EQUIPMENT
PLAYGROUND
POWER POLE
EXISTING
CLASSROOM UNITS (TYP.)
TAP BOX - 1 PER 2 OR 3
ELECTRICAL
SERVICE ACROSS ROAD
NEW OVERHEAD PRIMARY
ENTERGY TO EXTEND
COORDINATE WITH
SERVICE
OVERHEAD ELECTRICAL
CONNECT TO EXISTING
CONDUITS
UNDERGROUND
FED FROM
SERVICE PANELS
AS SHOWN
SERVICE PANELS
CONDUITS TO
UNDERGROUND
SERVICE IN
EXTEND ELECTRIC
TRANSFORMER
167 KVA
POLE-MOUNTED
SCHEDULE 40 CONDUIT
THIS AREA: 3 FT BURY,
UG ELECTRICAL SERVICE
S O
L
IC
IT
A T
IO
N N
O
F
IL
E N
A M
E
D W
N B
Y
C K
D B
Y
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F
IL
E N
U M
B E
R
S
IZ
E
S U
B M
IT
T E
D B
Y
P L
O T S
C A
L E
P L
O T D
A T
E
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C O
N T
R A
C T N
O
D A
T E
A P
P R
®of Engineers
US Army Corps of Engineers
US Army Corps
ID
Sheet
/1
/2
C R
IT
IC
A L P
U B
L
IC
F
A C
IL
IT
Y
O R
A N
G E
F
IE
L D
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
SHEET KEYNOTES
LEGEND
ELECTRICAL CONDUIT
PRIMARY ELEC. CONDUIT
OVERHEAD ELECTRIC (EXISTING)
OVERHEAD ELECTRIC (PROPOSED)
ELECTRICAL NOTES
TAP BOX
A N
S I
D
P R
F
D B
S
E L E
C T
R
IC
A L S
IT
E P
L A
N
E-101
O R
N G
E -1
X X
X .d g n
SP 1
TB 1
TB 2
TB 4
SP 2
EXISTING POWER POLE
F E
M A D
R -4
-T
X
O R
A N
G E
F
IE
L D T
X
NEW POWER POLE
N
60'0 30'
G A
L V
E S
T O
N D
IS
T R
IC
T
G A
L V
E S
T O
N T
X
TB 3
SHOWN ON PLANS.
PERFORMED BY ENTERGY TO INSTALL ELECTRICAL SERVICES
PAYMENT/REIMBURSEMENT TO ENTERGY FOR WORK
5. CONTRACTOR RESPONSIBLE FOR
CLASSROOM UNITS.
ROUTED SO AS TO MAINTAIN FIRE ACCESS AROUND
4. CONTRACTOR TO ENSURE NEW ELECTRICAL SERVICE IS
TO CONSTRUCTION FOR UTILITY LOCATES.
CONSTRUCTION. CONTRACTOR SHALL CALL TEXAS811 PRIOR
FOR VERIFYING ALL UTILITIES PRIOR TO BEGINNING
UTILITIES WITHIN THE PROJECT AREA AND IS RESPONSIBLE
3. THE CONTRACTOR SHALL BE AWARE OF THE EXISTING
SPECIFIC LOCATIONS.
ENTERGY, (409-679-6225) AND CONTRACTING OFFICER ON
SHOWN IN APPROXIMATE LOCATIONS. COORDINATE WITH
2. THE POLES AND ASSOCIATED 400 AMP SERVICES ARE
COORDINATED.
WILL CONTINUE TO BE REQUIRED. OUTAGES WILL NEED TO BE
1. THE EXISTING SCHOOL ELECTRICAL SERVICE IS IN USE. AND
E L E
M E
N T
A R
Y S
C H
O O
L
CONDUCTOR.
AWG GREEN THHN OR XHHW2 STRANDED
SERVICE PANELS. IN THEATER/CLASSROOM USE #10
AND CANOPY SUPPORTS SHALL BE BONDED TO
ALL MISCELLANEOUS METAL RAILING, STAIRS POSTS
CONNECT TO GROUND LUG IN TAP BOX.
TAP BOXES - SEPARATE BY 6 FT. USE #1 AWG WIRE TO
TWO 10 FT. GROUND RODS TO BE INSTALLED NEAR
PRIMARY LINES.
ENTERGY WILL PROVIDE AND INSTALL OVERHEAD
ENTERGY.
EXISTING POLE WILL BE RE-GUYED AS NECESSARY BY
ORANGEFIELD ROAD TO SERVE PROPOSED SITE.
PLACE TO EXTEND SERVICE ACROSS
NEW OVERHEAD PRIMARY SERVICE TO BE PUT IN
SERVICE PANEL
POWER POLE
EXISTING
SERVICE
OVERHEAD ELECTRICAL
CONNECT TO EXISTING
TRANSFORMER AS SHOWN
SERVICE TO POLE-MOUNTED
EXTEND ELECTRIC
TRANSFORMER AS SHOWN
SERVICE TO POLE-MOUNTED
EXTEND PRIMARY ELECTRIC
CLASSROOM UNITS (TYP.)
TAP BOX - 1 PER 2 OR 3
ELECTRICAL
TO OVERHEAD ELECTRIC LINE
CLEARANCE FROM BUILDING
MAINTAIN 7.5' HORIZONTAL
TRANSFORMER AND
25 KVA
POLE-MOUNTED
S O
L
IC
IT
A T
IO
N N
O
F
IL
E N
A M
E
D W
N B
Y
C K
D B
Y
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F
IL
E N
U M
B E
R
S
IZ
E
S U
B M
IT
T E
D B
Y
P L
O T S
C A
L E
P L
O T D
A T
E
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C O
N T
R A
C T N
O
D A
T E
A P
P R
®of Engineers
US Army Corps of Engineers
US Army Corps
/1
/2
C R
IT
IC
A L P
U B
L
IC
F
A C
IL
IT
Y
O R
A N
G E
F
IE
L D
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
SHEET KEYNOTES
LEGEND
ELECTRICAL CONDUIT
PRIMARY ELEC. CONDUIT
OVERHEAD ELECTRIC (EXISTING)
OVERHEAD ELECTRIC (PROPOSED)
ELECTRICAL NOTES
TAP BOX
A N
S I
D
P R
F
D B
S
H
IG
H S
C H
O O
L
E L E
C T
R
IC
A L S
IT
E P
L A
N
E-102
O R
N G
E -1
X X
X .d g n
G A
L V
E S
T O
N T
X
G A
L V
E S
T O
N D
IS
T R
IC
T
O R
A N
G E
F
IE
L D T
X
F E
M A D
R -4
-T
X
EXISTING POWER POLE
20' 40'0
N
NEW POWER POLE
TB 1
TB 2
SP 1
SHOWN ON PLANS.
PERFORMED BY ENTERGY TO INSTALL ELECTRICAL SERVICES
PAYMENT/REIMBURSEMENT TO ENTERGY FOR WORK
4. CONTRACTOR RESPONSIBLE FOR
TO CONSTRUCTION FOR UTILITY LOCATES.
CONSTRUCTION. CONTRACTOR SHALL CALL TEXAS811 PRIOR
FOR VERIFYING ALL UTILITIES PRIOR TO BEGINNING
UTILITIES WITHIN THE PROJECT AREA AND IS RESPONSIBLE
3. THE CONTRACTOR SHALL BE AWARE OF THE EXISTING
SPECIFIC LOCATIONS.
ENTERGY, (409-679-6225) AND CONTRACTING OFFICER ON
SHOWN IN APPROXIMATE LOCATIONS. COORDINATE WITH
2. THE POLES AND ASSOCIATED 400 AMP SERVICES ARE
COORDINATED.
WILL CONTINUE TO BE REQUIRED. OUTAGES WILL NEED TO BE
1. THE EXISTING SCHOOL ELECTRICAL SERVICE IS IN USE. AND
TYP.
CONDUCTOR.
AWG GREEN THHN OR XHHW2 STRANDED
SERVICE PANELS. IN THEATER/CLASSROOM USE #10
AND CANOPY SUPPORTS SHALL BE BONDED TO
ALL MISCELLANEOUS METAL RAILING, STAIRS POSTS
CONNECT TO GROUND LUG IN TAP BOX.
TAP BOXES - SEPARATE BY 6 FT. USE #1 AWG WIRE TO
TWO 10 FT. GROUND RODS TO BE INSTALLED NEAR
PRIMARY LINES.
ENTERGY WILL PROVIDE AND INSTALL OVERHEAD
ENTERGY.
EXISTING POLE WILL BE RE-GUYED AS NECESSARY BY
SHOWN.
EXISTING ELECTRIC UTILITY AND EXTEND SERVICE AS
COORDINATE WITH ENTERGY TO CONNECT TO
3" PVC
3" PVC5
F
T
SOCKET
METER
PANEL
SERVICE
AND SOCKET MOUNTING
BOARD FOR PANEL
POST-MOUNTED
M
IN
2' MAX.
M A
X
3" PVC
3-500 MCM
3" PVC
3-500 MCM
(TYP.)
TO UNITS
TAP BOX
IN 1-1/2" PVC
3 1/0, 1#6 GND
IN 2-1/2 IN. GRS
3-250 MCM, 1#4 GND
2-3 CLASSROOMS
TYPICAL OF
RODS
GROUND
TWO
SPARE
FOR
PROVIDE
FOR SIZING
SEE E-101, E-102
TRANSFORMER
/1
/2
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
O R
N G
E -5
X X
X .d g n
CLASSROOM UNIT CLASSROOM UNIT CLASSROOM UNIT
CONDUIT
PVC SERVICE
LOOP SUCH THAT EACH CLASSROOM UNIT WILL CONNECT TO TWO OTHERS.
CONDUCTORS SHALL BE SET INTO GRAVEL BUT NOT TRENCHED. MAKE A CONTINUOUS
DAISY CHAIN #4 AWG BARE GROUND CONDUCTOR BETWEEN ALL CLASSROOM UNITS.
CONNECT SUPPLEMENTAL GROUND CONDUCTOR TO SERVICE PANELBOARD GROUND.
KEYNOTES:
N.T.S.
DETAIL
SUPPLEMENTARY GROUNDING OF CLASSROOM UNITS
SCALE:
N .T .S
A N
S I
D
E L E
C T
R
IC
A L D
E T
A
IL
S
E-501
M A
U R
P R
F
D B
S
S H
E E
T O
F
C R
IT
IC
A L P
U B
L
IC
F
A C
IL
IT
Y
O R
A N
G E
F
IE
L D T
X
G A
L V
E S
T O
N D
IS
T R
IC
T
G A
L V
E S
T O
N T
X
N.T.S.
DETAIL
TYPICAL ONE LINE DIAGRAM - SERVICE PANEL TO CLASSROOMS
SCALE: N.T.S.
DETAIL
TYPICAL RISER DIAGRAM - UTILITY POLE TO SERVICE PANEL
SCALE:
F E
M A D
R -4
-T
X
O R
A N
G E
F
IE
L D
SERVICE
120/240 V
250A 250A
CLASSROOM UNITS CLASSROOM UNITS
FUSE CUTOUT
METER
400 A
PANEL
SERVICE
OUTDOOR
250A
3 TAP BOXES MAY SERVE TWO OR THREE CLASSROOM UNITS.
TO ASSIST IN PULLING CONDUCTORS.
CONDUITS RUN FROM THE SERVICE PANEL ARE GRS. USE SWEEPS AND CONDULETS
PANEL WITH THREE 250 AMP BRANCH BREAKERS.
PROVIDE AND INSTALL INDUSTRY STANDARD OUTDOOR 400 AMP 120/240V SERVICE
KEYNOTES:
DEPTH 3 FT WHERE NOTED ON PLANS.
SERVICE TO BE LOCATED UNDERGROUND IN SCHEDULE 40 PVC CONDUIT AT BURY
1/0. VERIFY WITH LOCAL CODE REQUIREMENTS.
FEET APART. THE CODE REQUIRED GROUND CONDUCTORS ARE NO LARGER THAN
CONTRACTOR TO PROVIDE AND INSTALL TWO 10 FOOT GROUND RODS PLACED 6
GENERALLY FACE THE CLASSROOMS THAT IT SERVES.
GROUND FOR STABILITY. THE ORIENTATION OF THE SERVICE PANEL SHALL
X 6 TIMBER OR TWO 4 X 4 INCH TREATED TIMBERS. BURY TIMBER 3 FEET INTO
AWAY FROM POLE. THE SERVICE PANEL SHALL BE MOUNTED USING ONE TREATED 6
CONTRACTOR TO PROVIDE AND INSTALL SERVICE PANEL, APPROXIMATELY 6 FEET
WITH THE GROUND.
SERVICE PANEL. THE CONDUIT SHALL BE EMBEDDED INTO GRAVEL OR BURIED FLUSH
CONTRACTOR TO PROVIDE AND INSTALL CONDUIT AND CONDUCTORS TO THE
SOCKET.
CONTRACTOR TO PROVIDE AND INSTALL INDUSTRY STANDARD 400 AM METER
MAKE CONNECTION TO TRANSFORMER.
THREE 500 MCM CONDUCTORS. LEAVE ADEQUATE PIGTAIL LENGTH FOR UTILITY TO
CONTRACTOR TO PROVIDE AND INSTALL 3 INCH PVC CONDUIT, WEATHER HEAD AND
ENTERGY UTILITY.
POLE, TRANSFORMER AND ASSOCIATED ITEMS PROVIDED AND INSTALLED BY
120/240 V
KVA = SEE E-101, E-102
S O
L
IC
IT
A T
IO
N N
O
F
IL
E N
A M
E
D W
N B
Y
C K
D B
Y
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F
IL
E N
U M
B E
R
S
IZ
E
S U
B M
IT
T E
D B
Y
P L
O T S
C A
L E
P L
O T D
A T
E
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C O
N T
R A
C T N
O
D A
T E
A P
P R
®of Engineers
US Army Corps of Engineers
US Army Corps
15' TYP.
EXISTING GRADE
CONCRETE ANCHORS
CAST IN PLACE
6" TYP.
CONCRETE ANCHORS
CAST IN PLACE
ON GRADE
CONDUITS LAYING
BLOCK FROM ADHERING
TO KEEP CONCRETE
MATERIAL ON GROUND
PUT PLASTIC OR OTHER
3"
PLASTIC
SET ON
(TYP.)
CLASSROOM UNITS
PVC CONDUITS TO
GROUND LUG/BOLT
BLOCKS (TYP.)
TAP TERMINAL
GRS CONDUIT
INCOMING
/1
/2
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
O R
N G
E -5
X X
X .d g n
N .T .S
A N
S I
D
E L E
C T
R
IC
A L D
E T
A
IL
S
E-502
INCHES SPACE BETWEEN.
3. CONDUIT SPACING SHALL BE TO INDUSTRY PRACTICE AND NOT CLOSER THAN 2
ON PIPING.
WATER/WASTE PIPING. BLOCK UP CONDUITS WHERE REQUIRED TO AVOID LOAD
2. GENERALLY CONDUITS WILL BE RUN ABOVE GROUND AND INSTALLED ABOVE
FACILITATE WATER AND WASTER WATER PIPING.
1. CONDUITS CAN BE INSTALLED UNDERGROUND OR ABOVE GROUND TO
NOTES:
4 TAMP CONCRETE SO THAT IT IS WELL CONSOLIDATED.
SHEETING ON THE GROUND TO PREVENT ADHERING.
THE CONCRETE CONDUIT ANCHOR SHALL BE PLACED OVER PLASTIC OR OTHER
CONDUITS BY 2" AND BE 6" THICK.
CONCRETE CONDUIT ANCHOR TO EXTEND 3" PAST CONDUIT SIDE AND COVER
CONCRETE CONDUIT ANCHORS SHALL GENERALL BE PLACED EVERY 15 FT.
KEYNOTES:
N.T.S.
DETAIL
CONDUIT ANCHOR INSTALLATION
SCALE:
N.T.S.
DETAIL
SWITCHGEAR SETTING
SCALE:
N
L1
L2
UL LISTED CONNECTOR.
GROUND LUG SHALL BOND ENCLOSURE AND CONDUCTOR GROUND WIRES.
TWO 1/16" HOLES IN BOTTOM TO DRAIN.
SET TAP BOX ABOVE GROUND AND LEVEL GRAVEL SO THAT IT CAN DRAIN. DRILL
CONDUCTORS. UL LISTED 90° DC WITH INSULATING COVERS.
TAP TERMINAL BLOCKS SHALL BE CONFIGURED FOR INCOMING AND OUTGOING
FOR ALL CONDUIT ENTRANCES AND WIRE BENDING SPACE. UL LISTED.
TAP BOX ENCLOSURE SHALL BE TYPE 4 16 GA. CRS MINIMUM. SIZE PER CODE
KEYNOTES:
APPROX. 24" X 24"
S H
E E
T O
F
M A
U R
P R
F
D B
S C
R
IT
IC
A L P
U B
L
IC
F
A C
IL
IT
Y
O R
A N
G E
F
IE
L D T
X
F E
M A D
R -4
-T
X G
A L
V E
S T
O N D
IS
T R
IC
T
G A
L V
E S
T O
N T
X O
R A
N G
E F
IE
L D
S O
L
IC
IT
A T
IO
N N
O
F
IL
E N
A M
E
D W
N B
Y
C K
D B
Y
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F
IL
E N
U M
B E
R
S
IZ
E
S U
B M
IT
T E
D B
Y
P L
O T S
C A
L E
P L
O T D
A T
E
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C O
N T
R A
C T N
O
D A
T E
A P
P R
®of Engineers
US Army Corps of Engineers
US Army Corps
File details come from the government source that posted it.