Question 2.pdf

PDF 475 KB Posted

Attached to
POL Tank Inspection AEC- Arnold Air Station
Solicitation number
W9128F22Q0111
Issued by

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Question:

SCOPE states:

ITEM NO SUPPLIES/SERVICES QUANTITY UNIT PRICE AMOUNT

0004 1 Job:

- STI Internal Tank Inspect FAC 870 FFP All work to conduct Kick-Off Meeting, complete STI Internal tank inspection, fuel removal/transfer, tank cleaning, UT scanning, complete visual inspection of containment, and complete DRAFT and FINAL reports

Can we have access to supporting documentation/drawings for Tank 870.

Also Attachment B states the manway is 36" and has only 1, confirm this drawing matches the tank on site?

Data in the previous 653 report states" Shell Manholes OBSERVATION: The tank is equipped with one 24-inch and one 30-inch manhole which is less than the current requirement for two 36-inch manholes.

How many manways need to be secured with new gaskets and bolts?

What are the correct sizes?

What is the bolt diameter of the manways?

What size bolts are requested?

Answer:

Received this from the installation:

The 30" manway has the following characteristics:

42 bolts 3/4" bold diameter x 4" bolt length Diameter of the manway cover 38 3/4" Diameter of the bolt hole pattern 36 1/2"

The 20" manway has the following characteristics:

24 bolts 3/4" bold diameter x 4" bolt length

Diameter of the manway cover 24 3/4" Diameter of the bolt hole pattern 22 1/2"

We do not have drawings.