USAG Wiesbaden Directorate Public Works

DIRECTORATE OF EMERGENCY SERVICES

FIRE AND EMERGENCY SERVICES

Technical Standard for the Connection of Fire Alarm

Systems in the Area of the United States Army Garrison Wiesbaden

“DEDICATION TO SUPPORT”

DEPARTMENT OF THE ARMY

UNITED STATES ARMY GARRISON, Wiesbaden

UNIT 29623

APO AE 09005-9623

IMWB-PW-ES July 18, 2016

MEMORANDUM FOR

SUBJECT: Technical Standard for the Connection of Fire Alarm Systems in the Area of the United States Army Garrison Wiesbaden.

Table of Contents

1. Preface

2. Scope of Application within the USAG Wiesbaden footprint………………………………………………………………….7

3. Legal Foundations

3.1 Responsibilities……………………………………………………………………………………………………………………………… 8

3.2 General Provisions

3.3 Fire Alarm Control Panel (FACP)

3.4 Fire Command Center

3.5 Fire Department Lockbox and Release Element

3.6 Technical Requirements

3.7 Fire Panel programming…………………………………………………………………………………………………………….. 12

3.8 Fire suppression systems…………………………………………………………………………………………………………… 12

4. Pictographs and Symbols

4.1 Line Cards and Building Lay-out Plans

4.2 2 Annunciator Panel

5 Signal Devices

5.1 Audible Signal Devices

5.2 Optical Signal Devices

6 Detection and Control Devices

6.1 General Requirements

6.2 Pull Stations

6.3 Automatic Detectors

6.4 Smoke Aspirating Systems

6.5 External Control of periphery systems

6.6 Central Fire Alarm Systems Control Unit

6.7 Transmission

6.8 Suspended Ceilings and False Floors

7 Final Acceptance

8 Maintenance and Repair of Fire Alarm Systems

9 Glossary of Acronyms, Abbreviations & Terminology

Appendix Listing:

APP-A-Feuerwehrlaufkarten Muster APP-B Feuerwehrplan MUSTER APP-C Evacuation Plan Sample Bi-Lingual 2015 APP-D Technical Requirements EN + DE APP-E Fire Alarm System Programming

1. Preface

Outlined technical standard for the connection of Fire Alarm Systems (TCS –Technical

Connection Standard) will serve as a monitoring tool for the US Army Garrison

Wiesbaden as well as a planning tool for Directorate of Public Works planning engineers. Purpose of this standard is to ensure contract reliability for the contractor, the contracting party, planning engineers and installation firms.

Planning engineers/offices and installation firms shall prove their professional qualification IAW DIN 14675, DIN EN 54, NFPA 72, NFPA 101 and all related regulations in current version by submitting respective certificates to the contracting entity prior to contract award.

Determination of the required extent of protection rests within the scope of responsibility of the USAG Wiesbaden, Fire Prevention Division.

This standard may be subject to purpose related deviations. Conception, planning and constructional deviations are subject to prior justification and do require coordination with, and the approval of both, the USAG Wiesbaden, Directorate of Public Works as well as the USAG Wiesbaden, Fire Prevention Division. Any deviation shall be documented in writing.

The following provisions of the TCS are a binding part of each contract pertaining to project planning, project construction, maintenance and repair of Fire Alarm Systems and shall be attached to the respective solicitation documents.

The USAG Wiesbaden Fire & Emergency Services Division will update the provisions of this TCS as needed and/or as relevant underlying provisions change.

In general the following requirements respectively guidelines for planning, installation and modification of Fire Alarm Systems shall be met.

2. Scope of Application within the USAG Wiesbaden

The jurisdictional area of the USAG Wiesbaden extends to any installation within the regional area of the USAG Wiesbaden.

The provisions of this TCS do not apply to occupancies used by the US Air Force and which, in case of fire alarm, fall within their range of responsibility.

Nevertheless, it is the intent that that these provisions be implemented in those buildings as well to the farthest extent possible.

3. Legal Foundations

Below listed guidelines and regulations shall be observed for planning/design and construction of Fire Alarm Systems:

UFC 3-600-01 Unified Facility Criteria - Fire protection engineering for facilities

UFC 3-600-02 Unified Facility Criteria – Operation and maintenance: inspection, testing, and maintenance of fire protection systems

NFPA 13 Installation of Sprinkler Systems NFPA 20 Installation of Stationary Pumps NFPA 72 National Fire Alarm and Signaling Code ANSI/NFPA NFPA 75 Fire Protection of Information Technology Equipment NFPA 76 Fire Protection of Telecommunications Facilities NFPA 80 Fire Doors and Other Opening Protectives NFPA 80A, Protection of

Buildings from Exterior Fire Exposures NFPA 88A Parking Structures NFPA 90A Installation of Air-Conditioning and Ventilating Systems NFPA 90B Installation of Warm Air Heating and Air-Conditioning Systems NFPA 92A Standard for Smoke Control Systems Utilizing Barriers and Pressure

Differences NFPA 101 Life Safety Code, NFC

DIN 0833 1-4 Gefahrenmeldeanlagen für Brand und Einbruch (Fire and Intrusion Alarm Systems)

DIN 14675 Brandmeldeanlagen - Aufbau und Betrieb (Fire Alarm Systems – Design and Operation)

DIN EN 54 Brandmeldeanlagen (Fire Alarm Systems)

DIN 14661 Feuerwehr-Bedienfeld für Brandmeldeanlagen (Fire Department Control Panel (FACP) for Fire Alarm Systems)

DIN 14662 Feuerwehr-Anzeigetableau (Anunciator Panel)

DIN 14034 Graphische Symbole (Pictographs and Symbols)

TAB Technische Anschlussbedingungen Brandmeldeanlagen der

USAG Wiesbaden(Technical Connection Standard Fire alarm Systems - USAG Wiesbaden)

The provisions of NFPA and VDS shall be observed whenever required and technically feasible.

3.1 Responsibilities

The sole responsibility for implementation planning and construction rests with the U.S.

Army Contracting Officer’s Representative (COR) representing the Contracting Officer.

The Contracting Officer’s Representative serves as the point of contact for all project-related issues for both, contractors and U.S. agencies. Any project related inquiries shall be forwarded through his/her office to the responsible U.S. division

3.2 General Provisions

Planning and construction/modification of fire alarm systems shall comply with the provisions outlined in section 3 above.

The ordering party will prepare the request for the required data lines. Type of required line quality (Provider) is subject to coordination with the USAG Wiesbaden, DPW, Electrical Branch as well as 5th Signal Command / 2nd Signal Command.

The contractor shall provide a concept, meeting the requirements of DIN 14675. The concept provided is subject to the responsible Fire Department’s review and approval.

Documentation (design concept, specifications and construction plans) related to new installation or modification of existing fire alarm systems do generally require prior approval of/release by the responsible Fire Department.

Programming of fire alarm systems and clear text data entry is the responsibility of the installation firm. Text to be entered and graphics to be used are subject to prior coordination with the responsible USAG Wiesbaden Fire Department. The program code shall be handed over in digital (CD or DVD) and hard copy format.

Concept planning shall provide for widest elimination of intrusion and false alarms.

Central fire alarm system units shall process system related information only.

Upon completion of fire alarm system extensions and/or modifications final acceptance is required. The final acceptance shall be performed as outlined in section 7.

3.3 Fire Alarm Control Panel (FACP)

A dedicated room or casing of fire resistive construction shall house the fire alarm control panel in each respective building. At least one optical smoke detector shall be installed in each fire alarm control panel room/enclosure.

The maximum height of the mounted fire alarm control panel is not to exceed 1 700mm measured from the upper edge of the unit to the top edge of the floor. An additional

230 Volt socket shall be installed in the vicinity of the panel (max. distance 2m) for maintenance and repair purposes.

The fire alarm system fuse element (230V supply) shall be marked red in the electrical distribution panel and labeled in German and English. A respective notification shall be visibly mounted at/in the fire alarm control panel (e.g basement, distribution panel #25, fuse # 19).

3.4 Fire Command Center

A Fire Department Information and Control Center (Feuerwehr Informations und Bedien

System [FIBS]) shall be provided, in the Fire Department main access route. The Fire

Command Center shall be enclosed with a steel-sheet housing (except items D and E), furnished with a Fire Department locking system (except item D) and include the following components (subject to coordination with U.S. Fire Department):

A – Annunciator Panel

B – Fire Department Control Panel

C – Line Cards

D – Building Layout plan (as described in section 4.1)

E - Building Layout Panel (as described in section 4.2)

F- Adequate illumination of Fire Command Center and Building Layout plan The building layout plan shall be mounted near the Fire Command Center.

The type of locking system to be installed shall be coordinated with the responsible Fire

Department.

A flashing light furnished with a yellow (Bernsteinfarben) spherical cap, and a minimum spray water protection level meeting the requirement of IP54, shall be mounted on the outside wall next to the first entrance in the main access route, for identification of the to indicate the route to the initial information location (fire command center/central fire alarm unit//annunciator panel).

3.4.1 If building is equipped with Fire Alarm System controlled Ventilation shut off, the reset shall not be automatically after fire alarm reset! For effective reactivation of ventilation system after false calls etc., a manual switch should be built into the FDICC, allowing the FD Personnel to reset the system. FD Personnel cannot reset system if no reset switch is provided, so DPW Personnel will be responsible for reseting the system.

3.5 Fire Department Lockbox and Release Element

Design and type of locking system for the Fire Department Lockbox/Key Safe is subject to prior coordination with the responsible Fire Department. Standard, if not described differently, is the Fire Department Key Depot IAW VdS 2105, Type SD 3 (VdS FSD 3)

Design and type of locking system for the Fire Department Lockbox shall be coordinated with the responsible USAG Wiesbaden Fire Department.

The Lockbox Type VdS SD 3 are subject of connection to the Fire Alarm System as outlined in DIN 14675, with the exception that the Key Safe signal for “missing key” or

“door open” have to cause a trouble signal on the Fire Alarm system, which resets automatically if the key is locked in the safe and the door is shut.

3.6 Technical Requirements

The purpose of these technical requirements is to ensure all fire alarm system components are planned and installed, IAW NFPA 72, NFPA 75, NFPA 76, DIN 0833, DIN 14675, DIN EN 54, DIN 14661 and DIN 14662. In general it must be ensured that all components are 100% (100 percent) “ESSER” compatible, to ensure required communications between Fire Alarm Panels and receiving stations is functioning in its most optimal utilization of the systems. Fire alarm systems/panels announced as discontinued production, by the manufacturer, must be replaced with current systems, latest if affected by renovations, or prior to lack of replacement components so that a continued functioning of the system is no longer granted by regular maintenance. For detailed information, see Appendix D.

3.7 Fire Alarm Panel programming

For programming instructions of text for alarm component abbreviations, location, occupancy/use on the fire command center (FIBS) and identically on the fire alarm panel, see Appendix E.

3.8 Fire suppression systems

The purpose of these fire suppression system requirements is to ensure all fire suppression system components are planned and installed, IAW NFPA 13,NFPA 20, NFPA 72, NFPA 75, NFPA 76, DIN 0833, DIN 14675, DIN 14661 and DIN 14662. In general it must be ensured that all components are 100% (100 percent) compatible to the standard implemented in USAG Wiesbaden (Apartments : EXG.: Flamefast, Open

Facilities: Ansul R102, to ensure required communications between Suppression system, Fire Alarm Panels and receiving stations is functioning in its most optimal utilization of the systems. Fire alarm systems/panels announced as discontinued production, by the manufacturer, must be replaced with current systems, latest if affected by renovations, or prior to lack of replacement components so that a continued functioning of the system is no longer granted by regular maintenance. Dormitories and apartments require suppression systems when indicated. If there is no sprinkler system installed as required…..

4. Pictographs and Symbols

4.1 Line Cards and Building Lay-out Plans

4.1.1 Symbols

Symbols and color code as outlined in DIN 14675 shall be used.

4.1.2 Alignment

The true to side traffic area indicating the access route to the alarm address shall be marked at the lower edge of each call card. There shall be a north pointer on each call card in the upper right corner.

4.1.3 Tabs

Tabs measuring approx. 25 x 25mm shall be permanently affixed to each line card.

Tabs shall be laminated on both sides, with the printed line number on each side.

4.1.4 Format

Double-sided, colored Line Cards shall be furnished for each individual alarm circuit, if required. Line Cards shall be prepared utilizing CAD technique, must include explanation of symbols, and show a true-to-scale building layout plan. All cards shall be prepared in DIN A4 format, or if needed based on building size, DIN A3 (German standard paper size DIN A4, DIN A3) using full card size. Standard USAG Fire

Department Wiesbaden color code and symbols shall be used. Electronic version of

Line Cards (CD) will be submitted on date of the final turn-over of the alarm system containing the established Line Cards in .pdf and .dwg format.(see also Appendix A)

4.1.5 Sprinkler Systems und Wall Hydrants

Each installed water flow device requires an individual call card. The location of the sprinkler station shall be identified on a separate call card. In case sprinkler systems supply water to wall hydrants, the hydrants shall be equipped with initiating devices connected to the fire alarm unit. Opening a valve will activate the fire alarm. Line Cards shall be prepared for those wall hydrants and the respective hydrants shall be marked like detectors.

4.1.6 Acceptance

Review and release of Line Cards by the USAG Wiesbaden Fire Department is required prior to acceptance. The Fire Department shall forward any information on deficiencies found or the release of Line Cards in writing (e.g. via email).

4.1.7 Building Evacuation Plans

• Evacuation plans, Evacuation plans have to be made IAW HN Workplace Safety

Rules ASR A 1.3 and IAW DIN 4844.

Evacuation plans shall be laminated and mounted in a frameless picture holder behind

Perspex® at locations determined by the USAG Wiesbaden Fire Department. The plan size shall be no less than DIN A3 (A2 as required by building size), see Appendix C.

4.1.8 Fire Department Response Plans

Fire Department Response Plans (Feuerwehrplan), if required by governing law (US and/or Host Nation) or as required by the Authority having Jurisdiction (USAG

Wiesbaden Fire Department), must be prepared in accordance with DIN 14095, consisting of Object information, Overview Plan, Floor plan for every floor, and if required for special objects, as well as a strom drain / sewage system plan. Plans shall be size A3, laminated, and foldable in A-4 and stored in a folder. Quantities of needed plans may vary and will be determined on a case by case basis by the USAG

Wiesbaden Fire Department. (see also Appendix B)

4.2 Annunciator Panel

Annunciator panels shall be designed transparent with LED lights behind Perspex® in an aluminum frame, in facilities with multiple portions, sub Fire Alarm systems, substructures, or as requested by USAG Wiesbaden Fire Department, in order to allow quick overview of the alarm location. These panels are to indicate any controlled peripheral systems such as fire dampers, smoke and heat ventilation systems, wall hydrants, sprinkler systems etc. For execution planning, a printed version of the annunciator panel in original size will be submitted to the responsible Fire Department for release.

Each floor shall be depicted separately and lettering shall be German and English

Annunciator panels may be designed as a diagram showing distinctive points within the building (points of access, stairwells, hallways and the like) as well as locations of alarm initiating devices (individual detectors and detection lines).

A legend defining symbols, colored markings for ventilation stations, sprinkler stations, fire dampers, wall hydrants etc. as well as for each alarm-initiating device (LEDs for panels) will be included.

Layout panels shall be correctly mounted as to fit their actual position.

The locations of the sprinkler and ventilation stations shall be marked.

Indicator lights shall comply with the following color code:

RED ⇒ non–automatic detectors – push button devices/pull stations

YELLOW ⇒ automatic detectors

GREEN ⇒ location of fire alarm systems and remote system

BLUE ⇒ automatic sprinkler system

WHITE ⇒ other notifications (e.g. activated fire damper)

Viewer’s position shall be marked accordingly (symbol) and the layout panel will be equipped with a test button for the indicator lights.

Fire damper activation may be shown as collective initiation from the ventilation station.

This type of activation needs to be shown as a trouble call, and, if necessary reference the ventilation station.

5 Signal Devices

5.1 Audible Signal Devices

The total noise level of both, signal devices and ambient noise is not to exceed

110 dBA. The volume of the signal devices shall be 15 dB above the regular ambient noise level or 5 dB above the maximum noise level. Point of measurement is 1.5m above finish floor level.

NFPA 72 Chapter 18.4 and 18.5 lists additional requirements for private occupancies and dormitories.

Audible signal intervals.

Off > a = 0,5 sec ± 10 %

On > b = 0,5 sec ± 10 %

Off > c = 1,5 sec ± 10 %

Audible signal shall be synchronized within the alarm area.

5.2 Optical Signal Devices

Flash frequency of optical signal devices shall be no less than 1 Hz and is not to exceed

2 Hz with a maximum luminosity of 1 000 cd. Flash frequencies of optical signal devices shall be synchronized in the visible range. Optical devices shall be furnished with white caps. The maximum installation height is not to exceed 9.1m.

Luminosity not to be exceeded by wall mounted signal devices:

Extract from NFPA 72 Table 18.5.5.4.1(a)

Where the hallway width is no more than 6.1m signal devices may be installed up to a distance of 4.57m from the end of the hallway. The maximum distance between two signal devices is not to exceed 30.5m.

max. room size in m min. luminosity (1 signal device) - cd max. luminosity (4 signal devices; 1 per wall) - cd

6,1 15 NA

8,53 30 NA

9,14 34 NA

12,2 60 15 13,7 75 19 15,2 94 30 16,5 110 30 16,8 115 30 18,3 `35 30 19,2 150 37 20,7 177 43 21,3 184 60

The following light intensity levels for ceiling mounted signal devices are not to be exceeded:

max. room size - m max. room height - m min. luminosity (1 signal device) - cd

6,1 3 15 9,1 3 30

12,2 3 60 13,4 3 75 6,1 6,1 30 9,1 6,1 45

13,4 6,1 75 14,0 6,1 80 6,1 9,1 55 9,1 9,1 75

15,2 9,1 95 16,2 9,1 110 16,8 9,1 115 18 9,1 135

19,2 9,1 150 Extract from NFPA 72 Table 18.5.5.4.1(b)

In health care occupancies the installation of signal devices shall be limited to optical devices.

6 Detection and Control Devices

6.1 General Requirements

Data entry including clear text and graphical diagram shall be made for each detector and each detection group in the respective fire control center computer system. A printout of the data entries will be submitted for each individual detection group per fire alarm system to the USAG Wiesbaden Fire Department for approval.

All detectors and detection groups shall be permanently marked showing line and detector number (e.g. 10/01, 10/02, 10/03). Size of lettering will be proportional to the respective room height and ceiling design. Lettering shall be easily and reliably legible without auxiliary means. Lettering will be black letters on white background. Markings shall be mounted to enable reading from the way of approach.

6.1.1 Brandname and compatibility to other systems included 100% guarantied compliance to fire alarm main panel Due to the inclusion of all interfaces (Brandname „ESSER“, fire alarm systems, mobile fire department operations center (fallback option, installed in mobile container, 100% absorption of the fixed monitoring station in case of failure)), mass information systems, building control elevator systems, recording equipment, video intercom, door controller, interface for operating the radio, telephony possibility, loudspeaker Bldg-system, Airfield

Operations (PCAS Primary Crash Alarm System (red telephone line)) and an interface to the Military Police (Police Desk)) as well as to the control center technology

(management system), must be paid attention to compatibility when choosing the brands or components to be installed systems.

The systems must be 100% compatible. All listed buildings in the said properties obtain

IP - transmission equipment. All public buildings (kindergardens, hotel, schools, churches, gyms, etc.) will also receive a GSM - transmission device. In case of failure of the first communication path, a connection is established via a further independent communication path.

6.2 Pull Stations (Manual Fire Alarm Activation Device)

Pull stations will be mounted between 1.07m and a max. of 1.22m above the top edge of the floor. The same provisions apply for pull stations installed inside wall-hydrants.

The maximum distance to the door opening is not to exceed. 1.54m.

6.3 Automatic Detectors

Automatic detectors shall be protected from contamination during construction work, this is the responsibility of the contractor and or sub-contractors. In general, the installation of ionization type smoke detectors is not authorized.

Automatic detectors shall be installed in such a way, that indication light and label are clearly visible from the route of access.

In buildings equipped with conventional point detectors preference shall be given to the installation of a combination of detector and signal device.

6.4 Smoke Aspirating Systems

In case smoke aspirating systems are being installed, the following provisions apply:

One detection line shall cover no more than four (4) rooms (the maximum area of four

(4) rooms is not to exceed 400 m2 with separated fire areas being considered)

6.5 External Control of periphery systems

The following periphery systems shall be controlled in case of fire alarm and/or provided for manual control at the Fire Department Control Panel for the following functions:

A. HVAC System(s) - Off

B. Smoke Control Systems, - IAW concept - Open

C. Elevators - IAW concept

D. Suppression Systems - IAW concept - Activate E. Fire Dampers - IAW concept -

Close Type of control is subject to coordination with the USAG Wiesbaden

Fire Department on a case-by-case basis.

Elevator controls require specific coordination with the U.S. Fire Department. Elevators shall not stop at the fire floor in case of fire alarm.

Suppression systems containing gaseous extinguishing agents may be activated by fire alarm systems.

The fire alarm system shall have the feature to activate an external voice controlled evacuation system.

No type of fire alarm system shall be installed/extended, for which manufacturer support is no longer available and/or which is lacking VdS approval.

6.6 Central Fire Alarm Systems Control Unit

Interconnection of individual fire alarm systems (proprietary systems) shall be optional as well as connectivity to supervising computer systems. The compatibility of the fire alarm system to be installed with the software used in the Fire Alarm Control Center computer systems will be guaranteed. In addition the fire alarm system shall have all required characteristics and meet the respective criteria. In general, fire alarm systems shall be connected to the master system of the respective manufacturer located in the

Fire Alarm Control Center, thus ensuring unlimited availability of the entire scope of technical options. Details shall be coordinated with the U.S. Fire Department prior to execution.

6.7 Transmission

As a rule, adequate data/signal lines shall be used to transmit signals between a fire alarm system and the Fire Alarm Control Center. As an exception and for technical reasons only, main notification devices may be installed. All listed buildings in the said properties obtain IP - transmission equipment. All public buildings (kindergardens, hotel, schools, churches, gyms, etc.) will also receive a GSM - transmission devices. In case of failure of the first communication path, a connection is established via a further independent communication path.

Data/signal lines for the transmission of signals shall have the required quality and, as a rule, are to be provided by the U.S. Army, Signal Command, DCO. The respective requests, outlining the required line quality, will be prepared in time by the ordering technical division.

6.8 Suspended Ceilings and False Floors

Detectors installed in suspended ceilings shall be accessible without any extra effort.

For this purpose a specifically marked removable ceiling part shall be installed below each detector.

Floor panels above detectors mounted in false floors shall be marked accordingly. In order to prevent floor panels from accidentally being switched these floor panels shall be secured to the false floor with a chain.

The appropriate lifting tool for the floor panels shall be visibly stored in the immediate vicinity of the Fire Command Center.

Detectors in suspended ceilings shall be marked with parallel indicator devices parallel below the detector. Optical parallel indicators with red spherical caps will be installed the line and detector number must be noted on the parallel indicator or next to it.

Floor panels above detectors shall be marked with the respective line and detector number, the marking shall be everlasting.

7 Final Acceptance

Fire alarm systems shall be connected to the respective Fire Alarm Control Center prior to final acceptance by the COR and the responsible Fire Department, but will not be left in an operational until official acceptance of the building.

Flawless operation of the fire alarm system including all components installed as well as specific software and programming are pre-requisites for the acceptance. Programming data will be submitted to the ordering party in digital and hard copy format. Acceptance will be based upon the specifications, including all approved comments, deviations

(additional requirements or deletions), as well as plans and measurement records.

Certified personnel shall review the submitted documentation, ensure completeness, and check the technical execution of the project for correctness. This also includes manufacturer software and programming. The acceptance record shall document the condition of the fire alarm system itself, all installed components and controls.

Acceptance will be conducted, based upon the provisions of this technical connection standard as well as applicable rules and regulations and has to be documented.

Necessary graphics, texts, control software and pre-fire plans (quantitiy of pre-fire-plans as required in each specific contract/project, by the USAG Wiesbaden Fire

Department) IAW DIN 14095 will be submitted to the USAG Wiesbaden Fire

Prevention Office.

The Fire Department shall be informed about the acceptance inspection at least five (5) works days prior to the scheduled date. As a rule, partial acceptance and pre-acceptance inspections are not authorized.

Upon completion of construction work, or in a timely manner, however, not later than 14 work days after the system has been taken into service, the following documents shall be submitted to the COR, threefold (German/English), in binders and as digital

CD/DVD, including register and table of contents:

Documentation of final acceptance IAW section 9, DIN 14675

Matrix of system controls, including layout plan of all controlled safety related systems

Fire alarm system concept, including documentation of deviations

One set of the documentation as well as the system concept itself will be deposited at the Fire Alarm System.

The installation firm will be responsible for giving an instruction on the operation of the system.

8 Maintenance and Repair of Fire Alarm Systems

Maintenance and repair shall comply with the provisions outlined in Chapter 2 Table 2.1

UFC 3-600-02. In general, malfunctions shall be corrected within 24 hours. Non-conformity will be accepted in justified cases only, after following prior coordination with the ordering party. The responsible Fire Alarm Control Center shall be notified via telephone no. …DSN: example given 337 5883 or (to be defined) or in person of any work to be performed on fire alarm systems including disconnections and/or re-connections.

The responsible USAG Wiesbaden Fire Department’s, Fire Prevention Office shall be informed of any extension/modification to be performed on fire alarm detection systems at least 10 days prior to the scheduled date of execution.

A logbook shall be deposited at the fire alarm system.

Any actions taken e.g. maintenance and repair work as well as actions taken by responding Fire Department units, shall be entered in a legible manner. Respective cases/enclosures for depositing logbooks shall be mounted.

The contractor will submit documentation of routine maintenance performed to the respective Fire Department without prior request.

9 Glossary of Acronyms, Abbreviations & Terminology

English German Anunciator panel FAT Feuerwehranzeigetableau Fire Department lockbox FSD Feuerwehrschlüsseldepot FD lockbox release element FSE Freischaltelement Fire Suppression system FSS Löschsystem top edge of the floor OKF Oberkante Fußboden Technical Standard for

Connection TAB Technische

Anschlussbedingungen notification device ÜE Übertragungseinrichtung Association of Property

Insurance Companies (Germany) VdS VdS Schadenverhütung

Fire Department Control Panel FBF Feuerwehrbedienfeld electrical distribution panel UV Unterverteilung push button device/pull Station Druckknopfmelder/ Handmelder cd candela -SI unit for luminosity cd Candela/Basiseinheit für

Lichtstärke COR Contracting Officer’s

Representative stellv. Vertragsoffizier dB decibel dB Dezibel DES Directorate of Emergency

Services

DIN German Institute for Standardization

DIN Deutsches Institut für Normung

DoD Department of Defense DoD U.S. Verteidigungsministerium DPW Directorate of Public Works DSN Defense Switch Network DSN U.S. militärisches Telefonnetz e.g. exempli gratia – for example z.B. zum Beispiel etc. et cetera (and so on) etc. et cetera/und so weiter (usw.)

FACC Fire Alarm Control Center FACC Feuerwehrleitstelle (U.S.)

FACP Fire Alarm Control Panel BMZ Brandmeldezentrale FAS Fire Alarm System BMA Brandmeldeanlage FSCS Fire Command Center FIZ Feuerwehr Informationszentrale Hz Hertz – SI unit for frequencies Hz Hertz – Basiseinheit für Frequenz LED light emmitting diode LED Leuchtdiode max. maximum max. maximal min. minimum min. mindestens NFPA National Fire Protection

Association NFPA U.S. Brandschutzvereinigung

SAS Smoke Attraction System RAS Rauchansaugsystem UFC Unified Facilities Criteria Bauordnung für U.S.

Militäreirichtungen

Prepared by Date Signature

Ruehl A.

Dep. Chief O&M, Chief CB

07/20/16 RUEHL.ADRIAN.DANIEL.1501950 Digitally signed by RUEHL.ADRIAN.DANIEL.1501950323 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USA, 323 cn=RUEHL.ADRIAN.DANIEL.1501950323 Date: 2016.07.20 14:37:32 +02'00'

Corzelius D. Fire Chief

07/20/16 Digitally signed by CORZELIUS.DANIEL.1274826530

CORZELIUS.DANIEL.1274826530 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USA, cn=CORZELIUS.DANIEL.1274826530 Date: 2016.07.20 14:33:00 +02'00'

Johnson E.

DPW Director

Morrell K.

Inspector

07/20/16 MORRELL.KARIN.WILHELMINE.128 Digitally signed by MORRELL.KARIN.WILHELMINE.1286682177 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USA, 6682177 cn=MORRELL.KARIN.WILHELMINE.1286682177 Date: 2016.07.20 14:36:18 +02'00'

1090622761.civ Typewritten Text 02/23/16

1. Preface
3. Legal Foundations
3.1 Responsibilities
3.2 General Provisions
3.3 Fire Alarm Control Panel (FACP)
3.4 Fire Command Center
3.5 Fire Department Lockbox and Release Element
3.6 Technical Requirements
3.7 Fire Alarm Panel programming
4. Pictographs and Symbols
4.1 Line Cards and Building Lay-out Plans
5 Signal Devices
5.1 Audible Signal Devices
5.2 Optical Signal Devices
6 Detection and Control Devices
6.1 General Requirements
6.2 Pull Stations (Manual Fire Alarm Activation Device)
6.3 Automatic Detectors
6.4 Smoke Aspirating Systems
6.5 External Control of periphery systems
6.6 Central Fire Alarm Systems Control Unit
6.7 Transmission
6.8 Suspended Ceilings and False Floors
7 Final Acceptance
8 Maintenance and Repair of Fire Alarm Systems
9 Glossary of Acronyms, Abbreviations & Terminology