Question # Document, Page #, Paragraph # Question Answer

Number of evacuations of the Dry alarm valve station (Trockenalarm Ventilstation-

TAV)

No historical data is available.

Type foam mixing systems Type: Mechanical valve low pressure activated (insert mixing device/ valve) with connected jockey pumps to ensure the right pressure to get the concentration to the wet piping system. No further data is available at this time. Additional data will be provided upon award.

Type and dimensions of the wet alarm valve station/ nassalarm ventilstation (NAV), dry alarm valve station/trockenalarm ventilstation (TAV), throwback flap/ruckschlagklappe (RSK)

No data is available at this time. Additional data will be provided upon award.

Type of flow detector with or without ZoneCheck

No data is available at this time. Additional data will be provided upon award.

Type and performance (electrical power and output of the pump) of the disel pump (no power replacement system)

No data is available at this time. Additional data will be provided upon award.

Is it possible that we get a deferment to submit the offer by 14 days because the site visit took place on January 1, 2019 and subcontractors are not able to send us their offers in time.

Solicitation due date is hereby extended.

GFP Module Supplement to Attachment 7 What should be entered for GFP Module Attachment Supplement to Attachment 7.

Interested vendors are not responsible for completing the GFP Module Supplement to Attachment 7. It is for informational purposes only.