A.01.25_existing_conditions_within_scope_of_17Q34.pdf
PDF 43 KB Posted
- Solicitation number
- W9127N-17-Q-0034
About this file
List of existing conditions to be repaired within the scope of this contract.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
• 1-P2-7, Visitor Orientation Building at PH2, glass elevator #7 does not run. Contractor recommends replacing relay RC121 with a MG shutdown timer.
• 6-P2-12, Fish View Building on Washington Shore, elevator does not run. Contractor finds a 46 fault in log for Door Op/ Gate Hatch Locks. Recommends adjusting door equipment on each landing.
• P4-P2-21, Visitor gallery 113 level PH2, escalator is turned off. Contractor recommends replacement of governor/speed sensor.
• 03-P2-16, Visitor Orientation Building 75 level to 90 level escalator is turned off. Right side handrail no longer moving. Steps and left side handrail still functions.
• 03-P2-17, Visitor Orientation Building 75 level to 90 level escalator is turned off. Contractor recommends replacement of bull gear bearing.
**Still in service, but known issue**
• 2-P1-2, PH1 elevator intermittent issue noted in log as Seismic Fault or Break Trip Failure.
Contractor recommended repairs in order of most likely to remedy:
1. Replace PM circuit
2. Replace TC-MPI circuit board
3. Replace AC dive