08_DwgsQuadD_05-F_1of1.pdf

PDF 7 MB Posted

Attached to
FY15 PKG A-005 Repair Building 449, Quad D, Schofield Barracks, Hawaii
Solicitation number
W9128A-15-B-0003
Issued by

About this file

Fire Protection Drawings

View the file

Other files

File Type Posted
15-B-0003_Bid_Abstract.pdf PDF
15-B-0003-AM-0002.pdf PDF
15-B-0003-AM-0001.pdf PDF
01_DwgsQuadD-G-L_1of1.pdf PDF
15b0003b_QuadD_Tech_Specs.pdf PDF
07_DwgsQuadD_04b-A_2of2.pdf PDF
06_DwgsQuadD_04a-A_1of2.pdf PDF
05_DwgsQuadD_03b-S_2of2.pdf PDF
04_DwgsQuadD_03a-S_1of2.pdf PDF
09_DwgsQuadD_06-P-M-E-T_1of1.pdf PDF
15b0003a_QuadD_Solicitation.pdf PDF
03_DwgsQuadD_02b-C_2of2.pdf PDF
02_DwgsQuadD_02a-C_1of2.pdf PDF
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BUILDING CODE SUMMARY:

INTERNATIONAL CODES, INTERNATIONAL CODE COUNCIL:

IBC INTERNATIONAL BUILDING CODE, 2012 EDITION, EXCLUDING CHAPTER 10 MEANS

OF EGRESS REQUIREMENTS

NATIONAL FIRE CODES, NATIONAL FIRE PROTECTION ASSOCIATION STANDARDS INCLUDING:

NFPA 1 UNIFORM FIRE CODE, 2012

NFPA 10 PORTABLE FIRE EXTINGUISHERS, 2013

NFPA 13 INSTALLATION OF SPRINKLER SYSTEMS, 2013

NFPA 24 PRIVATE FIRE SERVICE MAINS, 2013

NFPA 70 NATIONAL ELECTRICAL CODE, 2014

NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE, 2013

NFPA 101 LIFE SAFETY CODE, 2012

UNIFIED FACILITIES CRITERIA:

UFC 1-200-01 GENERAL BUILDING REQUIREMENTS, 1 JULY 2013, WITH CHANGE 1, 1 SEPTEMBER 2013 UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES, 26 SEPTEMBER 2006, WITH CHANGE 3, 1 MARCH 2013

UFC 4-021-01 MASS NOTIFICATION SYSTEM, 9 APRIL 2008 WITH CHANGE 1, JANUARY 2010

PROJECT ADDRESS: SCHOFIELD BARRACKS, OAHU, HAWAII

PROJECT DESCRIPTION: REPAIR BUILDING 449, QUAD D

OCCUPANCY IBC OCCUPANCY NFPA OCCUPANCY

CONSTRUCTION:

ALLOWABLE: TYPE I-A, I-B, II-A, II-B

PROVIDED: TYPE II-B

FIRE RESISTANCE REQUIREMENTS:

BUILDING ELEMENT MATERIAL REQUIRED RATING PROVIDED RATING SECTION

STRUCTURAL FRAME NON-COMBUSTIBLE 0 HR 0 HR TABLE 601

BEARING WALLS - EXTERIOR NON-COMBUSTIBLE 0 HR 0 HR TABLE 601

BEARING WALLS - INTERIOR NON-COMBUSTIBLE 0 HR 0 HR TABLE 601

NONBEARING WALLS - EXTERIOR NON-COMBUSTIBLE 0 HR 0 HR TABLE 602

NONBEARING WALLS - INTERIOR NON-COMBUSTIBLE 0 HR 0 HR TABLE 601

SHAFT ENCLOSURES NON-COMBUSTIBLE 1 HR 1 HR NFPA 101, 7.2.2.6.3

FLOORS & FLOOR-CEILINGS 0 HR 0 HR TABLE 601

ROOF 0 HR 0 HR TABLE 601

CONSTRUCTION REQUIREMENTS: FOR GENERAL STRUCTURAL DESIGN CRITERIA SEE STRUCTURAL SHEET

ACTS AND REGULATIONS:

ADA/ABA AMERICANS WITH DISABILITIES ACT ACCESSIBILITY AND ARCHITECTURAL BARRIERS ACT

ACCESSIBILITY GUIDELINES JULY 23.2004

1ST FLOOR

OCCUPANCY ALLOWABLE AREA MODIFIED AREA ACTUAL AREA

BUILDING HEIGHT AND NUMBER OF STORIES:

BUILDING: ALLOWABLE: PROVIDED:

BLDG 449 75 FT, 3 STORIES 54 FT, 3 STORIES

EXPOSURE PROTECTION:

BUILDING FIRE SEPARATION REQUIRED FOR UNRATED WALL : PROVIDED:

BLDG 449 10FT >10 FT

OCCUPANT LOAD FACTOR AND TOTAL CALCULATED LOAD:

OCCUPANT LOAD FACTOR

BUSINESS USE - 100 SF / PERSON

TOTAL CALCULATED LOAD

FIRST FLOOR: BUSINESS & STORAGE

LIFE SAFETY CODE SUMMARY:

NUMBER OF EXITS:

BUILDING: REQUIRED: PROVIDED:

1ST FLOOR 2*

2ND FLOOR 3*

DISCHARGE FROM EXITS:

REQUIRED:

EXITS FROM THE FIRST FLOOR DISCHARGE DIRECTLY TO THE OUTSIDE, TO WALKWAYS

THAT LEAD TO THE PUBLIC WAY. FROM THE SECOND AND THIRD FLOORS CORRIDORS

DISCHARGE TO AN EXTERIOR LANAI WITH OUTSIDE EXIT STAIRS THAT DISCHARGE

DIRECTLY TO THE OUTSIDE ON THE FIRST FLOOR.

PROVIDED:

EXITS SHALL TERMINATED DIRECTLY, AT A PUBLIC WAY OR AT EXTERIOR EXIT DISCHARGE.

ASSEMBLY USE - 15 SF / PERSON

BUSINESS B NEW BUSINESS (CHAPTER 38)

ASSEMBLY A-3 NEW ASSEMBLY (CHAPTER 12)

SECOND FLOOR: BUSINESS & STORAGE

B 23,000 SF ------ -------

STORAGE S-1 STORAGE (CHAPTER 42)

S-1 17,500 SF ------ ------

2ND AND 3RD FLOORS

TOTAL BUILDING:

TOTAL ALLOWABLE ACTUAL AREA

A-3 106,875 SF 66,450 SF

BUILDING SEPARATION

NORTH:

EAST:

SOUTH:

WEST:

29 FT WAIANAE AVENUE

22 FT ACCESS ROAD

15 FT ACCESS ROAD AND PARKING

22 FT ACCESS ROAD

NON-COMBUSTIBLE

CLASSROOMS - 20 SF / PERSON

EXERCISE ROOM W/O EQUIPMENT - 15 SF / PERSON

- 290 PEOPLE

- 348 PEOPLE

THIRD FLOOR: BUSINESS, STORAGE & ASSEMBLY - 514 PEOPLE

MINIMUM FIRE PROTECTION RATINGS FOR OPENING PROTECTIVES IN FIRE RESISTANCE - RATED ASSEMBLES

WALLS AND PARTITIONS FIRE DOOR ASSEMBLES

NO RATING 20 MINIUTESMOKE PARTITIONS

3RD FLOOR 4* 4

CAPACITY OF MEAN OF EGRESS:

BUILDING: REQUIRED CAPACITY: PROVIDED CAPACITY:

1ST FLOOR 290 PEOPLE

2ND FLOOR 348 PEOPLE

3RD FLOOR 514 PEOPLE 587 PEOPLE

1120 PEOPLE

587 PEOPLE

MEAN OF EGRESS:

TRAVEL DISTANCE

ALLOWED:

TRAVEL DISTANCE

PROVIDED:

1ST FLOOR 300 FT 124 FT

2ND FLOOR 300 FT 207 FT

3RD FLOOR 250 FT 250 FT

COMMON PATH

OF TRAVEL

ALLOWED:

COMMON PATH

OF TRAVEL

PROVIDED:

1ST FLOOR 100 FT 68 FT

2ND FLOOR 100 FT 70 FT

3RD FLOOR 75 FT 53 FT

DEAD END

CORRIDOR

ALLOWED:

DEAD END

CORRIDOR

PROVIDED:

1ST FLOOR 50 FT 0 FT

2ND FLOOR 50 FT 0 FT

3RD FLOOR 20 FT 15 FT

ALLOWABLE AREA:

* ADDITIONAL EXITS WILL BE NEEDED TO SATISFY CAPACITY REQUIREMENTS

THE NFPA 101 LIFE SAFETY ANALYSIS IS BASED ON THE RULES FOR MIXED OCCUPANCIES (NFPA 101, 6.1.14.3)

THIS ANALYSIS IS BASED ON THE IBC RULES FOR NON-SEPARATED OCCUPANCIES.

35,625 SF 22,150 SFA-3 9,500 SF

-STORAGE USE 300 SF / PERSON

B 23,000 SF ------ -------

S-1 17,500 SF ------ ------

35,625 SF 22,150 SFA-3 9,500 SF

EXERCISE ROOM W/ EQUIPMENT - 50 SF / PERSON

EXTERIOR WALL OPENINGS 0 HR 0 HR TABLE 705.8

NON-COMBUSTIBLE

09/30/2016 Expiration Date of the License

AINROFICF

E

A

NOITCETORPERI

F

LAO

ST

T

R E

S

RED

PROFESS IONAL

ENG

IN

E E

RS

A

M

UE

S. DANNAW

AY

LET

I

G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

/2

/2

:4 :4

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

R

T A

HONOLULU DISTRICT

R O

J P

S S

D

F-001

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

C O

D E

I N

F O

R M

A T

IO

N

S H

E E

T

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F -0

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

S 6"

A V E N U EW A I A N A E

E 1622600

N

U/ E

U/E

U/EU/E

U/E

U/E

D1 2"

D1 2"

D48"

D18"

D

D8" D36"D36"D10" D12"

D 12"D

12"

D12"

D24"

D 18"

D24"

S10"

S10"

S8

S8 s

0°

5.9

310° 21' 32" 679.95

3/4"G R

3/4"G

R 3/4"G

3/ 4" G

W4"

W8

E/W12 E/W12 E/W12

UP

NO PARKINGNO PARKINGNO PARKINGNO PARKING

N O

P A R K

IN

G

N O

P A R K

IN

G

NO PARKING NO PARKING NO PARKING NO PARKING

D

D

D

S

S

S

S

S

S

S

S

S

W

W

W

W

W

W W

W

W

WW

W

WW

W

W

W

UP UP

FD

FD

FD

FD

FD

FD

FA FA FA FA FA FA

FH1

FH2

350'-0" FROM FH1

F R

O M

F H

60'-0" FROM FIRE HYDRANT TO

FIRE DEPARTMENT CONNECTION

FIRE DEPARTMENT CONNECTION

20'-0" TO

PAVED ACCESS

BACKFLOW PREVENTER

50'-0" FROM BUILDING

FIRE TRUCK ACCESS ROUTE

BUILDING SEPARARTION REQUIREMENT

BUILDING CODE SITE LEGEND

FIRE HYDRANT

FA

FIRE DEPARTMENT CONNECTION

09/30/2016 Expiration Date of the License

AI

NROFICF

E A

N

OITCETORP

ERI

F

LAO

S

T T

R E

S R

ED

PROFESS IONAL

EN

G

IN

E

E

RS

A M

U

E

S. DANNA

W

AY

LE

T

I G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

A s i n d ic a te d

/2

/2

:4 :5

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

F-002

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

B U

IL

D

IN

G

S

IT

E C

O D

E P

L A

N

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F -0

1" = 20'-0"

BUILDING SITE CODE PLAN

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P

UP UP

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

A

B

C

D

E

S S

SS

SS

S

S

S

S

S

S

S

S

S68 /1

30/124

/4

145/NA

20/117

25/113

145/NA

20/115

/1

VENDING

100D

LANAI

100B

LANAI

100A

RECYCLE 1A

ELEC 1B

COMMANDER 1B

CSM 1B

ARMS VAULT #3B

ARMS VAULT #2B

DUTY OFFICER 1A

MECHANICAL 1A

ARMS VAULT #2A

S-2 OFFICE 1A

STORAGE 1A-2

FRSA

RE-ENLIST 1A

STORAGE 1A-1

FIRE RISER ROOM

S-3 CONF

S-1 OFFICE

COMMAND SUPPLY 1B

CORR

161A

SR HR SGT 1B

DUTY OFFICER 1B

S-4 OFFICE 1B

CENTRAL FILES

CSM 1A

XO 1A

S-3 OPS SGT 1A

S-6 OFFICE 1A

ELEC 1A

TELECOM 1A

S-3 OFFICE 1A

S-3 CONF

S-3 OFFICE 1A

COMMAND CONF ROOM 1B

XO 1B

CMD OPEN OFFICE

STORAGE 1B

TELECOM 1B

MECHANICAL ROOM 1B

COPY

S-2 OFFICE 1A

CHAPLAIN ASST

CHAPLAIN

S-6 OFFICE 1A

OPEN OFFICE 1A

S-3 OPS SGT 1A

CORR

161B

SECURE DOCUMENT'S 1A

SECURE DOCUMENTS 1A

S-1 OFFICER 1A

COMMAND CONFERENCE

S-4 OFFICE 1A

CENTRAL FILES 1A

CORR

101A

COMMANDER 1A

CMD OPEN OFFICE

COMMAND TOILET 1A

COMMAND SUPPLY 1A

OPEN OFFICE 1B

SR HR SGT 1A

CORR

101B

ARMS VAULT #3A

SS S S S

SS

S

S

SS

S

S

S

S

S

S

S S

S

S

S

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

A

B

C

D

E

S S S S

S S

S

SS

S S

S

S

S

S

S

S

S S S

S

S

S S

S

S

S

S

S

S

S

SS

S

S S

S

S

70/147

87/146

34/207

87/146

50/131

87/146

/1

87/146

/9

TRAVEL DISTANCES ARE MEASURED

TO THE GROUND FLOOR IN

ACCORDANCE WITH NFPA 101, 7.6.3

COMMANDER 2A

LANAI

200B

LANAI

200A

NBC STORAGE 2A

UNIT STORAGE 2A-1

XO 2A

PLATOON 2A-D

PLATOON 2A-C

PLATOON 2A-B

PLATOON 2A-A

COMMAND CONFERENCE ROOM 2A

RECYCLE 2A

ELEC 2A

TELECOM 2A

MECHANICAL ROOM 2A

COMM STORAGE 2A

STORAGE 2A-2

CORR

201B

COMMAND OPEN OFFICE

COMMAND STORAGE 2A

PLATOON 2B-D

PLATOON 2B-C

PLATOON 2B-B

PLATOON 2B-A

COMMAND CONFERENCE ROOM 2B

UNIT STORAGE 2B-2

UNIT STORAGE 2B-1

CLASSROOM 2B

CLASSROOM 2A

UNIT STORAGE 2A-3

UNIT STORAGE 2A-2

SECURE STORAGE 2B

UNIT STORAGE 2B-3

1 SGT 2B

XO 2B

COMMAND STORAGE 2B

COMMAND OPEN OFFICE

MECHANICAL ROOM 2B

264TELECOM 2B

STORAGE 2B-2

ELEC 2B

RECYCLE 2B

CORR

201A

CORR

COMM STORAGE 2B

CORR

232A

TRAINING ROOM 2B

STORAGE 2B-3

CORR

NBC STORAGE 2B

CORR

244A

CORR

232B

TRAINING ROOM 2A

259 STORAGE 2A-1

1 SGT 2A

SECURE STORAGE 2A

CORR

CLASSROOM 2C

CORR

244B

COMMANDER 2B

S

S S S

S

S

SMOKE PARTITION

LEGEND

SYMBOL DESCRIPTION

S

EXIT PATH, COMMON PATH OF TRAVEL (FEET) /

TRAVEL DISTANCE (FEET)

COMMON PATH OF TRAVEL

XX / XX

FIRE EXIT

XX / XX OCCUPANT LOAD / EXGRESS CAPACITY

DEAD END (FEET)

XX

OCCUPANCY LEGEND

SYMBOL DESCRIPTION

B, BUSINESS

S-1, STORAGE

09/30/2016 Expiration Date of the License

AINROFICF

E

A

NOITCETORPERI

F

LAO

ST

T

R E

S

RED

PROFESS IONAL

ENG

IN

E E

RS

A

M

UE

S. DANNAW

AY

LET

I

G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

A s i n d ic a te d

/2

/2

:4 :0

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

F-101

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

F

IR

S T

A N

D S

E C

O N

D F

L O

O R

L

IF

E

S A

F E

T Y

C O

D E

P L A

N

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F -1

SCALE:

0 16' 32'

1/16" = 1' - 0"

16' 32'

1/16" = 1'-0" C1

FIRST FLOOR - LIFE SAFETY CODE PLAN

1/16" = 1'-0" A1

SECOND FLOOR - LIFE SAFETY CODE PLAN

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P

FDFD

FD

FD

FD

FD

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

A

B

C

D

E

S

S

S

S S

S

SS

S

S S

S S

S

S

SS

S S

S

S

S

SS

129/146

/1

73 50 /2

129/146

0/

129/146 129/146

/1

27/176

TRAVEL DISTANCES ARE MEASURED TO

THE GROUND FLOOR IN ACCORDANCE

WITH NFPA 101, 7.6.3

COMMANDER 3B

COMMANDER 3A

XO 3B

1 SGT 3B

GYM

LANAI

300A

LANAI

300B

PLATOON 3B-B

PLATOON 3B-C

PLATOON 3B-D

COMM STORAGE 3B

1 SGT 3A

COMMAND STORAGE 3A

XO 3A

COMM STORAGE 3A

PLATOON 3A-D

PLATOON 3A-C

PLATOON 3A-B

PLATOON 3A-A

COMMAND CONFERENCE ROOM 3A

STORAGE 3A

UNIT STORAGE 3A

RECYCLE 3A

TELECOM ROOM 3A

CORR

301B

ELEC 3A

COMMAND CONFERENCE ROOM 3B

PLATOON 3B-A

NBC STORAGE 3B

STORAGE 3B

MECHANICAL ROOM 3B

MECHANICAL ROOM 3A

CORR

STAIR

TELECOM 3B

OFFICE

ELEC 3B

COMMAND STORAGE 3B

NBC STORAGE 3A

UNIT STORAGE 3B

TRAINING ROOM 3A

CORR

330B

CORR

301A

COMMAND OPEN OFFICE

TRAINING ROOM 3B

COMMAND OPEN OFFICE

CORR

SECURE STORAGE 3A

SECURE STORAGE 3B

CORR

330A

S S

S

S S

S S

S

S

S

S

S

SMOKE PARTITION

LEGEND

SYMBOL DESCRIPTION

S

EXIT PATH, COMMON PATH OF TRAVEL (FEET) /

TRAVEL DISTANCE (FEET)

COMMON PATH OF TRAVEL

XX / XX

FIRE EXIT

XX / XX OCCUPANT LOAD / EXGRESS CAPACITY

DEAD END (FEET)

XX

OCCUPANCY LEGEND

SYMBOL DESCRIPTION

B, BUSINESS

S-1, STORAGE

A-3, ASSEMBLY

16 17

C

D

09/30/2016 Expiration Date of the License

AINROFICF

E

A

NOITCETORPERI

F

LAO

ST

T

R E

S

RED

PROFESS IONAL

ENG

IN

E E

RS

A

M

UE

S. DANNAW

AY

LET

I

G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

A s i n d ic a te d

/2

/2

:4 :0

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

F-102

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

T H

IR

D

F L O

O R

L

IF

E

S A

F E

T Y

C O

D E

P L A

N

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F -1

SCALE:

0 16' 32'

1/16" = 1' - 0"

16' 32'

1/16" = 1'-0" C1

THIRD FLOOR - LIFE SAFETY CODE PLAN

1/8" = 1'-0"

LOFT - LIFE SAFETY CODE PLAN

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

A

B

C

D

E

F F

F A

C P

F F

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

A

B

C

D

E

F F F F

P

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

A

B

C

D

E

F F

I

F F

09/30/2016 Expiration Date of the License

AI

NROFICF

E A

N

OITCETORP

ERI

F

LAO

S

T T

R E

S R

ED

PROFESS IONAL

EN

G

IN

E

E

RS

A M

U

E

S. DANNA

W

AY

LE

T

I G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

/1

/2

/2

:4 :0

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

FD101

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

F

IR

S T

S

E C

O N

D A

N D

T H

IR

D

F L O

O R

F

IR

E

A L

A R

M D

E M

O L

IT

IO

N

P L A

N

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F D

1/16" = 1'-0" C1

FIRST FLOOR FIRE ALARM DEMOLITION PLAN

1/16" = 1'-0" B1

SECOND FLOOR FIRE ALARM DEMOLITION PLAN

1/16" = 1'-0" A1

THIRD FLOOR FIRE ALARM DEMOLITION PLAN NOTE:

DEVICE LOCATIONS ARE PROVIDED FOR BIDDING PURPOSES ONLY. ACTUAL DEVICE LOCATIONS AND

QUANTITIES ARE TO BE FIELD VERIFIED. DEMOLISH ALL EXISTING FIRE ALARM DEVICES INCLUDING

CONDDUIT AND WIRING.

SCALE:

0 16' 32'

1/16" = 1' - 0"

16' 32'

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P

FA

FTR

LOC

FACP

WF

FEP

DESCRIPTION

24 VOLT RELAY 24

MANUAL DOUBLE-ACTION PULL STATION

ALARM PRESSURE SWITCH

SYMBOL

FIRE ALARM RACEWAY

COMBINATION FIRE ALARM INTERFACE/TRANSMITTER

TAMPER SWITCH

LOCAL OPERATING CONSOLE PANEL

FIRE ALARM/MASS NOTIFICATION SYSTEM CONTROL PANEL

WALL MOUNTED FIRE ALARM/MASS NOTIFICATION SPEAKER. SPEAKER WATT TAP SHALL BE SET TO 1/2 WATT UNLESS

OTHERWISE INDICATED ON THE DRAWINGS.

ABOVE FINISH FLOORAFF

PHOTOELECTRIC SYSTEM SMOKE DETECTOR

WP WEATHERPROOF

TYP TYPICAL

ADDRESSABLE OUTPUT MODULE

ADDRESSABLE INPUT MODULE

BOOSTER POWER SUPPLY

WATER FLOW SWITCH

FIRE PROTECTION SYMBOLS AND ABBREVIATIONS

ELEVATOR PHOTOELECTRIC SYSTEM SMOKE DETECTOR

WALL MOUNTED VISUAL DEVICE WITH CLEAR COLOR LENS WITH MARKINGS "FIRE", CANDELA RATING AS INDICATED ON THE DRAWINGS.

ANT FIRE ALARM ANTENNA

XX

VS

PS

F

AIM

AOM

R

P

P/E

SURGE PROTECTORSP

S

CEILING MOUNTED FIRE ALARM/MASS NOTIFICATION SPEAKER. SPEAKER WATT TAP SHALL BE SET TO 1/2 WATT UNLESS

OTHERWISE INDICATED ON THE DRAWINGS.S

C

C

XX

WALL MOUNTED COMBINED AUDIO/VISUAL DEVICE WITH CLEAR COLOR LENS WITH MARKINGS "FIRE", CANDELA RATING AS INDICATED ON THE DRAWINGS. SPEAKER WATT TAP TO BE SET TO 1/2 WATT UNLESS OTHERWISE INDICATED ON THE DRAWINGS.

CEILING MOUNTED COMBINED AUDIO/VISUAL DEVICE WITH CLEAR COLOR LENS WITH MARKINGS "FIRE", CANDELA RATING AS INDICATED ON THE DRAWINGS. SPEAKER WATT TAP TO BE SET TO 1/2 WATT UNLESS OTHERWISE INDICATED ON THE DRAWINGS.

XX

XX

C

XX

M

M

WALL MOUNTED COMBINED AUDIO/VISUAL DEVICE WITH AMBER COLOR LENS WITH MARKINGS "ALERT", CANDELA RATING AS INDICATED ON THE DRAWINGS. SPEAKER WATT TAP TO BE SET TO 1/2 WATT UNLESS OTHERWISE INDICATED ON THE DRAWINGS.

CEILING MOUNTED COMBINED AUDIO/VISUAL DEVICE WITH AMBER COLOR LENS WITH MARKINGS "ALERT", CANDELA RATING AS INDICATED ON THE DRAWINGS. SPEAKER WATT TAP TO BE SET TO 1/2 WATT UNLESS OTHERWISE INDICATED ON THE DRAWINGS.

CEILING MOUNTED VISUAL DEVICE WITH CLEAR COLOR LENS WITH MARKINGS "FIRE", CANDELA RATING AS INDICATED ON THE DRAWINGS.

XX

RATE COMPENSATION TYPE HEAT SENSOR

R/C

MTR MASS NOTIFICATION TRANSCEIVER

FCV FLOOR CONTROL VALVE

FIRE DEPARTMENT CONNECTION

CEILING MOUNTED VISUAL DEVICE WITH AMBER COLOR LENS WITH MARKINGS "ALERT", CANDELA RATING AS INDICATED ON THE DRAWINGS.

XX

M

DUCT SMOKE DETECTOR, AIR HANDLING UNIT

XX

WALL MOUNTED VISUAL DEVICE WITH AMBER COLOR LENS WITH MARKINGS "ALERT", CANDELA RATING AS INDICATED ON THE DRAWINGS.

XX

M

FIRE ALARM / MASS NOTIFICATION NOTES:

1. THE FIRE ALARM / MASS NOTIFICATION SYSTEM SHALL BE DESIGNED AND INSTALLED IN

ACCORDANCE WITH NFPA 72-2013, UFC 3-600-01, UFC 4-021-01 AND SPECIFICATION SECTION 28 31 76.

2. ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED OR FM APPROVED.

3. DEVICE LOCATIONS AND CONDUIT ROUTING ARE CONCEPTUAL. FINAL

QUANTITY AND LAYOUT SHALL BE IN ACCORDANCE WITH APPLICABLE

CODES, MANUFACTURER'S RECOMMENDATIONS, AND EQUIPMENT LISTINGS.

COORDINATE LOCATIONS WITH CEILING INSTALLATION AND OTHER DEVICES.

4. ALL FIRE ALARM CONDUIT SHALL BE 3/4" MINIMUM. ALL CONDUIT IN

FINISHED AREAS SHALL BE CONCEALED.

SYNCHRONIZE ALL VISUAL NOTIFICATION APPLIANCES. SYNCHRONIZE ALL

AUDIBLE NOTIFICATION APPLIANCES.

5.

THE FIRE ALARM SIGNAL SHALL BE A TEMPORAL THREE PATTERN TONE.6.

VISUAL NOTIFICATION APPLIANCES SHALL BE IN ACCORDANCE WITH NFPA 72.7.

SIGNALING LINE CIRCUITS SHALL BE CLASS A, INITIATING DEVICE

CIRCUITS SHALL BE CLASS A, NOTIFICATION APPLIANCE CIRCUITS SHALL BE

CLASS A.

8.

SMOKE DETECTORS SHALL BE LOCATED A MINIMUM OF 3 FEET FROM

SUPPLY AND RETURN AIR DIFFUSERS.

PROVIDE SIGNAGE AT THE FIRE ALARM CONTROL PANEL IDENTIFYING THE

POWER PANEL AND CIRCUIT.

10.

MASS NOTIFICATION TESTING SHALL INCLUDE INTELLIGIBILITY MEASUREMENTS. THE

CIS VALUE SHALL BE 0.80 OR HIGHER PER UFC 04-021-01.

9.

11.

PROVIDE A CABINET NEXT TO THE FIRE ALARM PANEL LABELED "FIRE ALARM

DOCUMENTS". THE BOX SHALL CONTAIN THE FINAL RECORD OF COMPLETION AND THE

FIRE ALARM AS-BUILT UPDATED APPROVED SHOP DRAWINGS.

12.

AUTOMATIC SPRINKLER SYSTEM NOTES:

1. THE SPRINKLER SYSTEM DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA 13-2013, UFC 3-600-01 AND SPECIFICATION SECTION 21 13 13.00 10. THE CONTRACTOR SHALL VERIFY THE LOCATION ALL SPRINKLER SYSTEM

COMPONENTS AND COORDINATE WITH THE VARIOUS TRADES.

2. ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED OR FM APPROVED.

3. AUTOMATIC SPRINKLER PROTECTION SHALL BE PROVIDED THROUGHOUT THE BUILDINGS.

4.

5. THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY DESIGNED IN ACCORDANCE WITH NFPA 13. SPRINKLER SYSTEM

DESIGN CRITERIA SHALL BE AS FOLLOWS:

WET PIPE SYSTEMS

ALL AREAS OF THE BUILDING EXCEPT AS NOTED BELOW:

OCCUPANCY HAZARD CLASSIFICATION: HC-1

DESIGN DENSITY: 0.10 GPM/SF

DESIGN AREA: 1,500 SF

SPRINKLER TYPE: QUICK RESPONSE TYPE, CORROSION RESISTANT IN EXTERIOR LANAIS

SPRINKLER TEMPERATURE: ORDINARY, EXCEPT INTERMEDIATE IN GYM

HOSE STREAM: 250 GPM (ACCOUNTED FOR IN ADJUSTED WATER SUPPLY)

MECHANICAL SPACES:

OCCUPANCY HAZARD CLASSIFICATION: HC-2

DESIGN DENSITY: 0.20 GPM/SF

DESIGN AREA: 2,500 SF

SPRINKLER TYPE: QUICK RESPONSE TYPE

SPRINKLER TEMPERATURE: INTERMEDIATE

HOSE STREAM: 250 GPM (ACCOUNTED FOR IN ADJUSTED WATER SUPPLY)

6. SPRINKLERS SHALL BE LOCATED IN THE CENTER OF CEILING TILES WHERE APPLICABLE. CORROSION RESISTANT SPRINKLERS SHALL

BE PROVIDED NEAR SHOWERS.

7. SPRINKLER PIPING SHALL COMPLY WITH NFPA 13, EXCEPT THAT COPPER AND PLASTIC PIPE SHALL NOT BE PERMITTED.

8. THE PIPE ROUTING AND SPRINKLER LOCATIONS ARE CONCEPTUAL. THE CONTRACTOR SHALL INSTALL THE SYSTEM IN ACCORDANCE WITH THE APPLICABLE CODES, MANUFACTURER'S RECOMMENDATIONS AND EQUIPMENT LISTINGS.

9. PIPING SHALL BE PROVIDED WITH EARTHQUAKE PROTECTION IN ACCORDANCE WITH NFPA 13 INCLUDING BRANCH LINE RESTRAINT.

10. ALL SPRINKLER PIPING IN FINISHED AREAS SHALL BE CONCEALED FROM VIEW.

11. ALL SPRINKLERS IN AREAS EXPOSED TO THE ELEMENTS SHALL BE CORROSION RESISTANT. ALL SPRINKLER PIPING SHALL BE PAINTED.

12. PROVIDE A PRESSURE RELIEF VALVE ON THE FIRE SPRINKLER RISER PER NFPA 13-2013.

WATER SUPPLY INFORMATION: AT THE BASE OF RISER.

STATIC PRESSURE: 59 PSI

RESIDUAL PRESSURE: 39 PSI

FLOW AT RESIDUAL PRESSURE: 521 GPM

13. PROVIDE SLEEVES THROUGH CONCRETE/MASONRY WALLS AND FLOORS. SLEEVES SHALL BE NOMINAL 2" LARGER THAN THE PIPE GOING THROUGH IT FOR PIPE SLEEVES 3-1/2" AND SMALLER, AND NOMINAL 4" LARGER THAN THE PIPE

GOING THROUGH IT FOR PIPE SLEEVE 4" AND LARGER.

14. PROVIDE LISTED SPRINKLER GUARDS IN ACCORDANCE WITH NFPA 13.

15. CONDUCT INSPECTIONS AND HYDROSTATIC TESTS IN ACCORDANCE WITH NFPA 13.

STORAGE ROOMS:

OCCUPANCY HAZARD CLASSIFICATION: MISCELLANEOUS STORAGE UP TO 10 FEET

DESIGN DENSITY: 0.20 GPM/SF

DESIGN AREA: 1,500 SF

SPRINKLER TYPE: QUICK RESPONSE TYPE

SPRINKLER TEMPERATURE: ORDINARY

HOSE STREAM: 250 GPM (ACCOUNTED FOR IN ADJUSTED WATER SUPPLY)

NFPA 13 DESIGN AREA REDUCTIONS BASED ON USE OF QUICK RESPONSE SPRINKLERS IS NOT PERMITTED.

THE WATER SUPPLY SHOWN HAS BEEN ADJUSTED FROM A HYDRANT FLOW TEST CONDUCTED BY S.S. DANNAWAY ASSOCIATES ON FOOTE AVENUE. THE ADJUSTED SUPPLY SHOWN ACCOUNTS FOR HOSE STREAM AND A 12 PSI LOSS THROUGH THE DOUBLE CHECK BACKFLOW PREVENTER . PRIOR TO THE PREPARATION OF SPRINKLER SHOP DRAWINGS, IF UTILITY IMPROVEMENTS ARE COMPLETED TO ADD FIRE HYDRANTS WITHIN THE QUAD COURTYARD, A FLOW TEST MAY BE PERFORMED BY THE CONTRACTOR IN ACCORDANCE WITH NFPA 291. A FIRE PROTECTION ENGINEER, OR AN ENGINEER

EXPERIENCED IN WATER FLOW TESTING MUST PERFORM OR WITNESS THE FLOW TEST.

ALL CANDELA VALUES SHOWN ARE CONCEPTUAL AND ARE THE MINIMUM UNDERATED

VALUES BASED ON THE DEVICE LOCATIONS SHOWN. IF THE MANUFACTURER'S DATA

REQUIRES THAT THE APPLIANCES BE DERATED. IT IS THE RESPONSIBILITY OF THE

CONTRACTOR TO PROVIDE STROBE COVERAGE BASED ON THE MANUFACTURER'S

REQUIRED DERATED VALUES AND SPACED IN ACCORDANCE WITH NFPA 72.

13.

CALCULATIONS SHALL INCLUDE A MINIMUM 10% CUSHION FROM THE DESIGN WATER SUPPLY BASED ON A WATER SUPPLY

DRAWING PARALLEL TO THE ORIGINAL WATER SUPPLY.

09/30/2016 Expiration Date of the License

AINROFICF

E

A

NOITCETORPERI

F

LAO

ST

T

R E

S

RED

PROFESS IONAL

ENG

IN

E E

RS

A

M

UE

S. DANNAW

AY

LET

I

G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

/2

/2

:4 :1

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

FA001

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

F I R

E P

R O

T E

C T

IO

N

N O

T E

S A

N D

L E

G E

N D

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F A

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P

UP

FD

FD

FD

M

M

30 30

M

M

15 15

M

M

15 15

M

W P

M

C

C

M

C

M

C

M

C

M

C

C

C

C

C

M

C

C

M

C

C

M

C

C

M

C

C

C

M

C

M

M

C

M

C

C

M

C

M

M

M

C

C

M

C

C

C

M

C

C

M

C

C

C

C

M

C

M

C

M

C

M

C

M

C

C

C

M

W P

M

C

M

C

M

C

S

C

C

M

C

M

C

M

W P

W P

S

C

S

C

S

C

S

C

S

C

S

C S

C

S

C

S

C

S

C

S

C

S

C

S

C

S

C F

A C

P F

T R

M T

R

P

F E

P F

E P

P

ANT ANT

LOC

W P

F

WP

F

C

S

C

S

C

S

C

S

C

C

C

M

F E

P

W P

AHU-1

WP

F

WP 110

WP 60

M

110, WP

WP 60

M

WP

F

WP 60

M

WP

F

WP

F

110, WP

WP 30

M

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F O

R C

O N

T

IN

U A

T

IO

N

S E

E S

H E

E T

F A

M A

T C

H L

IN

E

A

COMMAND CONFERENCE

S-4 OFFICE 1A

CENTRAL FILES 1A

WOMEN'S TOILET

MEN'S TOILET

XO 1A

CSM 1A

COMMANDER 1A

COMMAND SUPPLY 1A

CMD OPEN OFFICE

S-1 OFFICER 1A

CORR

101A

COMMAND TOILET 1A

SR HR SGT 1A

DUTY OFFICER 1A

ARMS VAULT #3A

ARMS VAULT #3B

SECURE DOCUMENTS 1A

CORR

101B

RECYCLE 1A

ELEC 1A

STORAGE 1A-2

MECHANICAL 1A

TELECOM 1A

LANAI

100A

S-2 OFFICE 1A

S-6 OFFICE 1A

S-3 OPS SGT 1A

S-3 OFFICE 1A

S-3 CONF

RE-ENLIST 1A

FRSA

OPEN OFFICE 1A

COPY

STORAGE 1A-1

VENDING

100D

BREEZEWAY

100C

PROVIDE WEATHERPROOF

ENCLOSURE FOR LOC

09/30/2016 Expiration Date of the License

AINROFICF

E

A

NOITCETORPERI

F

LAO

ST

T

R E

S

RED

PROFESS IONAL

ENG

IN

E E

RS

A

M U

E

S. DANNAW

AY

LE

T

I G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

/8

/2

/2

:4 :2

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

FA101

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

P A

R T

IA

L F

IR

S

T F

L O

O R

W E

S T

F

IR

E

A L A

R M

/M A

S S

N O

T

IF

IC

A

T I O

N P

L A

N

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F A

SCALE:

0 8' 16'

1/8" = 1' - 0"

8' 16'

1/8" = 1'-0" B1

PARTIAL FIRST FLOOR WEST - FIRE ALARM/MASS NOTIFICATION PLAN

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

R

NOTE:

ALL CANDELA VALUES SHOWN ARE THE MINIMUM UNDERATED VALUES. IF THE MANUFACTURER'S DATA REQUIRES THAT THE APPLIANCES BE

DERATED, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE STROBE COVERAGE BASED ON THE MANUFACTURER'S REQUIRED

DERATED VALUES AND SPACED IN ACCORDANCE WITH NFPA 72.

UP

FD

W P

M

W P

M

S

C

W P

W P

30 30

M

M

30 30

M

M

M

15 30

M

34 34

M

M

5M 1

C

M

C

C

M

C

C

M

C

C

M

C

C

C

M

C

M

C

M

C

S

C

C

S

C

C

M

C

C

M

S

C

S

C

S

C

S

C

S

C

S

C

S

C

S

C

S

C

C

C

M

C

C

M

C

M

C

C

C

C

C

C

M

C

M

C

M

C

C

C

M

S

C

S

C

S

C

S

C

C

C

C

M

C

M

C

M

C

M

C

15 15

C

M

WF

VS

F E

P

P

ANT ANT

W P

F

LOC

WP

F

C

C

M

M

C

C

C

M

C

M

C

C

M

S

C

S

C

FEPFEP

W P

WP 30

AHU-2

WP

F

110, WP

WP 60

M

WP

F

110, WP

WP 60

M

WP 60M

WP

F

110, WP

WP 60

M

WP

F

VS

VS

PS

12 13 14 15 16 17 18 19 20 21 22 23

A

B

C

D

E

F O

R C

O N

T

IN

U A

T

IO

N

S E

E S

H E

E T

F A

M A

T C

H L

IN

E

A

S-3 CONF

VENDING

100D

OPEN OFFICE 1B

FIRE RISER ROOM

ARMS VAULT #2B

S-3 OFFICE 1A

S-3 OPS SGT 1A

S-6 OFFICE 1A

S-2 OFFICE 1A

SECURE DOCUMENT'S 1A

MEN'S TOILET

WOMEN'S TOILET

CENTRAL FILES

S-4 OFFICE 1B

COMMAND CONF ROOM 1B

ARMS VAULT #2A

CHAPLAIN

ELEC 1B

166STORAGE 1B

CHAPLAIN ASST

MECHANICAL ROOM 1B

TELECOM 1B

CORR

161B

XO 1B

CSM 1B

COMMANDER 1B

CMD OPEN OFFICE

S-1 OFFICE

COMMAND SUPPLY 1B

CMD TOILET 1B

CORR

161A

SR HR SGT 1B

DUTY OFFICER 1B

JAN

LANAI

100B

LANAI

100B

BREEZEWAY

100C

PROVIDE WEATHERPROOF

ENCLOSURE FOR LOC

09/30/2016 Expiration Date of the License

AINROFICF

E

A

NOITCETORPERI

F

LAO

ST

T

R E

S

RED

PROFESS IONAL

ENG

IN

E E

RS

A

M U

E

S. DANNAW

AY

LE

T

I G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

/8

/2

/2

:4 :2

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

FA102

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

P A

R T

IA

L F

IR

S

T F

L O

O R

E A

S T

F

IR

E

A L A

R M

/M A

S S

N O

T

IF

IC

A

T I O

N P

L A

N

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F A

SCALE:

0 8' 16'

1/8" = 1' - 0"

8' 16'

1/8" = 1'-0" B1

PARTIAL FIRST FLOOR EAST - FIRE ALARM/MASS NOTIFICATION PLAN

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

R

NOTE:

ALL CANDELA VALUES SHOWN ARE THE MINIMUM UNDERATED VALUES. IF THE MANUFACTURER'S DATA REQUIRES THAT THE APPLIANCES BE

DERATED, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE STROBE COVERAGE BASED ON THE MANUFACTURER'S REQUIRED

S

C

S

C

S

C

S

C S

C

S

C

S

C

S

C

S

C

S

C

S

C

S

C

S

C

S

C

S

C S

C

S

C

C

C

M

C

C

C

C

C

M

C

M

C

M

C

M

C

C

M

C

M

C

C

C

C

M

C

M

C

M

C

C

M

C

M

C

M

C

M

C

M

C

M

C

M

C

C

C

C

M

C

C

C

C

M

C

C

M S

C

C

C

M

C

C

M

C

M

C

C

C

C

M

C

M15

M

30 15

M

15 15

M

M

M

WP

M

WP

60 1515

M

WP,

M

WP, 60

C

C

C

M

C

M

C

C

M

S

C

S

C

S

C

C

M

C

S

C

C

C

C

C

M

F E

P F

E P

F E

P

P

WP

F

LOC

C

M

S

C

WP, 110

WP 60

AHU-3

WP 75

WP 15

M

WP, 60M WP 110WP 60

M

WP 60

M

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F O

R C

O N

T

IN

U A

T

IO

N

S E

E S

H E

E T

F A

M A

T C

H L

IN

E

A

COMMANDER 2A

LANAI

200A

NBC STORAGE 2A

UNIT STORAGE 2A-1

XO 2A

PLATOON 2A-D

PLATOON 2A-C

PLATOON 2A-B

PLATOON 2A-A

COMMAND CONFERENCE ROOM 2A

RECYCLE 2A

ELEC 2A

TELECOM 2A

MECHANICAL ROOM 2A

COMM STORAGE 2A

STORAGE 2A-2

CORR

201B

COMMAND OPEN OFFICE

COMMAND STORAGE 2A

CLASSROOM 2B

CLASSROOM 2A

UNIT STORAGE 2A-3

UNIT STORAGE 2A-2

CORR

201A WOMEN'S RESTROOM

JAN

MEN'S RESTROOM

CORR

TRAINING ROOM 2A

STORAGE 2A-1

1 SGT 2A

SECURE STORAGE 2A

CORR

MEN'S LATRINE & SHOWER

CLASSROOM 2C

JAN

CORR

244B

PROVIDE WEATHERPROOF

ENCLOSURE FOR LOC

09/30/2016 Expiration Date of the License

AINROFICF

E

A

NOITCETORPERI

F

LAO

ST

T

R E

S

RED

PROFESS IONAL

ENG

IN

E E

RS

A

M U

E

S. DANNAW

AY

LE

T

I G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

/8

/2

/2

:4 :3

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

FA103

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

P A

R T

IA

L S

E C

O N

D F

L O

O R

W E

S T

F

IR

E

A L A

R M

/M A

S S

N O

T

IF

IC

A

T I O

N P

L A

N

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F A

SCALE:

0 8' 16'

1/8" = 1' - 0"

8' 16'

1/8" = 1'-0" B1

PARTIAL SECOND FLOOR WEST - FIRE ALARM/MASS NOTIFICATION PLAN

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

R

NOTE:

ALL CANDELA VALUES SHOWN ARE THE MINIMUM UNDERATED VALUES. IF THE MANUFACTURER'S DATA REQUIRES THAT THE APPLIANCES BE

DERATED, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE STROBE COVERAGE BASED ON THE MANUFACTURER'S REQUIRED

S

C

S

C

C

M

C

M

S

C

S

C

C

M

S

C

S

C

S

C

S

C

S

C

S

C

S

C

S

C

S

C

S

C

S

C 30

C

S

C

S

C

C

C

C

C

C

C

M

C

M

C

M

C

M

C

M

C

M S

C

C

M

C

M

C

M

C

M

C

C

C

C

C

C

M

C

C

M

C

C

M

C

C

M

C

S

C

C

M

C

M

C

S

C

C S

C

C

M

C

M

C

C

M S

C

S

C

C

C

M

C

C

M

C

C

M

C

M

C

M

C

M

C

M30

C 30

C

C

C

C

M

C

M

WP

M

WP

M

15 30

M

M

15 15

M

15 15

M

C

WF

VS

F E

P

P

WP

F

WP

F

WP

F

LOC

M

M

15 30

M

30 15

M

C 60

C

S

C

F E

P

FEP

WP 60

AHU-4

WP 60

M

WP 110

WP 60

M

WP 110WP 75

M

WP 75

M

WP 75

WP 60

M

12 13 14 15 16 17 18 19 20 21 22 23

A

B

C

D

E

F O

R C

O N

T

IN

U A

T

IO

N

S E

E S

H E

E T

F A

M A

T C

H L

IN

E

A

LANAI

200B

PLATOON 2B-D

PLATOON 2B-C

PLATOON 2B-B

PLATOON 2B-A

COMMAND CONFERENCE ROOM 2B

UNIT STORAGE 2B-2

UNIT STORAGE 2B-1

CLASSROOM 2B

CLASSROOM 2A

SECURE STORAGE 2B

UNIT STORAGE 2B-3

1 SGT 2B

XO 2B

COMMAND STORAGE 2B

COMMAND OPEN OFFICE

MECHANICAL ROOM 2B

TELECOM 2B

STORAGE 2B-2

ELEC 2B

RECYCLE 2B

COMM STORAGE 2B

CORR

232A

TRAINING ROOM 2B

STORAGE 2B-3

WOMEN'S RESTROOM

JAN

MEN'S RESTROOM

CORR

NBC STORAGE 2B

245 CORR

244A

CORR

232B

CLASSROOM 2C

JAN

CORR

244B

WOMEN'S LATRINE & SHOWER

COMMANDER 2B

PROVIDE WEATHERPROOF

ENCLOSURE FOR LOC

09/30/2016 Expiration Date of the License

AINROFICF

E

A

NOITCETORPERI

F

LAO

ST

T

R E

S

RED

PROFESS IONAL

ENG

IN

E E

RS

A

M U

E

S. DANNAW

AY

LE

T

I G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

/8

/2

/2

:4 :4

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

FA104

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

P A

R T

IA

L S

E C

O N

D F

L O

O R

E A

S T

F

IR

E

A L A

R M

/M A

S S

N O

T

IF

IC

A

T I O

N P

L A

N

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F A

SCALE:

0 8' 16'

1/8" = 1' - 0"

8' 16'

1/8" = 1'-0" B1

PARTIAL SECOND FLOOR PLAN EAST - FIRE ALARM/MASS NOTIFICATION PLAN

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

R

NOTE:

ALL CANDELA VALUES SHOWN ARE THE MINIMUM UNDERATED VALUES. IF THE MANUFACTURER'S DATA REQUIRES THAT THE APPLIANCES BE

DERATED, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE STROBE COVERAGE BASED ON THE MANUFACTURER'S REQUIRED

FD

FD

FD

S

C

S

C

S

C

S

C

C

M

C

C

C

M

C

C

C

C

C

C

M

C

M

C

M

C

M

C

M

C

M

C

M

C

M

C

C

C

C

C

C

M

C

M

C

M

C

M

C

C

M

C

M

C

M

C

M

C

C

C

C

M

M

15 15

M

30 15

M

WP, 30 WP,

M

M

WP

30WP

M

M

M

M

S

M S

M

M

94 60

M

M

FEPFEP

FEP

P

WP

F

LOC

C

M

C

M

30 15 15

M

M

M

AHU-5

WP 110

WP 60

M

WP 60

M

WP, 110 WP 75

WP 60

M

WP 75

M

WP 75

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F O

R C

O N

T

IN

U A

T

IO

N

S E

E S

H E

E T

F A

M A

T C

H L

IN

E

A

COMMANDER 3A

GYM

LANAI

300A

1 SGT 3A

COMMAND STORAGE 3A

XO 3A

COMM STORAGE 3A

PLATOON 3A-D

PLATOON 3A-C

PLATOON 3A-B

PLATOON 3A-A

COMMAND CONFERENCE ROOM 3A

STORAGE 3A

UNIT STORAGE 3A

RECYCLE 3A

TELECOM ROOM 3A

CORR

301B

ELEC 3A

JAN

MECHANICAL ROOM 3A

CORR

NBC STORAGE 3A

TRAINING ROOM 3A

MEN'S LATRINE & SHOWER

CORR

301ACOMMAND OPEN OFFICE

WOMEN'S RESTROOM

SECURE STORAGE 3A

PROVIDE WEATHERPROOF

ENCLOSURE FOR LOC

09/30/2016 Expiration Date of the License

AINROFICF

E

A

NOITCETORPERI

F

LAO

ST

T

R E

S

RED

PROFESS IONAL

ENG

IN

E E

RS

A

M U

E

S. DANNAW

AY

LE

T

I G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

/8

/2

/2

:4 :4

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

FA105

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

P A

R T

IA

L T

H

IR

D F

L O

O R

W E

S T

F

IR

E

A L A

R M

/M A

S S

N O

T

IF

IC

A

T I O

N P

L A

N

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F A

SCALE:

0 8' 16'

1/8" = 1' - 0"

8' 16'

1/8" = 1'-0" B1

PARTIAL THIRD FLOOR WEST - FIRE ALARM/MASS NOTIFICATION PLAN

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

R

NOTE:

ALL CANDELA VALUES SHOWN ARE THE MINIMUM UNDERATED VALUES. IF THE MANUFACTURER'S DATA REQUIRES THAT THE APPLIANCES BE

DERATED, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE STROBE COVERAGE BASED ON THE MANUFACTURER'S REQUIRED

FD

M

M

94 60

M

MS

M

MS

C

C

C

C

C

C

C

C

M

C

M

C

M

C

M

C

M

C

M

C

M

C

M

C

M

S

C

S

C

S

C

S

C

C

C

M

C

M

C

S

C

C

C

C

M

C

M

C

C

M

C

M

C

C

M

C

M

C

M

C

C

M

C

S

C

S

C

S

C

C

M

C

C

M

C

M

M

M

W P

M3

W P

M

WP 30

M

WP, 30

WP 30

M

WP, 30

M

M

WF

VS

FEP

P

WP

F

WP

F

LOC

WP

F

C

C

M

M

F E

P F

E P

WP, 110

AHU-6

WP 75

M

WP 75 WP 110

WP 60

M

WP 60

M

WP 60

M

WP 110

WP 60

M

C

C

M

12 13 14 15 16 17 18 19 20 21 22 23

A

B

C

D

E

F O

R C

O N

T

IN

U A

T

IO

N

S E

E S

H E

E T

F A

M A

T C

H L

IN

E

A

COMMANDER 3B

XO 3B

1 SGT 3B

GYM

LANAI

300B

PLATOON 3B-B

PLATOON 3B-C

PLATOON 3B-D

COMM STORAGE 3B

COMMAND CONFERENCE ROOM 3B

PLATOON 3B-A

NBC STORAGE 3B

STORAGE 3B

MECHANICAL ROOM 3B

STAIR

TELECOM 3B

OFFICE

ELEC 3B

COMMAND STORAGE 3B

UNIT STORAGE 3B

CORR

330B

JAN

TRAINING ROOM 3B

COMMAND OPEN OFFICE

CORR

WOMEN'S RESTROOM

SECURE STORAGE 3B

CORR

330A

MEN'S LATRINE & SHOWER

PROVIDE WEATHERPROOF

ENCLOSURE FOR LOC

16 17

C

D

09/30/2016 Expiration Date of the License

AINROFICF

E

A

NOITCETORPERI

F

LAO

ST

T

R E

S

RED

PROFESS IONAL

ENG

IN

E E

RS

A

M U

E

S. DANNAW

AY

LE

T

I G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

/8

/2

/2

:4 :5

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

FA106

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

P A

R T

IA

L T

H

IR

D F

L O

O R

E A

S T

F

IR

E

A L A

R M

/M A

S S

N O

T

IF

IC

A

T I O

N P

L A

N

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F A

SCALE:

0 8' 16'

1/8" = 1' - 0"

8' 16'

1/8" = 1'-0" B1

PARTIAL THIRD FLOOR EAST - FIRE ALARM/MASS NOTIFICATION PLAN

1/8" = 1'-0"

LOFT - FIRE ALARM/MASS NOTIFICATION PLAN

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

R

NOTE:

ALL CANDELA VALUES SHOWN ARE THE MINIMUM UNDERATED VALUES. IF THE

MANUFACTURER'S DATA REQUIRES THAT THE APPLIANCES BE DERATED, IT IS

THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE STROBE COVERAGE

BASED ON THE MANUFACTURER'S REQUIRED DERATED VALUES AND SPACED

IN ACCORDANCE WITH NFPA 72.

NOTE:

ALL CANDELA VALUES SHOWN ARE THE MINIMUM UNDERATED VALUES. IF THE MANUFACTURER'S DATA

REQUIRES THAT THE APPLIANCES BE DERATED, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE

STROBE COVERAGE BASED ON THE MANUFACTURER'S REQUIRED DERATED VALUES AND SPACED IN

ACCORDANCE WITH NFPA 72.

VISUAL OR

AUDIO/VISUAL

DEVICE

MANUAL FIRE ALARM

PULL STATION

AUDIO DEVICE

WHERE LOW CEILING HEIGHT DO NOT PERMIT MOUNTING AT A MINIMUM OF 80", VISIBLE

APPLIANCES SHALL BE MOUNTED WITHIN 6" OF THE CEILING. THE ROOM SIZE COVERED

BY A STROBE OF A GIVEN VALUE SHALL BE REDUCED BY TWICE THE DIFFERENCE

BETWEEN THE MINIMUM MOUNTING HEIGHT OF 80" AND THE ACTUAL LOWER MOUNTING

HEIGHT.

AUDIO DEVICE MOUNTING HEIGHTS OTHER THAN REQUIRED ABOVE SHALL BE PERMITTED,

PROVIDED THAT THE SOUND PRESSURE LEVEL REQUIREMENTS BASED ON APPLICATION

(EX. PUBLIC MOD) ARE MET.

FIRE

FIRE

6'

" 7'

5'-0"

MAX.

4'

FINISHED FLOOR

1.

2.

NOTE:

GRADE

FLOOR

1" GALVANIZED RIGID

CONDUIT SUPPORT PIPE

RADIO FIRE ALARM

TRANSCEIVER

ROOF

ANTENNA

WALL MOUNTS

1" CONDUIT SUPPORT WITH

PULLING ELBOW PIPE W/

OFFSET BEND

T O

6"

F R

O M

P E

A K

O F

R O

O F

PROVIDE SUPPORT FOR

VERTICAL PORTION OF

RACEWAY ABOVE ROOF

CONNECT TO INDIVIDUAL GROUNDING ROD.

PROVIDE #6 BONDWIRE FROM INDIVIDUAL

GROUNDING ROD TO BUILDING GROUNDING

SYSTEM.

CONDUIT CLAMP

TO INDIVIDUAL GROUNDING

ROD PER NEC

COPPER WIRE SHALL NOT BE

SMALLER THAN #10 PER NEC

LIGHTNING ARRESTOR WITH

WEATHERPROOF ENCLOSURE,

SEE DETAIL

GROUNDING BUSHING

WEATHERPROOF ENCLOSURE

SIDE VIEW - WEATHERPROOF ENCLOSURE

COAXIAL CABLES

ARE NOT SHOWN

#10 COPPER

LIGHTNING ARRESTOR DETAIL

TOP OF DETECTOR

ACCEPTABLE HERE

DETECTOR LOCATION

IS ACCEPTABLE HERE

ABOVE ACCEPTABLE HEIGHT

BELOW ACCEPTABLE HEIGHT

CEILING

SIDEWALL

M A

X

IM

U M

1'

09/30/2016 Expiration Date of the License

AINROFICF

E

A

NOITCETORPERI

F

LAO

ST

T

R E

S

RED

PROFESS IONAL

ENG

IN

E E

RS

A

M

UE

S. DANNAW

AY

LET

I

G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

A s i n d ic a te d

/2

/2

:4 :5

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

FA501

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

F

IR

E A

L A

R M

/M A

S S

N O

T

IF

IC

A

T I O

N D

E T

A

IL

S

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F A

NTS

B2

MOUNTING HEIGHTS FOR ALARM DEVICES

NTS

B4

FIRE ALARM TRANCEIVER ANTENNA

NTS

C1

PROPER MOUNTING FOR SMOKE DETECTOR

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P

MANUAL PULL STATION ALARM ACTIVATION

GENERAL SUPERVISORY ACTIVATION

SMOKE DETECTOR ACTIVATION

RADIO FIRE ALARM TRANSCEIVER ZONES

WATER FLOW / PRESSURE SWITCH ACTIVATION

MASS NOTIFICATION SUPERVISORY ACTIVATION

GENERAL TROUBLE

SYSTEM INPUT

FIRE ALARM/ MASS NOTIFICATION SEQUENCE OF OPERATIONS

SYSTEM OUTPUT

TROUBLE ON FIRE ALARM EXTENDER PANEL

A B C D E F G

TRANSM

IT

A

LA

RM

T

O E

M

ERG

ENCY F

O

RCES

ACTIV

ATE V

IS

IB

LE

A

ND A

UDIB

LE

A

LA

RM

A

NNUNCIA

TO

R

TRANSM

IT

S

UPERVIS

O

RY A

LA

RM

T O E

M

ERG

ENCY F

O

RCES

TRANSM

IT

T

RO

UBLE

A

LA

RM

T O E

M

ERG

ENCY F

O

RCES

ACTIV

ATE M

ASS N

O

TIF

IC

ATIO

N V

IS

IB

LE

S

UPERVIS

O

RY A

NNUNCIA

TO

R

ACTIV

ATE V

IS

IB

LE

A

ND A

UDIB

LE

S

UPERVIS

O

RY A

NNUNCIA

TO

R

ACTIV

ATE V

IS

IB

LE

A

ND A

UDIB

LE

T

RO

UBLE

A

NNUNCIA

TO

R

ACTIV

ATE A

LL

F

IR

E A

LA

RM

N O

TIF

IC

ATIO

N A

PPLI

ANCES A

ND B

RO

ADCAST F

IR

E A

LA

RM

M

ESSAG

E

ACTIV

ATE M

ASS N

O

TIF

IC

ATIO

N V

IS

UAL

APPLI

ANCES

BRO

ADCAST M

ASS N

O

TIF

IC

ATI

O N M

ESSAG

E

TRANSM

IT

M

ASS N

O

TIF

IC

ATIO

N S

UPERVIS

O

RY T

O E

M

ERG

ENCY F

O

RCES

TEM

PO

RARIL

Y A

ND IM

M

EDIA

TELY

D

EACTIV

ATE A

LL

F

IR

E A

LA

RM

V

IS

UAL

NO

TIF

IC

ATIO

N A

PPLI

ANCES.

SPRINKLER RISER OR FLOOR WATER FLOW OR PRESSURE SWITCH

MANUAL PULL STATION

SMOKE DETECTOR ABOVE PANEL

SINGLE BREAK OR SINGLE GROUND FAULT IN FIRE ALARM CIRCUIT

ACTIVATION OF MASS NOTIFICATION LIVE OR RECORDED MESSAGE

ACTIVATION OF MASS NOTIFICATION LIVE OR RECORDED MESSAGE DURING AN ACTIVE ALARM *

SPRINKLER VALVE TAMPER SWITCH

H I J K L M

A B C D E F G H I J K L M

NOTE:

1. IF THE SEQUENCE INDICATED HERE CONFLICTS WITH SPECIFICATION, THIS CONTROL

SEQUENCE SUPERCEDES SPECIFICATION SEQUENCE.

* FIRE ALARM NOTIFICATION APPLIANCE OVERRIDE TO BE AUTOMATIC UPON ACTIVATION OF

MASS SYSTEM PRE-RECORDED MESSAGE OR MICROPHONE

SHUTDO

W

N A

SSO

CIA

TED A

HU

DUCT SMOKE DETECTOR9 9

N

N

O

O

IN

IT

IA

TIO

N D

EVIC

ES A

ND O

CCUPANT

NO

TIF

IC

ATIO

N A

PPLI

ANCE O

PERATI

O N M

AIN

TAIN

ED

DEACTIV

ATE M

ASS N

O

TIF

IC

ATIO

N V

IS

UAL

APPLI

ANCES

COMPLETION OF MASS NOTIFICATION LIVE OR RECORDED BROADCAST DURING AN ACTIVE ALARM10 10

09/30/2016 Expiration Date of the License

AINROFICF

E

A

NOITCETORPERI

F

LAO

ST

T

R E

S

RED

PROFESS IONAL

ENG

IN

E E

RS

A

M U

E

S. DANNAW

AY

LE

T

I G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

/2

/2

:4 :5

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

FA601

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

F

IR

E A

L A

R M

/M A

S S

N O

T

IF

IC

A

T I O

N S

E Q

U E

N C

E O

F O

P E

R A

T

IO

N S

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F A

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P

AIM AIM

S-1 OFFICE

CORR

101A

LANAI

100A

DUTY OFFICER 1A

SR HR SGT 1A

ARMS VAULT #3A

LANAI

100A

ARMS VAULT #3B

RECYCLE 1A

ELEC 1A

MECHANICAL 1A

TELECOM 1A

STORAGE 1A-2

COPY

STORAGE 1A-1

LANAI

100A

OPEN OFFICE 1A

BREEZEWAY

100C

VENDING

100D

FIRE RISER ROOM

BREEZEWAY

100C

LANAI

100B

ARMS VAULT #2B

STORAGE 1B

TELECOM 1B

MECHANICAL ROOM 1B

CHAPLAIN ASST

ELEC 1B

CHAPLAIN

ARMS VAULT #2A

SR HR SGT 1B

DUTY OFFICER 1B

LANAI

100B

CORR

161A

CMD TOILET 1B

COMMAND SUPPLY 1B

CMD OPEN OFFICE

CSM 1B

XO 1B

COMMAND CONF ROOM 1B

CMD OPEN OFFICE

S-4 OFFICE 1B

CENTRAL FILES

CORR

161B

LANAI

100B

COMMANDER 1B

OPEN OFFICE 1A

FTR FACP

ANTENNA

LIGHTNING ARRESTOR

TO GROUND

1P, 20A

1P, 20A

FOR

CONTINUATION,

SEE ELECTRICAL

DRAWING

C

WP

F

C

M

C

M

C

M

LOC

M

M

P

M

M

M

M

M

M

C C

WP

F

C

M

C

M

C

C

M S

C

S

S

C

S

C

S

C

S

C

S

C

S

C

WP

F

M

WP

X 3

WFVS

75WP

M

WP

F

110 34

M

M

M

M

M

FEP

P

1P, 20A

C

M

C

C

M

C

LOC

C

M

C

C

M

C

M

WP

F

C

C

M

C

M

C

M

C

M

C

C

M

C

C

M

C

C

M

C

C

M

C

S

C

S

C

S

C

S

C

C

M

C

C

C

M

C

C

M

C

S

C

C

M

C

S

C

C

FOR

CONT.

ON THIS

SHEET,

SEE

A

A FOR

CONT.

ON THIS

SHEET,

SEE

B

B FOR

CONT.

SEE

C

BACK TO FACP

SP

FEP

1P, 20A

SP

ON

SHEET

FA603

SPSP

X 3

BACK TO FACP

LANAI

100A

WP

F

LANAI

100B

WP

F

P

LANAI

100B

15WP 30WP

AOM

P, AHU-1

R SHUTDOWN AHU-1

AOM

P, AHU-2

R SHUTDOWN AHU-2

MTR

ANTENNA

LIGHTNING ARRESTOR

TO GROUND

M

WP

110WP

WP

F

M

WP

WP 110

WP

F

M

WP

WP 110

M

WP

110WP

M

WP

110WP

M

WP

AIM

VS

AIM

VS

AIM

PS

60WP

M

WP

F

M

WP

110WP

09/30/2016 Expiration Date of the License

AI

NROFICF

E A

N

OITCETORP

ERI

F

LAO

S

T T

R E

S R

ED

PROFESS IONAL

EN

G

IN

E

E

RS

A M

U

E

S. DANN

A W

A Y

LE

T

I G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

N O

S C

A L E

/2

/2

:5 :0

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

FA602

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

F

IR

E A

L A

R M

/M A

S S

N O

T

IF

IC

A

T I O

N R

IS

E

R D

IA

G

R A

M

F I R

S T

F L O

O R

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F A

- NO SCALE

A2

FIRE ALARM / MASS NOTIFICATION RISER DIAGRAM - FIRST FLOOR

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P

COMMAND SUPPLY 1A

CMD OPEN OFFICE

S-1 OFFICER 1A

COMMAND TOILET 1A

WOMEN'S TOILET

MEN'S TOILET

SECURE DOCUMENT'S 1A

CORR

161B

S-2 OFFICE 1A

S-6 OFFICE 1A

CORR

161B

S-3 OPS SGT 1A

S-3 OFFICE 1A

S-3 CONF

OPEN OFFICE 1B

BREEZEWAY

100C

FRSA

RE-ENLIST 1A

S-3 CONF

S-3 OFFICE 1A

S-3 OPS SGT 1A

CORR

101B

S-2 OFFICE 1A

S-6 OFFICE 1A

SECURE DOCUMENTS 1A

CORR

101B

WOMEN'S TOILET

MEN'S TOILET

CORR

101B

CORR

101B

COMMAND CONFERENCE

S-4 OFFICE 1A

CENTRAL FILES 1A

XO 1A

CSM 1A

COMMANDER 1A

M

M

C

M

C

S

C

C

M

C

M

C

C

M

C

C

M

C

C

M

C

C

M

C

C

M

C

S

C

S

C

C

M

C

S

C

S

C

S

C

75WP

M

WP

WP

F

C

M

C

C

M

C

C

M

C

C

M

C

C

M

C

C

M

C

C

M

C

C

M

C

S

C

C

C

M

C

M

M

S

C

C

M

M

C

M

C

S

C

S

C

C

M

C

S

C

S

C

C

M

C

C

M

C

C

M

C

M

C

M

C

C

M

C

C

M

C

C

C

M

C

S

C

C

C

M S

C

S

C

S

C

S

C

C

M

C

S

C

S

C

S

C

C FOR

CONT.

ON THIS

SHEET,

SEE

D

D FOR

CONT.

ON THIS

SHEET,

SEE

E

E

BACK TO FACP

BACK TO FACP

BACK TO FACP

BACK TO FACP

09/30/2016 Expiration Date of the License

AI

NROFICF

E A

N

OITCETORP

ERI

F

LAO

S

T T

R E

S R

ED

PROFESS IONAL

EN

G

IN

E

E

RS

A M

U

E

S. DANN

A W

A Y

LE

T

I G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

N O

S C

A L E

/2

/2

:4 :5

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

FA603

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

F

IR

E A

L A

R M

/M A

S S

N O

T

IF

IC

A

T I O

N R

IS

E

R D

IA

G

R A

M

F I R

S T

F L O

O R

C O

N T

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F A

NO SCALE

A2

FIRE ALARM / MASS NOTIFICATION RISER DIAGRAM - FIRST FLOOR CONT.

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P

CORR

201A

LANAI

200A

TRAINING ROOM 2A

STORAGE 2A-1

MEN'S RESTROOM

WOMEN'S RESTROOM

CORR

COMM STORAGE 2A

LANAI

200A

MECHANICAL ROOM 2A

STORAGE 2A-2

ELEC 2A

RECYCLE 2A

TELECOM 2A

NBC STORAGE 2A

CORR

LANAI

200A

MEN'S LATRINE & SHOWER

JAN

CLASSROOM 2C

NBC STORAGE 2B

LANAI

200B

CORR

244A

WOMEN'S LATRINE & SHOWER

STORAGE 2B-2

TELECOM 2B

LANAI

200B

MECHANICAL ROOM 2B

ELEC 2B

RECYCLE 2B

COMM STORAGE 2B

LANAI

200B

CORR

MEN'S RESTROOM

WOMEN'S RESTROOM

STORAGE 2B-3

TRAINING ROOM 2B

LANAI

200B

CORR

232A

COMMAND STORAGE 2B

COMMANDER 2B

1 SGT 2B

COMMAND OPEN OFFICE

LOC

M

PWP

F

X 3

S

C CC

30 15

M

C C

M

CC

M

M

M

CC

M S

C CC

M

M

C

M

M

M

M

CC

M

C

M

60, WP

60, WP

M

M

C

M

C

S

C

S

C

S

C

S

C

M

CC

M

CC

WP

F

30, WP

30, WP

M

M

M

M

WFVS

WP

F P

M

M

M

LOC

M

CC

M

M

M

CC

M

CC

WP

F

M

CC

M

CC

M

CC

M

CC

C

MS

C

S

C

C

M

C

C

FOR

CONT.

ON THIS

SHEET,

SEE

F

F FOR

CONT.

ON THIS

SHEET,

SEE

G

G FOR

CONT.

SEE

H

BACK TO FACP

FEP

1P, 20A

SP

FEP

1P, 20A

SP

TO FACP

ON FIRST

FLOOR

ON

SHEET

FA605

BACK TO FACP

BACK TO FACP

X 3

110WP

110WP

110WP

AOM

P, AHU-3

R SHUTDOWN AHU-3

AOM

P, AHU-4

R SHUTDOWN AHU-4

M

WP

75WP

60WP

M

M

WP

110WP

LANAI

200A

M

WP

60WP

M

WP 75

M

WP

M

WP

75WP

M

WP

09/30/2016 Expiration Date of the License

AI

NROFICF

E A

N

OITCETORP

ERI

F

LAO

S

T T

R E

S R

ED

PROFESS IONAL

EN

G

IN

E

E

RS

A M

U

E

S. DANN

A W

A Y

LE

T

I G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

N O

S C

A L E

/2

/2

:4 :5

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

FA604

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

F

IR

E A

L A

R M

/M A

S S

N O

T

IF

IC

A

T I O

N R

IS

E

R D

IA

G

R A

M

S E

C O

N D

F L O

O R

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F A

NO SCALE

A2

FIRE ALARM / MASS NOTIFICATION RISER DIAGRAM - SECOND FLOOR

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P

XO 2B

COMMAND CONFERENCE ROOM 2B

PLATOON 2B-A

PLATOON 2B-B

CORR

232B

PLATOON 2B-C

PLATOON 2B-D

CORR

232B

SECURE STORAGE 2B

CORR

232B

UNIT STORAGE 2B-3-1

220-1

CORR

232B

UNIT STORAGE 2B-2

CORR

244B

UNIT STORAGE 2B-1

CORR

244B

CLASSROOM 2B

CORR

244B

CLASSROOM 2A

CORR

244B

UNIT STORAGE 2A-3

CORR

244B

UNIT STORAGE 2A-2

CORR

244B

UNIT STORAGE 2A-1

CORR

201B

SECURE STORAGE 2A

CORR

201B

PLATOON 2A-D

PLATOON 2A-C

CORR

201B

PLATOON 2A-B

PLATOON 2A-A

COMMAND CONFERENCE ROOM 2A

XO 2A

1 SGT 2A

COMMANDER 2A

COMMAND OPEN OFFICE

COMMAND STORAGE 2A

M

CC

S

C

S

C

C

M

C

M

CC

M

CC

M

CC

M

CC

M

CC

S

C

C

S

C

S

C

C

M

C

S

C

S

C

C

M

C

S

C

C

M

C

S

C

S

C

C

M

C

C

M

C

M

C

S

C

S

C

M

C

S

C

S

C

C

M

C

C

M

C

S

C

S

C

C

M

C

C

C

M S

C

S

C

C

M

C

C

S

C

S

C

C

M

C

S

C

C

M S

C

S

C

C

M

C

C

M

C

S

C

S

C

C

M

C

C

M

C

S

C

S

C

C

M

C

S

C

S

C

C

M

C

S

C

C

M

C

C

M

C

C

C

M

C

C

M

C

S

C

S

C

C

M

C

C

M

C

C

M

C

C

M

C

S

C

S

C

C

M

C

C

M

C

M

C

H

C

FOR

CONT.

ON THIS

SHEET,

SEE

I

I FOR

CONT.

ON THIS

SHEET,

SEE

J

J

BACK TO FACP

BACK TO FACP

BACK TO FACP

09/30/2016 Expiration Date of the License

AI

NROFICF

E A

N

OITCETORP

ERI

F

LAO

S

T T

R E

S R

ED

PROFESS IONAL

EN

G

IN

E

E

RS

A M

U

E

S. DANN

A W

A Y

LE

T

I G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

N O

S C

A L E

/2

/2

:4 :0

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

FA605

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

F

IR

E A

L A

R M

/M A

S S

N O

T

IF

IC

A

T I O

N R

IS

E

R D

IA

G

R A

M

S E

C O

N D

F L O

O R

C O

N T

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F A

NO SCALE

A2

FIRE ALARM / MASS NOTIFICATION RISER DIAGRAM - SECOND FLOOR CONT.

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P

301A

LANAI

300A

SECURE STORAGE 3A

WOMEN'S RESTROOM

UNIT STORAGE 3A

LANAI

300A

UNIT STORAGE 3A

STORAGE 3A

CORR

RECYCLE 3A

ELEC 3A

MECHANICAL ROOM 3A

TELECOM ROOM 3A

GYM

LANAI

300A

GYM

LANAI

300B

GYM

STAIR

TELECOM 3B

LANAI

300B

MECHANICAL ROOM 3B

ELEC 3B

CORR

330A

LANAI

300B

UNIT STORAGE 3B

STORAGE 3B

WOMEN'S RESTROOM

SECURE STORAGE 3B

CORR

TRAINING ROOM 3B

COMMAND OPEN OFFICE

COMMANDER 3B

COMMAND STORAGE 3B

1 SGT 3B

XO 3B

COMMAND CONFERENCE ROOM 3B

COMMAND OPEN OFFICE

CORR

330B

PLATOON 3B-A

PLATOON 3B-B

CORR

330B

PLATOON 3B-C

PLATOON 3B-D

CORR

330B

COMM STORAGE 3B

NBC STORAGE 3B

LANAI

300B

LOC

30 60

M

PWP

F

X 3

30 30

M

M

CC

M

M

30 60

M

C C

M

M

30 30

M

M

M S

M

M

S

WP

F

M

M

M

WP

F

M

P

M

30 60

M

LOC

WFVS

C C

M

60 15

M

M

M

M

C

C

WP

F

M

C

C

M

C

C

S

C

S

C

C

M

C

M

C

C

M

C

M

C

C

M

C

C

S

C

S

C

C

M

C

S

C

S

C

S

C

C

M

C

C

M

C

C

M

C

C

M

C

C

M

C

C

M

C

S

C

C

M

C

C

M

C

M

FOR

CONT.

ON THIS

SHEET,

SEE

K

K FOR

CONT.

ON THIS

SHEET,

SEE

L

L FOR

CONT.

SEE

M

BACK TO FACP

FEP

1P, 20A

SP

FEP

1P, 20A

SP

TO FACP

ON FIRST

FLOOR

ON

SHEET

FA607

LANAI

300A

WP

F

X 3

BACK TO FACP

BACK TO FACP

WP 110

110WP

M

C

AOM

P, AHU-5

R SHUTDOWN AHU-5

AOM

P, AHU-6

R SHUTDOWN AHU-6

M

WP

110WP

M

WP

110WP

M

WP

75WP

M

WP

75WP

M

WP

110WP

M

WP 60

M

WP

110WP

M

WP

09/30/2016 Expiration Date of the License

AI

NROFICF

E A

N

OITCETORP

ERI

F

LAO

S

T T

R E

S R

ED

PROFESS IONAL

EN

G

IN

E

E

RS

A M

U

E

S. DANN

A W

A Y

LE

T

I G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

N O

S C

A L E

/2

/2

:4 :0

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

FA606

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

F

IR

E A

L A

R M

/M A

S S

N O

T

IF

IC

A

T I O

N R

I S E

R D

IA

G

R A

M

T H

IR

D

F L O

O R

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F A

NO SCALE

A2

FIRE ALARM / MASS NOTIFICATION RISER DIAGRAM - THIRD FLOOR

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P

330B

OFFICE

MEN'S LATRINE & SHOWER

GYM

MEN'S LATRINE & SHOWER

JAN

CORR

301B

NBC STORAGE 3A

COMM STORAGE 3A

CORR

301B

PLATOON 3A-D

PLATOON 3A-C

CORR

301B

PLATOON 3A-B

PLATOON 3A-A

CORR

301B

COMMAND CONFERENCE ROOM 3A

XO 3A

1 SGT 3A

COMMAND STORAGE 3A

COMMANDER 3A

COMMAND OPEN OFFICE

TRAINING ROOM 3A

C

M

C

C

M

C

30,WP

30,WP

M

30,WP

30,WP

M

30,WP

30,WP

M

MS

M

M

MS

30, WP

30, WP

M

30, WP

15, WP

M

M

C

M

C

C

M

C

C

M

C

C

M

C

C

M

C

C

M

C

M

C

C

M

C

C

M

C

C

M

C

S

C

S

C

C

M

C

S

C

S

C

C

M

C

C

M

C

M

C

M

C

C

M

C

C

M

C

M FOR

CONT.

ON THIS

SHEET,

SEE

N

N

BACK TO FACP

BACK TO FACP

BACK TO FACP

C

M

C

09/30/2016 Expiration Date of the License

AI

NROFICF

E A

N

OITCETORP

ERI

F

LAO

S

T T

R E

S R

ED

PROFESS IONAL

EN

G

IN

E

E

RS

A M

U

E

S. DANN

A W

A Y

LE

T

I G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

N O

S C

A L E

/2

/2

:4 :0

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

FA607

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

F

IR

E A

L A

R M

/M A

S S

N O

T

IF

IC

A

T I O

N R

I S E

R D

IA

G

R A

M

T H

IR

D

F L O

O R

C O

N T

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F A

NO SCALE

A2

FIRE ALARM / MASS NOTIFICATION RISER DIAGRAM - THIRD FLOOR CONT.

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P

UP UP

FD

FD

FD

FD

FD

FD

FD

FD

FD

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

A

B

C

D

E

FCV

PROVIDE WET PIPE FIRE SPRINKLER

PROTECTION WITHIN THIS

BOUNDARY

FLOOR CONTROL VALVE,

SEE DETAIL C2

FX501

FIRE SPRINKLER RISER

UP TO SECOND FLOOR,

SEE FOR CONT.A1

FX101

SEE CIVIL FOR CONTINUATION

VENDING

100D

LANAI

100B

LANAI

100A

RECYCLE 1A

ELEC 1B

COMMANDER 1B

CSM 1B

ARMS VAULT #3B

ARMS VAULT #2B

DUTY OFFICER 1A

MECHANICAL 1A

ARMS VAULT #2A

S-2 OFFICE 1A

STORAGE 1A-2

FRSA

RE-ENLIST 1A

STORAGE 1A-1

FIRE RISER ROOM

S-3 CONF

S-1 OFFICE

COMMAND SUPPLY 1B

158CORR

161A

SR HR SGT 1B

DUTY OFFICER 1B

S-4 OFFICE 1B

CENTRAL FILES

CSM 1A

XO 1A

S-3 OPS SGT 1A

S-6 OFFICE 1A

ELEC 1A

TELECOM 1A

S-3 OFFICE 1A

S-3 CONF

S-3 OFFICE 1A

COMMAND CONF ROOM 1B

XO 1B

CMD OPEN OFFICE

STORAGE 1B

TELECOM 1B

MECHANICAL ROOM 1B

COPY

S-2 OFFICE 1A

CHAPLAIN ASST

CHAPLAIN

S-6 OFFICE 1A

OPEN OFFICE 1A

S-3 OPS SGT 1A

CORR

161B

SECURE DOCUMENT'S 1A

SECURE DOCUMENTS 1A

S-1 OFFICER 1A

COMMAND CONFERENCE

S-4 OFFICE 1A

CENTRAL FILES 1A

CORR

101A

COMMANDER 1A

CMD OPEN OFFICE

COMMAND TOILET 1A

COMMAND SUPPLY 1A

OPEN OFFICE 1B

SR HR SGT 1A

CORR

101B

ARMS VAULT #3A

REMOTE FIRE

DEPARTMENT

CONNECTION

CHECK

VALVE

FIRE SPRINKLER RISER,

SEE DETAIL A2

FX501

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

A

B

C

D

E

F C

V

PROVIDE WET PIPE FIRE SPRINKLER

PROTECTION WITHIN THIS

BOUNDARY

FLOOR CONTROL VALVE,

SEE DETAIL C2

FX501

FIRE SPRINKLER RISER

DN TO FIRST FLOOR, UP

TO THIRD FLOOR,

COMMANDER 2A

LANAI

200B

LANAI

200A

NBC STORAGE 2A

UNIT STORAGE 2A-1

XO 2A

PLATOON 2A-D

PLATOON 2A-C

PLATOON 2A-B

PLATOON 2A-A

COMMAND CONFERENCE ROOM 2A

RECYCLE 2A

ELEC 2A

TELECOM 2A

MECHANICAL ROOM 2A

COMM STORAGE 2A

STORAGE 2A-2

CORR

201B

COMMAND OPEN OFFICE

COMMAND STORAGE 2A

PLATOON 2B-D

PLATOON 2B-C

PLATOON 2B-B

PLATOON 2B-A

COMMAND CONFERENCE ROOM 2B

UNIT STORAGE 2B-2

UNIT STORAGE 2B-1

CLASSROOM 2B

CLASSROOM 2A

UNIT STORAGE 2A-3

UNIT STORAGE 2A-2

SECURE STORAGE 2B

UNIT STORAGE 2B-3

1 SGT 2B

XO 2B

COMMAND STORAGE 2B

COMMAND OPEN OFFICE

MECHANICAL ROOM 2B

TELECOM 2B

STORAGE 2B-2

ELEC 2B

RECYCLE 2B

CORR

201A

CORR

COMM STORAGE 2B

CORR

232A

TRAINING ROOM 2B

STORAGE 2B-3

CORR

238NBC STORAGE 2B

CORR

244A

CORR

232B

TRAINING ROOM 2A

STORAGE 2A-1

1 SGT 2A

SECURE STORAGE 2A

CORR

MEN'S LATRINE & SHOWER

CLASSROOM 2C

JAN

CORR

244B

WOMEN'S LATRINE & SHOWER

COMMANDER 2B

SPRINKLER HAZARD TABLE

SYMBOL SPRINKLER HAZARD CLASSIFICATION

HC-1

HC-2

MISCELLANEOUS STORAGE <= 10'-0"

09/30/2016 Expiration Date of the License

AINROFICF

E

A

NOITCETORPERI

F

LAO

ST

T

R E

S

RED

PROFESS IONAL

ENG

IN

E E

RS

A

M U

E

S. DANNAW

AY

LE

T

I G

No. 1130

SHEET

IDENTIFICATION

1 2 3 4 5

D R

A W

N B

Y

D E

S

IG

N B

Y

S B

M T

B Y

S

IZ

E

F

IL

E N

A M

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

C K

D B

Y

US Army Corps of Engineers ® x

D

C

B

A

F

IL

E N

U M

B E

R

P L

O T

S C

A L E

P L

O T

D A

T E

SHEET OF

A s i n d ic a te d

/2

/2

:4 :2

A

M

S C

H O

F

IE

L D

B A

R R

A C

K S

H

A W

A

II

J U

L

A

HONOLULU DISTRICT

R O

J P

S S

D

FX101

H O

N O

L U

L U

D

IS

T R

IC

T

F T

S

H A

F T

E R

H

A W

A

II

D E

S

IG

N B

R A

N C

H B

U

IL

D

IN

G

F T

S H

A F

T E

R H

I

-5

R O

F

IR

S T

A N

D S

E C

O N

D F

L O

O R

F

IR

E

S P

R

IN

K L E

R P

L A

N

F Y

P K

G A

- 0 R

E P

A

IR

B U

IL

D

I N G

Q

U A

D D

F X

1/16" = 1'-0" C1

FIRST FLOOR - FIRE SPRINKLER PLAN

1/16" = 1'-0" A1

SECOND FLOOR - FIRE SPRINKLER PLAN

SCALE:

0 16' 32'

1/16" = 1' - 0"

16' 32'

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P

FDFD

FD

FD

FD

FD

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

A

B

C

D

E

F C

V

PROVIDE WET PIPE FIRE SPRINKLER

PROTECTION WITHIN THIS

BOUNDARY

FLOOR CONTROL VALVE,

SEE DETAIL C2

FX501

FIRE SPRINKLER RISER

DN TO SECOND FLOOR

COMMANDER 3B

COMMANDER 3A

XO 3B

1 SGT 3B

GYM

LANAI

300A

LANAI

300B

PLATOON 3B-B

PLATOON 3B-C

PLATOON 3B-D

COMM STORAGE 3B

1 SGT 3A

COMMAND STORAGE 3A

XO 3A

COMM STORAGE 3A

PLATOON 3A-D

PLATOON 3A-C

PLATOON 3A-B

PLATOON 3A-A

COMMAND CONFERENCE ROOM 3A

STORAGE 3A

UNIT STORAGE 3A

RECYCLE 3A

TELECOM ROOM 3A

CORR

301B

E…