• 1-P2-7, Visitor Orientation Building at PH2, glass elevator #7 does not run. Contractor recommends replacing relay RC121 with a MG shutdown timer.

• 6-P2-12, Fish View Building on Washington Shore, elevator does not run. Contractor finds a 46 fault in log for Door Op/ Gate Hatch Locks. Recommends adjusting door equipment on each landing.

• P4-P2-21, Visitor gallery 113 level PH2, escalator is turned off. Contractor recommends replacement of governor/speed sensor.

• 03-P2-16, Visitor Orientation Building 75 level to 90 level escalator is turned off. Right side handrail no longer moving. Steps and left side handrail still functions.

• 03-P2-17, Visitor Orientation Building 75 level to 90 level escalator is turned off. Contractor recommends replacement of bull gear bearing.

**Still in service, but known issue**

• 2-P1-2, PH1 elevator intermittent issue noted in log as Seismic Fault or Break Trip Failure.

Contractor recommended repairs in order of most likely to remedy:

1. Replace PM circuit

2. Replace TC-MPI circuit board

3. Replace AC dive