BUILDING CODE SUMMARY:
INTERNATIONAL CODES, INTERNATIONAL CODE COUNCIL:
IBC INTERNATIONAL BUILDING CODE, 2012 EDITION, EXCLUDING CHAPTER 10 MEANS
OF EGRESS REQUIREMENTS
NATIONAL FIRE CODES, NATIONAL FIRE PROTECTION ASSOCIATION STANDARDS INCLUDING:
NFPA 1 UNIFORM FIRE CODE, 2012
NFPA 10 PORTABLE FIRE EXTINGUISHERS, 2013
NFPA 13 INSTALLATION OF SPRINKLER SYSTEMS, 2013
NFPA 24 PRIVATE FIRE SERVICE MAINS, 2013
NFPA 70 NATIONAL ELECTRICAL CODE, 2014
NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE, 2013
NFPA 101 LIFE SAFETY CODE, 2012
UNIFIED FACILITIES CRITERIA:
UFC 1-200-01 GENERAL BUILDING REQUIREMENTS, 1 JULY 2013, WITH CHANGE 1, 1 SEPTEMBER 2013 UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES, 26 SEPTEMBER 2006, WITH CHANGE 3, 1 MARCH 2013
UFC 4-021-01 MASS NOTIFICATION SYSTEM, 9 APRIL 2008 WITH CHANGE 1, JANUARY 2010
PROJECT ADDRESS: SCHOFIELD BARRACKS, OAHU, HAWAII
PROJECT DESCRIPTION: REPAIR BUILDING 449, QUAD D
OCCUPANCY IBC OCCUPANCY NFPA OCCUPANCY
CONSTRUCTION:
ALLOWABLE: TYPE I-A, I-B, II-A, II-B
PROVIDED: TYPE II-B
FIRE RESISTANCE REQUIREMENTS:
BUILDING ELEMENT MATERIAL REQUIRED RATING PROVIDED RATING SECTION
STRUCTURAL FRAME NON-COMBUSTIBLE 0 HR 0 HR TABLE 601
BEARING WALLS - EXTERIOR NON-COMBUSTIBLE 0 HR 0 HR TABLE 601
BEARING WALLS - INTERIOR NON-COMBUSTIBLE 0 HR 0 HR TABLE 601
NONBEARING WALLS - EXTERIOR NON-COMBUSTIBLE 0 HR 0 HR TABLE 602
NONBEARING WALLS - INTERIOR NON-COMBUSTIBLE 0 HR 0 HR TABLE 601
SHAFT ENCLOSURES NON-COMBUSTIBLE 1 HR 1 HR NFPA 101, 7.2.2.6.3
FLOORS & FLOOR-CEILINGS 0 HR 0 HR TABLE 601
ROOF 0 HR 0 HR TABLE 601
CONSTRUCTION REQUIREMENTS: FOR GENERAL STRUCTURAL DESIGN CRITERIA SEE STRUCTURAL SHEET
ACTS AND REGULATIONS:
ADA/ABA AMERICANS WITH DISABILITIES ACT ACCESSIBILITY AND ARCHITECTURAL BARRIERS ACT
ACCESSIBILITY GUIDELINES JULY 23.2004
1ST FLOOR
OCCUPANCY ALLOWABLE AREA MODIFIED AREA ACTUAL AREA
BUILDING HEIGHT AND NUMBER OF STORIES:
BUILDING: ALLOWABLE: PROVIDED:
BLDG 449 75 FT, 3 STORIES 54 FT, 3 STORIES
EXPOSURE PROTECTION:
BUILDING FIRE SEPARATION REQUIRED FOR UNRATED WALL : PROVIDED:
BLDG 449 10FT >10 FT
OCCUPANT LOAD FACTOR AND TOTAL CALCULATED LOAD:
OCCUPANT LOAD FACTOR
BUSINESS USE - 100 SF / PERSON
TOTAL CALCULATED LOAD
FIRST FLOOR: BUSINESS & STORAGE
LIFE SAFETY CODE SUMMARY:
NUMBER OF EXITS:
BUILDING: REQUIRED: PROVIDED:
1ST FLOOR 2*
2ND FLOOR 3*
DISCHARGE FROM EXITS:
REQUIRED:
EXITS FROM THE FIRST FLOOR DISCHARGE DIRECTLY TO THE OUTSIDE, TO WALKWAYS
THAT LEAD TO THE PUBLIC WAY. FROM THE SECOND AND THIRD FLOORS CORRIDORS
DISCHARGE TO AN EXTERIOR LANAI WITH OUTSIDE EXIT STAIRS THAT DISCHARGE
DIRECTLY TO THE OUTSIDE ON THE FIRST FLOOR.
PROVIDED:
EXITS SHALL TERMINATED DIRECTLY, AT A PUBLIC WAY OR AT EXTERIOR EXIT DISCHARGE.
ASSEMBLY USE - 15 SF / PERSON
BUSINESS B NEW BUSINESS (CHAPTER 38)
ASSEMBLY A-3 NEW ASSEMBLY (CHAPTER 12)
SECOND FLOOR: BUSINESS & STORAGE
B 23,000 SF ------ -------
STORAGE S-1 STORAGE (CHAPTER 42)
S-1 17,500 SF ------ ------
2ND AND 3RD FLOORS
TOTAL BUILDING:
TOTAL ALLOWABLE ACTUAL AREA
A-3 106,875 SF 66,450 SF
BUILDING SEPARATION
NORTH:
EAST:
SOUTH:
WEST:
29 FT WAIANAE AVENUE
22 FT ACCESS ROAD
15 FT ACCESS ROAD AND PARKING
22 FT ACCESS ROAD
NON-COMBUSTIBLE
CLASSROOMS - 20 SF / PERSON
EXERCISE ROOM W/O EQUIPMENT - 15 SF / PERSON
- 290 PEOPLE
- 348 PEOPLE
THIRD FLOOR: BUSINESS, STORAGE & ASSEMBLY - 514 PEOPLE
MINIMUM FIRE PROTECTION RATINGS FOR OPENING PROTECTIVES IN FIRE RESISTANCE - RATED ASSEMBLES
WALLS AND PARTITIONS FIRE DOOR ASSEMBLES
NO RATING 20 MINIUTESMOKE PARTITIONS
3RD FLOOR 4* 4
CAPACITY OF MEAN OF EGRESS:
BUILDING: REQUIRED CAPACITY: PROVIDED CAPACITY:
1ST FLOOR 290 PEOPLE
2ND FLOOR 348 PEOPLE
3RD FLOOR 514 PEOPLE 587 PEOPLE
1120 PEOPLE
587 PEOPLE
MEAN OF EGRESS:
TRAVEL DISTANCE
ALLOWED:
TRAVEL DISTANCE
PROVIDED:
1ST FLOOR 300 FT 124 FT
2ND FLOOR 300 FT 207 FT
3RD FLOOR 250 FT 250 FT
COMMON PATH
OF TRAVEL
ALLOWED:
COMMON PATH
OF TRAVEL
PROVIDED:
1ST FLOOR 100 FT 68 FT
2ND FLOOR 100 FT 70 FT
3RD FLOOR 75 FT 53 FT
DEAD END
CORRIDOR
ALLOWED:
DEAD END
CORRIDOR
PROVIDED:
1ST FLOOR 50 FT 0 FT
2ND FLOOR 50 FT 0 FT
3RD FLOOR 20 FT 15 FT
ALLOWABLE AREA:
* ADDITIONAL EXITS WILL BE NEEDED TO SATISFY CAPACITY REQUIREMENTS
THE NFPA 101 LIFE SAFETY ANALYSIS IS BASED ON THE RULES FOR MIXED OCCUPANCIES (NFPA 101, 6.1.14.3)
THIS ANALYSIS IS BASED ON THE IBC RULES FOR NON-SEPARATED OCCUPANCIES.
35,625 SF 22,150 SFA-3 9,500 SF
-STORAGE USE 300 SF / PERSON
B 23,000 SF ------ -------
S-1 17,500 SF ------ ------
35,625 SF 22,150 SFA-3 9,500 SF
EXERCISE ROOM W/ EQUIPMENT - 50 SF / PERSON
EXTERIOR WALL OPENINGS 0 HR 0 HR TABLE 705.8
NON-COMBUSTIBLE
09/30/2016 Expiration Date of the License
AINROFICF
E
A
NOITCETORPERI
F
LAO
ST
T
R E
S
RED
PROFESS IONAL
ENG
IN
E E
RS
A
M
UE
S. DANNAW
AY
LET
I
G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
/2
/2
:4 :4
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
R
T A
HONOLULU DISTRICT
R O
J P
S S
D
F-001
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
C O
D E
I N
F O
R M
A T
IO
N
S H
E E
T
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F -0
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
S 6"
A V E N U EW A I A N A E
E 1622600
N
U/ E
U/E
U/EU/E
U/E
U/E
D1 2"
D1 2"
D48"
D18"
D
D8" D36"D36"D10" D12"
D 12"D
12"
D12"
D24"
D 18"
D24"
S10"
S10"
S8
S8 s
0°
5.9
310° 21' 32" 679.95
3/4"G R
3/4"G
R 3/4"G
3/ 4" G
W4"
W8
E/W12 E/W12 E/W12
UP
NO PARKINGNO PARKINGNO PARKINGNO PARKING
N O
P A R K
IN
G
N O
P A R K
IN
G
NO PARKING NO PARKING NO PARKING NO PARKING
D
D
D
S
S
S
S
S
S
S
S
S
W
W
W
W
W
W W
W
W
WW
W
WW
W
W
W
UP UP
FD
FD
FD
FD
FD
FD
FA FA FA FA FA FA
FH1
FH2
350'-0" FROM FH1
F R
O M
F H
60'-0" FROM FIRE HYDRANT TO
FIRE DEPARTMENT CONNECTION
FIRE DEPARTMENT CONNECTION
20'-0" TO
PAVED ACCESS
BACKFLOW PREVENTER
50'-0" FROM BUILDING
FIRE TRUCK ACCESS ROUTE
BUILDING SEPARARTION REQUIREMENT
BUILDING CODE SITE LEGEND
FIRE HYDRANT
FA
FIRE DEPARTMENT CONNECTION
09/30/2016 Expiration Date of the License
AI
NROFICF
E A
N
OITCETORP
ERI
F
LAO
S
T T
R E
S R
ED
PROFESS IONAL
EN
G
IN
E
E
RS
A M
U
E
S. DANNA
W
AY
LE
T
I G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
A s i n d ic a te d
/2
/2
:4 :5
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
F-002
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
B U
IL
D
IN
G
S
IT
E C
O D
E P
L A
N
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F -0
1" = 20'-0"
BUILDING SITE CODE PLAN
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P
UP UP
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
A
B
C
D
E
S S
SS
SS
S
S
S
S
S
S
S
S
S68 /1
30/124
/4
145/NA
20/117
25/113
145/NA
20/115
/1
VENDING
100D
LANAI
100B
LANAI
100A
RECYCLE 1A
ELEC 1B
COMMANDER 1B
CSM 1B
ARMS VAULT #3B
ARMS VAULT #2B
DUTY OFFICER 1A
MECHANICAL 1A
ARMS VAULT #2A
S-2 OFFICE 1A
STORAGE 1A-2
FRSA
RE-ENLIST 1A
STORAGE 1A-1
FIRE RISER ROOM
S-3 CONF
S-1 OFFICE
COMMAND SUPPLY 1B
CORR
161A
SR HR SGT 1B
DUTY OFFICER 1B
S-4 OFFICE 1B
CENTRAL FILES
CSM 1A
XO 1A
S-3 OPS SGT 1A
S-6 OFFICE 1A
ELEC 1A
TELECOM 1A
S-3 OFFICE 1A
S-3 CONF
S-3 OFFICE 1A
COMMAND CONF ROOM 1B
XO 1B
CMD OPEN OFFICE
STORAGE 1B
TELECOM 1B
MECHANICAL ROOM 1B
COPY
S-2 OFFICE 1A
CHAPLAIN ASST
CHAPLAIN
S-6 OFFICE 1A
OPEN OFFICE 1A
S-3 OPS SGT 1A
CORR
161B
SECURE DOCUMENT'S 1A
SECURE DOCUMENTS 1A
S-1 OFFICER 1A
COMMAND CONFERENCE
S-4 OFFICE 1A
CENTRAL FILES 1A
CORR
101A
COMMANDER 1A
CMD OPEN OFFICE
COMMAND TOILET 1A
COMMAND SUPPLY 1A
OPEN OFFICE 1B
SR HR SGT 1A
CORR
101B
ARMS VAULT #3A
SS S S S
SS
S
S
SS
S
S
S
S
S
S
S S
S
S
S
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
A
B
C
D
E
S S S S
S S
S
SS
S S
S
S
S
S
S
S
S S S
S
S
S S
S
S
S
S
S
S
S
SS
S
S S
S
S
70/147
87/146
34/207
87/146
50/131
87/146
/1
87/146
/9
TRAVEL DISTANCES ARE MEASURED
TO THE GROUND FLOOR IN
ACCORDANCE WITH NFPA 101, 7.6.3
COMMANDER 2A
LANAI
200B
LANAI
200A
NBC STORAGE 2A
UNIT STORAGE 2A-1
XO 2A
PLATOON 2A-D
PLATOON 2A-C
PLATOON 2A-B
PLATOON 2A-A
COMMAND CONFERENCE ROOM 2A
RECYCLE 2A
ELEC 2A
TELECOM 2A
MECHANICAL ROOM 2A
COMM STORAGE 2A
STORAGE 2A-2
CORR
201B
COMMAND OPEN OFFICE
COMMAND STORAGE 2A
PLATOON 2B-D
PLATOON 2B-C
PLATOON 2B-B
PLATOON 2B-A
COMMAND CONFERENCE ROOM 2B
UNIT STORAGE 2B-2
UNIT STORAGE 2B-1
CLASSROOM 2B
CLASSROOM 2A
UNIT STORAGE 2A-3
UNIT STORAGE 2A-2
SECURE STORAGE 2B
UNIT STORAGE 2B-3
1 SGT 2B
XO 2B
COMMAND STORAGE 2B
COMMAND OPEN OFFICE
MECHANICAL ROOM 2B
264TELECOM 2B
STORAGE 2B-2
ELEC 2B
RECYCLE 2B
CORR
201A
CORR
COMM STORAGE 2B
CORR
232A
TRAINING ROOM 2B
STORAGE 2B-3
CORR
NBC STORAGE 2B
CORR
244A
CORR
232B
TRAINING ROOM 2A
259 STORAGE 2A-1
1 SGT 2A
SECURE STORAGE 2A
CORR
CLASSROOM 2C
CORR
244B
COMMANDER 2B
S
S S S
S
S
SMOKE PARTITION
LEGEND
SYMBOL DESCRIPTION
S
EXIT PATH, COMMON PATH OF TRAVEL (FEET) /
TRAVEL DISTANCE (FEET)
COMMON PATH OF TRAVEL
XX / XX
FIRE EXIT
XX / XX OCCUPANT LOAD / EXGRESS CAPACITY
DEAD END (FEET)
XX
OCCUPANCY LEGEND
SYMBOL DESCRIPTION
B, BUSINESS
S-1, STORAGE
09/30/2016 Expiration Date of the License
AINROFICF
E
A
NOITCETORPERI
F
LAO
ST
T
R E
S
RED
PROFESS IONAL
ENG
IN
E E
RS
A
M
UE
S. DANNAW
AY
LET
I
G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
A s i n d ic a te d
/2
/2
:4 :0
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
F-101
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
F
IR
S T
A N
D S
E C
O N
D F
L O
O R
L
IF
E
S A
F E
T Y
C O
D E
P L A
N
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F -1
SCALE:
0 16' 32'
1/16" = 1' - 0"
16' 32'
1/16" = 1'-0" C1
FIRST FLOOR - LIFE SAFETY CODE PLAN
1/16" = 1'-0" A1
SECOND FLOOR - LIFE SAFETY CODE PLAN
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P
FDFD
FD
FD
FD
FD
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
A
B
C
D
E
S
S
S
S S
S
SS
S
S S
S S
S
S
SS
S S
S
S
S
SS
129/146
/1
73 50 /2
129/146
0/
129/146 129/146
/1
27/176
TRAVEL DISTANCES ARE MEASURED TO
THE GROUND FLOOR IN ACCORDANCE
WITH NFPA 101, 7.6.3
COMMANDER 3B
COMMANDER 3A
XO 3B
1 SGT 3B
GYM
LANAI
300A
LANAI
300B
PLATOON 3B-B
PLATOON 3B-C
PLATOON 3B-D
COMM STORAGE 3B
1 SGT 3A
COMMAND STORAGE 3A
XO 3A
COMM STORAGE 3A
PLATOON 3A-D
PLATOON 3A-C
PLATOON 3A-B
PLATOON 3A-A
COMMAND CONFERENCE ROOM 3A
STORAGE 3A
UNIT STORAGE 3A
RECYCLE 3A
TELECOM ROOM 3A
CORR
301B
ELEC 3A
COMMAND CONFERENCE ROOM 3B
PLATOON 3B-A
NBC STORAGE 3B
STORAGE 3B
MECHANICAL ROOM 3B
MECHANICAL ROOM 3A
CORR
STAIR
TELECOM 3B
OFFICE
ELEC 3B
COMMAND STORAGE 3B
NBC STORAGE 3A
UNIT STORAGE 3B
TRAINING ROOM 3A
CORR
330B
CORR
301A
COMMAND OPEN OFFICE
TRAINING ROOM 3B
COMMAND OPEN OFFICE
CORR
SECURE STORAGE 3A
SECURE STORAGE 3B
CORR
330A
S S
S
S S
S S
S
S
S
S
S
SMOKE PARTITION
LEGEND
SYMBOL DESCRIPTION
S
EXIT PATH, COMMON PATH OF TRAVEL (FEET) /
TRAVEL DISTANCE (FEET)
COMMON PATH OF TRAVEL
XX / XX
FIRE EXIT
XX / XX OCCUPANT LOAD / EXGRESS CAPACITY
DEAD END (FEET)
XX
OCCUPANCY LEGEND
SYMBOL DESCRIPTION
B, BUSINESS
S-1, STORAGE
A-3, ASSEMBLY
16 17
C
D
09/30/2016 Expiration Date of the License
AINROFICF
E
A
NOITCETORPERI
F
LAO
ST
T
R E
S
RED
PROFESS IONAL
ENG
IN
E E
RS
A
M
UE
S. DANNAW
AY
LET
I
G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
A s i n d ic a te d
/2
/2
:4 :0
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
F-102
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
T H
IR
D
F L O
O R
L
IF
E
S A
F E
T Y
C O
D E
P L A
N
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F -1
SCALE:
0 16' 32'
1/16" = 1' - 0"
16' 32'
1/16" = 1'-0" C1
THIRD FLOOR - LIFE SAFETY CODE PLAN
1/8" = 1'-0"
LOFT - LIFE SAFETY CODE PLAN
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
A
B
C
D
E
F F
F A
C P
F F
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
A
B
C
D
E
F F F F
P
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
A
B
C
D
E
F F
I
F F
09/30/2016 Expiration Date of the License
AI
NROFICF
E A
N
OITCETORP
ERI
F
LAO
S
T T
R E
S R
ED
PROFESS IONAL
EN
G
IN
E
E
RS
A M
U
E
S. DANNA
W
AY
LE
T
I G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
/1
/2
/2
:4 :0
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
FD101
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
F
IR
S T
S
E C
O N
D A
N D
T H
IR
D
F L O
O R
F
IR
E
A L
A R
M D
E M
O L
IT
IO
N
P L A
N
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F D
1/16" = 1'-0" C1
FIRST FLOOR FIRE ALARM DEMOLITION PLAN
1/16" = 1'-0" B1
SECOND FLOOR FIRE ALARM DEMOLITION PLAN
1/16" = 1'-0" A1
THIRD FLOOR FIRE ALARM DEMOLITION PLAN NOTE:
DEVICE LOCATIONS ARE PROVIDED FOR BIDDING PURPOSES ONLY. ACTUAL DEVICE LOCATIONS AND
QUANTITIES ARE TO BE FIELD VERIFIED. DEMOLISH ALL EXISTING FIRE ALARM DEVICES INCLUDING
CONDDUIT AND WIRING.
SCALE:
0 16' 32'
1/16" = 1' - 0"
16' 32'
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P
FA
FTR
LOC
FACP
WF
FEP
DESCRIPTION
24 VOLT RELAY 24
MANUAL DOUBLE-ACTION PULL STATION
ALARM PRESSURE SWITCH
SYMBOL
FIRE ALARM RACEWAY
COMBINATION FIRE ALARM INTERFACE/TRANSMITTER
TAMPER SWITCH
LOCAL OPERATING CONSOLE PANEL
FIRE ALARM/MASS NOTIFICATION SYSTEM CONTROL PANEL
WALL MOUNTED FIRE ALARM/MASS NOTIFICATION SPEAKER. SPEAKER WATT TAP SHALL BE SET TO 1/2 WATT UNLESS
OTHERWISE INDICATED ON THE DRAWINGS.
ABOVE FINISH FLOORAFF
PHOTOELECTRIC SYSTEM SMOKE DETECTOR
WP WEATHERPROOF
TYP TYPICAL
ADDRESSABLE OUTPUT MODULE
ADDRESSABLE INPUT MODULE
BOOSTER POWER SUPPLY
WATER FLOW SWITCH
FIRE PROTECTION SYMBOLS AND ABBREVIATIONS
ELEVATOR PHOTOELECTRIC SYSTEM SMOKE DETECTOR
WALL MOUNTED VISUAL DEVICE WITH CLEAR COLOR LENS WITH MARKINGS "FIRE", CANDELA RATING AS INDICATED ON THE DRAWINGS.
ANT FIRE ALARM ANTENNA
XX
VS
PS
F
AIM
AOM
R
P
P/E
SURGE PROTECTORSP
S
CEILING MOUNTED FIRE ALARM/MASS NOTIFICATION SPEAKER. SPEAKER WATT TAP SHALL BE SET TO 1/2 WATT UNLESS
OTHERWISE INDICATED ON THE DRAWINGS.S
C
C
XX
WALL MOUNTED COMBINED AUDIO/VISUAL DEVICE WITH CLEAR COLOR LENS WITH MARKINGS "FIRE", CANDELA RATING AS INDICATED ON THE DRAWINGS. SPEAKER WATT TAP TO BE SET TO 1/2 WATT UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
CEILING MOUNTED COMBINED AUDIO/VISUAL DEVICE WITH CLEAR COLOR LENS WITH MARKINGS "FIRE", CANDELA RATING AS INDICATED ON THE DRAWINGS. SPEAKER WATT TAP TO BE SET TO 1/2 WATT UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
XX
XX
C
XX
M
M
WALL MOUNTED COMBINED AUDIO/VISUAL DEVICE WITH AMBER COLOR LENS WITH MARKINGS "ALERT", CANDELA RATING AS INDICATED ON THE DRAWINGS. SPEAKER WATT TAP TO BE SET TO 1/2 WATT UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
CEILING MOUNTED COMBINED AUDIO/VISUAL DEVICE WITH AMBER COLOR LENS WITH MARKINGS "ALERT", CANDELA RATING AS INDICATED ON THE DRAWINGS. SPEAKER WATT TAP TO BE SET TO 1/2 WATT UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
CEILING MOUNTED VISUAL DEVICE WITH CLEAR COLOR LENS WITH MARKINGS "FIRE", CANDELA RATING AS INDICATED ON THE DRAWINGS.
XX
RATE COMPENSATION TYPE HEAT SENSOR
R/C
MTR MASS NOTIFICATION TRANSCEIVER
FCV FLOOR CONTROL VALVE
FIRE DEPARTMENT CONNECTION
CEILING MOUNTED VISUAL DEVICE WITH AMBER COLOR LENS WITH MARKINGS "ALERT", CANDELA RATING AS INDICATED ON THE DRAWINGS.
XX
M
DUCT SMOKE DETECTOR, AIR HANDLING UNIT
XX
WALL MOUNTED VISUAL DEVICE WITH AMBER COLOR LENS WITH MARKINGS "ALERT", CANDELA RATING AS INDICATED ON THE DRAWINGS.
XX
M
FIRE ALARM / MASS NOTIFICATION NOTES:
1. THE FIRE ALARM / MASS NOTIFICATION SYSTEM SHALL BE DESIGNED AND INSTALLED IN
ACCORDANCE WITH NFPA 72-2013, UFC 3-600-01, UFC 4-021-01 AND SPECIFICATION SECTION 28 31 76.
2. ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED OR FM APPROVED.
3. DEVICE LOCATIONS AND CONDUIT ROUTING ARE CONCEPTUAL. FINAL
QUANTITY AND LAYOUT SHALL BE IN ACCORDANCE WITH APPLICABLE
CODES, MANUFACTURER'S RECOMMENDATIONS, AND EQUIPMENT LISTINGS.
COORDINATE LOCATIONS WITH CEILING INSTALLATION AND OTHER DEVICES.
4. ALL FIRE ALARM CONDUIT SHALL BE 3/4" MINIMUM. ALL CONDUIT IN
FINISHED AREAS SHALL BE CONCEALED.
SYNCHRONIZE ALL VISUAL NOTIFICATION APPLIANCES. SYNCHRONIZE ALL
AUDIBLE NOTIFICATION APPLIANCES.
5.
THE FIRE ALARM SIGNAL SHALL BE A TEMPORAL THREE PATTERN TONE.6.
VISUAL NOTIFICATION APPLIANCES SHALL BE IN ACCORDANCE WITH NFPA 72.7.
SIGNALING LINE CIRCUITS SHALL BE CLASS A, INITIATING DEVICE
CIRCUITS SHALL BE CLASS A, NOTIFICATION APPLIANCE CIRCUITS SHALL BE
CLASS A.
8.
SMOKE DETECTORS SHALL BE LOCATED A MINIMUM OF 3 FEET FROM
SUPPLY AND RETURN AIR DIFFUSERS.
PROVIDE SIGNAGE AT THE FIRE ALARM CONTROL PANEL IDENTIFYING THE
POWER PANEL AND CIRCUIT.
10.
MASS NOTIFICATION TESTING SHALL INCLUDE INTELLIGIBILITY MEASUREMENTS. THE
CIS VALUE SHALL BE 0.80 OR HIGHER PER UFC 04-021-01.
9.
11.
PROVIDE A CABINET NEXT TO THE FIRE ALARM PANEL LABELED "FIRE ALARM
DOCUMENTS". THE BOX SHALL CONTAIN THE FINAL RECORD OF COMPLETION AND THE
FIRE ALARM AS-BUILT UPDATED APPROVED SHOP DRAWINGS.
12.
AUTOMATIC SPRINKLER SYSTEM NOTES:
1. THE SPRINKLER SYSTEM DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA 13-2013, UFC 3-600-01 AND SPECIFICATION SECTION 21 13 13.00 10. THE CONTRACTOR SHALL VERIFY THE LOCATION ALL SPRINKLER SYSTEM
COMPONENTS AND COORDINATE WITH THE VARIOUS TRADES.
2. ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED OR FM APPROVED.
3. AUTOMATIC SPRINKLER PROTECTION SHALL BE PROVIDED THROUGHOUT THE BUILDINGS.
4.
5. THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY DESIGNED IN ACCORDANCE WITH NFPA 13. SPRINKLER SYSTEM
DESIGN CRITERIA SHALL BE AS FOLLOWS:
WET PIPE SYSTEMS
ALL AREAS OF THE BUILDING EXCEPT AS NOTED BELOW:
OCCUPANCY HAZARD CLASSIFICATION: HC-1
DESIGN DENSITY: 0.10 GPM/SF
DESIGN AREA: 1,500 SF
SPRINKLER TYPE: QUICK RESPONSE TYPE, CORROSION RESISTANT IN EXTERIOR LANAIS
SPRINKLER TEMPERATURE: ORDINARY, EXCEPT INTERMEDIATE IN GYM
HOSE STREAM: 250 GPM (ACCOUNTED FOR IN ADJUSTED WATER SUPPLY)
MECHANICAL SPACES:
OCCUPANCY HAZARD CLASSIFICATION: HC-2
DESIGN DENSITY: 0.20 GPM/SF
DESIGN AREA: 2,500 SF
SPRINKLER TYPE: QUICK RESPONSE TYPE
SPRINKLER TEMPERATURE: INTERMEDIATE
HOSE STREAM: 250 GPM (ACCOUNTED FOR IN ADJUSTED WATER SUPPLY)
6. SPRINKLERS SHALL BE LOCATED IN THE CENTER OF CEILING TILES WHERE APPLICABLE. CORROSION RESISTANT SPRINKLERS SHALL
BE PROVIDED NEAR SHOWERS.
7. SPRINKLER PIPING SHALL COMPLY WITH NFPA 13, EXCEPT THAT COPPER AND PLASTIC PIPE SHALL NOT BE PERMITTED.
8. THE PIPE ROUTING AND SPRINKLER LOCATIONS ARE CONCEPTUAL. THE CONTRACTOR SHALL INSTALL THE SYSTEM IN ACCORDANCE WITH THE APPLICABLE CODES, MANUFACTURER'S RECOMMENDATIONS AND EQUIPMENT LISTINGS.
9. PIPING SHALL BE PROVIDED WITH EARTHQUAKE PROTECTION IN ACCORDANCE WITH NFPA 13 INCLUDING BRANCH LINE RESTRAINT.
10. ALL SPRINKLER PIPING IN FINISHED AREAS SHALL BE CONCEALED FROM VIEW.
11. ALL SPRINKLERS IN AREAS EXPOSED TO THE ELEMENTS SHALL BE CORROSION RESISTANT. ALL SPRINKLER PIPING SHALL BE PAINTED.
12. PROVIDE A PRESSURE RELIEF VALVE ON THE FIRE SPRINKLER RISER PER NFPA 13-2013.
WATER SUPPLY INFORMATION: AT THE BASE OF RISER.
STATIC PRESSURE: 59 PSI
RESIDUAL PRESSURE: 39 PSI
FLOW AT RESIDUAL PRESSURE: 521 GPM
13. PROVIDE SLEEVES THROUGH CONCRETE/MASONRY WALLS AND FLOORS. SLEEVES SHALL BE NOMINAL 2" LARGER THAN THE PIPE GOING THROUGH IT FOR PIPE SLEEVES 3-1/2" AND SMALLER, AND NOMINAL 4" LARGER THAN THE PIPE
GOING THROUGH IT FOR PIPE SLEEVE 4" AND LARGER.
14. PROVIDE LISTED SPRINKLER GUARDS IN ACCORDANCE WITH NFPA 13.
15. CONDUCT INSPECTIONS AND HYDROSTATIC TESTS IN ACCORDANCE WITH NFPA 13.
STORAGE ROOMS:
OCCUPANCY HAZARD CLASSIFICATION: MISCELLANEOUS STORAGE UP TO 10 FEET
DESIGN DENSITY: 0.20 GPM/SF
DESIGN AREA: 1,500 SF
SPRINKLER TYPE: QUICK RESPONSE TYPE
SPRINKLER TEMPERATURE: ORDINARY
HOSE STREAM: 250 GPM (ACCOUNTED FOR IN ADJUSTED WATER SUPPLY)
NFPA 13 DESIGN AREA REDUCTIONS BASED ON USE OF QUICK RESPONSE SPRINKLERS IS NOT PERMITTED.
THE WATER SUPPLY SHOWN HAS BEEN ADJUSTED FROM A HYDRANT FLOW TEST CONDUCTED BY S.S. DANNAWAY ASSOCIATES ON FOOTE AVENUE. THE ADJUSTED SUPPLY SHOWN ACCOUNTS FOR HOSE STREAM AND A 12 PSI LOSS THROUGH THE DOUBLE CHECK BACKFLOW PREVENTER . PRIOR TO THE PREPARATION OF SPRINKLER SHOP DRAWINGS, IF UTILITY IMPROVEMENTS ARE COMPLETED TO ADD FIRE HYDRANTS WITHIN THE QUAD COURTYARD, A FLOW TEST MAY BE PERFORMED BY THE CONTRACTOR IN ACCORDANCE WITH NFPA 291. A FIRE PROTECTION ENGINEER, OR AN ENGINEER
EXPERIENCED IN WATER FLOW TESTING MUST PERFORM OR WITNESS THE FLOW TEST.
ALL CANDELA VALUES SHOWN ARE CONCEPTUAL AND ARE THE MINIMUM UNDERATED
VALUES BASED ON THE DEVICE LOCATIONS SHOWN. IF THE MANUFACTURER'S DATA
REQUIRES THAT THE APPLIANCES BE DERATED. IT IS THE RESPONSIBILITY OF THE
CONTRACTOR TO PROVIDE STROBE COVERAGE BASED ON THE MANUFACTURER'S
REQUIRED DERATED VALUES AND SPACED IN ACCORDANCE WITH NFPA 72.
13.
CALCULATIONS SHALL INCLUDE A MINIMUM 10% CUSHION FROM THE DESIGN WATER SUPPLY BASED ON A WATER SUPPLY
DRAWING PARALLEL TO THE ORIGINAL WATER SUPPLY.
09/30/2016 Expiration Date of the License
AINROFICF
E
A
NOITCETORPERI
F
LAO
ST
T
R E
S
RED
PROFESS IONAL
ENG
IN
E E
RS
A
M
UE
S. DANNAW
AY
LET
I
G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
/2
/2
:4 :1
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
FA001
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
F I R
E P
R O
T E
C T
IO
N
N O
T E
S A
N D
L E
G E
N D
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F A
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P
UP
FD
FD
FD
M
M
30 30
M
M
15 15
M
M
15 15
M
W P
M
C
C
M
C
M
C
M
C
M
C
C
C
C
C
M
C
C
M
C
C
M
C
C
M
C
C
C
M
C
M
M
C
M
C
C
M
C
M
M
M
C
C
M
C
C
C
M
C
C
M
C
C
C
C
M
C
M
C
M
C
M
C
M
C
C
C
M
W P
M
C
M
C
M
C
S
C
C
M
C
M
C
M
W P
W P
S
C
S
C
S
C
S
C
S
C
S
C S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C F
A C
P F
T R
M T
R
P
F E
P F
E P
P
ANT ANT
LOC
W P
F
WP
F
C
S
C
S
C
S
C
S
C
C
C
M
F E
P
W P
AHU-1
WP
F
WP 110
WP 60
M
110, WP
WP 60
M
WP
F
WP 60
M
WP
F
WP
F
110, WP
WP 30
M
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F O
R C
O N
T
IN
U A
T
IO
N
S E
E S
H E
E T
F A
M A
T C
H L
IN
E
A
COMMAND CONFERENCE
S-4 OFFICE 1A
CENTRAL FILES 1A
WOMEN'S TOILET
MEN'S TOILET
XO 1A
CSM 1A
COMMANDER 1A
COMMAND SUPPLY 1A
CMD OPEN OFFICE
S-1 OFFICER 1A
CORR
101A
COMMAND TOILET 1A
SR HR SGT 1A
DUTY OFFICER 1A
ARMS VAULT #3A
ARMS VAULT #3B
SECURE DOCUMENTS 1A
CORR
101B
RECYCLE 1A
ELEC 1A
STORAGE 1A-2
MECHANICAL 1A
TELECOM 1A
LANAI
100A
S-2 OFFICE 1A
S-6 OFFICE 1A
S-3 OPS SGT 1A
S-3 OFFICE 1A
S-3 CONF
RE-ENLIST 1A
FRSA
OPEN OFFICE 1A
COPY
STORAGE 1A-1
VENDING
100D
BREEZEWAY
100C
PROVIDE WEATHERPROOF
ENCLOSURE FOR LOC
09/30/2016 Expiration Date of the License
AINROFICF
E
A
NOITCETORPERI
F
LAO
ST
T
R E
S
RED
PROFESS IONAL
ENG
IN
E E
RS
A
M U
E
S. DANNAW
AY
LE
T
I G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
/8
/2
/2
:4 :2
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
FA101
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
P A
R T
IA
L F
IR
S
T F
L O
O R
W E
S T
F
IR
E
A L A
R M
/M A
S S
N O
T
IF
IC
A
T I O
N P
L A
N
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F A
SCALE:
0 8' 16'
1/8" = 1' - 0"
8' 16'
1/8" = 1'-0" B1
PARTIAL FIRST FLOOR WEST - FIRE ALARM/MASS NOTIFICATION PLAN
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
NOTE:
ALL CANDELA VALUES SHOWN ARE THE MINIMUM UNDERATED VALUES. IF THE MANUFACTURER'S DATA REQUIRES THAT THE APPLIANCES BE
DERATED, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE STROBE COVERAGE BASED ON THE MANUFACTURER'S REQUIRED
DERATED VALUES AND SPACED IN ACCORDANCE WITH NFPA 72.
UP
FD
W P
M
W P
M
S
C
W P
W P
30 30
M
M
30 30
M
M
M
15 30
M
34 34
M
M
5M 1
C
M
C
C
M
C
C
M
C
C
M
C
C
C
M
C
M
C
M
C
S
C
C
S
C
C
M
C
C
M
S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C
C
C
M
C
C
M
C
M
C
C
C
C
C
C
M
C
M
C
M
C
C
C
M
S
C
S
C
S
C
S
C
C
C
C
M
C
M
C
M
C
M
C
15 15
C
M
WF
VS
F E
P
P
ANT ANT
W P
F
LOC
WP
F
C
C
M
M
C
C
C
M
C
M
C
C
M
S
C
S
C
FEPFEP
W P
WP 30
AHU-2
WP
F
110, WP
WP 60
M
WP
F
110, WP
WP 60
M
WP 60M
WP
F
110, WP
WP 60
M
WP
F
VS
VS
PS
12 13 14 15 16 17 18 19 20 21 22 23
A
B
C
D
E
F O
R C
O N
T
IN
U A
T
IO
N
S E
E S
H E
E T
F A
M A
T C
H L
IN
E
A
S-3 CONF
VENDING
100D
OPEN OFFICE 1B
FIRE RISER ROOM
ARMS VAULT #2B
S-3 OFFICE 1A
S-3 OPS SGT 1A
S-6 OFFICE 1A
S-2 OFFICE 1A
SECURE DOCUMENT'S 1A
MEN'S TOILET
WOMEN'S TOILET
CENTRAL FILES
S-4 OFFICE 1B
COMMAND CONF ROOM 1B
ARMS VAULT #2A
CHAPLAIN
ELEC 1B
166STORAGE 1B
CHAPLAIN ASST
MECHANICAL ROOM 1B
TELECOM 1B
CORR
161B
XO 1B
CSM 1B
COMMANDER 1B
CMD OPEN OFFICE
S-1 OFFICE
COMMAND SUPPLY 1B
CMD TOILET 1B
CORR
161A
SR HR SGT 1B
DUTY OFFICER 1B
JAN
LANAI
100B
LANAI
100B
BREEZEWAY
100C
PROVIDE WEATHERPROOF
ENCLOSURE FOR LOC
09/30/2016 Expiration Date of the License
AINROFICF
E
A
NOITCETORPERI
F
LAO
ST
T
R E
S
RED
PROFESS IONAL
ENG
IN
E E
RS
A
M U
E
S. DANNAW
AY
LE
T
I G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
/8
/2
/2
:4 :2
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
FA102
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
P A
R T
IA
L F
IR
S
T F
L O
O R
E A
S T
F
IR
E
A L A
R M
/M A
S S
N O
T
IF
IC
A
T I O
N P
L A
N
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F A
SCALE:
0 8' 16'
1/8" = 1' - 0"
8' 16'
1/8" = 1'-0" B1
PARTIAL FIRST FLOOR EAST - FIRE ALARM/MASS NOTIFICATION PLAN
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
NOTE:
ALL CANDELA VALUES SHOWN ARE THE MINIMUM UNDERATED VALUES. IF THE MANUFACTURER'S DATA REQUIRES THAT THE APPLIANCES BE
DERATED, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE STROBE COVERAGE BASED ON THE MANUFACTURER'S REQUIRED
S
C
S
C
S
C
S
C S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C S
C
S
C
C
C
M
C
C
C
C
C
M
C
M
C
M
C
M
C
C
M
C
M
C
C
C
C
M
C
M
C
M
C
C
M
C
M
C
M
C
M
C
M
C
M
C
M
C
C
C
C
M
C
C
C
C
M
C
C
M S
C
C
C
M
C
C
M
C
M
C
C
C
C
M
C
M15
M
30 15
M
15 15
M
M
M
WP
M
WP
60 1515
M
WP,
M
WP, 60
C
C
C
M
C
M
C
C
M
S
C
S
C
S
C
C
M
C
S
C
C
C
C
C
M
F E
P F
E P
F E
P
P
WP
F
LOC
C
M
S
C
WP, 110
WP 60
AHU-3
WP 75
WP 15
M
WP, 60M WP 110WP 60
M
WP 60
M
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F O
R C
O N
T
IN
U A
T
IO
N
S E
E S
H E
E T
F A
M A
T C
H L
IN
E
A
COMMANDER 2A
LANAI
200A
NBC STORAGE 2A
UNIT STORAGE 2A-1
XO 2A
PLATOON 2A-D
PLATOON 2A-C
PLATOON 2A-B
PLATOON 2A-A
COMMAND CONFERENCE ROOM 2A
RECYCLE 2A
ELEC 2A
TELECOM 2A
MECHANICAL ROOM 2A
COMM STORAGE 2A
STORAGE 2A-2
CORR
201B
COMMAND OPEN OFFICE
COMMAND STORAGE 2A
CLASSROOM 2B
CLASSROOM 2A
UNIT STORAGE 2A-3
UNIT STORAGE 2A-2
CORR
201A WOMEN'S RESTROOM
JAN
MEN'S RESTROOM
CORR
TRAINING ROOM 2A
STORAGE 2A-1
1 SGT 2A
SECURE STORAGE 2A
CORR
MEN'S LATRINE & SHOWER
CLASSROOM 2C
JAN
CORR
244B
PROVIDE WEATHERPROOF
ENCLOSURE FOR LOC
09/30/2016 Expiration Date of the License
AINROFICF
E
A
NOITCETORPERI
F
LAO
ST
T
R E
S
RED
PROFESS IONAL
ENG
IN
E E
RS
A
M U
E
S. DANNAW
AY
LE
T
I G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
/8
/2
/2
:4 :3
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
FA103
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
P A
R T
IA
L S
E C
O N
D F
L O
O R
W E
S T
F
IR
E
A L A
R M
/M A
S S
N O
T
IF
IC
A
T I O
N P
L A
N
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F A
SCALE:
0 8' 16'
1/8" = 1' - 0"
8' 16'
1/8" = 1'-0" B1
PARTIAL SECOND FLOOR WEST - FIRE ALARM/MASS NOTIFICATION PLAN
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
NOTE:
ALL CANDELA VALUES SHOWN ARE THE MINIMUM UNDERATED VALUES. IF THE MANUFACTURER'S DATA REQUIRES THAT THE APPLIANCES BE
DERATED, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE STROBE COVERAGE BASED ON THE MANUFACTURER'S REQUIRED
S
C
S
C
C
M
C
M
S
C
S
C
C
M
S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C 30
C
S
C
S
C
C
C
C
C
C
C
M
C
M
C
M
C
M
C
M
C
M S
C
C
M
C
M
C
M
C
M
C
C
C
C
C
C
M
C
C
M
C
C
M
C
C
M
C
S
C
C
M
C
M
C
S
C
C S
C
C
M
C
M
C
C
M S
C
S
C
C
C
M
C
C
M
C
C
M
C
M
C
M
C
M
C
M30
C 30
C
C
C
C
M
C
M
WP
M
WP
M
15 30
M
M
15 15
M
15 15
M
C
WF
VS
F E
P
P
WP
F
WP
F
WP
F
LOC
M
M
15 30
M
30 15
M
C 60
C
S
C
F E
P
FEP
WP 60
AHU-4
WP 60
M
WP 110
WP 60
M
WP 110WP 75
M
WP 75
M
WP 75
WP 60
M
12 13 14 15 16 17 18 19 20 21 22 23
A
B
C
D
E
F O
R C
O N
T
IN
U A
T
IO
N
S E
E S
H E
E T
F A
M A
T C
H L
IN
E
A
LANAI
200B
PLATOON 2B-D
PLATOON 2B-C
PLATOON 2B-B
PLATOON 2B-A
COMMAND CONFERENCE ROOM 2B
UNIT STORAGE 2B-2
UNIT STORAGE 2B-1
CLASSROOM 2B
CLASSROOM 2A
SECURE STORAGE 2B
UNIT STORAGE 2B-3
1 SGT 2B
XO 2B
COMMAND STORAGE 2B
COMMAND OPEN OFFICE
MECHANICAL ROOM 2B
TELECOM 2B
STORAGE 2B-2
ELEC 2B
RECYCLE 2B
COMM STORAGE 2B
CORR
232A
TRAINING ROOM 2B
STORAGE 2B-3
WOMEN'S RESTROOM
JAN
MEN'S RESTROOM
CORR
NBC STORAGE 2B
245 CORR
244A
CORR
232B
CLASSROOM 2C
JAN
CORR
244B
WOMEN'S LATRINE & SHOWER
COMMANDER 2B
PROVIDE WEATHERPROOF
ENCLOSURE FOR LOC
09/30/2016 Expiration Date of the License
AINROFICF
E
A
NOITCETORPERI
F
LAO
ST
T
R E
S
RED
PROFESS IONAL
ENG
IN
E E
RS
A
M U
E
S. DANNAW
AY
LE
T
I G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
/8
/2
/2
:4 :4
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
FA104
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
P A
R T
IA
L S
E C
O N
D F
L O
O R
E A
S T
F
IR
E
A L A
R M
/M A
S S
N O
T
IF
IC
A
T I O
N P
L A
N
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F A
SCALE:
0 8' 16'
1/8" = 1' - 0"
8' 16'
1/8" = 1'-0" B1
PARTIAL SECOND FLOOR PLAN EAST - FIRE ALARM/MASS NOTIFICATION PLAN
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
NOTE:
ALL CANDELA VALUES SHOWN ARE THE MINIMUM UNDERATED VALUES. IF THE MANUFACTURER'S DATA REQUIRES THAT THE APPLIANCES BE
DERATED, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE STROBE COVERAGE BASED ON THE MANUFACTURER'S REQUIRED
FD
FD
FD
S
C
S
C
S
C
S
C
C
M
C
C
C
M
C
C
C
C
C
C
M
C
M
C
M
C
M
C
M
C
M
C
M
C
M
C
C
C
C
C
C
M
C
M
C
M
C
M
C
C
M
C
M
C
M
C
M
C
C
C
C
M
M
15 15
M
30 15
M
WP, 30 WP,
M
M
WP
30WP
M
M
M
M
S
M S
M
M
94 60
M
M
FEPFEP
FEP
P
WP
F
LOC
C
M
C
M
30 15 15
M
M
M
AHU-5
WP 110
WP 60
M
WP 60
M
WP, 110 WP 75
WP 60
M
WP 75
M
WP 75
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F O
R C
O N
T
IN
U A
T
IO
N
S E
E S
H E
E T
F A
M A
T C
H L
IN
E
A
COMMANDER 3A
GYM
LANAI
300A
1 SGT 3A
COMMAND STORAGE 3A
XO 3A
COMM STORAGE 3A
PLATOON 3A-D
PLATOON 3A-C
PLATOON 3A-B
PLATOON 3A-A
COMMAND CONFERENCE ROOM 3A
STORAGE 3A
UNIT STORAGE 3A
RECYCLE 3A
TELECOM ROOM 3A
CORR
301B
ELEC 3A
JAN
MECHANICAL ROOM 3A
CORR
NBC STORAGE 3A
TRAINING ROOM 3A
MEN'S LATRINE & SHOWER
CORR
301ACOMMAND OPEN OFFICE
WOMEN'S RESTROOM
SECURE STORAGE 3A
PROVIDE WEATHERPROOF
ENCLOSURE FOR LOC
09/30/2016 Expiration Date of the License
AINROFICF
E
A
NOITCETORPERI
F
LAO
ST
T
R E
S
RED
PROFESS IONAL
ENG
IN
E E
RS
A
M U
E
S. DANNAW
AY
LE
T
I G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
/8
/2
/2
:4 :4
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
FA105
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
P A
R T
IA
L T
H
IR
D F
L O
O R
W E
S T
F
IR
E
A L A
R M
/M A
S S
N O
T
IF
IC
A
T I O
N P
L A
N
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F A
SCALE:
0 8' 16'
1/8" = 1' - 0"
8' 16'
1/8" = 1'-0" B1
PARTIAL THIRD FLOOR WEST - FIRE ALARM/MASS NOTIFICATION PLAN
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
NOTE:
ALL CANDELA VALUES SHOWN ARE THE MINIMUM UNDERATED VALUES. IF THE MANUFACTURER'S DATA REQUIRES THAT THE APPLIANCES BE
DERATED, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE STROBE COVERAGE BASED ON THE MANUFACTURER'S REQUIRED
FD
M
M
94 60
M
MS
M
MS
C
C
C
C
C
C
C
C
M
C
M
C
M
C
M
C
M
C
M
C
M
C
M
C
M
S
C
S
C
S
C
S
C
C
C
M
C
M
C
S
C
C
C
C
M
C
M
C
C
M
C
M
C
C
M
C
M
C
M
C
C
M
C
S
C
S
C
S
C
C
M
C
C
M
C
M
M
M
W P
M3
W P
M
WP 30
M
WP, 30
WP 30
M
WP, 30
M
M
WF
VS
FEP
P
WP
F
WP
F
LOC
WP
F
C
C
M
M
F E
P F
E P
WP, 110
AHU-6
WP 75
M
WP 75 WP 110
WP 60
M
WP 60
M
WP 60
M
WP 110
WP 60
M
C
C
M
12 13 14 15 16 17 18 19 20 21 22 23
A
B
C
D
E
F O
R C
O N
T
IN
U A
T
IO
N
S E
E S
H E
E T
F A
M A
T C
H L
IN
E
A
COMMANDER 3B
XO 3B
1 SGT 3B
GYM
LANAI
300B
PLATOON 3B-B
PLATOON 3B-C
PLATOON 3B-D
COMM STORAGE 3B
COMMAND CONFERENCE ROOM 3B
PLATOON 3B-A
NBC STORAGE 3B
STORAGE 3B
MECHANICAL ROOM 3B
STAIR
TELECOM 3B
OFFICE
ELEC 3B
COMMAND STORAGE 3B
UNIT STORAGE 3B
CORR
330B
JAN
TRAINING ROOM 3B
COMMAND OPEN OFFICE
CORR
WOMEN'S RESTROOM
SECURE STORAGE 3B
CORR
330A
MEN'S LATRINE & SHOWER
PROVIDE WEATHERPROOF
ENCLOSURE FOR LOC
16 17
C
D
09/30/2016 Expiration Date of the License
AINROFICF
E
A
NOITCETORPERI
F
LAO
ST
T
R E
S
RED
PROFESS IONAL
ENG
IN
E E
RS
A
M U
E
S. DANNAW
AY
LE
T
I G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
/8
/2
/2
:4 :5
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
FA106
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
P A
R T
IA
L T
H
IR
D F
L O
O R
E A
S T
F
IR
E
A L A
R M
/M A
S S
N O
T
IF
IC
A
T I O
N P
L A
N
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F A
SCALE:
0 8' 16'
1/8" = 1' - 0"
8' 16'
1/8" = 1'-0" B1
PARTIAL THIRD FLOOR EAST - FIRE ALARM/MASS NOTIFICATION PLAN
1/8" = 1'-0"
LOFT - FIRE ALARM/MASS NOTIFICATION PLAN
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
NOTE:
ALL CANDELA VALUES SHOWN ARE THE MINIMUM UNDERATED VALUES. IF THE
MANUFACTURER'S DATA REQUIRES THAT THE APPLIANCES BE DERATED, IT IS
THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE STROBE COVERAGE
BASED ON THE MANUFACTURER'S REQUIRED DERATED VALUES AND SPACED
IN ACCORDANCE WITH NFPA 72.
NOTE:
ALL CANDELA VALUES SHOWN ARE THE MINIMUM UNDERATED VALUES. IF THE MANUFACTURER'S DATA
REQUIRES THAT THE APPLIANCES BE DERATED, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE
STROBE COVERAGE BASED ON THE MANUFACTURER'S REQUIRED DERATED VALUES AND SPACED IN
ACCORDANCE WITH NFPA 72.
VISUAL OR
AUDIO/VISUAL
DEVICE
MANUAL FIRE ALARM
PULL STATION
AUDIO DEVICE
WHERE LOW CEILING HEIGHT DO NOT PERMIT MOUNTING AT A MINIMUM OF 80", VISIBLE
APPLIANCES SHALL BE MOUNTED WITHIN 6" OF THE CEILING. THE ROOM SIZE COVERED
BY A STROBE OF A GIVEN VALUE SHALL BE REDUCED BY TWICE THE DIFFERENCE
BETWEEN THE MINIMUM MOUNTING HEIGHT OF 80" AND THE ACTUAL LOWER MOUNTING
HEIGHT.
AUDIO DEVICE MOUNTING HEIGHTS OTHER THAN REQUIRED ABOVE SHALL BE PERMITTED,
PROVIDED THAT THE SOUND PRESSURE LEVEL REQUIREMENTS BASED ON APPLICATION
(EX. PUBLIC MOD) ARE MET.
FIRE
FIRE
6'
" 7'
5'-0"
MAX.
4'
FINISHED FLOOR
1.
2.
NOTE:
GRADE
FLOOR
1" GALVANIZED RIGID
CONDUIT SUPPORT PIPE
RADIO FIRE ALARM
TRANSCEIVER
ROOF
ANTENNA
WALL MOUNTS
1" CONDUIT SUPPORT WITH
PULLING ELBOW PIPE W/
OFFSET BEND
T O
6"
F R
O M
P E
A K
O F
R O
O F
PROVIDE SUPPORT FOR
VERTICAL PORTION OF
RACEWAY ABOVE ROOF
CONNECT TO INDIVIDUAL GROUNDING ROD.
PROVIDE #6 BONDWIRE FROM INDIVIDUAL
GROUNDING ROD TO BUILDING GROUNDING
SYSTEM.
CONDUIT CLAMP
TO INDIVIDUAL GROUNDING
ROD PER NEC
COPPER WIRE SHALL NOT BE
SMALLER THAN #10 PER NEC
LIGHTNING ARRESTOR WITH
WEATHERPROOF ENCLOSURE,
SEE DETAIL
GROUNDING BUSHING
WEATHERPROOF ENCLOSURE
SIDE VIEW - WEATHERPROOF ENCLOSURE
COAXIAL CABLES
ARE NOT SHOWN
#10 COPPER
LIGHTNING ARRESTOR DETAIL
TOP OF DETECTOR
ACCEPTABLE HERE
DETECTOR LOCATION
IS ACCEPTABLE HERE
ABOVE ACCEPTABLE HEIGHT
BELOW ACCEPTABLE HEIGHT
CEILING
SIDEWALL
M A
X
IM
U M
1'
09/30/2016 Expiration Date of the License
AINROFICF
E
A
NOITCETORPERI
F
LAO
ST
T
R E
S
RED
PROFESS IONAL
ENG
IN
E E
RS
A
M
UE
S. DANNAW
AY
LET
I
G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
A s i n d ic a te d
/2
/2
:4 :5
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
FA501
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
F
IR
E A
L A
R M
/M A
S S
N O
T
IF
IC
A
T I O
N D
E T
A
IL
S
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F A
NTS
B2
MOUNTING HEIGHTS FOR ALARM DEVICES
NTS
B4
FIRE ALARM TRANCEIVER ANTENNA
NTS
C1
PROPER MOUNTING FOR SMOKE DETECTOR
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P
MANUAL PULL STATION ALARM ACTIVATION
GENERAL SUPERVISORY ACTIVATION
SMOKE DETECTOR ACTIVATION
RADIO FIRE ALARM TRANSCEIVER ZONES
WATER FLOW / PRESSURE SWITCH ACTIVATION
MASS NOTIFICATION SUPERVISORY ACTIVATION
GENERAL TROUBLE
SYSTEM INPUT
FIRE ALARM/ MASS NOTIFICATION SEQUENCE OF OPERATIONS
SYSTEM OUTPUT
TROUBLE ON FIRE ALARM EXTENDER PANEL
A B C D E F G
TRANSM
IT
A
LA
RM
T
O E
M
ERG
ENCY F
O
RCES
ACTIV
ATE V
IS
IB
LE
A
ND A
UDIB
LE
A
LA
RM
A
NNUNCIA
TO
R
TRANSM
IT
S
UPERVIS
O
RY A
LA
RM
T O E
M
ERG
ENCY F
O
RCES
TRANSM
IT
T
RO
UBLE
A
LA
RM
T O E
M
ERG
ENCY F
O
RCES
ACTIV
ATE M
ASS N
O
TIF
IC
ATIO
N V
IS
IB
LE
S
UPERVIS
O
RY A
NNUNCIA
TO
R
ACTIV
ATE V
IS
IB
LE
A
ND A
UDIB
LE
S
UPERVIS
O
RY A
NNUNCIA
TO
R
ACTIV
ATE V
IS
IB
LE
A
ND A
UDIB
LE
T
RO
UBLE
A
NNUNCIA
TO
R
ACTIV
ATE A
LL
F
IR
E A
LA
RM
N O
TIF
IC
ATIO
N A
PPLI
ANCES A
ND B
RO
ADCAST F
IR
E A
LA
RM
M
ESSAG
E
ACTIV
ATE M
ASS N
O
TIF
IC
ATIO
N V
IS
UAL
APPLI
ANCES
BRO
ADCAST M
ASS N
O
TIF
IC
ATI
O N M
ESSAG
E
TRANSM
IT
M
ASS N
O
TIF
IC
ATIO
N S
UPERVIS
O
RY T
O E
M
ERG
ENCY F
O
RCES
TEM
PO
RARIL
Y A
ND IM
M
EDIA
TELY
D
EACTIV
ATE A
LL
F
IR
E A
LA
RM
V
IS
UAL
NO
TIF
IC
ATIO
N A
PPLI
ANCES.
SPRINKLER RISER OR FLOOR WATER FLOW OR PRESSURE SWITCH
MANUAL PULL STATION
SMOKE DETECTOR ABOVE PANEL
SINGLE BREAK OR SINGLE GROUND FAULT IN FIRE ALARM CIRCUIT
ACTIVATION OF MASS NOTIFICATION LIVE OR RECORDED MESSAGE
ACTIVATION OF MASS NOTIFICATION LIVE OR RECORDED MESSAGE DURING AN ACTIVE ALARM *
SPRINKLER VALVE TAMPER SWITCH
H I J K L M
A B C D E F G H I J K L M
NOTE:
1. IF THE SEQUENCE INDICATED HERE CONFLICTS WITH SPECIFICATION, THIS CONTROL
SEQUENCE SUPERCEDES SPECIFICATION SEQUENCE.
* FIRE ALARM NOTIFICATION APPLIANCE OVERRIDE TO BE AUTOMATIC UPON ACTIVATION OF
MASS SYSTEM PRE-RECORDED MESSAGE OR MICROPHONE
SHUTDO
W
N A
SSO
CIA
TED A
HU
DUCT SMOKE DETECTOR9 9
N
N
O
O
IN
IT
IA
TIO
N D
EVIC
ES A
ND O
CCUPANT
NO
TIF
IC
ATIO
N A
PPLI
ANCE O
PERATI
O N M
AIN
TAIN
ED
DEACTIV
ATE M
ASS N
O
TIF
IC
ATIO
N V
IS
UAL
APPLI
ANCES
COMPLETION OF MASS NOTIFICATION LIVE OR RECORDED BROADCAST DURING AN ACTIVE ALARM10 10
09/30/2016 Expiration Date of the License
AINROFICF
E
A
NOITCETORPERI
F
LAO
ST
T
R E
S
RED
PROFESS IONAL
ENG
IN
E E
RS
A
M U
E
S. DANNAW
AY
LE
T
I G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
/2
/2
:4 :5
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
FA601
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
F
IR
E A
L A
R M
/M A
S S
N O
T
IF
IC
A
T I O
N S
E Q
U E
N C
E O
F O
P E
R A
T
IO
N S
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F A
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P
AIM AIM
S-1 OFFICE
CORR
101A
LANAI
100A
DUTY OFFICER 1A
SR HR SGT 1A
ARMS VAULT #3A
LANAI
100A
ARMS VAULT #3B
RECYCLE 1A
ELEC 1A
MECHANICAL 1A
TELECOM 1A
STORAGE 1A-2
COPY
STORAGE 1A-1
LANAI
100A
OPEN OFFICE 1A
BREEZEWAY
100C
VENDING
100D
FIRE RISER ROOM
BREEZEWAY
100C
LANAI
100B
ARMS VAULT #2B
STORAGE 1B
TELECOM 1B
MECHANICAL ROOM 1B
CHAPLAIN ASST
ELEC 1B
CHAPLAIN
ARMS VAULT #2A
SR HR SGT 1B
DUTY OFFICER 1B
LANAI
100B
CORR
161A
CMD TOILET 1B
COMMAND SUPPLY 1B
CMD OPEN OFFICE
CSM 1B
XO 1B
COMMAND CONF ROOM 1B
CMD OPEN OFFICE
S-4 OFFICE 1B
CENTRAL FILES
CORR
161B
LANAI
100B
COMMANDER 1B
OPEN OFFICE 1A
FTR FACP
ANTENNA
LIGHTNING ARRESTOR
TO GROUND
1P, 20A
1P, 20A
FOR
CONTINUATION,
SEE ELECTRICAL
DRAWING
C
WP
F
C
M
C
M
C
M
LOC
M
M
P
M
M
M
M
M
M
C C
WP
F
C
M
C
M
C
C
M S
C
S
S
C
S
C
S
C
S
C
S
C
S
C
WP
F
M
WP
X 3
WFVS
75WP
M
WP
F
110 34
M
M
M
M
M
FEP
P
1P, 20A
C
M
C
C
M
C
LOC
C
M
C
C
M
C
M
WP
F
C
C
M
C
M
C
M
C
M
C
C
M
C
C
M
C
C
M
C
C
M
C
S
C
S
C
S
C
S
C
C
M
C
C
C
M
C
C
M
C
S
C
C
M
C
S
C
C
FOR
CONT.
ON THIS
SHEET,
SEE
A
A FOR
CONT.
ON THIS
SHEET,
SEE
B
B FOR
CONT.
SEE
C
BACK TO FACP
SP
FEP
1P, 20A
SP
ON
SHEET
FA603
SPSP
X 3
BACK TO FACP
LANAI
100A
WP
F
LANAI
100B
WP
F
P
LANAI
100B
15WP 30WP
AOM
P, AHU-1
R SHUTDOWN AHU-1
AOM
P, AHU-2
R SHUTDOWN AHU-2
MTR
ANTENNA
LIGHTNING ARRESTOR
TO GROUND
M
WP
110WP
WP
F
M
WP
WP 110
WP
F
M
WP
WP 110
M
WP
110WP
M
WP
110WP
M
WP
AIM
VS
AIM
VS
AIM
PS
60WP
M
WP
F
M
WP
110WP
09/30/2016 Expiration Date of the License
AI
NROFICF
E A
N
OITCETORP
ERI
F
LAO
S
T T
R E
S R
ED
PROFESS IONAL
EN
G
IN
E
E
RS
A M
U
E
S. DANN
A W
A Y
LE
T
I G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
N O
S C
A L E
/2
/2
:5 :0
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
FA602
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
F
IR
E A
L A
R M
/M A
S S
N O
T
IF
IC
A
T I O
N R
IS
E
R D
IA
G
R A
M
F I R
S T
F L O
O R
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F A
- NO SCALE
A2
FIRE ALARM / MASS NOTIFICATION RISER DIAGRAM - FIRST FLOOR
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P
COMMAND SUPPLY 1A
CMD OPEN OFFICE
S-1 OFFICER 1A
COMMAND TOILET 1A
WOMEN'S TOILET
MEN'S TOILET
SECURE DOCUMENT'S 1A
CORR
161B
S-2 OFFICE 1A
S-6 OFFICE 1A
CORR
161B
S-3 OPS SGT 1A
S-3 OFFICE 1A
S-3 CONF
OPEN OFFICE 1B
BREEZEWAY
100C
FRSA
RE-ENLIST 1A
S-3 CONF
S-3 OFFICE 1A
S-3 OPS SGT 1A
CORR
101B
S-2 OFFICE 1A
S-6 OFFICE 1A
SECURE DOCUMENTS 1A
CORR
101B
WOMEN'S TOILET
MEN'S TOILET
CORR
101B
CORR
101B
COMMAND CONFERENCE
S-4 OFFICE 1A
CENTRAL FILES 1A
XO 1A
CSM 1A
COMMANDER 1A
M
M
C
M
C
S
C
C
M
C
M
C
C
M
C
C
M
C
C
M
C
C
M
C
C
M
C
S
C
S
C
C
M
C
S
C
S
C
S
C
75WP
M
WP
WP
F
C
M
C
C
M
C
C
M
C
C
M
C
C
M
C
C
M
C
C
M
C
C
M
C
S
C
C
C
M
C
M
M
S
C
C
M
M
C
M
C
S
C
S
C
C
M
C
S
C
S
C
C
M
C
C
M
C
C
M
C
M
C
M
C
C
M
C
C
M
C
C
C
M
C
S
C
C
C
M S
C
S
C
S
C
S
C
C
M
C
S
C
S
C
S
C
C FOR
CONT.
ON THIS
SHEET,
SEE
D
D FOR
CONT.
ON THIS
SHEET,
SEE
E
E
BACK TO FACP
BACK TO FACP
BACK TO FACP
BACK TO FACP
09/30/2016 Expiration Date of the License
AI
NROFICF
E A
N
OITCETORP
ERI
F
LAO
S
T T
R E
S R
ED
PROFESS IONAL
EN
G
IN
E
E
RS
A M
U
E
S. DANN
A W
A Y
LE
T
I G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
N O
S C
A L E
/2
/2
:4 :5
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
FA603
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
F
IR
E A
L A
R M
/M A
S S
N O
T
IF
IC
A
T I O
N R
IS
E
R D
IA
G
R A
M
F I R
S T
F L O
O R
C O
N T
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F A
NO SCALE
A2
FIRE ALARM / MASS NOTIFICATION RISER DIAGRAM - FIRST FLOOR CONT.
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P
CORR
201A
LANAI
200A
TRAINING ROOM 2A
STORAGE 2A-1
MEN'S RESTROOM
WOMEN'S RESTROOM
CORR
COMM STORAGE 2A
LANAI
200A
MECHANICAL ROOM 2A
STORAGE 2A-2
ELEC 2A
RECYCLE 2A
TELECOM 2A
NBC STORAGE 2A
CORR
LANAI
200A
MEN'S LATRINE & SHOWER
JAN
CLASSROOM 2C
NBC STORAGE 2B
LANAI
200B
CORR
244A
WOMEN'S LATRINE & SHOWER
STORAGE 2B-2
TELECOM 2B
LANAI
200B
MECHANICAL ROOM 2B
ELEC 2B
RECYCLE 2B
COMM STORAGE 2B
LANAI
200B
CORR
MEN'S RESTROOM
WOMEN'S RESTROOM
STORAGE 2B-3
TRAINING ROOM 2B
LANAI
200B
CORR
232A
COMMAND STORAGE 2B
COMMANDER 2B
1 SGT 2B
COMMAND OPEN OFFICE
LOC
M
PWP
F
X 3
S
C CC
30 15
M
C C
M
CC
M
M
M
CC
M S
C CC
M
M
C
M
M
M
M
CC
M
C
M
60, WP
60, WP
M
M
C
M
C
S
C
S
C
S
C
S
C
M
CC
M
CC
WP
F
30, WP
30, WP
M
M
M
M
WFVS
WP
F P
M
M
M
LOC
M
CC
M
M
M
CC
M
CC
WP
F
M
CC
M
CC
M
CC
M
CC
C
MS
C
S
C
C
M
C
C
FOR
CONT.
ON THIS
SHEET,
SEE
F
F FOR
CONT.
ON THIS
SHEET,
SEE
G
G FOR
CONT.
SEE
H
BACK TO FACP
FEP
1P, 20A
SP
FEP
1P, 20A
SP
TO FACP
ON FIRST
FLOOR
ON
SHEET
FA605
BACK TO FACP
BACK TO FACP
X 3
110WP
110WP
110WP
AOM
P, AHU-3
R SHUTDOWN AHU-3
AOM
P, AHU-4
R SHUTDOWN AHU-4
M
WP
75WP
60WP
M
M
WP
110WP
LANAI
200A
M
WP
60WP
M
WP 75
M
WP
M
WP
75WP
M
WP
09/30/2016 Expiration Date of the License
AI
NROFICF
E A
N
OITCETORP
ERI
F
LAO
S
T T
R E
S R
ED
PROFESS IONAL
EN
G
IN
E
E
RS
A M
U
E
S. DANN
A W
A Y
LE
T
I G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
N O
S C
A L E
/2
/2
:4 :5
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
FA604
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
F
IR
E A
L A
R M
/M A
S S
N O
T
IF
IC
A
T I O
N R
IS
E
R D
IA
G
R A
M
S E
C O
N D
F L O
O R
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F A
NO SCALE
A2
FIRE ALARM / MASS NOTIFICATION RISER DIAGRAM - SECOND FLOOR
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P
XO 2B
COMMAND CONFERENCE ROOM 2B
PLATOON 2B-A
PLATOON 2B-B
CORR
232B
PLATOON 2B-C
PLATOON 2B-D
CORR
232B
SECURE STORAGE 2B
CORR
232B
UNIT STORAGE 2B-3-1
220-1
CORR
232B
UNIT STORAGE 2B-2
CORR
244B
UNIT STORAGE 2B-1
CORR
244B
CLASSROOM 2B
CORR
244B
CLASSROOM 2A
CORR
244B
UNIT STORAGE 2A-3
CORR
244B
UNIT STORAGE 2A-2
CORR
244B
UNIT STORAGE 2A-1
CORR
201B
SECURE STORAGE 2A
CORR
201B
PLATOON 2A-D
PLATOON 2A-C
CORR
201B
PLATOON 2A-B
PLATOON 2A-A
COMMAND CONFERENCE ROOM 2A
XO 2A
1 SGT 2A
COMMANDER 2A
COMMAND OPEN OFFICE
COMMAND STORAGE 2A
M
CC
S
C
S
C
C
M
C
M
CC
M
CC
M
CC
M
CC
M
CC
S
C
C
S
C
S
C
C
M
C
S
C
S
C
C
M
C
S
C
C
M
C
S
C
S
C
C
M
C
C
M
C
M
C
S
C
S
C
M
C
S
C
S
C
C
M
C
C
M
C
S
C
S
C
C
M
C
C
C
M S
C
S
C
C
M
C
C
S
C
S
C
C
M
C
S
C
C
M S
C
S
C
C
M
C
C
M
C
S
C
S
C
C
M
C
C
M
C
S
C
S
C
C
M
C
S
C
S
C
C
M
C
S
C
C
M
C
C
M
C
C
C
M
C
C
M
C
S
C
S
C
C
M
C
C
M
C
C
M
C
C
M
C
S
C
S
C
C
M
C
C
M
C
M
C
H
C
FOR
CONT.
ON THIS
SHEET,
SEE
I
I FOR
CONT.
ON THIS
SHEET,
SEE
J
J
BACK TO FACP
BACK TO FACP
BACK TO FACP
09/30/2016 Expiration Date of the License
AI
NROFICF
E A
N
OITCETORP
ERI
F
LAO
S
T T
R E
S R
ED
PROFESS IONAL
EN
G
IN
E
E
RS
A M
U
E
S. DANN
A W
A Y
LE
T
I G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
N O
S C
A L E
/2
/2
:4 :0
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
FA605
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
F
IR
E A
L A
R M
/M A
S S
N O
T
IF
IC
A
T I O
N R
IS
E
R D
IA
G
R A
M
S E
C O
N D
F L O
O R
C O
N T
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F A
NO SCALE
A2
FIRE ALARM / MASS NOTIFICATION RISER DIAGRAM - SECOND FLOOR CONT.
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P
301A
LANAI
300A
SECURE STORAGE 3A
WOMEN'S RESTROOM
UNIT STORAGE 3A
LANAI
300A
UNIT STORAGE 3A
STORAGE 3A
CORR
RECYCLE 3A
ELEC 3A
MECHANICAL ROOM 3A
TELECOM ROOM 3A
GYM
LANAI
300A
GYM
LANAI
300B
GYM
STAIR
TELECOM 3B
LANAI
300B
MECHANICAL ROOM 3B
ELEC 3B
CORR
330A
LANAI
300B
UNIT STORAGE 3B
STORAGE 3B
WOMEN'S RESTROOM
SECURE STORAGE 3B
CORR
TRAINING ROOM 3B
COMMAND OPEN OFFICE
COMMANDER 3B
COMMAND STORAGE 3B
1 SGT 3B
XO 3B
COMMAND CONFERENCE ROOM 3B
COMMAND OPEN OFFICE
CORR
330B
PLATOON 3B-A
PLATOON 3B-B
CORR
330B
PLATOON 3B-C
PLATOON 3B-D
CORR
330B
COMM STORAGE 3B
NBC STORAGE 3B
LANAI
300B
LOC
30 60
M
PWP
F
X 3
30 30
M
M
CC
M
M
30 60
M
C C
M
M
30 30
M
M
M S
M
M
S
WP
F
M
M
M
WP
F
M
P
M
30 60
M
LOC
WFVS
C C
M
60 15
M
M
M
M
C
C
WP
F
M
C
C
M
C
C
S
C
S
C
C
M
C
M
C
C
M
C
M
C
C
M
C
C
S
C
S
C
C
M
C
S
C
S
C
S
C
C
M
C
C
M
C
C
M
C
C
M
C
C
M
C
C
M
C
S
C
C
M
C
C
M
C
M
FOR
CONT.
ON THIS
SHEET,
SEE
K
K FOR
CONT.
ON THIS
SHEET,
SEE
L
L FOR
CONT.
SEE
M
BACK TO FACP
FEP
1P, 20A
SP
FEP
1P, 20A
SP
TO FACP
ON FIRST
FLOOR
ON
SHEET
FA607
LANAI
300A
WP
F
X 3
BACK TO FACP
BACK TO FACP
WP 110
110WP
M
C
AOM
P, AHU-5
R SHUTDOWN AHU-5
AOM
P, AHU-6
R SHUTDOWN AHU-6
M
WP
110WP
M
WP
110WP
M
WP
75WP
M
WP
75WP
M
WP
110WP
M
WP 60
M
WP
110WP
M
WP
09/30/2016 Expiration Date of the License
AI
NROFICF
E A
N
OITCETORP
ERI
F
LAO
S
T T
R E
S R
ED
PROFESS IONAL
EN
G
IN
E
E
RS
A M
U
E
S. DANN
A W
A Y
LE
T
I G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
N O
S C
A L E
/2
/2
:4 :0
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
FA606
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
F
IR
E A
L A
R M
/M A
S S
N O
T
IF
IC
A
T I O
N R
I S E
R D
IA
G
R A
M
T H
IR
D
F L O
O R
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F A
NO SCALE
A2
FIRE ALARM / MASS NOTIFICATION RISER DIAGRAM - THIRD FLOOR
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P
330B
OFFICE
MEN'S LATRINE & SHOWER
GYM
MEN'S LATRINE & SHOWER
JAN
CORR
301B
NBC STORAGE 3A
COMM STORAGE 3A
CORR
301B
PLATOON 3A-D
PLATOON 3A-C
CORR
301B
PLATOON 3A-B
PLATOON 3A-A
CORR
301B
COMMAND CONFERENCE ROOM 3A
XO 3A
1 SGT 3A
COMMAND STORAGE 3A
COMMANDER 3A
COMMAND OPEN OFFICE
TRAINING ROOM 3A
C
M
C
C
M
C
30,WP
30,WP
M
30,WP
30,WP
M
30,WP
30,WP
M
MS
M
M
MS
30, WP
30, WP
M
30, WP
15, WP
M
M
C
M
C
C
M
C
C
M
C
C
M
C
C
M
C
C
M
C
M
C
C
M
C
C
M
C
C
M
C
S
C
S
C
C
M
C
S
C
S
C
C
M
C
C
M
C
M
C
M
C
C
M
C
C
M
C
M FOR
CONT.
ON THIS
SHEET,
SEE
N
N
BACK TO FACP
BACK TO FACP
BACK TO FACP
C
M
C
09/30/2016 Expiration Date of the License
AI
NROFICF
E A
N
OITCETORP
ERI
F
LAO
S
T T
R E
S R
ED
PROFESS IONAL
EN
G
IN
E
E
RS
A M
U
E
S. DANN
A W
A Y
LE
T
I G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
N O
S C
A L E
/2
/2
:4 :0
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
FA607
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
F
IR
E A
L A
R M
/M A
S S
N O
T
IF
IC
A
T I O
N R
I S E
R D
IA
G
R A
M
T H
IR
D
F L O
O R
C O
N T
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F A
NO SCALE
A2
FIRE ALARM / MASS NOTIFICATION RISER DIAGRAM - THIRD FLOOR CONT.
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P
UP UP
FD
FD
FD
FD
FD
FD
FD
FD
FD
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
A
B
C
D
E
FCV
PROVIDE WET PIPE FIRE SPRINKLER
PROTECTION WITHIN THIS
BOUNDARY
FLOOR CONTROL VALVE,
SEE DETAIL C2
FX501
FIRE SPRINKLER RISER
UP TO SECOND FLOOR,
SEE FOR CONT.A1
FX101
SEE CIVIL FOR CONTINUATION
VENDING
100D
LANAI
100B
LANAI
100A
RECYCLE 1A
ELEC 1B
COMMANDER 1B
CSM 1B
ARMS VAULT #3B
ARMS VAULT #2B
DUTY OFFICER 1A
MECHANICAL 1A
ARMS VAULT #2A
S-2 OFFICE 1A
STORAGE 1A-2
FRSA
RE-ENLIST 1A
STORAGE 1A-1
FIRE RISER ROOM
S-3 CONF
S-1 OFFICE
COMMAND SUPPLY 1B
158CORR
161A
SR HR SGT 1B
DUTY OFFICER 1B
S-4 OFFICE 1B
CENTRAL FILES
CSM 1A
XO 1A
S-3 OPS SGT 1A
S-6 OFFICE 1A
ELEC 1A
TELECOM 1A
S-3 OFFICE 1A
S-3 CONF
S-3 OFFICE 1A
COMMAND CONF ROOM 1B
XO 1B
CMD OPEN OFFICE
STORAGE 1B
TELECOM 1B
MECHANICAL ROOM 1B
COPY
S-2 OFFICE 1A
CHAPLAIN ASST
CHAPLAIN
S-6 OFFICE 1A
OPEN OFFICE 1A
S-3 OPS SGT 1A
CORR
161B
SECURE DOCUMENT'S 1A
SECURE DOCUMENTS 1A
S-1 OFFICER 1A
COMMAND CONFERENCE
S-4 OFFICE 1A
CENTRAL FILES 1A
CORR
101A
COMMANDER 1A
CMD OPEN OFFICE
COMMAND TOILET 1A
COMMAND SUPPLY 1A
OPEN OFFICE 1B
SR HR SGT 1A
CORR
101B
ARMS VAULT #3A
REMOTE FIRE
DEPARTMENT
CONNECTION
CHECK
VALVE
FIRE SPRINKLER RISER,
SEE DETAIL A2
FX501
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
A
B
C
D
E
F C
V
PROVIDE WET PIPE FIRE SPRINKLER
PROTECTION WITHIN THIS
BOUNDARY
FLOOR CONTROL VALVE,
SEE DETAIL C2
FX501
FIRE SPRINKLER RISER
DN TO FIRST FLOOR, UP
TO THIRD FLOOR,
COMMANDER 2A
LANAI
200B
LANAI
200A
NBC STORAGE 2A
UNIT STORAGE 2A-1
XO 2A
PLATOON 2A-D
PLATOON 2A-C
PLATOON 2A-B
PLATOON 2A-A
COMMAND CONFERENCE ROOM 2A
RECYCLE 2A
ELEC 2A
TELECOM 2A
MECHANICAL ROOM 2A
COMM STORAGE 2A
STORAGE 2A-2
CORR
201B
COMMAND OPEN OFFICE
COMMAND STORAGE 2A
PLATOON 2B-D
PLATOON 2B-C
PLATOON 2B-B
PLATOON 2B-A
COMMAND CONFERENCE ROOM 2B
UNIT STORAGE 2B-2
UNIT STORAGE 2B-1
CLASSROOM 2B
CLASSROOM 2A
UNIT STORAGE 2A-3
UNIT STORAGE 2A-2
SECURE STORAGE 2B
UNIT STORAGE 2B-3
1 SGT 2B
XO 2B
COMMAND STORAGE 2B
COMMAND OPEN OFFICE
MECHANICAL ROOM 2B
TELECOM 2B
STORAGE 2B-2
ELEC 2B
RECYCLE 2B
CORR
201A
CORR
COMM STORAGE 2B
CORR
232A
TRAINING ROOM 2B
STORAGE 2B-3
CORR
238NBC STORAGE 2B
CORR
244A
CORR
232B
TRAINING ROOM 2A
STORAGE 2A-1
1 SGT 2A
SECURE STORAGE 2A
CORR
MEN'S LATRINE & SHOWER
CLASSROOM 2C
JAN
CORR
244B
WOMEN'S LATRINE & SHOWER
COMMANDER 2B
SPRINKLER HAZARD TABLE
SYMBOL SPRINKLER HAZARD CLASSIFICATION
HC-1
HC-2
MISCELLANEOUS STORAGE <= 10'-0"
09/30/2016 Expiration Date of the License
AINROFICF
E
A
NOITCETORPERI
F
LAO
ST
T
R E
S
RED
PROFESS IONAL
ENG
IN
E E
RS
A
M U
E
S. DANNAW
AY
LE
T
I G
No. 1130
SHEET
IDENTIFICATION
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N B
Y
S B
M T
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
D B
Y
US Army Corps of Engineers ® x
D
C
B
A
F
IL
E N
U M
B E
R
P L
O T
S C
A L E
P L
O T
D A
T E
SHEET OF
A s i n d ic a te d
/2
/2
:4 :2
A
M
S C
H O
F
IE
L D
B A
R R
A C
K S
H
A W
A
II
J U
L
A
HONOLULU DISTRICT
R O
J P
S S
D
FX101
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S
H A
F T
E R
H
A W
A
II
D E
S
IG
N B
R A
N C
H B
U
IL
D
IN
G
F T
S H
A F
T E
R H
I
-5
R O
F
IR
S T
A N
D S
E C
O N
D F
L O
O R
F
IR
E
S P
R
IN
K L E
R P
L A
N
F Y
P K
G A
- 0 R
E P
A
IR
B U
IL
D
I N G
Q
U A
D D
F X
1/16" = 1'-0" C1
FIRST FLOOR - FIRE SPRINKLER PLAN
1/16" = 1'-0" A1
SECOND FLOOR - FIRE SPRINKLER PLAN
SCALE:
0 16' 32'
1/16" = 1' - 0"
16' 32'
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P
FDFD
FD
FD
FD
FD
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
A
B
C
D
E
F C
V
PROVIDE WET PIPE FIRE SPRINKLER
PROTECTION WITHIN THIS
BOUNDARY
FLOOR CONTROL VALVE,
SEE DETAIL C2
FX501
FIRE SPRINKLER RISER
DN TO SECOND FLOOR
COMMANDER 3B
COMMANDER 3A
XO 3B
1 SGT 3B
GYM
LANAI
300A
LANAI
300B
PLATOON 3B-B
PLATOON 3B-C
PLATOON 3B-D
COMM STORAGE 3B
1 SGT 3A
COMMAND STORAGE 3A
XO 3A
COMM STORAGE 3A
PLATOON 3A-D
PLATOON 3A-C
PLATOON 3A-B
PLATOON 3A-A
COMMAND CONFERENCE ROOM 3A
STORAGE 3A
UNIT STORAGE 3A
RECYCLE 3A
TELECOM ROOM 3A
CORR
301B
E…