Appendix H.pdf
PDF 4 MB Posted
- Attached to
- Offutt AFB Flight Line Support Facilities Federal contract opportunity
- Solicitation number
- W9128F-21-R-0092
About this file
This document contains a solicitation for construction services for Offutt AFB Flight Line Support Facilities. The solicitation is seeking proposals for construction of facilities to support flight line operations at Offutt Air Force Base in Nebraska. Services required include engineering, construction, and renovation of structures and utilities to support aircraft maintenance and operations. Proposals are due by June 15, 2021 and the contract is to be awarded by September 30, 2021. The selected contractor will be responsible for meeting all specifications and drawings contained in the appendices to the solicitation. The soliciting agency is the Department of the Army Corps of Engineers Omaha District.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Am_0005.pdf | ||
| Am_0004.pdf | ||
| Appendix D-Rcd Dwgs-All Buildings Combined-AM03.pdf | ||
| Am_0003.pdf | ||
| Am_0003-Drawings.pdf | ||
| Am_0002.pdf | ||
| Am_0002-Drawings.pdf | ||
| Am_0004-Drawing.pdf | ||
| Am_0001-Drawings.pdf | ||
| Appendix G.pdf | ||
| Appendix F.pdf | ||
| Am_0001.pdf | ||
| W9128F-21-R-0092-Specs.pdf | ||
| OF64 - ADVERTISEMENT.PDF | ||
| Appendix D - Record Drawings.pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Engineering Flight CC
Utilities Lead
Electrical Lead
EA Superintendent
HVAC Lead
Project Manager
CEM
Structures Lead
Airfield Superintendent
Commander
Project Engineer
Safety
CAPT Griffin
CAPT Poulin
MSgt Franks
SMSgt Aquino
N/A
819 REDHORSE
REPAIR GENERATOR, TACAN B568
OFFUTT AFB, NEBRASKA
PROJECT
LOCATION
SMSgt Aquino
C-S
Sheet List Table Sheet Number Sheet Title
1 of 8 C-S Cover Sheet 2 of 8 C-1 Site Plan 3 of 8 C-2 Layout Plan 4 of 8 S-1 Grounding and Stub up Plan 5 of 8 S-2 Trench Details 6 of 8 E-1 One Line Diagram 7 of 8 E-2 Electrical Details and Notes 8 of 8 E-3 Electrical Schedules
C-1
C-2
S-1
S-2
E-1
N
E-3 cumminspower.com ©2013 Cummins Power Generation Inc. | S-1562e (8/13)
Specification sheet
Diesel generator set V2203-M series engine 20 kW EPA emissions
Description
Cummins Power Generation commercial generator sets are fully integrated power generation systems providing optimum performance, reliability and versatility for stationary standby and prime power applications.
Features
Kubota heavy-duty engine - Rugged 4-cycle, liquid-cooled, industrial diesel delivers reliable power, low emissions and fast response to load changes.
Alternator - Several alternator sizes offer selectable motor starting capability with low reactance 2/3 pitch windings, low waveform distortion with non-linear loads and fault clearing short-circuit capability.
Control system - The PowerCommand® 1.1 electronic control is standard equipment and provides total genset system integration including automatic remote starting/stopping, precise frequency and voltage regulation, alarm and status message display, output metering, auto-shutdown at fault detection and NFPA 110 Level 1 compliance.
Cooling system - Standard integral set-mounted radiator system, designed and tested for rated ambient temperatures, simplifies facility design requirements for rejected heat.
Enclosures - Optional weather protective and sound attenuated enclosures are available.
Fuel tanks - Dual wall sub-base fuel tanks are also available.
NFPA - The genset accepts full rated load in a single step in accordance with NFPA 110 for Level 1 systems.
Warranty and service - Backed by a comprehensive warranty and worldwide distributor network.
Standby rating Prime rating Continuous rating Data sheets
Model 60 Hz kW (kVA)
50 Hz kW (kVA)
60 Hz kW (kVA)
50 Hz kW (kVA)
60 Hz kW (kVA)
50 Hz kW (kVA) 60 Hz 50 Hz
DSKBA 20 (25) 18.2 (22.7) D-3373
Generator set specifications Governor regulation class Voltage regulation, no load to full load ± 1% Random voltage variation ± 1% Frequency regulation Isochronous Random frequency variation ± 0.25% Radio frequency emissions compliance
Engine specifications Bore 87.0 mm (3.43 in) Stroke 92.4 mm (3.64 in) Displacement 2.20 litres (134.1 in3) Configuration Cast iron, in-line, 4 cylinder
Battery capacity 350 amps minimum at ambient temperature of -18 °C to 0 °C (0 °F to 32 °F)
Battery charging alternator 40 amps Starting voltage 12 volt, negative ground Fuel system Indirect injection: low or ultra low sulfur, number 2 diesel fuel Fuel filter Single element, spin-on fuel filter with water separator Air cleaner type Dry replaceable element Lube oil filter type(s) Spin-on, full flow Standard cooling system High ambient radiator
Alternator specifications Design Brushless, 4 pole, drip proof, revolving field Stator 2/3 pitch Rotor Single bearing, flexible discs Insulation system Class H Standard temperature rise 125 ºC standby at 40 ºC ambient Exciter type Torque match (shunt) Phase rotation A (U), B (V), C (W) Alternator cooling Direct drive centrifugal blower fan AC waveform total harmonic distortion < 7% no load to full linear load, < 3% for any single harmonic Telephone influence factor (TIF) < 40 per NEMA MG1-22.43 Telephone harmonic factor (THF) < 3
Available voltages
60 Hz Three phase line-neutral/line-line 60 Hz Single phase line-neutral/line-line
• 120/208
• 120/240 Delta
• 139/240
• 220/380
• 240/416
• 277/480
• 347/600 • 120/240
Note: Consult factory for other voltages.
Generator set options and accessories
Engine 120 V 1000 W coolant heater Fuel system 24 hour sub-base tank
(dual wall) Regional fuel tank code kits
Alternator 105 °C rise 120 V 100 W anti-condensation heater Single phase Exhaust System Engine exhaust muffler
(mounted)
Generator set Battery Battery charger Enclosure: aluminum, steel, weather protective or sound attenuated
Export box packaging Main line circuit breaker
PowerCommand Network Communications Module
(NCM)
Remote annunciator panel Spring isolators 2 year prime power warranty 2 year standby power warranty 5 year basic power warranty
Note: Some options may not be available on all models - consult factory for availability.
Control system PCC 1302
PowerCommand control is an integrated generator set control system providing voltage regulation, engine protection, operator interface and isochronous governing (optional). Major features include:
• Battery monitoring and testing features and smart starting control system.
• Standard PCCNet interface to devices such as remote annunciator for NFPA 110 applications.
• Control boards potted for environmental protection.
• Control suitable for operation in ambient temperatures from -40 °C to +70 °C (-40 °F to +158 °F) and altitudes to 5000 meters (13,000 feet).
• Prototype tested; UL, CSA, and CE compliant.
• InPower™ PC-based service tool available for detailed diagnostics.
Operator/display panel
• Manual off switch
• Alpha-numeric display with pushbutton access for viewing engine and alternator data and providing setup, controls and adjustments (English or international symbols)
• LED lamps indicating genset running, not in auto, common warning, common shutdown, manual run mode and remote start
• Suitable for operation in ambient temperatures from -20 °C to +70 °C
• Bargraph display (optional)
AC protection
• Over current warning and shutdown
• Over and under voltage shutdown
• Over and under frequency shutdown
• Over excitation (loss of sensing) fault
• Field overload
Engine protection
• Overspeed shutdown
• Low oil pressure warning and shutdown
• High coolant temperature warning and shutdown
• Low coolant level warning or shutdown
• Low coolant temperature warning
• High, low and weak battery voltage warning
• Fail to start (overcrank) shutdown
• Fail to crank shutdown
• Redundant start disconnect
• Cranking lockout
• Sensor failure indication
• Low fuel level warning or shutdown
• Fuel-in-rupture-basin warning or shutdown
Alternator data
• Line-to-line and Line-to-neutral AC volts
• 3-phase AC current
• Frequency
• Total kVa
Engine data
• DC voltage
• Lube oil pressure
• Coolant temperature
• Engine speed
Other data
• Genset model data
• Start attempts, starts, running hours
• Fault history
• RS485 Modbus® interface
• Data logging and fault simulation (requires InPower service tool)
Digital governing (optional)
• Integrated digital electronic isochronous governor
• Temperature dynamic governing
Digital voltage regulation
• Integrated digital electronic voltage regulator
• 2-phase line-to-line sensing
• Configurable torque matching
Control functions
• Time delay start and cooldown
• Cycle cranking
• PCCNet interface
• (2) Configurable inputs
• (2) Configurable outputs
• Remote emergency stop
• Glow plug control (some models)
Options Auxiliary output relays (2) 120/240 V, 100 W anti-condensation heater Remote annunciator with (3) configurable inputs and
(4) configurable outputs PMG alternator excitation PowerCommand iWatch web server for remote monitoring and alarm notification (loose) Auxiliary, configurable signal inputs (8) and configurable relay outputs (8) Digital governing AC output analog meters (bargraph)
- Color-coded graphical display of:
- 3-phase AC voltage
- 3-phase current
- Frequency
- kVa
Remote operator panel PowerCommand 2.2 control with AmpSentry protection
For further detail see document S-1531.
North America 1400 73rd Avenue N.E.
Minneapolis, MN 55432
USA
Phone 763 574 5000 Fax 763 574 5298
©2013 Cummins Power Generation Inc. All rights reserved.
Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
S-1562e (8/13) cumminspower.com
Emergency standby power (ESP):
Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. Emergency Standby Power (ESP) is in accordance with ISO 8528. Fuel Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.
Limited-time running power (LTP):
Applicable for supplying power to a constant electrical load for limited hours. Limited Time Running Power (LTP) is in accordance with ISO 8528.
Prime power (PRP):
Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten percent overload capability is available in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.
Base load (continuous) power (COP):
Applicable for supplying power continuously to a constant electrical load for unlimited hours. Continuous Power (COP) in accordance with ISO 8528, ISO 3046, AS 2789, DIN 6271 and BS 5514.
This outline drawing is for reference only. See respective model data sheet for specific model outline drawing number.
Do not use for installation design
Model Dim “A” mm (in.)
Dim “B” mm (in.)
Dim “C” mm (in.)
Set Weight* dry kg (lbs)
Set Weight* wet kg (lbs)
DSKBA 1700 (66.9) 787 (31.0) 928 (36.5) 568 (1252)
* Weights represent a set with standard features. See outline drawings for weights of other configurations.
Codes and standards Codes or standards compliance may not be available with all model configurations – consult factory for availability.
This generator set is designed in facilities certified to ISO 9001 and manufactured in facilities certified to ISO 9001 or ISO 9002.
The generator set is available Listed to UL 2200, Stationary Engine Generator Assemblies.
The Prototype Test Support (PTS) program verifies the performance integrity of the generator set design. Cummins Power Generation products bearing the PTS symbol meet the prototype test requirements of NFPA 110 for Level 1 systems.
U.S. EPA
Engine certified to U.S. EPA Nonroad Source Emissions Standards, 40 CFR 1039, Tier 4.
All low voltage models are CSA certified to product class 4215-01.
International Building Code
The generator set package is available certified for seismic application in accordance with the following International Building Code:
IBC2000, IBC2003, IBC2006, IBC2009 and
IBC2012.
Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s electrical system except through an approved device or after building main switch is open.
BTPC
bypass isolation transfer switch open or closed transition 150 – 4000 amps
BTPC bypass isolation transfer switches combine a drawout automatic transfer switch with isolation mechanism and a manual bypass switch, to provide redundant power transfer and re-transfer capability for critical-need applications requiring a reliable power supply to the load. BTPC switches are available with closed transition for transferring critical loads without interruption.
Like conventional transfer switches, BTPC transfer switches are designed for operation and switching of electrical loads between primary power and standby generator sets. The switch monitors both power sources, signals generator set startup, automatically transfers power and returns the load to the primary power source when the utility returns and stabilizes.
Features
PowerCommand® control: A fully featured microprocessor-based control with digital display. Controls allow operator to enter settings and make adjustments to software-enabled features easily and accurately.
Accommodates up to 8 event schedules.
Closed transition available: By briefly connecting the two sources (for 100 msec or less), the transfer from the alternate source back to the normal source occurs without interruption in the power supply to loads.
Programmed transition: Open transition timing can be adjusted to completely disconnect the load from both sources for a programmed time period, as recommended by NEMA
MG-1 for transfer of inductive loads.
Closed door drawout operation:
Bypass and total isolation of the automatic transfer switch occurs behind closed doors, to provide arc flash protection for operator.
For critical loads: Suitable for use in emergency, legally required and optional standby applications.
BTPC | 2
S-1271v (9/12)
BTPC bypass-isolation transfer switch
Advanced transfer switch mechanism: Unique bi-directional linear actuator provides smooth, continuous transfer switch action during automatic operation.
Robust control system design:
Optically isolated logic inputs and isolation transformers for AC power inputs provide high-voltage surge protection.
Main contacts: Heavy-duty silver alloy contacts with multi-leaf arc chutes are rated for 100% load interruption. They require no routine contact maintenance and provide 100% continuous current ratings.
Communications capability: The transfer switch is capable of communicating with other transfer switches, SCADA networked accessories, or Cummins Power
Generation generators utilizing
LonWorks® protocol.
Easy service/access: Single-plug harness connection and compatible terminal markings simplify servicing.
Access space is ample. Door-mounted controls are field-programmable; no tool is required.
Complete product line: Cummins
Power Generation offers a wide range of equipment, accessories and services to suit virtually any backup power application.
Warranty and service: Products are backed by a comprehensive warranty and a worldwide network of distributors with factory-trained service technicians.
BTPC | 3
Transfer switch mechanism Bypass mechanism
Transfer switch mechanism is electrically operated and mechanically held in the Source 1 and Source 2 positions. The transfer switch incorporates electrical and mechanical interlocks to prevent inadvertent interconnection of the sources.
Independent break-before-make action is used for both 3-pole and 4-pole/ switched neutral switches. This design allows use of sync check operation when required, or control of the operating speed of the transfer switch for proper transfer of motor and rectifier-based loads (programmed transition feature).
True 4-pole switching allows for proper ground (earth) fault sensing and consistent, reliable operation for the life of the transfer switch. The neutral poles of the transfer switch have the same ratings as the phase poles and are operated by a common crossbar mechanism, eliminating the possibility of incorrect neutral operation at any point in the operating cycle, or due to failure of a neutral operator.
High pressure silver alloy contacts resist burning and pitting. Separate arcing surfaces further protect the main contacts. Contact wear is reduced by multiple leaf arc chutes that cool and quench the arcs. Barriers separate the phases to prevent interphase flashover.
A transparent protective cover allows visual inspection while inhibiting inadvertent contact with energized components.
Switch mechanism, including contact assemblies, is third party certified to verify suitability for applications requiring high endurance switching capability for the life of the transfer switch. Withstand and closing ratings are validated using the same set of contacts, further demonstrating the robust nature of the design.
Manual bypass switch mechanism allows the operator to select either the normal or emergency source by closing the bypass contacts. Visual indicators show bypass “source selected”, bypass
"closed" or "open" to either source, and automatic transfer switch isolation or
"disable." Bypass of the automatic switch is accomplished with permanently mounted, mechanically operated devices without disturbing the power supply to system loads, and without opening enclosure door.
Isolation contacts allow the automatic transfer switch and the bypass switch to be separated electrically and mechanically. The automatic transfer switch is isolated by a drawout mechanism similar to that used on power circuit breakers on transfer switches rated 1200 amps and less. On
1600-4000 amp models the drawout carriage is wheel-mounted.
Protective safety shutters, provided on switches up to and including 1200 amps, cover the stationary power terminals on the bypass switch when the automatic transfer switch is isolated and removed.
The drawout mechanism can be latched in one of three positions: “connected”, “test”, and “isolated”. In the connected position the mechanism is locked. In the test position, the automatic switch is isolated but the controls receive power.
In the isolated position, the automatic switch is completely isolated.
The bypass switch mechanism is identical to the automatic switch except it is mechanically operated rather than electrically operated. Mechanical interlocks prevent operation of the bypass or automatic switches in any mode that would result in the interconnection of the sources.
BTPC | 4
Power command control
PowerCommand controls are microprocessor based and developed specifically for automatic transfer switch operation. The control includes the features and options required for most applications.
Flash memory stores the control settings.
Contents of the memory are not lost even if power to the controller is lost.
On-board battery maintains the real-time clock setting and the engine start time delay.
Panels
Basic indicator panel:
Source available/connected LED indicators
Test/exercise/bypass buttons
Digital display: Standard
Analog bar graph meter display: optional
(D009)
Control functions: Level 2 control
Open transition (in-phase)
Open transition (programmed)
Closed transition: Includes fail-to-disconnect timer to prevent extended paralleling with the utility
Utility-to-genset applications
Utility-to-utility applications
Genset-to-genset applications
Software adjustable time delays:
Engine start: 0 to 120 sec
Transfer normal to emergency: 0 to 120 sec
Re-transfer emergency to normal: 0 to 30 min
Engine stop: 0 to 30 min
Programmed transition: 0 to 60 sec
Undervoltage sensing: 3-phase normal, 3-phase emergency
Accuracy: ±2%
Pickup: 85% to 98% of nominal voltage
Dropout: 75% to 98% of pickup setting
Dropout time delay: 0.1 to 1.0 sec
Overvoltage sensing: 3-phase normal, 3-phase emergency
Accuracy: ±2%
Pickup: 95% to 99% of dropout setting
Dropout: 105% to 135% of nominal voltage
Dropout time delay: 0.5 to 120 sec
Over/under frequency sensing: Normal and emergency
Accuracy: ±0.05Hz
Pickup: ±5% to ±20% of nominal frequency
Dropout: ±1% beyond pickup
Dropout time delay: 0.1 to 15.0 sec
Voltage imbalance sensing:
Dropout: 2% to 10%
Pickup: 90% of dropout
Time delay: 2.0 to 20.0 sec
Phase rotation sensing:
Time delay: 100 msec
Loss of single phase detection
Time delay: 100 msec
Loss of single phase detection:
Time delay: 100 msec
Programmable genset exerciser: Eight events/schedules with or without load
BTPC | 5
PowerCommand control (continued)
Time-delay functions
Engine start: Prevents nuisance genset starts due to momentary power variation or loss. Not included in utility-to-utility systems.
Transfer normal to emergency: Allows genset to stabilize before application of load. Prevents power interruption if normal source variation or loss is momentary. Allows staggered transfer of loads in multiple transfer switch systems. For genset-to-genset applications, delays transfer of load from lead to secondary generator.
Re-transfer emergency to normal: Allows the utility to stabilize before re-transfer of load.
Prevents needless power interruption if return of normal source is momentary. Allows staggered transfer of loads in multiple transfer switch systems. For genset-to-genset applications, delays re-transfer of load from secondary back to lead generator.
Engine stop: Maintains availability of the genset for immediate reconnection if the normal source fails shortly after transfer. Allows gradual genset cool-down by running unloaded. Not included in utility-to-utility applications.
Elevator pre-transfer signal: Requires optional relay signal module (M023). Delays transfer for pre-set interval of 0-60 seconds to prevent a power interruption during elevator operation.
User interfaces
Basic interface panel: LED indicators provide at-a-glance source and transfer switch status for quick summary of system conditions. Test and override buttons allow delays to be bypassed for rapid system checkout.
Digital display: The digital display provides a convenient method for monitoring load power conditions, adjusting transfer switch parameters, monitoring PowerCommand network status or reviewing transfer switch events. Password protection limits access to adjustments to authorized personnel. The digital display (M018) is standard on the BTPC.
User interface options
Bar graph meter display (D009): An LED bar graph display provides an easy-to-read indicator of the level of power being supplied to the load.
Information displayed includes: 3-phase voltage and current, power factor, and kilowatts. Green, amber and red LEDs provide at-a-glance indication of system acceptability.
Front panel security key (M017): Locks front panel to prevent access to digital control settings. Prevents unauthorized activation of transfer or test functions.
Control options
Relay signal module (M023): Provides relay output contacts for sending information to the building monitoring and control system. Relay outputs include: Source 1 connected/available, Source 2 connected/available, not in auto, test/exercise active, failed to disconnect, failed to synchronize, failed to transfer/re-transfer, and elevator control pre-transfer signal.
Loadshed (M007): Removes the load from the emergency power source by driving the transfer switch to the neutral position when signaled remotely. Transfers load back to the emergency source when the signal contacts open.
Immediately re-transfers back to the primary source when available. For utility-to-generator applications only.
PowerCommand network interface (M031):
Provides connection to the PowerCommand network. LonWorks compatible for integration with building monitoring and control system.
Load power and load current monitoring
(M022): Measures load phase and neutral, current, power factor, real power (kW) and apparent power (kVA). Warns of excessive neutral current resulting from unbalanced or nonlinear loads. Minimum current level detection is 3%.
BTPC | 6
Specifications
Voltage rating 600 VAC, 50 or 60 Hz
Arc interruption
Multiple leaf arc chutes provide dependable arc interruption.
Neutral bar
A full current-rated neutral bar with lugs is standard on enclosed 3-pole transfer switches.
Auxiliary contacts
Two isolated contacts (one for each source) indicating switch position are provided for customer use. Contacts are normally open, and close to indicate connection to the source.
Wired to terminal block for easy access. Rated at 10 amps continuous at 250VAC maximum.
UL recognized and CSA-certified.
Operating temperature -40 ° F (-40 ° C) to 140 ° F (60 ° C)
Storage temperature -40 ° F (-40 ° C) to 140 ° F (60 ° C)
Humidity Up to 95% relative, non-condensing
Altitude Up to 10,000 ft (3,000 m) without de-rating
Surge withstand ratings
Voltage surge performance and testing in compliance with the requirements of IEEE
C62.41 (Category B3) and IEEE C62.45.
Total transfer time (source-to-source)
Will not exceed 6 cycles at 60 Hz with normal voltage applied to the actuator and without programmed transition enabled.
Manual operation
External manual operator is provided via the bypass and isolation mechanism, providing quickmake/quick-break operation under load.
Certifications
All switches are UL 1008 listed and labeled, with UL-type rated cabinets and UL-listed CU-AL terminals.
All switches comply with NFPA 70, 99 and 110
(Level 1 systems).
All switches are certified to CSA 178.1-07
Requirements for Transfer Switches.
All switches comply with NEMA ICS 10.
Suitable for use in emergency, legally required and standby applications per NEC 700, 701 and 702.
All switches comply with IEEE 446 Recommended
Practice for Emergency and Standby Power
Systems.
This transfer switch is designed and manufactured in facilities certified to ISO9001.
BTPC | 7
Transition modes
Open transition/programmed: Controls the time required for the device to switch from source to source, so that the load-generated voltages decay to a safe level before connecting to an energized source. Recommended by
NEMA MG1 to prevent nuisance-tripping breakers and load damage. Adjustable 0-10 seconds, default 0 seconds. Programmed transition is standard on 150-1000 amp switches, and optional on 1200-4000 amps.
Open transition/in-phase: Initiates open transition transfer when in-phase monitor senses both sources are in phase. Operates in a break-before-make sequence. Includes ability to enable programmed transition as a back-up on
150 – 1000 amp switches and 1200 – 4000 amp switches that support programmed or closed transition. If sources are not in phase within 120 seconds, the system will transfer using programmed transition.
Closed transition: Used in applications where loads are sensitive to the momentary power interruption that occurs when performing open transition between sources. Closed transition is accomplished by briefly (<100 msec) paralleling two good sources to eliminate the momentary break in the power supply.
Genset-to-genset: Either genset can be designated as the lead genset. If the lead genset goes down or is taken offline, the transfer switch starts the second genset and transfers the load.
The control can be programmed to alternate between the two gensets at a set interval up to
336 hours (2 weeks).
BTPC | 8
UL withstand and closing ratings
The transfer switches listed below must be protected by circuit breakers or fuses. Referenced drawings include detailed listings of specific breakers or fuse types that must be used with the respective transfer switches. Consult with your distributor/dealer to obtain the necessary drawings. Withstand and Closing
Ratings (WCR) are stated in symmetrical RMS amperes.
Fuse protection
Transfer switch ampere
MCCB protection Current limited breaker protection
WCR at volts max with specific manufacturers
MCCBs
Max
MCCB
rating
Drawing reference
With specific current limiting breakers (CLB)
Max CLB rating
Drawing reference
150, 225, 260
30,000 at 480 25,000 at 600 400 A 0098-6889
200,000 at 480 400 A
0098-6919 100,000 at 600
100,000 at
300, 400, 600
65,000 at 480 65,000 at 600 1200 A 0098-6887
200,000 at 480 1200 A
0098-6923 100,000 at 600
100,000 at
800, 1000
65,000 at 480 65,000 at 600 1400 A 0098-6891
200,000 at 480 1400 A
0098-6924 100,000 at 600
100,000 at
1000, 1200 (closed transition)
85,000 at 480 65,000 at 600 1600 A 0098-7312
85,000 at 480 1600 A Use MCCB ratings 65,000 at 600 65,000 at 600
1600, 2000 100,000 at 480 65,000 at 600
4000 A Use 3 Cycle
Ratings 100,000 at 480 65,000 at 600
4000 A Use 3 Cycle
Ratings
100,000 at 480 65,000 at 600
4000 A Use 3 Cycle
Ratings 100,000 at 480 65,000 at 600
4000 A Use 3 Cycle
Ratings
100,000 at 480 85,000 at 600
5000 A 0098-8576 100,000 at 480 5000 A Use MCCB ratings 85,000 at 600 85,000 at 600
Transfer switch ampere
WCR at volts max. with current limiting fuses Max fuse, size and type Drawing reference
150, 225, 260 200,000 at 600 600 A Class J, RK1, RK5 or 1200 A Class L, T 0098-6889
300, 400, 600 200,000 at 600 600 A Class J, RK1, RK5 or 1200 A Class L, T 0098-6887
800, 1000 200,000 at 600 600 A Class J, RK1, RK5, 1200 A Class T, or 2000 A Class L 0098-6891
200,000 at 480
2000 A Class L 0098-7312 150,000 at 600
1600, 2000 200,000 at 480 2500 A Class L NA
3000 200,000 at 480 4000 A Class L NA
200,000 at 480
6000 A Class L 0098-8576 150,000 at 600
BTPC | 9
3-cycle ratings
Transfer switch lug capacities
All lugs accept copper or aluminum wire unless indicated otherwise.
Enclosures
The transfer switch and control are floor-mounted in a key-locking e
Transfer switch ampere
WCR at volts max 3-cycle rating
Max MCCB rating Drawing reference
50,000 at 480
1600 A 0098-7312 42,000 at 600
1600, 2000 100,000 at 480 4000 A N/A
3000 100,000 at 480 4000 A N/A
100,000 at 480
5000 A 0098-8576 85,000 at 600
Amp rating Cables per phase Size
150, 225 1 #6 AWG to 300 MCM
260 1 #6 AWG to 400 MCM
150, 225, 260¹ 1 #4 AWG to 500 MCM
300, 400 1 #3/0 AWG to 600 MCM
300, 400 2 #3/0 AWG to 250 MCM
300, 400¹ 2 #2 AWG to 600 MCM
600 2 250 MCM to 500 MCM
600¹ 2 #2 AWG to 600 MCM
800, 1000 4² 250 MCM to 500 MCM
800, 1000¹ 3 300 MCM to 750 MCM
1200 4 #2 AWG to 600 MCM
1600, 2000 8 #2 AWG to 750 MCM (lugs optional)
3000 8 #2 AWG to 750 MCM (lugs optional)
4000 12 #2 AWG to 600 MCM (lugs optional)
Note 1: Optional lug capacities on accessories spec sheet AC-166.
Note 2: Four-wire for neutral bar is 3-pole only.
Note 3: Mechanical and compression lugs are available as options
BTPC | 10
Enclosures
The transfer switch and control are floor-mounted in a key-locking enclosure. Wire bend space complies with 2008 NEC.
Dimensions - transfer switch in UL Type 1 enclosure
Amp rating
Height Width
Depth
Weight 3-pole type
Outline drawing
Door closed Door open in mm in mm in mm in mm lb kg
150, 225, 260 71.75 1822 36.00 915 22.75 578 55.2 1402 564 256 310-0538
300, 400, 600 83.25 2115 36.00 914 22.75 578 55.2 1403 639 291 500-4726
800, 1000 90.00 2290 48.00 1219 27.75 705 62.5 1588 1097 499 310-0570
1200 3-pole¹ 90.00 2290 40.00 1016 27.00 686 67.0 1702 1980 898 310-0566
1200 4-pole¹ 90.00 2290 46.00 1168 27.00 686 73.0 1854 2185 991 310-0566
1600, 2000 3-pole² 79.64 2023 40.76 1035 63.00 1600 102.1 2593 3139 1424 A030s193
1600, 2000 4-pole² 79.64 2023 46.26 1175 63.00 1600 107.6 2733 3538 1605 A030x111
3000 3-pole² 79.64 2023 40.76 1035 63.00 1600 102.1 2593 3513 1594 A030s195
3000 4-pole² 79.64 2023 46.26 1175 63.00 1600 107.6 2733 4081 1851 A030x113
4000 3-pole² 90.00 2290 47.50 1210 81.00 2060 128.5 3270 4730 2145 500-4488
4000 4-pole² 90.00 2290 54.00 1370 81.00 2060 135.0 3430 5930 2689 500-4488
Note 1: Dimensions shown for Type 1 are for top entry only. If bottom or side entry is required, an adapter bay is required and the depth increases by 14 in (356 mm). See outline drawing. Adapter needs to be part of the original order.
Note 2: 1600-4000 amp switches are rear-connected. Rear or side access is required for cabling.
BTPC | 11
Dimensions - transfer switch in UL Type 3R, 4, 4X or 12 enclosure
Amp rating
Height Width
Depth
Weight
Cabinet type
Outline drawing
Door closed Door open in mm in mm in mm in mm lb kg
150, 225, 260
71.75 1822 36.00 915 22.75 578 55.20 1402 564 256 3R, 12 310-0651
71.75 1822 36.00 915 22.75 578 55.20 1402 564 256 4, 4x 310-0652
300, 400, 600
83.25 2115 36.00 915 22.75 578 55.20 1402 639 290 3R, 12 500-4726
83.25 2115 36.00 915 22.75 578 55.20 1402 639 290 4, 4x 500-4727
800,1000
90.00 2290 48.00 1214 27.75 705 62.50 1534 1097 498 3R 310-0711
90.00 2290 48.00 1214 27.75 705 62.50 1534 1097 498 4, 4x, 12 310-0712
1200 3-pole¹ 1200 4-pole¹
90.00 2290 40.00 1016 28.25 718 65.50 1654 1980 748 3R, 12, 4, 4x 310-0734
90.00 2290 46.00 1168 28.25 718 71.69 1821 2185 991 3R, 12, 4, 4x 310-0734
1600, 2000 3-pole² 79.64 2023 40.76 1035 63.00 1600 102.1 2593 3139 1424 3R A030s193
1600, 2000 4-pole² 79.64 2023 46.26 1175 63.00 1600 107.6 2733 3538 1605 3R A030x111
3000 3-pole² 79.64 2023 40.76 1035 63.00 1600 102.1 2593 3513 1594 3R A030s195
3000 4-pole² 79.64 2023 46.26 1175 63.00 1600 107.6 2733 4081 1851 3R A030x113
4000 3-pole² 90.00 2290 48.50 1232 81.75 2076 131.00 3308 4730 2145 3R 500-4489
4000 4-pole² 90.00 2290 55.00 1397 81.75 2076 137.00 3473 5930 2689 3R 500-4489
Submittal detail
Note 1: 1200 amp switches are top entry only.
Note 2: 1600-4000 amp switches are rear-connected. Rear or side access is required for cabling.
BTPC | 12
Submittal detail
Amperage ratings
Voltage ratings
R038 190
R021 208
R022 220
R023 240
R024 380
R025 416
R035 440
R026 480
R027 600
Pole configuration
A028 Poles - 3 (solid neutral)
A029 Poles - 4 (switched neutral)
Frequency
A044 60 Hertz
A045 50 Hertz
Transfer mode
A077 Open transition/in-phase
A078 Open transition/programmed
A079 Closed transition
Application
A035 Utility-to-genset
A036 Utility-to-utility
A037 Genset-to-genset
System options
A041 Single phase, 2-wire or 3-wire
A042 Three phase, 3-wire or 4-wire
Enclosure
B001 Type 1: Indoor use, provides some protection against dirt (similar to IEC type IP30)
B002 Type 3R:Intended for outdoor use, provides some protection from dirt, rain and snow (similar to
IEC type IP34)
B003 Type 4: Indoor or outdoor use, provides some protection from wind-blown dust and water spray (similar to IEC type IP65)
B004 Open Construction: No enclosure - includes automatic transfer switch and controls (call factory for dimensions)
B010 Type 12: Indoor use, some protection from dust (similar to IEC type IP61)
B025 Type 4X: Stainless steel, indoor or outdoor use, provides some protection from corrosion (similar to IEC Type IP65)
Standards
A046 UL 1008/CSA certification
A064 NFPA 20 compliant (not available 1200-
4000 amp switches)
A080 Seismic certification
Control options
M017 Security key - front panel
M022 Load monitoring (min current level 3%)
M023 Relay signal module. Includes pre-transfer module for elevator control
M031 LonWorks Network Communications
Module FTT-10
Meter
D009 Analog bar graph meter
Battery chargers
K001 2 A, 12/24 V
KB59 15 A, 12 V
KB60 12 A, 24 V
Protective relays
M045 Paralleling timer and lockout relays, ANSI/IEEE 62PL and 86
M046 Paralleling timer and lockout and reverse power relays, single phase, ANSI/IEEE 62PL, 86 and 32R
M047 Paralleling timer and lockout and reverse power relays, three phase, ANSI/IEEE 62PL, 86 and 32R
BTPC | 13
Auxiliary relays
Relays are UL listed and factory installed. All relays provide two normally closed isolated contacts rated 10 amps at 600 VAC. Relay terminals accept from one 18 gauge to two 12 gauge wires per terminal.
L101 24 VDC coil - installed, not wired (for customer use)
L102 24 VDC coil - emergency position - relay energized when switch in source 2 (emergency) position
L103 24 VDC coil - normal position - relay energized when switch in source 1 (normal) position
L201 12 VDC coil - installed, not wired (for customer use)
L202 12 VDC coil - emergency position - relay energized when switch in source 2 (emergency) position
L203 12 VDC coil - normal position - relay energized when switch in source 1 (normal) position
Miscellaneous options
M003 Terminal block - 30 points (not wired)
M007 Loadshed - from emergency - drives switch to neutral position when remote signal contact closes (utility-to-genset only)
N009 Power connect - bus stabs (150-1000 amp open construction only)
Optional lug kits
N046 Mechanical lugs – accept up to 8 #2 - 600
MCM cables per phase (1600-3000 amps only)
N047 Mechanical lugs – accept up to 8 750 MCM cables per phase (1600-3000 amps only)
N050 Compression lugs – accept up to 8 500
MCM cables per phase (1600-3000 amps only)
N051 Compression lugs – accept up to 8 600
MCM cables per phase (1600-3000 amps only)
N052 Compression lugs – accept up to 8 750
MCM cables per phase (1600-3000 amps only)
N056 Mechanical lugs – accept up to 12 750 MCM cables per phase (4000 amps only)
Warranty
G010 Years 0-2: Parts, labor and travel
Years 3-5: Parts only
Years 6-10: Main contacts only
G013 Years 0-5: Parts, labor and travel
Years 6-10: Main contacts only
Shipping
A051 Packing - export box
Accessories
AC-166 Accessories specification sheet
North America 1400 73rd Avenue N.E.
Minneapolis, MN 55432 USA
Phone 763 574 5000 Fax 763 574 5298
Asia Pacific 10 Toh Guan Road #07-01 TT International Tradepark Singapore 608838
Phone 65 6417 2388 Fax 65 6417 2399
Brazil Rua Jati, 310 Guarulhos – Sao Paulo
CEP – 07180-140
Phone 55 11 2186 4195 Fax 55 11 2186 4729
Europe, CIS, Middle East & Africa Manston Park Columbus Ave.
Manston Ramsgate Kent CT 12 5BF United Kingdom
Phone 44 1843 255000 Fax 44 1843 255902 www.cumminspower.com
©2012 Cummins Power Generation All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Specifications are subject to change without notice.
s-1271v (9/12)
| OFFUTT- TACAN B568 - 100% |
| Gen Specs |
| Spec Sheet BTPC |