Motor Control Center Configuration.pdf
PDF 94 KB Posted
- Attached to
- Garrison Dam Spillway Transformers and Disconnects Replacement Federal contract opportunity
- Solicitation number
- W9128F24Q0055
About this file
This document appears to be a circuit designation and breaker size information for a Motor Control Center (MCC) related to a federal contract opportunity. The key details are:
The federal contract opportunity is for the "Garrison Dam Spillway Transformers and Disconnects Replacement" project, with solicitation number W9128F24Q0055. The project involves replacing the existing 13.8kV/480V transformers, disconnect switches, and motor control centers at the Garrison Dam Spillway. The new transformers will be delta-wye configuration, with the size to be determined based on available space, access routes, and ampacity of existing conductors. High resistance grounding will be added to both transformers. The existing switchboard and MCC will be replaced. The North American Industry Classification System (NAICS) code is 335311 - Power, Distribution and Specialty Transformer Manufacturing, with a small business size standard of 800 employees. The solicitation documents will be posted on SAM.gov, and all questions should be directed to the Contract Specialist.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment - AM0003 - Extend Due Date - 4 Sep 24.pdf | ||
| RFI and Responses GA Spillway Transformer and Disconnects 8.16.24.pdf | ||
| Solicitation Amendment - AM0002 - 08.16.2024.pdf | ||
| RFI and Responses GA Spillway Transformer and Disconnects 8.13.24.pdf | ||
| RFI and Responses GA Spillway Transformer and Disconnects.pdf | ||
| Drawings GA Spillway Transformers and Disconnects.PDF | ||
| Solicitation - W9128F24Q0055 - GA Transformers and Disconnects.pdf | ||
| Specs GA Replace Spillway Transformers and Disconnects specs.pdf | ||
| AM0001 W9128F24Q0055 - GA Transformers and Disconnects_07.19.2024.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
480V Spillway MCC Circuit Designation Breaker Size/Trip Rating Indicating lights/Control Switches
Incoming 480v Feeder # 1(transformer 1) 400 amp Kirk Key interlocked with Emergency Generator and Incoming Feeder #2 Incoming 480v Feeder # 2(transformer 2) 400 amp Kirk Key interlocked with Emergency Generator and Incoming Feeder #1
Emergency Generator 150 amp Kirk Key interlocked with both Incoming Feeders 1 and 2 Bubbler Compressor 1 150 amp none Bubbler Compressor 2 150 amp none
Crest Structure Lighting Transformer 50 amp none Building Lighting Transformer 30 amp none
Mono Rail Crane Feeder 60 amp none Building Heaters, 1st Floor 30 amp none Building Heaters, 2nd Floor 30 amp none
Power Receptacles 60 amp none Power Receptacles 60 amp none
Spare 60 amp none Spare 60 amp none
Tainter Gate Feeder 1 250 amp none Tainter Gate Feeder 2 250 amp none