F-001 - LIFE SAFETY CODE ANALYSIS..pdf
PDF 105 KB Posted
- Attached to
- 403873 FLW AIT Barracks Complex II Phase 2
- Solicitation number
- W912DQ25RA004
About this file
This is a Life Safety Code Analysis document for an Advanced Individual Training (AIT) Barracks/Company Operations Facility (B/COF) project located at Fort Leonard Wood, Missouri. The six-story, 180,500 square foot building will include 310 total dwelling units (150 two-person and 160 three-person), multipurpose rooms, learning labs, day rooms, laundry facilities, administrative spaces, and storage areas. The facility is designed as Type IB construction, fully sprinklered, with comprehensive fire protection features including a new wet pipe sprinkler system, fire alarm control panel, mass notification system, emergency lighting, and exit signage. The building is classified as a mixed-use occupancy with residential (R-2), business (B), assembly (A-3), and storage (S-1) spaces, designed to comply with International Building Code (IBC) and National Fire Protection Association (NFPA) 101 Life Safety Code requirements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TABULAR VALUE
FULLY-SPRINKLERED
(SF)
FRONTAGE INCREASE
(% / SF)
ACTUAL AREA
(SF NOT INCLUDING
CORRIDORS)
R-2 NOT APPLICABLE UNLIMITED 37,202
CODE REFERENCE: IBC TABLE 504.3, IBC TABLE 506.2, AND IBC SECTION 508GENERAL INFORMATION:
BUILDING SUMMARY
ADVANCED INDIVIDUAL TRAINING (AIT) BARRACKS/COMPANY OPERATIONS FACILITY (B/COF)
PROJECT LOCATED IN FORT LEONARD WOOD, MISSOURI.
THE AIT B/COF IS A SIX-STORY STRUCTURE APPROXIMATELY 180,500 SQUARE FEET (SF) IN GROSS AREA. THE SIXTH FLOOR BEING UNOCCUPIED MECHANICAL ROOM. THE FACILITY WILL INCLUDE 150
TWO PERSON DWELLINGS AND 160 THREE PERSON DWELLINGS, TWO MULTIPURPOSE ROOMS (W/
MOVEABLE PARTIONS THAT DIVIDES EACH INTO THREE CLASS ROOMS), LEARNING LABS, DAY
ROOMS, LAUNDRY, ADMINISTRATIVE SUPPORT SPACES, STORAGE, AND SUPPLY ROOMS.
SUMMARY OF FIRE PROTECTION FEATURES:
PROTECT THROUGHOUT PER NFPA 13 AND UFC 3-600-01
NFPA 101
ALL OCCUPANCIES SHALL BE PROTECTED THROUGHOUT BY AN APPROVED, AUTOMATIC SPRINKLER
SYSTEM.
NEW WET PIPE SPRINKLER SYSTEM THROUGHOUT THE ENTIRE BUILDING IN ACCORDANCE WITH
UFC 3-600-01 AND NFPA 13.
WATER FOR THE SPRINKLER SYSTEM WILL BE SUPPLIED BY AN EXTENSION TO THE EXISTING
WATER MAIN SERVING THE ADJACENT FACILITIES. REFERENCE CIVIL DRAWINGS FOR MORE
INFORMATION.
NEW FIRE ALARM CONTROL PANEL (FACP) WILL BE LOCATED IN THE FIRE PUMP ROOM. THE
BUILDING WILL BE PROVIDED WITH A REMOTE ANNUNCIATOR IN THE MAIN LOBBY. SEPARATE FIRE ALARM AND MASS NOTIFICATION TRANSCEIVERS ARE REQUIRED. THE MASS NOTIFICATION SYSTEM
WILL BE FULLY INTERFACED WITH THE FIRE ALARM EQUIPMENT TO PROVIDE ALL FUNCTIONS
NECESSARY FOR INTERFACE WITH ALL LOCAL FEATURES.
FIRE EXTINGUISHER LOCATIONS, EMERGENCY LIGHTING, AND EXIT SIGNS IN ACCORDANCE WITH
NFPA 10, NFPA 101, AND UFC 3-600-01.
MEANS OF EGRESS WILL COMPLY WITH NFPA 101 AND AS INDICATED FOR THE PROJECT
APPLICABLE CODES AND STANDARDS REFERENCES:
THE APPLICABLE CODES AND STANDARDS FOR THE PROJECT ARE AS FOLLOWS:
UFC 1-200-01: DOB GENERAL BUILDING REQUIREMENTS
UFC 3-600-01: FIRE PROTECTION ENGINEERING FOR FACILITIES, CHANGE 6, MAY 2021
UFC 4-021-01: MASS NOTIFICATION SYSTEMS, CHANGE 1, JANUARY 2010
INTERNATIONAL BUILDING CODE (IBC), 2021 EDITION
NFPA 10: STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2022
NFPA 13: STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2022
NFPA 24: STANDARD FOR THE INSTALLATION OF PRIVATE SERVICE MAINS AND THEIR APPURTENANCES, 2022
NFPA 70: NATIONAL ELECTRICAL CODE, 2020
NFPA 72: NATIONAL FIRE ALARM AND SIGNALING CODE, 2022
NFPA 80: FIRE DOORS AND WINDOWS, 2022
NFPA 90A: STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS, 2021
NFPA 101: LIFE SAFETY CODE, 2021
OTHER REFERENCED CODES AND STANDARDS AS APPLICABLE.
BUILDING CODE ANALYSIS
DESIGN AND CONSTRUCTION WILL BE IN ACCORDANCE WITH THE FIRE RESISTIVE CONSTRUCTION
REQUIREMENTS, MAXIMUM ALLOWABLE FLOOR AREA AND BUILDING HEIGHT LIMITATIONS, AND
BUILDING SEPARATION/EXPOSURE PROTECTION REQUIREMENTS OF THE IBC, SELECTED FIRE
RESISTIVE CONSTRUCTION REQUIREMENTS OF NFPA 101, AND APPLICABLE REQUIREMENTS OF THE
REFERENCED UFCS.
OCCUPANCY CLASSIFICATION CODE REFERENCE:
IBC 508.3, 508.2.4, 304, 308.5, 1004.5, NFPA 101 SECTION 28.3.1
REQUIRED: THE BUILDING WILL COMPLY WITH THE MEANS OF EGRESS, CONSTRUCTION TYPE,
PROTECTION, AND OTHER SAFEGUARDS BASED ON THE USE OF EACH PORTION.
BUILDING CONSTRUCTION
THE BUILDING IS DESIGNED AS TYPE IB CONSTRUCTION AS DEFINED BY IBC CHAPTER 6 AND
COMPLIES WITH THE HEIGHT AND AREA LIMITS FOR MIXED-USE SEPARATED BUILDING.
FIRE RESISTANCE RATING REQUIREMENTS FOR TYPE IB CONSTRUCTION, IBC TABLE 601
PRIMARY STRUCTURAL FRAME
BEARING WALLS
EXTERIOR
INTERIOR
EXTERIOR NON-BEARING WALLS AND PARTITIONS
INTERIOR NON-BEARING WALLS AND PARTITIONS
FLOOR CONSTRUCTION AND SECONDARY MEMBERS
ROOF CONSTRUCTION AND SECONDARY MEMBERS
REQUIRED RATING
2 - HOUR
2 - HOUR
2 - HOUR
0 - HOUR
0 - HOUR, 1/2 HOUR REQUIRED
BETWEEN DWELLING UNITS
2 - HOUR
1 - HOUR
EXTERIOR EXPOSURE PROTECTION
CODE REFERENCE: IBC 602
REQUIRED: BELOW IN ACCORDANCE WITH IBC TABLE 602 FOR EXTERIOR WALL ASSEMBLIES AND IBC TABLE 705.8 FOR PROTECTION OF EXTERIOR WALL OPENINGS. UNLIMITED UNPROTECTED EXTERIOR WALL OPENINGS AREA PERMITTED FOR BUILDINGS WHOSE EXTERIOR BEARING WALLS, EXTERIOR NON-BEARING WALLS, AND EXTERIOR PRIMARY STRUCTURAL FRAME ARE NOT REQUIRED TO BE FIRE-
RESISTANCE RATED PER IBC 705.8.1, EXCEPTION 2
TYPE IB CONSTRUCTION, IBC TABLE 705.5
FIRE SEPARATION
DISTANCE (FEET)
< 5 FEET 2 - HOUR
REQUIRED EXTERIOR FIRE-RESISTANCE RATING
5 - 10 FEET 1 - HOUR
10 - 30 FEET 1 - HOUR
> 30 FEET 0 - HOUR
PROVIDED: THE FIRE SEPARATION DISTANCE FOR THE BUILDING IS GREATER THAN 30 FEET, WHICH
ALLOWS THE EXTERIOR WALLS TO BE NON- RATED, NON-COMBUSTIBLE CONSTRUCTION. THE
MAXIMUM AREA OF UNPROTECTED EXTERIOR WALL OPENINGS IS UNLIMITED.
FIRE-RESISTANCE RATED CONSTRUCTION
FIRE-RESISTANCE RATED CONSTRUCTION IS REQUIRED TO COMPLY WITH NFPA 101 FOR INTERNAL PARTITIONS PER UFC 3-600-01. PER UFC 3-600-01, SMOKE BARRIERS ARE NOT REQUIRED IN THE
BUILDING WHEN FULLY PROTECTED BY AN AUTOMATIC FIRE SPRINKLER SYSTEM.
THE FOLLOWING SEPARATIONS ARE PROVIDED IN THE BUILDING:
OCCUPANCY SEPARATIONS
- DWELLING UNIT 1/2 FIRE BARRIERS
ENCLOSURE PROTECTION
- EXIT ENCLOSURES, 2 HOUR FIRE BARRIER
- CORRIDORS, 1/2 HOUR FIRE BARRIER
- DWELLING UNITS, 1/2 HOUR FIRE BARRIERS
- LAUNDRY ROOMS, 1 HOUR FIRE BARRIERS
- BOILER ROOMS, 1 HOUR FIRE BARRIERS
- STORAGE ROOMS, 1 HOUR FIRE BARRIERS
- SHAFT ENCLOSURES (NFPA 90A, 5.3.4.2)
- VERTICAL OPENINGS (NFPA 101 8.6) 1 HOUR FIRE BARRIER / SMOKE BARRIER
DOOR REQUIREMENTS
- DOORS IN 1/2 HOUR RATED WALLS
- 20 MINUTE FIRE RATING, WITH DOOR CLOSERS
- DOORS IN 1 HOUR RATED WALLS
- 45 MINUTE FIRE RATING, WITH DOOR CLOSERS
- DOORS IN 2 HOUR RATED WALLS
- 1 1/2 HOUR RATING, WITH DOOR CLOSERS
INTERIOR FINISHES
- WALLS, EXIT ENCLOSURES, CLASS A
- WALLS, LOBBIES AND CORRIDORS, CLASS A OR B
- WALLS, OTHER SPACES, CLASS A, B, OR C
- FLOORS, EXIT ENCLOSURES AND CORRIDORS, CLASS II
CODE REFERENCE: UFC 3-600-1 SECTION 7-2, NFPA 101 SECTION 28.3.1.
REQUIRED: FIRE-RESISTANCE RATED CONSTRUCTION (1-HR FIRE BARRIER) REQUIRED AT ENCLOSED
VERTICAL OPENINGS. LAUNDRY ROOMS GREATER THAT 100 SF W/ 1 HOUR SEPARATION AND
SPRINKLERED.
PROVIDED: FIRE-RESISTANCE RATED CONSTRUCTION AS SHOWN ON THE LIFE SAFETY PLANS.
TYPE I-B, FULLY SPRINKLERED, SIX-STORY:
USE OF IBC AND NFPA 101
IBC - USE FOR CONSTRUCTION TYPE, FIRE RESISTANCE, HEIGHT (UFC 3-600-01), AREA IS UNLIMITED
AND SEPARATION IS 40 FEET.
NFPA 101 - USE FOR EGRESS, SAFETY TO LIFE AND NONBEARING PARTITION FIRE RESISTANCE. FOR
CONFLICTS WITH IBC, COMPLY WITH NFPA 101.
OCCUPANCY CLASSIFICATION
THE PRIMARY OCCUPANCY OF THE BUILDING IS RESIDENTIAL - DORMITORY OCCUPANCY. THE
VARIOUS OCCUPANCIES WILL NOT BE SEPARATED FROM EACH OTHER;
THIS DESIGN IS CLASSIFIED AS DORMITORY RATHER THAN APARTMENT DUE TO EACH DWELLING
NOT HAVING INDEPENDENT COOKING FACILITIES
MEANS OF EGRESS
THE MEANS OF EGRESS FOR THE BUILDING WILL COMPLY WITH THE REQUIREMENTS FOR RESIDENTIAL- DORMITORY OCCUPANCIES AS OUTLINED IN NFPA 101, CHAPTER 28. MEANS OF EGRESS COMPONENTS
ARE BASED ON THE PROVISIONS FOR FULLY-SPRINKLERED BUILDINGS.
REFER TO THE LIFE SAFETY PLANS FOR DETAILS ON THE MEANS OF EGRESS.
NUMBER EXITS
THE MINIMUM NUMBER OF EXITS PROVIDED FROM EACH STORY AND EACH INDIVIDUAL SPACE SHALL BE
IN ACCORDANCE WITH NFPA 101, CHAPTER 28.
EXITS FROM STORY
CODE REFERENCE: NFPA 101 SECTION 7.4.1.2 AND SECTION 28.2.4
REQUIRED: A MINIMUM OF TWO EXITS ARE REQUIRED FROM ANY STORY OF THE BUILDING.
PROVIDED: THE BUILDING IS PROVIDED WITH SIX (6) EXITS FROM THE INTERIOR CORRIDORS AND MAIN
ENTRANCE VESTIBULE.
EXITS FROM SPACES
CODE REFERENCE: IBC TABLE 1006.2.1
REQUIRED: EVERY ROOM OR SPACE GREATER WITH AN OCCUPANT LOAD GREATER THAN 49 IS
REQUIRED TO BE PROVIDED WITH A MINIMUM OF TWO EXIT ACCESS DOORS. THESE EXIT ACCESS DOORS SHALL BE PROVIDED WITH ACCESS TO SEPARATE EXITS. THESE EXITS ARE PERMITTED TO OPEN TO A COMMON CORRIDOR GIVEN THAT THE CORRIDOR LEADS TO SEPARATE EXITS LOCATED IN
OPPOSITE DIRECTIONS.
EVERY MULTIPURPOSE ROOM IS REQUIRED TO BE PROVIDED WITH TWO EXIT ACCESS DOORS DUE TO
OCCUPANT LOAD EXCEEDING 49 PERSONS.
BASED ON THE USE, THE BUILDING IS CLASSIFIED AS SEPARATED MIXED USED WITH THE
FOLLOWING OCCUPANCIES:
1. RESIDENTIAL R-2 (IBC), RESIDENTIAL - DORMITORY (NFPA 101)
2. BUSINESS GROUP B (OFFICES, DAY ROOMS) IBC, BUSINESS (NFPA 101)
3. ASSEMBLY A-3 (IBC), ASSEMBLY W/O FIXED SEATING (NFPA 101)
4. STORAGE GROUP S-1 (IBC), STORAGE (NFPA 101)
A 1-HOUR FIRE BARRIER IS PROVIDED AROUND THE LAUNDRY ROOM PER NFPA 101 SECTION
14.3.2.1(2). THESE SEPARATION REQUIREMENTS ARE NOT OCCUPANCY SEPARATIONS.
EGRESS ARRANGEMENT
MIXED USE OCCUPANCY, SPRINKLER PROTECTED
COMPONENT MAXIMUM DISTANCE
RESIDENTIAL - DORMITORY
DEAD END CORRIDOR NFPA 101 - 28.2.5.3
50 FEET
EXIT TRAVEL DISTANCE
MIXED USE OCCUPANCY, SPRINKLER PROTECTED
ASSEMBLY MAX TRAVEL DISTANCE BETWEEN ANY
POINT IN A ROOM AND AN EXIT NFPA 101 - 12.2.6
250 FEET
RESIDENTIAL - DORMITORY TRAVEL DISTANCE
BETWEEN ANY POINT IN A ROOM AND AN EXIT
NFPA 101 - 28.2.6
200 FEET
DOOR REMOTENESS (NFPA 101)
EXIT - EXIT ACCESS DOORS, SEPARATED BY 1/3 OVERALL DIAGONAL.
DOORS ARE REQUIRED TO SWING IN THE DIRECTION OF EGRESS TRAVEL WHEN SERVING A ROOM OR
AREA WITH AN OCCUPANT LOAD OF 50 PERSONS OR MORE PER NFPA 101 SECTION 7.2.1.4.2.
THE FORCES REQUIRED TO OPEN ANY DOOR LEAF MANUALLY IN A MEANS OF EGRESS ARE NOT
PERMITTED TO EXCEED 15 LBF TO RELEASE THE LATCH, 30 LBF TO SET THE LEAF IN MOTION, AND 15 LBF TO OPEN THE LEAF PER NFPA 101, 7.2.1.7. THE EGRESS DOOR OPENING FORCES ARE ALSO
LIMITED BY THE ABA WHEN NON-RATED. (ABA SECTION 404.2.9).
CODE REFERENCE: NFPA 101 SECTIONS 7.2
REQUIRED: SEE DISCUSSION ABOVE FOR EGRESS ARRANGEMENT, DOOR SWING, AND OPENING
FORCE CRITERIA.
PROVIDED: EGRESS ARRANGEMENT, DOOR SWING, AND OPENING FORCE WILL COMPLY WITH
REQUIREMENTS SUMMARIZED ABOVE. TRAVEL DISTANCES, COMMON PATH, AND DEAD-END
CORRIDORS DO NOT EXCEED THE LIMITS FOR THE OCCUPANCY INVOLVED.
OCCUPANT LOAD
THE OCCUPANT LOAD IS BASED ON THE OCCUPANT LOADING FACTORS OF NFPA 101, TABLE 7.3.1.2
OCCUPANT LOAD
USE OCCUPANT LOAD FACTOR
ASSEMBLY (W/O FIXED SEATING) 15 SF PER PERSON (NET)
RESIDENTIAL - DORMITORY 200 SF PER PERSON (GROSS)
CIRCULATION 150 SF PER PERSON (GROSS)
STORAGE 500 SF PER PERSON (GROSS)
THE OCCUPANT LOAD FOR EACH FLOOR IS IDENTIFIED ON THE LIFE SAFETY PLANS.
MEANS OF EGRESS CAPACITY
THE FOLLOWING EGRESS CAPACITY FACTORS APPLY PER NFPA 101, TABLE 7.3.3.1
EGRESS CAPACITY FACTORS (WIDTH/PERSON)
LEVEL COMPONENETS AND
RAMPS
0.2 INCHES PER PERSON
STAIRWAYS 0.3 INCHES PER PERSON
PER NFPA 101 SECTION 7.2.1, A MINIMUM CLEAR DOOR WIDTH OF 32 INCHES IS REQUIRED.
CODE REFERENCE: NFPA 101 SECTION 7.2.1, 7.2.2 & 7.3.3.1
REQUIRED: CALCULATE MEANS OF EGRESS CAPACITY USING CRITERIA SUMMARIZED ABOVE. COMPLY
WITH MINIMUM CLEAR DOOR WIDTH OF 32 INCHES.
PROVIDED: EGRESS CAPACITY CALCULATIONS ARE SHOWN ON THE LIFE SAFETY PLANS. SUFFICIENT
EGRESS CAPACITY IS PROVIDED FROM THE BUILDING.
ILLUMINATION OF MEANS OF EGRESS
AHJ DETERMINES DESIGNATED EXIT ACCESS, AND EXIT DISCHARGE, AISLES, CORRIDORS, WALKWAYS, ETC. FOR EGRESS ILLUMINATION AND EMERGENCY LIGHTING (NFPA 101-7.8.1.1, 7.9.1.2)
ILLUMINATION OF MEANS OF EGRESS IS REQUIRED OCCUPANCIES IN ACCORDANCE WITH NFPA 101.
THE FLOORS AND WALKING SURFACES WITHIN AN EXIT AND WITHIN PORTIONS OF THE EXIT ACCESS AND EXIT DISCHARGE ARE REQUIRED TO BE ILLUMINATED IN ACCORDANCE WITH NFPA 101 SECTION 7.8.
CODE REFERENCE: NFPA 101 SECTION 7.8
REQUIRED: THE EGRESS LIGHTING IS REQUIRED TO BE PROVIDED SUCH THAT THE FAILURE OF ANY SINGLE LIGHTING UNIT DOES NOT RESULT IN AN ILLUMINATION LEVEL OF LESS THAN 0.2 FT-CANDLE
(2.2 LUX) IN ANY DESIGNATED AREA.
PROVIDED: ILLUMINATION OF MEANS OF EGRESS WILL BE PROVIDED TO COMPLY WITH
REQUIREMENTS OF NFPA 101 SECTION 7.8.
EMERGENCY LIGHTING
EMERGENCY LIGHTING WILL BE PROVIDED THROUGHOUT THE BUILDING IN ACCORDANCE WITH NFPA
101 SECTION 7.9.1. EMERGENCY LIGHTING SHALL BE PROVIDED IN CORRIDORS, RESTROOMS,
INTERIOR ROOMS WITHOUT NATURAL LIGHT, EXIT ACCESS, AT EXIT DISCHARGE AT EXTERIOR OF BUILDING AND IN ALL OCCUPIED ROOMS, INCLUDING THE MECHANICAL AND ELECTRICAL ROOMS PER
THE STANDARD DESIGN CRITERIA FOR CHILD DEVELOPMENT CENTERS.
EMERGENCY LIGHTING PROVIDED FOR EGRESS ILLUMINATION DURING POWER FAILURE, 1 FT-CANDLE AVERAGE AT GROUND, WITH 0.1 FT-CANDLE MINIMUM. IN 1-1/2 HOURS CAN DECREASE TO 0.6 FT-
CANDLES AVERAGE, AND 0.06 FT-CANDLES MINIMUM (NFPA 101-7.9, 7.9.2)
REFER TO THE ELECTRICAL DRAWINGS FOR LOCATIONS OF EMERGENCY LIGHTING.
CODE REFERENCE: NFPA 101 SECTION 7.9
REQUIRED: SEE ABOVE FOR DISCUSSION ON REQUIRED SYSTEM CHARACTERISTICS.
PROVIDED: EMERGENCY LIGHTING WILL BE PROVIDED THROUGHOUT THE BUILDING AS REQUIRED BY NFPA 101. EMERGENCY LIGHTING WILL BE PROVIDED AT THE EXIT DISCHARGE ON THE EXTERIOR OF THE BUILDING. EMERGENCY LIGHTING WILL ALSO BE PROVIDED IN ALL OCCUPIED ROOMS, INCLUDING
THE MECHANICAL AND ELECTRICAL ROOM.
EXIT SIGNAGE
EXIT SIGNS WILL COMPLY WITH THE CHARACTERISTICS OF NFPA 101 SECTION 7.10.
REFER TO THE ELECTRICAL DRAWINGS FOR LOCATIONS OF EXIT SIGNS.
CODE REFERENCE: NFPA 101 SECTION 7.10 & SECTION 16.2.10
REQUIRED: EXIT SIGNS ARE REQUIRED TO BE LOCATED ABOVE EACH EXIT ACCESS DOOR AND SUCH THAT NO POINT IN AN EXIT ACCESS CORRIDOR IS IN EXCESS OF THE RATED VIEWING DISTANCE, OR 100 FT, WHICHEVER IS LESS, FROM THE NEAREST SIGN. EXIT ACCESS DOORS REQUIRING EXIT
MARKINGS INCLUDES EXTERIOR EXIT DOORS PROVIDED.
PROVIDED: EXIT SIGNS WILL BE PROVIDED FOR AT EACH EXIT DOOR). ADDITIONAL SIGNS ARE
PROVIDED AS REQUIRED TO MARK THE MEANS OF EGRESS.
FIRE EXTINGUISHERS
FIRE EXTINGUISHERS ARE REQUIRED TO BE PROVIDED IN ACCORDANCE WITH THE IBC, NFPA 10 AND UFC 3-600-01. PER IBC SECTION 906.1 FIRE EXTINGUISHERS SHALL BE INSTALLED IN GROUP A, B, R-2, S-1 OCCUPANCIES MEETING THE SPACING AND RATING REQUIREMENTS FOR FIRE EXTINGUISHERS FOR CLASS A FIRE HAZARDS. FIRE EXTINGUISHERS SHALL BE PROVIDED AS FOLLOWS PER NFPA 10
TABLE 6.2.1.1 AND IBC TABLE 906.3(1):
CRITERIA
MINIMUM RATED SINGLE
EXTINGUISHER
2-A
LIGHT HAZARD
OCCUPANCY
ORDINARY HAZARD
OCCUPANCY
2-A
MAXIMUM FLOOR AREA PER
UNIT OF A
3,000 SF 1,500 SF
MAXIMUM FLOOR AREA FOR
EXTINGUISHER
11,250 SF 11,250 SF
MAXIMUM TRAVEL DISTANCE
TO EXTINGUISHER
75 FT 75 FT
FIRE ALARM AND MASS NOTIFICATION
THE FIRE ALARM AND MASS NOTIFICATION SYSTEMS DESIGNED AS SEPERATE TRANSCEIVERS AND
ANTENNAS AS REQUIRED IN UFC 3-600-01 AND UFC 4-021-01.
THE SYSTEM REPPORTS TO THE D-21 SYSTEM LOCATED AT BUILDING 580. THE NUMBER OF ZONES REPORTING TO THE D-21 FROM THE BUILDING SHALL BE COORDINATED WITH THE FORT LEONARD
WOOD (FLW) FIRE DEPARTMENT.
THE FIRE ALARM AND MASS NOTIFICATION SHARE SPEAKERS AND VISUAL “ALERT” APPLIANCES AS
IDENTIFIED IN UFC 3-600-01.
THE SYSTEM HAS TEXT MESSAGING IN COMPLIANCE WITH THE ENGINEERING AND CONSTRUCTION
BULLITEN ECB 2018-17.
ALL FIRE ALARM CONDUCTORS SHALL BE IN CONDUIT PER UFC 3-600-01.
OVERALL BUILIDNG AREA 180,73 GSF
- 1ST FLOOR 52,091 GSF
- 2ND THRU 5TH FLOOR 31,730 (EACH FLOOR)
- 6TH FLOOR (MECH RM) 1,462 GSF
IBC SECTION 906.1, EXCEPTION 2, PORTABLE FIRE EXTINGUISHERS SHALL ONLY BE REQUIRED IN SPECIAL-HAZARD AREAS, SUCH AS THE MECHANICAL ROOM, WHERE EACH MULTIPURPOSE ROOM IS PROVIDED WITH A PORTABLE FIRE EXTINGUISHER HAVING A MINIMUM RATING OF 2-A:20-B:C.
FULLY RECESSED CABINETS WITH SEE-THROUGH DOORS ARE REQUIRED TO BE PROVIDED IN THE FINISHED SPACES, MOUNTING BRACKETS (HOOKS) ARE PERMITTED IN STORAGE AND MECHANICAL AREAS. FIRE EXTINGUISHERS WILL BE MINIMUM 10-LB ABC TYPE UNLESS LARGER IS REQUIRED FOR THE
HAZARD IN ACCORDANCE WITH NFPA 10.
PORTABLE EXTINGUISHERS WITH A GROSS WEIGHT NOT EXCEEDING 40 POUNDS ARE REQUIRED TO BE INSTALLED SO THE MAXIMUM HEIGHT TO THE OPERATING HANDLE IS AT 48 INCHES ABOVE THE
FINISHED FLOOR FOR FRONT APPROACH TO COMPLY WITH ABA. PER NFPA 10, PORTABLE
EXTINGUISHERS WITH A GROSS WEIGHT EXCEEDING 40 POUNDS SHALL BE INSTALLED SO THE TOP IS
NOT MORE THAN 42 INCHES ABOVE THE FLOOR. THE CLEARANCE BETWEEN THE FLOOR AND THE
BOTTOM OF INSTALLED HAND-HELD PORTABLE EXTINGUISHES IS REQUIRED TO BE AT LEAST 4 INCHES.
FIRE EXTINGUISHERS WILL BE MOUNTED AT A HEIGHT TO ALSO COMPLY WITH ABA REQUIREMENTS.
IBC OCCUPANCY
A-3 NOT APPLICABLE UNLIMITED 4,540
B NOT APPLICABLE UNLIMITED 13,746
S-1 NOT APPLICABLE UNLIMITED 2,671
BUILDING ELEMENT
S-1 R-2, B, & A-3
1 - HOUR
1 - HOUR
1 - HOUR
0 - HOUR
COMMON PATH OF TRAVEL NFPA 101 - 28.2.5.2
50 FEET
100 FEET
50 FEET
BUSINESS
DEAD END CORRIDOR NFPA 101 - 38.2.5.3
COMMON PATH OF TRAVEL NFPA 101 - 38.2.5.2.2
ASSEMBLY
DEAD END CORRIDOR NFPA 101 - 12.2.5.3
COMMON PATH OF TRAVEL NFPA 101 - 12.2.5.2 75 FEET
20 FEET
BUSINESS MAX TRAVEL DISTANCE BETWEEN ANY
POINT IN A ROOM AND AN EXIT NFPA 101 - 38.2.6
300 FEET
COMPONENT MAXIMUM DISTANCE
BUSINESS 150 SF PER PERSON (GROSS)
EGRESS ARRANGEMENT
THE MEANS OF EGRESS ARRANGEMENT IS REQUIRED TO COMPLY WITH THE CRITERIA FOR FULLY
SPRINKLERED MIXED USE OCCUPANCIES PER NFPA 101:
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
US Army Corps of Engineers
S O
L
IC
IT
A
T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T
E D
B Y
D A
T E
C O
N T
R A
C T
N O
C
H E
C K
E D
B Y
D R
A W
N B
Y
IS
S
U E
D A
T E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
A
D D
IT
IO
N O
F S
H E
E T
O C
T
F-001
L
IF
E S
A F
E T
Y C
O D
E A
N A
L Y
S
IS
F O
R T
L E
O N
A R
D W
O O
D M
IS
S
O U
R I
K A
N S
A S
C
IT
Y D
IS
T
R
IC
T J M c L A
U G
H L
IN
J M c L A
U G
H L
IN
C B
R O
W N
K W
A T
S O
N
A U
G U
S T
S E
E C
O V
E R
S H
E E
T
S E
E C
O V
E R
S H
E E
T
F
IL
E N
A M
E
RTA
A
IT
T R
A
IN
IN
G
C O
M P
L E
X
P
A R
T
P N
F
Y
A
IT
C o m p le x C
M I_
R V
T A
I.
rv t
E
T
H S
T R
E E
T
K A
N S
A S
C
IT
Y M
O
A N
S I D
| Sheets |
| F-001 - LIFE SAFETY CODE ANALYSIS |
File details come from the government source that posted it. Updated .