Amendment 0006. The purpose of modification 0006 is to revise Section J and provide responses to industry questions.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
The purpose of this amendment is revise Section J and provide responses to Industry Questions, Attachment 4. Revisions to Section J, has been highlighted in yellow .
1. CONTRACT ID CODE PAGE OF PAGES
J 1 25
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 14-Oct-2016
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W9124M-16-R-0003
X 9B. DATED (SEE ITEM 11)
10-Aug-2016
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
14-Oct-2016
CODE
MICC, FORT BRAGG
MICC CENTER - FORT BRAGG
2175 REILLY ROAD STOP A
FORT BRAGG NC 28310-5000
W91247 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
W9124M-16-R-0003
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION J - LIST OF DOCUMENTS, EXHIBITS AND OTHER ATTACHMENTS
The following have been modified:
ATTACHMENT 4
Attachment 4.
GOVERNMENT RESPONSE TO CONTRACTOR QUESTIONS
Ques tion Nu
Reference Question Response
1 PWS C.1.7.17, RFP
Section L.3.3
1) C.1.7.17 states that our safety plan is to be included in our proposal. L.3.3 requires a 'summary' of our safety plan to be included in our proposal.
Which is required, our entire plan or a summary?
Our plan would far exceed the allowable page count for our proposal, but we are confused as to what a 'summary' should include....Can you provide guidance for this?
2) Please confirm that the maximum annual amount of $15 million is to be inserted in each 001 Line Item in Section B (along with the Manpower Reporting requirements items) since B.1 subsequently requires coefficient bids for each period.
3) Since C.3.10 indicates that an annual economic adjustment will be made in the UPB, is it not contrary to require a coefficient bid for each year?
1) A summary of the company safety plan is required in response to the solicitation. The entire company safety plan shall be submitted for approval after award, prior to commencing work.
2) The annual maximum value of the Job Order Contract for the Base Year is $15M.
The offeror should provide a proposed amount for CLINs 0001 & 0002 and each corresponding option year.
3) There will be NO economic adjustment applied. The Construction Task Catalog will be updated each year.
2 Section L.3.2 The table in Section L.3.2 lists the maximum page count at 30 pages for Tabs A-F in Volume II. TAB F contains Element 3, the Renovation Mock Project which includes a complete construction cost breakdown and technical narrative that may come out to be 30 or more pages alone. We request that this tab be excluded from the page restriction in Volume II, so that we have the ability to submit a complete mock project package.
See Amendment 0002, page count for TAB F Renovation Mock Project should read 10 pages.
3 Section L Are there any limitations on file size for the AMRDEC electronic submission?
See AMRDEC user guide at http://www.nps.edu/Visitors/AMRDEC_SAFE_Gettin g_Started_Guide.pdf
You may add up to 25 files per package, so long as the total file size does not exceed 2GB
4 Section L.3.3,b(3)(d)i, Section L.3.3,b(3)(d)i, states to include a detailed narrative describing the roles and responsibilities of the key staffing positions in accordance with PWS Section C.1.9, should this read C.1.8?
See Amendment 0002, Section L.3.3,b (3)(d)i should read C.1.8.
Section L.3.2 Section L.3.2 Proposal Preparation Instructions states that the proposal shall be organized into four volumes, however only three volumes are listed in the table. Will you confirm there are only three volumes to be submitted?
See Amendment 0002, Section L.3.,2. should read three volumes.
6 Section L Will PDF files be allowed in place of MS Word files? This helps keep the file size down and makes it easier to insert forms as necessary in the proposal package.
No MS 2013 Word files shall be used.
7 Tab E Volume 1
The requirements under Tab E and Tab F in Volume I require both a bid bond and verification of our bonding capacity. Is the bid bond for the mock project?
There is no requirement for a bid bond for a “mock project”.
8 C.1.8.5 & C.1.8.6. Can the roles of the Quality Control Manager and Safety Manager be combined if one person meets all qualifications?
No. The Safety Manager may possibly be dual hatted with another key position…but not with the QC Manager.
9 Many of these questions have an effect on how we will proceed with our proposal and management plan. Will you consider answering questions before the due date of September 9th in order to expedite the proposal planning process?
Proposal questions will be addressed after September 9 and issued with Amendment 0002. Proposal submission date has been updated.
10 Technical Exhibit 4 (TE 4) of the RFP
Technical Exhibit 4 (TE_4) of the RFP is a pdf version of the current Price Book created by Gordian for the Stewart JOC. Is the government going to have Gordian release a sample version of the software for this RFP?
No, the government does not have a sample version of the Gordian software for release.
11 C.3.3 Would it be acceptable to have a PMO located off Post in a nearby location, i.e. Hinesville, rather than having PMO in a job trailer on site?
The Government prefers the contractor have a PMO located on the Installation.
12 Technical Exhibit 4 (TE_4), Attachment 3, Technical Exhibit 4 (TE_4), Attachment 3, under HVAC Scope of Work (page 73 of 97), item #6.
The Contractor shall remove and replace the existing ceiling tiles as necessary to facilitate.
Please verify that this is to be a remove and re-install existing ceiling tile.
Yes, remove and reinstall existing ceiling tile.
13 Section J Attachment
In review of the Mock JOC Project (Attachment 3), the format of the disciplines is out of line with CSI format (starts with a Plumbing Scope) and there are disciplines that run together on the same page (Plumbing into HVAC) while others are on separate pages (Structural and Electrical). Please confirm that there are only the four scopes, Plumbing, HVAC, Structural and Electrical.
Yes, there are only four scopes disciplines, Plumbing, HVAC, Structural, and Electrical.
14 Section J Attachment
How do you obtain plans for SMS: U.S. Army Fort Stewart and Hunter Amy Air Field (HAAF) Georgia, Job Order Contract (JOC). Any help would be greatly appreciated. Is there a link to download plans?
If the question pertains to the Mock Project, there is only a floor plan and the scope of work.
Floor plan will be posted with Amendment 0002
15 The RFP for the Ft. Stewart/HAAF JOC states that the Proposal Due Date is October 8, 2016 which is a Saturday. Is this correct or subject to change?
See Amendment 0002 date has been updated.
16 We would like to request clarification for Item No.
1002 Option “Contractor Manpower Reporting”. I have attempted to access the data collection website (Caution-http://www.ecmra.mil < Caution-http://www.ecmra.mil > ) to review what is required to no avail. I keep receiving error codes. Is there an additional government cost for accessing the secure website? Please clarify exactly what is needed on page 33 of 96 of the solicitation: (9) Estimated data collection cost; is this for government costs that we are responsible for or labor costs that we will incur for performing the reporting requirements?
Website is as follows https://cmra.army.mil . There is no cost to use this website.
If you need any additional assistance, please refer to the Help & References section of CMRA, or contact the CMRA Help Desk at contractormanpower@hqda.army.mil. refer to the Help & References section MRA, or contact the CMRA Help Desk at contractormanpower@hqda.army.mil.
17 Section J Attachment
We have received an ITB on the attached Job but no Plans are Showing up on Insight I was hoping you could send these to me or point me in the right direction to getting them.
There is only a floor plan for the Mock Project and will be posted with Amendment 0002.
18 Section J Attachment
We are about to bid this project, but we do not have the drawings only the specifications, could you point me to somebody that can?
There is only a floor plan for the Mock Project and will be posted with Amendment 0002.
19 Section L Page 89 – L.3.3.b.(3)(e) – “e” is missing Can we consider this item to be omitted from the
RFP?
See Amendment 0002 for update.
20 The original RFP had a proposal due date of Wednesday, 12-October 2016, yet on the conformed RFP posted to FBO on 12-Aug 2016 the proposal due date was changed to Saturday 08-October 2016
– is the new Saturday date correct?
See Amendment 0002 for update.
21 We would also like to confirm that the due date for proposals is Saturday, 8 October 2016 @ 3:00 PM EST as listed in Amendment 1.
See Amendment 0002 for update
22 Are there any restrictions on maximum file size for the AMRDEC SAFE electronic proposal submission?
See AMRDEC user guide at http://www.nps.edu/Visitors/AMRDEC_SAFE_Gettin g_Started_Guide.pdf
You may add up to 25 files per package, so long as the total file size does not exceed 2GB
23 Section L Section L.3.2 states that electronic copies of our proposal in MS Word are required. MS Word files can be quite large, will you allow PDF files to be used instead – with the exception of the MS Excel worksheet?
No, MS 2013 Word files shall be used
24 Section L L.3.2 – Says proposals shall be organized into 4 Volumes – yet only 3 Volumes are listed – Please clarify
See Amendment 0002, Section L.3.,2. should read three volumes.
25 Section L L.3.2 – Volume III – 2 electronic copies? Isn’t this submitted as electronic copy through AMRDEC – are you wanting us to submit it twice?
Only one Submission is required through the use of
AMRDEC.
26 Section L L.3.2 – All these Volumes will be containing documents that need to be scanned or merged into one document. Want to clarify that we can submit our proposal as a .pdf
\See instructions at L.3.2. depending on the volume will depend if you should use MS Word 2013 or MS Excel 2013. PDF or flat files will not be considered adequate
27 Section L L.3.2 – Volume III – you want as unprotected.
Again, want to confirm this can be submitted as a .pdf that is unprotected.
See instructions at L.3.2. Depending on the volume will depend if you should use MS Word 2013 or MS Excel 2013. PDF or flat files will not be considered adequate
28 Is Teaming of a Prime/Sub Team allowed?
Yes, teaming of a Prime/Sub Team is allowed.
30 Want to confirm there is no Past Performance required for this RFP.
No Past Performance is required.
31 The amount used for each Fort Stewart and HAAF is $15M, and another $1.5M for Non pre-price work, making the base year over $30M. The annual maximum is stated as $15M.
Is this a total annual maximum for combined Fort Stewart and HAAF?
If so, should the dollar values for the Estimated maximum contract value per year be adjusted to reflect a combined $15M for the year?
The annual yearly maximum is $15M as stated. It is inclusive of Ft. Stewart, HAAF and all types of work.
32 C.1.8.2. Is it allowable to dual-hat key personnel?
Particularly while the work is ramping up.
The only position that shall not be dual hatted is the Quality Control Manager.
33 What are the historical annual amounts performed? Historically the JOC has performed at $12M per year.
Note that real time work requirements and budgets dictate actual work performed, and the guaranteed minimums and maximums are as stated in the solicitation.
34 Who is the incumbent contractor?
There is no incumbent contractor.
35 The draft solicitation lists the bonding capacity requirements at $75M aggregate ($15M per year).
Will this be revised when the solicitation is released or this figure accurate?
See Final solicitation posted to FBO on 10 Aug 16.
See FAR 52.228-15, bonding capacity of $75M aggregate ($15M per year).
36 Section L Is there a preferable version for the Microsoft Excel to be used in the pricing of the mock project?
See Amendment 0002, has been change to include Price, Renovation Mock Project, MS Excel 2013
37 L 3.2 a. Page 85 4 volumes are called out, only 3 are identified as to content. Is there going to be a required Volume 4?
L 3.2 c. Page 86 Page Limit Includes. All appendices, charts, graphs, diagrams, tables, photographs, drawings, etc. All Appendices, Charts, Graphs, Diagrams, Tables, Photographs, Drawings or fold-outs used for charts or tables (8.5 x 14 fold-outs) will count as one (1) page
Does this mean that if we have, for example, eight total pages of various "Appendices, Charts, Graphs, Diagrams, Tables, Photographs, Drawings or fold-outs used for charts or tables (8.5 x 14 fold-outs)" that it would count for only one page or for eight?
Using the example provided, each document would count as one (1) page, for a total of eight (8) pages.
38 Section L, Vol II, Tab D, iii
Section L, Vol II, Tab D, iii states the offeror shall provide a summary of the company’s safety plan.
Section M, Factor 1, Element 1(c) and Section C, para C.1.7.17 state that the offeror’s submitted company safety plan will be evaluated. Are we required to submit a summary of our company safety plan, as specified in Section L, or are we required to submit our Company Safety Plan, in it’s entirety, as stated in Section M?
See Amendment 0002, C.1.17. The offeror shall provide a summary of the company’s safety plan. The full safety plan must be submitted for approval after award, prior to commencing work.
39 C.1.17 If our entire company safety health and accident plan is required, can it be excluded from the 30-page restriction in Volume II?
See Amendment 0002, C.1.17. Only a summary of the company’s safety plan is required in response to the solicitation.
40 C.1.8.2. The Key Personnel Education and Experience requirements listed in Section C.1.8.1.1 (PM) and C.1.8.13 (QCM) state the personnel may show additional work history in lieu of educational requirements. Would you also consider this for the other positions, including the Superintendent, Quality Control Inspector, and Estimator/Planner?
Concerning the experience and education requirements for the Superintendent, Quality Control Inspector, and Estimator/Planner, it is outlined in the solicitation as:
1) Graduate of an accredited technical in the appropriated field of study relating to the construction trade.
2) Equitable qualifications through a recognized union in the construction arena. e.g. Journeyman level
3) Be a current or former licensed owner/operator of a business specializing in the construction field.
41 Is there a preferred or required scheduling software?
(SOW C.5.4 does not specify).
No, there is not a preferred or required scheduling software.
42 Section J Attachment
SOW 12.26 requires (b) Microstation format (.dgn files), would AutoCAD-converted files be acceptable?
No. Microstation format (.dgn files) is a requirement.
43 a) I have an RFI on the bonding requirements - the RFP states that you have to have a $75M aggregate capacity and you can get up to $15M per year. All boding companies base aggregate amounts based on a 1 year period. So your RFP require should be $1- 2M single project with a $15M aggregate capacity per year - pls advise???
b) Also what is the amount of the bid bond - 20% of the guaranteed contract minimum per the FAR requirements?
a) See FAR 52.228-15, bonding capacity of $75M aggregate ($15M per year)
b) See FAR 52.228-1 The amount of the bid guarantee shall be 20% percent of the bid price or $3,000,000.00, whichever is less
44 Please see the attachment for our formal request for product substitution consideration on the U.S. Army Fort Stewart and Hunter Amy Air Field (HAAF) Georgia, Job Order Contract (JOC) project. We are submitting our MEL-ROL®Rolled, Self-Adhering Waterproofing Membrane for your consideration.
We appreciate your time in reviewing our request.
This is a good product, however, at this time please stick with the current scope and specs for this mock project.
The surface is already painted. We are simply asking for new paint over existing.
This is only a mock project and will NOT actually be performed.
45 In your general conditions you included sales tax. Is Georgia a non-exempt state for federal projects?
See http://dor.georgia.gov/sales-use-tax-fees-excise-taxes-regulations
46 Are there specific mandatory staffing increases required with increased work volume?
No SPECIFIC mandatory staffing increases are required with increased work load. The contractor is required to maintain adequate staffing to handle the workload in a satisfactory manner that meets all timeline requirements.
47 C.3.3. Will a location be provided on either base to set a job trailer for the duration of the project or is the contractor to have off-site facilities? If a job site trailer is required on base are they to be located at one specific base or at both sites?
C.3.3. Contractor’s Site Location/Lay-Down Site. The Contractor will be provided the use of a parcel of land at Fort. Stewart and at Hunter Army Airfield. The land will not be transferred to the Contractor and will remain in Government's control. These parcels of land shall be specified by the COR. Security fencing for the Contractor’s compound/storage area shall be the responsibility of the Contractor.
48 Section J Attachment
Is there a floor plan available for the seed project located within the RFP?
Yes, a floor plan available for the seed project and will be posted with Amendment 0002.
49 C.5.5 & C.5.7. Items (dd) under G&A state,” Removing and returning owner’s furniture and furnishings at jobsite”. Can you please clarify what types of furnishings are to be included in the coefficient?
Also, does “removing and returning” cover moving furniture only within the limits of construction or removing items off-site? Often times task such as moving and storing furniture, disassembly and reassembly of modular furniture exceeds the value of actual construction and is not included in the coefficient.
Removing and replacing typical office furniture such as desks, chairs, tables, and filing cabinets is included as a part of the coefficient.
Modular furniture is NOT included in this requirement.
It would be addressed with specific construction line items in the Construction Task catalog. All of this is addressed in the Construction Task Catalog.
Typically the furnishings are placed in a protected area on site.
50 Items (kk) states “all protection of surfaces, etc.”
Will exceptions be taken in areas such as servers rooms and other sensitive clean rooms where dust protection can make up a significant portion or the work?
For “out of the ordinary” dust protection requirements, specific protection line items in the Construction Task Catalog are employed. Routine dust protection shall be considered in the contractor’s coefficient. The Construction Task Catalog addresses this requirement.
51 C.1.11.1. Item (i) “Mobilization and Demobilization” Does this include mobilizing and demobilizing of line itemed equipment such as cranes, fork lifts etc?
In this case mobilization and demobilization pertains to the entire JOC program, i.e. the “contract”.
This reference does not pertain to individual task orders and the associated line itemed equipment.
52 Section J Attachment
Are we to apply the CCI to the seed project?
No, there is no option to apply a CCI in the Construction Task Catalog. The Catalog is already tailored/customized to this locality.
53 Upon reviewing the requirements, we noted that neither experience nor past performance was required to qualify for award of this contract. In order to promote fair competition between qualified contractors, we would like to request that the evaluation requirements include relevant experience or past performance.
In accordance with FAR 15.304 (3)(iii) the Contracting Officer (KO) has made a determination not to include past performance as an evaluation factor for this acquisition.
As part as the responsibility determination, the KO will use FAR 9.104-1 to determine if an offeror is deemed responsible, which includes ensuring the offeror has a satisfactory performance record.
This contract will be awarded based upon Lowest Price, Technically Acceptable basis (LPTA). FAR 15.101-2 requires any finding of “unacceptability” for past performance or experience under this type of evaluation to be referred to the Small Business Administration for a Certificate of Competency (COC).
Since the Contracting Officer is required under FAR 9.104-1 to determine if an awardee has a satisfactory performance record and necessary resources and technical capability to perform, there is no value added to the process to add this as an evaluation criteria.
54 Section L, Volume II
– Mission Capability Proposal
Is the required “phase-in plan” intended to cover JOC level considerations or individual task orders?
Requirements will differ for task orders. Is the desired “phase-in plan” a templatized plan which can be modified and applied to individual task orders of varying scope, complexity and type?
See C.1.11. Phase-in plan is required at the JOC level.
55 TE 3 Carpet Samples and patterns: Need clarification for manufacturer, style, type to provide samples. Not enough information is provided in the Detailed Submittal Requirements or in the Technical Specifications to provide sample.
Submittals shall meet specifications outlined in the solicitation. No particular manufacturers are specified.
56 TE 3 Ceramic Tile and grout colors: Need clarification for manufacturer, style, type to provide samples. Not enough information is provided in the Detailed Submittal Requirements or in the Technical Specifications to provide sample. Type of grout, epoxy, non-epoxy, etc. needs to be selected to provide correct color samples.
57 TE 3 Quarry Tile and Grout Colors: Need clarification for manufacturer, style, type to provide samples. Not enough information is provided in the Detailed Submittal Requirements or in the Technical Specifications to provide sample. Type of grout, epoxy, non-epoxy, etc. needs to be selected to provide correct color samples.
58 TE 3 Plastic Laminate samples: Need clarification for manufacturer, style, type to provide samples. Not enough information is provided in the Detailed
59 TE 3 Vinyl Flooring (VCT), cove base & vinyl transition strip samples: No information is provided to identify the VCT (style, pattern, size): size, type and style of the cove base or transition strips to provide samples.
Clarifying information is not provided in the task description.
60 TE 3 Acoustical Ceiling Panels: Need clarification for manufacturer, style, pattern to provide samples. Not enough information is provided in the Detailed
61 Volume I – TAB E – Bid Bond – We did not see any instructions to mail in the original & wanted to confirm that just a scan of our Bid Bond meets the RFP requirements?
See RFP Section I FAR 52.228-1 BID GUARANTEE.
62 Question/Answer #28 – States that Teaming is Allowed – We want to know if placing our Teaming Agreement in Volume I – TAB C is acceptable?
See RFP section L.3.3. Proposal Content (3) Tab C.
63 Question/Answer #29 is missing – Is #29 yet to be posted or just a miss-numbering matter and Q&A #29 can be considered omitted?
Question 29 is omitted.
64 Question/Answer #40 – states the required experience & education of personnel, yet Volume II
– TAB D (i) was updated to show that No resumes are required. We want to ask what meets the RFP requirements regarding the conveying of the experience & education of our key personnel.
Section RFP Section M Element 1 JOC Program Management Approach (a) Management Plan demonstrates the Contractor’s ability maintain their own workforce and the ability manage and maintain the required percentage (at a minimum at least 15%) of “in house” work performance into the JOC program.
The offeror describes how the efforts of this workforce will (or will not) integrate with subcontractor efforts.
The offeror demonstrated the capability to meet, sustain, and grow the workforce required to successfully perform the JOC requirements. The offeror described its Management Plan with the division of authority, between the home /corporate office and the site office and the offeror’s plan for daily and strategic management of resources. The management plan included a diagrammed organizational chart, with a detailed narrative describing the roles and responsibilities of the key staffing positions in accordance with PWS Section C.1.8.
65 Please clarify the roles of the Quality Control Manager and Quality Control Inspector.
Per C.1.8.5 Quality Control Manager is to perform daily inspections and be active at each jobsite.
C.1.8.8 - Doesn’t clearly define the Quality Control Inspector role/responsibility.
Can you please confirm if the Quality Control Manager as the overall managing role in regards to quality and the Quality Control Inspectors are supposed to be active at each jobsite and perform daily inspections.
Yes, this statement is correct. The Quality Control Manager is responsible for the Contractor's Quality Control Program and is the lead over the Quality Control Inspectors. The Quality Control Inspectors are required to be active at each jobsite and perform and document daily inspections.
66 Question #12 of the contractor’s Q&A issued with Amendment #3 states the ceiling tiles are to be removed and re-installed. The HVAC SOW, revised with Amendment #5, states to replace. Are they to be re-used or replaced with new?
Re-use existing tiles.
67 The floor plan provided with Amendment #5 has a note, “4’-0” HIGH LOW WALL ALIGN WITH COLUMN FURR OUT” The structural SOW does not refer to any additional wall construction – please confirm that this wall already exists.
Yes, this wall already exists.
68 Addendum #5, the revised HVAC SOW, item #2 requires the replacement of the existing exhaust fan of same type, size, voltage and CFM. Could the government supply that information?
The manufacturer and model were specified in the revision but here is the complete info. The exhaust fan is a Gemini 180 series, model GC-186, 115 volts, 231 CFM at 0.0SP. Manufactured by the Loren Cook Company.
(End of Summary of Changes)