Round_Two_Questions_and_Answers.pdf

PDF 113 KB Posted

Attached to
HVAC system replacement Federal contract opportunity
Solicitation number
W9124A-17-T-0010
Issued by
Department of the Army Materiel Command Army Contracting Command Aberdeen Proving Ground

About this file

Round two questions answered after the Site Visit on 04/27/2017.

View the file

Other files for this federal contract opportunity

Other files attached to HVAC system replacement, newest first.
File Type Posted
Round_Two_Additional_Questions_and_Answers_CORRECTION.docx DOCX document
Round_Two_Additional_Questions_and_Answers.docx DOCX document
Round_One_Questions_and_Answers.docx DOCX document
A07-Solicitation.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Round two questions from site visit. Metzger, Craig A Mr CIV USA IMCOM | UNITED STATES ARMY

HVAC system Questions and Answers for W9124A-17-T-0010

1.) Will contractor be responsible for removal of the old HVAC unit from property or will it be left onsite?

A: Contractor to provide removal

2.) SOV item 3.2.1.1 Recover refrigerant in current system. Will recovery cylinders be provided or should contractor include in bid proposal?

A: Contractor to provide and dispose of old refrigerant

3.) I heard the heater is broken, but the A/C still works. Can we replace the heater or do we have to replace the whole HVAC?

A: Replace entire unit with new.

4.) When specifically is the requirement due?

A: The requirement, as stated in the solicitation, shall be received electronically via e-mail no later than

10:00 AM local Arizona time.

5.) Does new system need to be tied into the existing building automation?

A: The system is not tied into any other system. It is a stand-alone system, which only provides cooling/heating for room 122. The unit does need to be controlled by a thermostat, to be located in a convenient location within the room.

The following questions follow the site visit, which encompassed visiting room 122 (the electronics shop), the outside fenced area (the heat exchanger/electrical area) & room 121 (the breaker room, labelled ‘mechanical room#2’), as well as, two rooms that adjoin the HVAC areas.