve (alarm check valve) to feed the new wet-pipe Class I standpipes. The new single feed main to the new fire suppression manifold shall originate at the fire pumps and be constantly charged with water (wet-pipe) until the base of the deluge valves. All control valves shall be of the OS&Y variety. All OS&Y valves shall be electrically supervised via a tamper switch by the fire alarm system. This group of pre-action sprinkler valves shall be provided with a single nitrogen generation supervisory gas system and manual pull station emergency activation release. The location of the new fire protection manifold shall be proposed by the contractor and agreed upon by the Government.

1.3.9.7 The fourth feed of the new fire protection manifold

shall serve all Class I 2 ½ standpipe connections in the BMEWS facility (excluding the six-inch standpipe riser in the high-rise stairwell). The existing 1 ½ inch standpipe outlets shall be demolished and capped at the pre-action sprinkler system feed main.

1.3.9.8 Provide a new dry-pipe sprinkler system for the heat

dissipation area enclosed by column lines “A” through “N” and “22” through “25” on the first floor. The dry-pipe deluge valve may be fed from the new fire suppression manifold. An additional outlet would be required if the dry-pipe valve were added to this manifold. Hydraulic design criteria shall be HC-2 (0.2 GPM per square foot) in accordance with the UFC 3-600-01;(Change 2; 1 February 2013) over the most remote 3,500 square feet. The second floor heat dissipation dry-pipe sprinklered area may be combined with the first floor heat dissipation dry-pipe sprinklered area requirement into a single dry-pipe zone. Provide nitrogen generation supervisory gas system for dry-pipe valve.

1.3.9.9 Provide laser sighting of all sprinkler pipe to verify correct pitch. Re-pitch all sprinkler pipe as required to comply with NFPA 13 (2010 edition); Chapter 8.16.2.3.2. Flush all sprinkler piping in accordance with NFPA 25 (2011 edition);

Appendix D.5. Provide ultrasound scanning of Government selected sprinkler piping.

1.3.9.10 Extend the existing pre-action automatic sprinkler

system into the non-sprinklered area…