F-001 - LIFE SAFETY CODE ANALYSIS..pdf

PDF 105 KB Posted

Attached to
403873 FLW AIT Barracks Complex II Phase 2
Solicitation number
W912DQ25RA004
Issued by

About this file

This is a Life Safety Code Analysis document for an Advanced Individual Training (AIT) Barracks/Company Operations Facility (B/COF) project located at Fort Leonard Wood, Missouri. The six-story, 180,500 square foot building will include 310 total dwelling units (150 two-person and 160 three-person), multipurpose rooms, learning labs, day rooms, laundry facilities, administrative spaces, and storage areas. The facility is designed as Type IB construction, fully sprinklered, with comprehensive fire protection features including a new wet pipe sprinkler system, fire alarm control panel, mass notification system, emergency lighting, and exit signage. The building is classified as a mixed-use occupancy with residential (R-2), business (B), assembly (A-3), and storage (S-1) spaces, designed to comply with International Building Code (IBC) and National Fire Protection Association (NFPA) 101 Life Safety Code requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TABULAR VALUE

FULLY-SPRINKLERED

(SF)

FRONTAGE INCREASE

(% / SF)

ACTUAL AREA

(SF NOT INCLUDING

CORRIDORS)

R-2 NOT APPLICABLE UNLIMITED 37,202

CODE REFERENCE: IBC TABLE 504.3, IBC TABLE 506.2, AND IBC SECTION 508GENERAL INFORMATION:

BUILDING SUMMARY

ADVANCED INDIVIDUAL TRAINING (AIT) BARRACKS/COMPANY OPERATIONS FACILITY (B/COF)

PROJECT LOCATED IN FORT LEONARD WOOD, MISSOURI.

THE AIT B/COF IS A SIX-STORY STRUCTURE APPROXIMATELY 180,500 SQUARE FEET (SF) IN GROSS AREA. THE SIXTH FLOOR BEING UNOCCUPIED MECHANICAL ROOM. THE FACILITY WILL INCLUDE 150

TWO PERSON DWELLINGS AND 160 THREE PERSON DWELLINGS, TWO MULTIPURPOSE ROOMS (W/

MOVEABLE PARTIONS THAT DIVIDES EACH INTO THREE CLASS ROOMS), LEARNING LABS, DAY

ROOMS, LAUNDRY, ADMINISTRATIVE SUPPORT SPACES, STORAGE, AND SUPPLY ROOMS.

SUMMARY OF FIRE PROTECTION FEATURES:

PROTECT THROUGHOUT PER NFPA 13 AND UFC 3-600-01

NFPA 101

ALL OCCUPANCIES SHALL BE PROTECTED THROUGHOUT BY AN APPROVED, AUTOMATIC SPRINKLER

SYSTEM.

NEW WET PIPE SPRINKLER SYSTEM THROUGHOUT THE ENTIRE BUILDING IN ACCORDANCE WITH

UFC 3-600-01 AND NFPA 13.

WATER FOR THE SPRINKLER SYSTEM WILL BE SUPPLIED BY AN EXTENSION TO THE EXISTING

WATER MAIN SERVING THE ADJACENT FACILITIES. REFERENCE CIVIL DRAWINGS FOR MORE

INFORMATION.

NEW FIRE ALARM CONTROL PANEL (FACP) WILL BE LOCATED IN THE FIRE PUMP ROOM. THE

BUILDING WILL BE PROVIDED WITH A REMOTE ANNUNCIATOR IN THE MAIN LOBBY. SEPARATE FIRE ALARM AND MASS NOTIFICATION TRANSCEIVERS ARE REQUIRED. THE MASS NOTIFICATION SYSTEM

WILL BE FULLY INTERFACED WITH THE FIRE ALARM EQUIPMENT TO PROVIDE ALL FUNCTIONS

NECESSARY FOR INTERFACE WITH ALL LOCAL FEATURES.

FIRE EXTINGUISHER LOCATIONS, EMERGENCY LIGHTING, AND EXIT SIGNS IN ACCORDANCE WITH

NFPA 10, NFPA 101, AND UFC 3-600-01.

MEANS OF EGRESS WILL COMPLY WITH NFPA 101 AND AS INDICATED FOR THE PROJECT

APPLICABLE CODES AND STANDARDS REFERENCES:

THE APPLICABLE CODES AND STANDARDS FOR THE PROJECT ARE AS FOLLOWS:

UFC 1-200-01: DOB GENERAL BUILDING REQUIREMENTS

UFC 3-600-01: FIRE PROTECTION ENGINEERING FOR FACILITIES, CHANGE 6, MAY 2021

UFC 4-021-01: MASS NOTIFICATION SYSTEMS, CHANGE 1, JANUARY 2010

INTERNATIONAL BUILDING CODE (IBC), 2021 EDITION

NFPA 10: STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2022

NFPA 13: STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2022

NFPA 24: STANDARD FOR THE INSTALLATION OF PRIVATE SERVICE MAINS AND THEIR APPURTENANCES, 2022

NFPA 70: NATIONAL ELECTRICAL CODE, 2020

NFPA 72: NATIONAL FIRE ALARM AND SIGNALING CODE, 2022

NFPA 80: FIRE DOORS AND WINDOWS, 2022

NFPA 90A: STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS, 2021

NFPA 101: LIFE SAFETY CODE, 2021

OTHER REFERENCED CODES AND STANDARDS AS APPLICABLE.

BUILDING CODE ANALYSIS

DESIGN AND CONSTRUCTION WILL BE IN ACCORDANCE WITH THE FIRE RESISTIVE CONSTRUCTION

REQUIREMENTS, MAXIMUM ALLOWABLE FLOOR AREA AND BUILDING HEIGHT LIMITATIONS, AND

BUILDING SEPARATION/EXPOSURE PROTECTION REQUIREMENTS OF THE IBC, SELECTED FIRE

RESISTIVE CONSTRUCTION REQUIREMENTS OF NFPA 101, AND APPLICABLE REQUIREMENTS OF THE

REFERENCED UFCS.

OCCUPANCY CLASSIFICATION CODE REFERENCE:

IBC 508.3, 508.2.4, 304, 308.5, 1004.5, NFPA 101 SECTION 28.3.1

REQUIRED: THE BUILDING WILL COMPLY WITH THE MEANS OF EGRESS, CONSTRUCTION TYPE,

PROTECTION, AND OTHER SAFEGUARDS BASED ON THE USE OF EACH PORTION.

BUILDING CONSTRUCTION

THE BUILDING IS DESIGNED AS TYPE IB CONSTRUCTION AS DEFINED BY IBC CHAPTER 6 AND

COMPLIES WITH THE HEIGHT AND AREA LIMITS FOR MIXED-USE SEPARATED BUILDING.

FIRE RESISTANCE RATING REQUIREMENTS FOR TYPE IB CONSTRUCTION, IBC TABLE 601

PRIMARY STRUCTURAL FRAME

BEARING WALLS

EXTERIOR

INTERIOR

EXTERIOR NON-BEARING WALLS AND PARTITIONS

INTERIOR NON-BEARING WALLS AND PARTITIONS

FLOOR CONSTRUCTION AND SECONDARY MEMBERS

ROOF CONSTRUCTION AND SECONDARY MEMBERS

REQUIRED RATING

2 - HOUR

2 - HOUR

2 - HOUR

0 - HOUR

0 - HOUR, 1/2 HOUR REQUIRED

BETWEEN DWELLING UNITS

2 - HOUR

1 - HOUR

EXTERIOR EXPOSURE PROTECTION

CODE REFERENCE: IBC 602

REQUIRED: BELOW IN ACCORDANCE WITH IBC TABLE 602 FOR EXTERIOR WALL ASSEMBLIES AND IBC TABLE 705.8 FOR PROTECTION OF EXTERIOR WALL OPENINGS. UNLIMITED UNPROTECTED EXTERIOR WALL OPENINGS AREA PERMITTED FOR BUILDINGS WHOSE EXTERIOR BEARING WALLS, EXTERIOR NON-BEARING WALLS, AND EXTERIOR PRIMARY STRUCTURAL FRAME ARE NOT REQUIRED TO BE FIRE-

RESISTANCE RATED PER IBC 705.8.1, EXCEPTION 2

TYPE IB CONSTRUCTION, IBC TABLE 705.5

FIRE SEPARATION

DISTANCE (FEET)

< 5 FEET 2 - HOUR

REQUIRED EXTERIOR FIRE-RESISTANCE RATING

5 - 10 FEET 1 - HOUR

10 - 30 FEET 1 - HOUR

> 30 FEET 0 - HOUR

PROVIDED: THE FIRE SEPARATION DISTANCE FOR THE BUILDING IS GREATER THAN 30 FEET, WHICH

ALLOWS THE EXTERIOR WALLS TO BE NON- RATED, NON-COMBUSTIBLE CONSTRUCTION. THE

MAXIMUM AREA OF UNPROTECTED EXTERIOR WALL OPENINGS IS UNLIMITED.

FIRE-RESISTANCE RATED CONSTRUCTION

FIRE-RESISTANCE RATED CONSTRUCTION IS REQUIRED TO COMPLY WITH NFPA 101 FOR INTERNAL PARTITIONS PER UFC 3-600-01. PER UFC 3-600-01, SMOKE BARRIERS ARE NOT REQUIRED IN THE

BUILDING WHEN FULLY PROTECTED BY AN AUTOMATIC FIRE SPRINKLER SYSTEM.

THE FOLLOWING SEPARATIONS ARE PROVIDED IN THE BUILDING:

OCCUPANCY SEPARATIONS

- DWELLING UNIT 1/2 FIRE BARRIERS

ENCLOSURE PROTECTION

- EXIT ENCLOSURES, 2 HOUR FIRE BARRIER

- CORRIDORS, 1/2 HOUR FIRE BARRIER

- DWELLING UNITS, 1/2 HOUR FIRE BARRIERS

- LAUNDRY ROOMS, 1 HOUR FIRE BARRIERS

- BOILER ROOMS, 1 HOUR FIRE BARRIERS

- STORAGE ROOMS, 1 HOUR FIRE BARRIERS

- SHAFT ENCLOSURES (NFPA 90A, 5.3.4.2)

- VERTICAL OPENINGS (NFPA 101 8.6) 1 HOUR FIRE BARRIER / SMOKE BARRIER

DOOR REQUIREMENTS

- DOORS IN 1/2 HOUR RATED WALLS

- 20 MINUTE FIRE RATING, WITH DOOR CLOSERS

- DOORS IN 1 HOUR RATED WALLS

- 45 MINUTE FIRE RATING, WITH DOOR CLOSERS

- DOORS IN 2 HOUR RATED WALLS

- 1 1/2 HOUR RATING, WITH DOOR CLOSERS

INTERIOR FINISHES

- WALLS, EXIT ENCLOSURES, CLASS A

- WALLS, LOBBIES AND CORRIDORS, CLASS A OR B

- WALLS, OTHER SPACES, CLASS A, B, OR C

- FLOORS, EXIT ENCLOSURES AND CORRIDORS, CLASS II

CODE REFERENCE: UFC 3-600-1 SECTION 7-2, NFPA 101 SECTION 28.3.1.

REQUIRED: FIRE-RESISTANCE RATED CONSTRUCTION (1-HR FIRE BARRIER) REQUIRED AT ENCLOSED

VERTICAL OPENINGS. LAUNDRY ROOMS GREATER THAT 100 SF W/ 1 HOUR SEPARATION AND

SPRINKLERED.

PROVIDED: FIRE-RESISTANCE RATED CONSTRUCTION AS SHOWN ON THE LIFE SAFETY PLANS.

TYPE I-B, FULLY SPRINKLERED, SIX-STORY:

USE OF IBC AND NFPA 101

IBC - USE FOR CONSTRUCTION TYPE, FIRE RESISTANCE, HEIGHT (UFC 3-600-01), AREA IS UNLIMITED

AND SEPARATION IS 40 FEET.

NFPA 101 - USE FOR EGRESS, SAFETY TO LIFE AND NONBEARING PARTITION FIRE RESISTANCE. FOR

CONFLICTS WITH IBC, COMPLY WITH NFPA 101.

OCCUPANCY CLASSIFICATION

THE PRIMARY OCCUPANCY OF THE BUILDING IS RESIDENTIAL - DORMITORY OCCUPANCY. THE

VARIOUS OCCUPANCIES WILL NOT BE SEPARATED FROM EACH OTHER;

THIS DESIGN IS CLASSIFIED AS DORMITORY RATHER THAN APARTMENT DUE TO EACH DWELLING

NOT HAVING INDEPENDENT COOKING FACILITIES

MEANS OF EGRESS

THE MEANS OF EGRESS FOR THE BUILDING WILL COMPLY WITH THE REQUIREMENTS FOR RESIDENTIAL- DORMITORY OCCUPANCIES AS OUTLINED IN NFPA 101, CHAPTER 28. MEANS OF EGRESS COMPONENTS

ARE BASED ON THE PROVISIONS FOR FULLY-SPRINKLERED BUILDINGS.

REFER TO THE LIFE SAFETY PLANS FOR DETAILS ON THE MEANS OF EGRESS.

NUMBER EXITS

THE MINIMUM NUMBER OF EXITS PROVIDED FROM EACH STORY AND EACH INDIVIDUAL SPACE SHALL BE

IN ACCORDANCE WITH NFPA 101, CHAPTER 28.

EXITS FROM STORY

CODE REFERENCE: NFPA 101 SECTION 7.4.1.2 AND SECTION 28.2.4

REQUIRED: A MINIMUM OF TWO EXITS ARE REQUIRED FROM ANY STORY OF THE BUILDING.

PROVIDED: THE BUILDING IS PROVIDED WITH SIX (6) EXITS FROM THE INTERIOR CORRIDORS AND MAIN

ENTRANCE VESTIBULE.

EXITS FROM SPACES

CODE REFERENCE: IBC TABLE 1006.2.1

REQUIRED: EVERY ROOM OR SPACE GREATER WITH AN OCCUPANT LOAD GREATER THAN 49 IS

REQUIRED TO BE PROVIDED WITH A MINIMUM OF TWO EXIT ACCESS DOORS. THESE EXIT ACCESS DOORS SHALL BE PROVIDED WITH ACCESS TO SEPARATE EXITS. THESE EXITS ARE PERMITTED TO OPEN TO A COMMON CORRIDOR GIVEN THAT THE CORRIDOR LEADS TO SEPARATE EXITS LOCATED IN

OPPOSITE DIRECTIONS.

EVERY MULTIPURPOSE ROOM IS REQUIRED TO BE PROVIDED WITH TWO EXIT ACCESS DOORS DUE TO

OCCUPANT LOAD EXCEEDING 49 PERSONS.

BASED ON THE USE, THE BUILDING IS CLASSIFIED AS SEPARATED MIXED USED WITH THE

FOLLOWING OCCUPANCIES:

1. RESIDENTIAL R-2 (IBC), RESIDENTIAL - DORMITORY (NFPA 101)

2. BUSINESS GROUP B (OFFICES, DAY ROOMS) IBC, BUSINESS (NFPA 101)

3. ASSEMBLY A-3 (IBC), ASSEMBLY W/O FIXED SEATING (NFPA 101)

4. STORAGE GROUP S-1 (IBC), STORAGE (NFPA 101)

A 1-HOUR FIRE BARRIER IS PROVIDED AROUND THE LAUNDRY ROOM PER NFPA 101 SECTION

14.3.2.1(2). THESE SEPARATION REQUIREMENTS ARE NOT OCCUPANCY SEPARATIONS.

EGRESS ARRANGEMENT

MIXED USE OCCUPANCY, SPRINKLER PROTECTED

COMPONENT MAXIMUM DISTANCE

RESIDENTIAL - DORMITORY

DEAD END CORRIDOR NFPA 101 - 28.2.5.3

50 FEET

EXIT TRAVEL DISTANCE

MIXED USE OCCUPANCY, SPRINKLER PROTECTED

ASSEMBLY MAX TRAVEL DISTANCE BETWEEN ANY

POINT IN A ROOM AND AN EXIT NFPA 101 - 12.2.6

250 FEET

RESIDENTIAL - DORMITORY TRAVEL DISTANCE

BETWEEN ANY POINT IN A ROOM AND AN EXIT

NFPA 101 - 28.2.6

200 FEET

DOOR REMOTENESS (NFPA 101)

EXIT - EXIT ACCESS DOORS, SEPARATED BY 1/3 OVERALL DIAGONAL.

DOORS ARE REQUIRED TO SWING IN THE DIRECTION OF EGRESS TRAVEL WHEN SERVING A ROOM OR

AREA WITH AN OCCUPANT LOAD OF 50 PERSONS OR MORE PER NFPA 101 SECTION 7.2.1.4.2.

THE FORCES REQUIRED TO OPEN ANY DOOR LEAF MANUALLY IN A MEANS OF EGRESS ARE NOT

PERMITTED TO EXCEED 15 LBF TO RELEASE THE LATCH, 30 LBF TO SET THE LEAF IN MOTION, AND 15 LBF TO OPEN THE LEAF PER NFPA 101, 7.2.1.7. THE EGRESS DOOR OPENING FORCES ARE ALSO

LIMITED BY THE ABA WHEN NON-RATED. (ABA SECTION 404.2.9).

CODE REFERENCE: NFPA 101 SECTIONS 7.2

REQUIRED: SEE DISCUSSION ABOVE FOR EGRESS ARRANGEMENT, DOOR SWING, AND OPENING

FORCE CRITERIA.

PROVIDED: EGRESS ARRANGEMENT, DOOR SWING, AND OPENING FORCE WILL COMPLY WITH

REQUIREMENTS SUMMARIZED ABOVE. TRAVEL DISTANCES, COMMON PATH, AND DEAD-END

CORRIDORS DO NOT EXCEED THE LIMITS FOR THE OCCUPANCY INVOLVED.

OCCUPANT LOAD

THE OCCUPANT LOAD IS BASED ON THE OCCUPANT LOADING FACTORS OF NFPA 101, TABLE 7.3.1.2

OCCUPANT LOAD

USE OCCUPANT LOAD FACTOR

ASSEMBLY (W/O FIXED SEATING) 15 SF PER PERSON (NET)

RESIDENTIAL - DORMITORY 200 SF PER PERSON (GROSS)

CIRCULATION 150 SF PER PERSON (GROSS)

STORAGE 500 SF PER PERSON (GROSS)

THE OCCUPANT LOAD FOR EACH FLOOR IS IDENTIFIED ON THE LIFE SAFETY PLANS.

MEANS OF EGRESS CAPACITY

THE FOLLOWING EGRESS CAPACITY FACTORS APPLY PER NFPA 101, TABLE 7.3.3.1

EGRESS CAPACITY FACTORS (WIDTH/PERSON)

LEVEL COMPONENETS AND

RAMPS

0.2 INCHES PER PERSON

STAIRWAYS 0.3 INCHES PER PERSON

PER NFPA 101 SECTION 7.2.1, A MINIMUM CLEAR DOOR WIDTH OF 32 INCHES IS REQUIRED.

CODE REFERENCE: NFPA 101 SECTION 7.2.1, 7.2.2 & 7.3.3.1

REQUIRED: CALCULATE MEANS OF EGRESS CAPACITY USING CRITERIA SUMMARIZED ABOVE. COMPLY

WITH MINIMUM CLEAR DOOR WIDTH OF 32 INCHES.

PROVIDED: EGRESS CAPACITY CALCULATIONS ARE SHOWN ON THE LIFE SAFETY PLANS. SUFFICIENT

EGRESS CAPACITY IS PROVIDED FROM THE BUILDING.

ILLUMINATION OF MEANS OF EGRESS

AHJ DETERMINES DESIGNATED EXIT ACCESS, AND EXIT DISCHARGE, AISLES, CORRIDORS, WALKWAYS, ETC. FOR EGRESS ILLUMINATION AND EMERGENCY LIGHTING (NFPA 101-7.8.1.1, 7.9.1.2)

ILLUMINATION OF MEANS OF EGRESS IS REQUIRED OCCUPANCIES IN ACCORDANCE WITH NFPA 101.

THE FLOORS AND WALKING SURFACES WITHIN AN EXIT AND WITHIN PORTIONS OF THE EXIT ACCESS AND EXIT DISCHARGE ARE REQUIRED TO BE ILLUMINATED IN ACCORDANCE WITH NFPA 101 SECTION 7.8.

CODE REFERENCE: NFPA 101 SECTION 7.8

REQUIRED: THE EGRESS LIGHTING IS REQUIRED TO BE PROVIDED SUCH THAT THE FAILURE OF ANY SINGLE LIGHTING UNIT DOES NOT RESULT IN AN ILLUMINATION LEVEL OF LESS THAN 0.2 FT-CANDLE

(2.2 LUX) IN ANY DESIGNATED AREA.

PROVIDED: ILLUMINATION OF MEANS OF EGRESS WILL BE PROVIDED TO COMPLY WITH

REQUIREMENTS OF NFPA 101 SECTION 7.8.

EMERGENCY LIGHTING

EMERGENCY LIGHTING WILL BE PROVIDED THROUGHOUT THE BUILDING IN ACCORDANCE WITH NFPA

101 SECTION 7.9.1. EMERGENCY LIGHTING SHALL BE PROVIDED IN CORRIDORS, RESTROOMS,

INTERIOR ROOMS WITHOUT NATURAL LIGHT, EXIT ACCESS, AT EXIT DISCHARGE AT EXTERIOR OF BUILDING AND IN ALL OCCUPIED ROOMS, INCLUDING THE MECHANICAL AND ELECTRICAL ROOMS PER

THE STANDARD DESIGN CRITERIA FOR CHILD DEVELOPMENT CENTERS.

EMERGENCY LIGHTING PROVIDED FOR EGRESS ILLUMINATION DURING POWER FAILURE, 1 FT-CANDLE AVERAGE AT GROUND, WITH 0.1 FT-CANDLE MINIMUM. IN 1-1/2 HOURS CAN DECREASE TO 0.6 FT-

CANDLES AVERAGE, AND 0.06 FT-CANDLES MINIMUM (NFPA 101-7.9, 7.9.2)

REFER TO THE ELECTRICAL DRAWINGS FOR LOCATIONS OF EMERGENCY LIGHTING.

CODE REFERENCE: NFPA 101 SECTION 7.9

REQUIRED: SEE ABOVE FOR DISCUSSION ON REQUIRED SYSTEM CHARACTERISTICS.

PROVIDED: EMERGENCY LIGHTING WILL BE PROVIDED THROUGHOUT THE BUILDING AS REQUIRED BY NFPA 101. EMERGENCY LIGHTING WILL BE PROVIDED AT THE EXIT DISCHARGE ON THE EXTERIOR OF THE BUILDING. EMERGENCY LIGHTING WILL ALSO BE PROVIDED IN ALL OCCUPIED ROOMS, INCLUDING

THE MECHANICAL AND ELECTRICAL ROOM.

EXIT SIGNAGE

EXIT SIGNS WILL COMPLY WITH THE CHARACTERISTICS OF NFPA 101 SECTION 7.10.

REFER TO THE ELECTRICAL DRAWINGS FOR LOCATIONS OF EXIT SIGNS.

CODE REFERENCE: NFPA 101 SECTION 7.10 & SECTION 16.2.10

REQUIRED: EXIT SIGNS ARE REQUIRED TO BE LOCATED ABOVE EACH EXIT ACCESS DOOR AND SUCH THAT NO POINT IN AN EXIT ACCESS CORRIDOR IS IN EXCESS OF THE RATED VIEWING DISTANCE, OR 100 FT, WHICHEVER IS LESS, FROM THE NEAREST SIGN. EXIT ACCESS DOORS REQUIRING EXIT

MARKINGS INCLUDES EXTERIOR EXIT DOORS PROVIDED.

PROVIDED: EXIT SIGNS WILL BE PROVIDED FOR AT EACH EXIT DOOR). ADDITIONAL SIGNS ARE

PROVIDED AS REQUIRED TO MARK THE MEANS OF EGRESS.

FIRE EXTINGUISHERS

FIRE EXTINGUISHERS ARE REQUIRED TO BE PROVIDED IN ACCORDANCE WITH THE IBC, NFPA 10 AND UFC 3-600-01. PER IBC SECTION 906.1 FIRE EXTINGUISHERS SHALL BE INSTALLED IN GROUP A, B, R-2, S-1 OCCUPANCIES MEETING THE SPACING AND RATING REQUIREMENTS FOR FIRE EXTINGUISHERS FOR CLASS A FIRE HAZARDS. FIRE EXTINGUISHERS SHALL BE PROVIDED AS FOLLOWS PER NFPA 10

TABLE 6.2.1.1 AND IBC TABLE 906.3(1):

CRITERIA

MINIMUM RATED SINGLE

EXTINGUISHER

2-A

LIGHT HAZARD

OCCUPANCY

ORDINARY HAZARD

OCCUPANCY

2-A

MAXIMUM FLOOR AREA PER

UNIT OF A

3,000 SF 1,500 SF

MAXIMUM FLOOR AREA FOR

EXTINGUISHER

11,250 SF 11,250 SF

MAXIMUM TRAVEL DISTANCE

TO EXTINGUISHER

75 FT 75 FT

FIRE ALARM AND MASS NOTIFICATION

THE FIRE ALARM AND MASS NOTIFICATION SYSTEMS DESIGNED AS SEPERATE TRANSCEIVERS AND

ANTENNAS AS REQUIRED IN UFC 3-600-01 AND UFC 4-021-01.

THE SYSTEM REPPORTS TO THE D-21 SYSTEM LOCATED AT BUILDING 580. THE NUMBER OF ZONES REPORTING TO THE D-21 FROM THE BUILDING SHALL BE COORDINATED WITH THE FORT LEONARD

WOOD (FLW) FIRE DEPARTMENT.

THE FIRE ALARM AND MASS NOTIFICATION SHARE SPEAKERS AND VISUAL “ALERT” APPLIANCES AS

IDENTIFIED IN UFC 3-600-01.

THE SYSTEM HAS TEXT MESSAGING IN COMPLIANCE WITH THE ENGINEERING AND CONSTRUCTION

BULLITEN ECB 2018-17.

ALL FIRE ALARM CONDUCTORS SHALL BE IN CONDUIT PER UFC 3-600-01.

OVERALL BUILIDNG AREA 180,73 GSF

- 1ST FLOOR 52,091 GSF

- 2ND THRU 5TH FLOOR 31,730 (EACH FLOOR)

- 6TH FLOOR (MECH RM) 1,462 GSF

IBC SECTION 906.1, EXCEPTION 2, PORTABLE FIRE EXTINGUISHERS SHALL ONLY BE REQUIRED IN SPECIAL-HAZARD AREAS, SUCH AS THE MECHANICAL ROOM, WHERE EACH MULTIPURPOSE ROOM IS PROVIDED WITH A PORTABLE FIRE EXTINGUISHER HAVING A MINIMUM RATING OF 2-A:20-B:C.

FULLY RECESSED CABINETS WITH SEE-THROUGH DOORS ARE REQUIRED TO BE PROVIDED IN THE FINISHED SPACES, MOUNTING BRACKETS (HOOKS) ARE PERMITTED IN STORAGE AND MECHANICAL AREAS. FIRE EXTINGUISHERS WILL BE MINIMUM 10-LB ABC TYPE UNLESS LARGER IS REQUIRED FOR THE

HAZARD IN ACCORDANCE WITH NFPA 10.

PORTABLE EXTINGUISHERS WITH A GROSS WEIGHT NOT EXCEEDING 40 POUNDS ARE REQUIRED TO BE INSTALLED SO THE MAXIMUM HEIGHT TO THE OPERATING HANDLE IS AT 48 INCHES ABOVE THE

FINISHED FLOOR FOR FRONT APPROACH TO COMPLY WITH ABA. PER NFPA 10, PORTABLE

EXTINGUISHERS WITH A GROSS WEIGHT EXCEEDING 40 POUNDS SHALL BE INSTALLED SO THE TOP IS

NOT MORE THAN 42 INCHES ABOVE THE FLOOR. THE CLEARANCE BETWEEN THE FLOOR AND THE

BOTTOM OF INSTALLED HAND-HELD PORTABLE EXTINGUISHES IS REQUIRED TO BE AT LEAST 4 INCHES.

FIRE EXTINGUISHERS WILL BE MOUNTED AT A HEIGHT TO ALSO COMPLY WITH ABA REQUIREMENTS.

IBC OCCUPANCY

A-3 NOT APPLICABLE UNLIMITED 4,540

B NOT APPLICABLE UNLIMITED 13,746

S-1 NOT APPLICABLE UNLIMITED 2,671

BUILDING ELEMENT

S-1 R-2, B, & A-3

1 - HOUR

1 - HOUR

1 - HOUR

0 - HOUR

COMMON PATH OF TRAVEL NFPA 101 - 28.2.5.2

50 FEET

100 FEET

50 FEET

BUSINESS

DEAD END CORRIDOR NFPA 101 - 38.2.5.3

COMMON PATH OF TRAVEL NFPA 101 - 38.2.5.2.2

ASSEMBLY

DEAD END CORRIDOR NFPA 101 - 12.2.5.3

COMMON PATH OF TRAVEL NFPA 101 - 12.2.5.2 75 FEET

20 FEET

BUSINESS MAX TRAVEL DISTANCE BETWEEN ANY

POINT IN A ROOM AND AN EXIT NFPA 101 - 38.2.6

300 FEET

COMPONENT MAXIMUM DISTANCE

BUSINESS 150 SF PER PERSON (GROSS)

EGRESS ARRANGEMENT

THE MEANS OF EGRESS ARRANGEMENT IS REQUIRED TO COMPLY WITH THE CRITERIA FOR FULLY

SPRINKLERED MIXED USE OCCUPANCIES PER NFPA 101:

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

US Army Corps of Engineers

S O

L

IC

IT

A

T

IO

N N

O

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

A

M A

R K

S

IZ

E

S U

B M

IT

T

E D

B Y

D A

T E

C O

N T

R A

C T

N O

C

H E

C K

E D

B Y

D R

A W

N B

Y

IS

S

U E

D A

T E

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

SHEET ID

A

D D

IT

IO

N O

F S

H E

E T

O C

T

F-001

L

IF

E S

A F

E T

Y C

O D

E A

N A

L Y

S

IS

F O

R T

L E

O N

A R

D W

O O

D M

IS

S

O U

R I

K A

N S

A S

C

IT

Y D

IS

T

R

IC

T J M c L A

U G

H L

IN

J M c L A

U G

H L

IN

C B

R O

W N

K W

A T

S O

N

A U

G U

S T

S E

E C

O V

E R

S H

E E

T

S E

E C

O V

E R

S H

E E

T

F

IL

E N

A M

E

RTA

A

IT

T R

A

IN

IN

G

C O

M P

L E

X

P

A R

T

P N

F

Y

A

IT

C o m p le x C

M I_

R V

T A

I.

rv t

E

T

H S

T R

E E

T

K A

N S

A S

C

IT

Y M

O

A N

S I D

Sheets
F-001 - LIFE SAFETY CODE ANALYSIS

File details come from the government source that posted it. Updated .