Appendix A Drawings.pdf

PDF 3 MB Posted

Attached to
USACE SPK DBB Construction - B-4156 Electrical Upgrades – Dugway Proving Ground, UT
Solicitation number
W9123824R0028
Issued by

About this file

This document contains the drawings and specifications for the electrical upgrade of Building 4156 at Dugway Proving Ground in Utah. The key details are:

The project consists of relocating and replacing the transformer at Building 4156, performing approximately 100 feet of trenching and new conduit, upsizing the generator, replacing the primary switchgear and automatic transfer switch. The magnitude of construction is between $1,000,000 and $5,000,000. The procurement will be a design-bid-build (DBB) contract, issued as a total small business set-aside with proposals due around August 12, 2024. The North American Industry Classification System (NAICS) code is 238210 - Electrical Contractors and Other Wiring Installation Contractors, with a $19 million small business size standard. The Product and Service Code (PSC) is anticipated to be Z2AA - Repair or Alteration of Office Buildings. A pre-proposal conference and/or site visit may be conducted. The solicitation documents include drawings and specifications for the electrical upgrades, which cover demolition plans, site plans, power plans, one-line diagrams, switchgear layout, and details.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BUILDING 4156 – ELECTRICAL UPGRADES 2134

APPENDIX A

DPG B4156 DRAWINGS

BUILDING 4156 – ELECTRICAL UPGRADES 2134

APPENDIX A

DPG B4156 ELECTRICAL UPGRADES

DUGWAY PROVING GROUND, UTAH

APPENDIX A – DRAWINGS

G-001 COVER SHEET

G-002 HAUL ROUTE

E-001 ELETRICAL LEGEND AND ABBREVIATIONS

ED101 ELECTRICAL DEMOLITION PLAN

ED102 DEMOLITION PLAN

ES101 ELECTRICAL SITE PLAN

E-101 POWER PLAN

E-102 PHASING

E-401 SWITCHGEAR LAYOUT

E-501 DETAILS

E-502 DETAILS

E-503 GROUNDING SYSTEM DIAGRAM

E-601 ONE-LINE DIAGRAM EXISTING

E-602 ONE-LINE DIAGRAM NEW

E-603 PANEL SCHEDULES

ISSUE DATE:

US Army Corps of Engineers

SOLICITATION NO.:

CONTRACT NO.:

Sacramento District

W91328-24-R-0028

W91328-XX-X-XXXX

MAY 2024

DUGWAY PROVING GROUND, UTAH

BUILDING 4156

ELECTRICAL UPGRADE

PN 471135

APPROVED FOR PUBLIC RELEASE. DISTRIBUTION UNLIMITED

DISTRIBUTION STATEMENT A

Chief, Design Branch

USACE SACRAMENTO SIGNATURE BLOCK

PREPARED UNDER THE DIRECTION OF:

Chad W. Caldwell P.E.

Col. Corps of Engineers, Sacramento District

APPROVED BY:

/s/ Mark (Rock) DeRocchi P.E.

Chief, Engineering Division

APPROVED FUNCTIONAL ADEQUACY:

/s/ Rick Wells R.A.

This project was designed by the Sacramento District of the U. S. Army Corps of Engineers.The initials or signatures and registration designations of individuals appear on these project documents within the scope of their employment as required by ER 1110-1-8152

G-001

S.

M

IT

C

H

EL

L

L

S A

E C

H A

O

L

N E

M E

T Z

G-001 - Cover Sheet.dwg

D E

S I G

N E

D

B

Y

D E

S C

R I P

T I O

N

A

M A

R K

S I Z

E

S U

B M

I T

T E

D

B

Y

S.

M

IT

C

H

EL

L

D A

T E

C O

N T

R A

C T

N

O

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

I S

S U

E

D

A T

E

SHEET ID

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

US Army Corps of Engineers

U S

A

R M

Y

C

O R

P S

F

E

N G

I N

E E

R S

S P

E

D E

S I G

N

F

I L

C O

R R

EC

TE

D F

IN

AL

D U

G W

A

R O

V I N

G

G

R O

U N

D

U

T

H

B U

I L D

I N

G

EL

EC

TR

IC

AL

U

PG

R

AD

C O

V E

R

S

H E

E T

S A

C R

A M

E N

D

I S

T R

I C

T

J S

TR

EE

T

SA

C R

AM

EN

TO

, C

A

M

AY

S

O L I C

I T

A T

I O

N

N

O

W

R

W X

X X

X

X X

X

AN

SI

D

STATE MAP

NTS

PROJECT

LOCATION

N

N AREA MAP

NTS

DITTO

UTAH

DUGWAY

GENERAL SHEETS

G-001 COVER SHEET

G-002 HAUL ROUTE

ELECTRICAL SHEETS

E-001

ED101

ES101

ED102

E-101

E-102

E-501

E-502

E-503

E-601

E-603

ELECTRICAL LEGEND AND

ABBREVIATIONS

ELECTRICAL DEMOLITION PLAN

ELECTRICAL SITE PLAN

DEMOLITION PLAN

POWER PLAN

PHASING

DETAILS

DETAILS

GROUNDING SYSTEM DIAGRAM

ONE-LINE DIAGRAM EXISTING

ONE-LINE DIAGRAM NEW

PANEL SCHEDULES

E-602

E-001 ELETRICAL LEGEND AND ABBREVIATIONS

ED101 ELECTRICAL DEMOLITION PLAN

ED102 DEMOLITION PLAN

ES101 ELECTRICAL SITE PLAN

E-101 POWER PLAN

E-102 PHASING

E-401 SWITCHGEAR LAYOUT

E-501 DETAILS

E-502 DETAILS

E-503 GROUNDING SYSTEM DIAGRAM

E-601 ONE-LINE DIAGRAM EXISTING

E-602 ONE-LINE DIAGRAM NEW

E-603 PANEL SCHEDULES

G-002

M

IT

C

H

EL

L

L

S A

E C

H A

O

L

N E

M E

T Z

D E

S I G

N E

D

B

Y

D E

S C

R I P

T I O

N

A

M A

R K

S I Z

E

S U

B M

I T

T E

D

B

M

IT

C

H

EL

L

D A

T E

C O

N T

R A

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

I S

S U

E

D

A T

E

SHEET ID

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

US Army Corps of Engineers

U S

A

R M

Y

C

O R

F

E

N G

I N

E E

R S

S P

D E

S I G

N

F

I

D U

G W

O

V I N

G

G

R O

U N

D

U

T

H

B

I L D

I N

G

EL

EC

TR

IC

AL

U

PG

R

AD

E

H A

U

T E

S A

C R

A M

E N

S

T R

I C

T

J S

TR

EE

T

SA

C R

AM

EN

TO

, C

A

M

AY

S

O L I C

I T

A T

I O

N

N

O

W

R

W X

X X

X

X X

X

AN

SI

D

K

T

Y

MAIN GATE

S

T

A

K

DPG LANDFILL

ENGLISH

VILLAGE

DITTO

HAUL

ROUTE

SITE

ACCESS

GATES

PROJECT

BOUNDARY

FENCE

LINE

B ST

C ST

A ST

T

H

S

T

R

D

S

T

N

D

S

T

N

N

NOTES:

1. CONTRACTOR STAGING AND STORAGE AREA TO BE DETERMINED AT THE PRE-CONSTRUCTION MEETING.

2. CONSTRUCTION CONTRACTORS MAY ACCESS THE BASE THROUGH THE MAIN GATE.

3. THE HAUL PATH SHOWN FROM THE MAIN GATE IS APPROXIMATELY 11.5+ MILES. CONTRACTOR MUST COORDINATE

WITH THE BASE OPERATIONS FOR COMPLYING WITH OPERATIONAL SAFETY REQUIREMENTS

4. UPON ARRIVAL AT A SECURITY GATE, ALL VEHICLE OCCUPANTS WILL BE REQUIRED TO SHOW IDENTIFICATION

BEFORE ENTERING THE BASE. A PICTURED IDENTIFICATION SUCH AS A DRIVER'S LICENSE WILL BE REQUIRED.

5. SPEED LIMIT: UNLESS OTHERWISE POSTED, THE SPEED LIMIT ON BASE IS 25 MPH

6. ALL TRUCKS MUST HAVE COMPANY NAME LOGOS ON THE DOOR SIDES.

7. NO PRIVATELY OWNED VEHICLES (POV) ALLOWED WITHIN THE CONSTRUCTION SITE.

8. THE CONTRACTOR SHALL VERIFY THE WORKING HOURS WITH THE BASE SECURITY FOR APPROVAL. PERSONNEL

CANNOT SHOW UP AT THE GATE WITHOUT PRIOR NOTIFICATION FOR ACCESS AND EXPECT TO GAIN ACCESS.

PROJECT SITE MAP

FIRST

AID

DINER

C O

M M

STARK RD

60003000

15003000 12000

C O

R R

EC

TE

D F

IN

AL

FLUSH FLOOR MOUNTED NEMA 5-20 DUPLEX RECEPTACLE

NEMA 5-20 DUPLEX RECEPTACLE.

FUSED DISCONNECT SWITCH. SIZE FUSES FOR EQUIPMENT BASED ON

MANUFACTURER RECOMMENDATIONS

SWITCHGEAR

POWER WIRING

EXTERIOR SITE

ABBREVIATIONS

NEMA 5-20 QUADRUPLEX RECEPTACLE

GROUNDING

DOWN CONDUCTOR CONNECTION TO GROUND

GROUNDING ROD

STATIC GROUNDING RECEPTACLE

MOTOR, SIZE AS SHOWN, OR PER MECHANICAL AND PLUMBING SCHEDULES.

J JUNCTION BOX OR EQUIPMENT BOX, SIZE VARIES

UNFUSED DISCONNECT SWITCH.

WHEN ADJACENT TO MOTOR, COMBINED MOTOR STARTER/DISCONNECT

SINGLE LINE DIAGRAM

A

UTILITY METER

SECONDARY UNIT SUBSTATION TRANSFORMER

CIRCUIT BREAKER

FUSED DISCONNECT

BREAKLINE

MOTOR

LUMINAIRE TAG. IF SHOWN, SECOND LINE IS SWITCH LABEL

FOR LUMINAIRE (SEE BELOW). SEE LUMINAIRE SCHEDULE,

SHEET E-501.

CALLOUTS

A-B

SWITCH TAG. FIRST LETTER DESIGNATES ROOM/AREA.

SECOND LETTER DESIGNTATES SWITCH SYSTEM IN ROOM.

M

EF-1

MECHANICAL OR PLUMBING EQUIPMENT TAG. SEE HVAC

EQUIPMENT SCHEDULES, SHEET M-601, OR PLUMBING

EQUIPMENT SCHEDULES, SHEET P-601.

(PP-1) - (1)

CIRCUIT CALLOUT. FIRST PERENTHESES IS PANEL NAME,

SECOND PERENTHESES IS CIRCUIT NUMBER IN THAT PANEL.

1 KEYNOTE CALLOUT. SEE KEYNOTE LEGEND ON RELEVANT

SHEETS.

SPD SURGE PROTECTIVE DEVICE

ARROW INDICATES HOMERUN OR CONTINUATION OF CIRCUIT.

HOMERUN WILL BE ANNOTATED WITH PANEL/CIRCUIT NUMBER.

DOTTED TICK MARK IS GROUND, LONG TICK MARK IS NEUTRAL,

SHORT TICK MARKS ARE NUMBER OF PHASE CONDUCTORS.(P1)-(1)

GENERAL LINES

DEMOLISHED

NEW

A-101

1 VIEW CALLOUT. TOP IS DETAIL NUMBER OF VIEW,

BOTTOM IS SHEET THAT VIEW APPEARS ON.

MATCHLINE

UNAFFECTED

A AMPERE

AC ABOVE COUNTER

ADA AMERICANS WITH DISABILITIES ACT

AFF ABOVE FINISHED FLOOR

AL ALUMINUM

1/C ONE CONDUCTOR

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CU COPPER

EF EXHAUST FAN

EMT ELECTRICAL METALLIC TUBING

EWC ELECTRIC WATER COOLER

FACP FIRE ALARM CONTROL PANEL

FM FREQUENCY MODULATION

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTION

HACR HEATING AIR CONDITIONING REFRIGERATION

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

HT HEIGHT

HZ HERTZ

IDS INTRUSION DETECTION SYSTEM

J JUNCTION BOX

KWH KILOWATT HOUR

LCP LIGHTING CONTROL PANEL

MCB MOLDED CASE CIRCUIT BREAKER/MAIN CIRCUIT BREAKER

MH METAL HALIDE

MLO MAIN LUGS ONLY

MTD MOUNTED

NEC NATIONAL ELECTRICAL CODE

NF NON FUSED

NO. NUMBER

OS OCCUPANCY SENSOR

PH PHASE

PIR PASSIVE INFRARED

RGS RIGID GALVANIZED STEEL

RMF RISK MANAGEMENT FRAMEWORK

TTB TELEPHONE TERMINAL BACKBOARD

TV TELEVISION

TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR

UNO UNLESS NOTED OTHERWISE

V VOLT

VA VOLTAMPERE

VVD VARIABLE VOLUME DAMPER

W WATTS

WP WATER PROOF

XFMR TRANSFORMER

LOC LOCAL OPERATING CONSOLE

ACU AUTONOMOUS CONTROL UNIT

MNS MASS NOTIFICATION SYSTEM

NEC NETWORK ENTERPRISE CENTER

CCTV CLOSED CIRCUIT TELEVISION

DT DUAL TECHNOLOGY (OCCUPANCY SENSOR)

U ULTRASONIC

DS DAYLIGHT SENSOR

PV PHOTOVOLTAIC

GND GROUND

LED LIGHT EMITTING DIODE

DVR DIGITAL VIDEO RECORDER

GROUNDING ROD TEST WELL

ACS ACCESS CONTROL SYSTEM

NOCT NOMINAL OPREATING CELL TEMPERATURE

MPPT MAXIMUM POWER POINT TRACKING

GENERAL NOTES

1. NOT ALL SYMBOLS SHOWN MAY BE USED IN

THIS DRAWING SET.

2. UNLESS NOTED OTHERWISE, ALL

CONDUCTORS SHALL BE COPPER.

3. TYPICALLY, REGULAR 20 AMP BRANCH

CIRCUITS SHALL BE SUPPLIED WITH #12

COPPER CONDUCTORS FOR HOT, NEUTRAL,

AND GREEN EQUIPMENT GROUND

CONDUCTORS, IN MINIMUM 3/4" CONDUIT.

4. IF CONTRACTOR INSTALLS MORE THAN 3

CURRENT CARRYING CONDUCTORS IN A

RACEWAY, CONTRACTOR SHALL BE

RESPONSIBLE FOR APPLYING AMPACITY

DERATING FACTORS TO THE CONDUCTORS,

AND RESIZING THE CONDUCTORS AS

NEEDED PER NEC ARTICLE 310.15(B)(3)(a).

5. UNLESS NOTED OTHERWISE THE WORD

DEMOLISH SHALL MEAN THE REMOVAL OF

SAID EQUIPMENT AND ASSOCIATED

COMPONENTS, AS DIRECTED BY THE

CONTRACTING OFFICER'S

REPRESENTATIVE.

6. THE WORD "DEMOLISH" TO MEAN UNLESS

DIRECTED OTHERWISE, THE CONTRACTOR

SHALL HAUL AWAY ALL DEMOLISHED

HAZARDOUS AND NON-HAZARDOUS

MATERIAL AND SHALL TRANSPORT THEM

OFF BASE/POST AND DISCARD AT A

LOCATION THAT MEETS STATE AND

FEDERAL LANDFlLL DISPOSAL

RESTRICTIONS.

7. THE WORD "PROVIDE" SHALL MEAN TO

"FURNISH AND INSTALL".

8. THE WORD "DISTRIBUTION" SHALL MEAN

"FROM POWER/FUEL SOURCE TO

LOAD/RECIPIENT".

9. THE WORD "MINIMIZE" SHALL MEAN

"REDUCE TO THE SMALLEST POSSIBLE

AMOUNT".

10. THE CONTRACTOR IS RESPONSIBLE FOR

REPAIRING CONTRACTOR CAUSED DAMAGE

TO EXISTING FEATURES IN ACCORDANCE

WITH LOCAL STANDARDS AT CONTRACTORS

EXPENSE AND NO ADDITIONAL COST TO THE

GOVERNMENT AND/OR OWNER.

CONTRACTOR REPAIRS TO RESTORE

DAMAGED COMPONENTS AND/OR

INFRASTRUCTURE SHALL BE TO LIKE NEW

CONDITION.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR

TESTING, STARTUP AND COMMISSIONING OF

NEW ELECTRICAL COMPONENTS AND FOR

RESTORING 100% FUNCTIONALITY OF

ELECTRICAL SYSTEM.

12. THE FACILITY CAN NOT BE WITHOUT

POWER. CONTRACTOR SHALL PROVIDE

TEMPORARY POWER TO THE BUILDING AT

ALL TIMES WHEN BUILDING IS NOT ON

COMMERCIAL POWER. THE ALLOWABLE

OUTAGES ARE WHEN POWER IS

TRANSFERED TO TEMPORARY POWER.

TRANSFORMER

ELECTRICAL MANHOLE

EXISTING ITEMS TO BE REMOVED

OVERHEAD PRIMARY ELECTRICAL LINE.

OVERHEAD SECONDARY ELECTRICAL LINE.

EX

HANDHOLE. "E" OR "C" DENOTES ELEC OR COMM

EP

ES

E

ESx

UNDERGROUND PRIMARY

UNDERGROUND SECONDARY

H

M

PULL BOX. "E" OR "C" DENOTES ELEC OR COMMPB

C

E

SM SINGLE MODE

REFERENCES

ALL FEATURES OF WORK SHALL MEET THE

FOLLOWING CRITERIA, WHERE APPLICABLE. THIS

LIST IS NOT ALL-INCLUSIVE. SEE SPECIFICATIONS

FOR ADDITIONAL CRITERIA.

NFPA 70, NATIONAL ELECTRICAL CODE (NEC), 2023

NFPA 70E, 2024

NFPA 75, 2024

NFPA 101, 2024

IEEE C2, 2023

IEEE 1584, 2018

ASHRAE 90.1, 2022

ASHRAE 189.1, 2020

UFC 1-200-02, Ch. 2, 2022 UFC 3-501-01, Ch. 2, 2023 UFC 3-520-01, Ch. 2, 2021 UFC 3-530-01, Ch. 1, 2023 UFC 3-550-01, Ch. 3, 2019 UFC 3-560-01, Ch. 3, 2023 UFC 3-575-01, Ch. 1, 2021 UFC 3-580-01, Ch. 1, 2016 UFC 4-010-01, Ch. 2, 2022

GFCI GROUND FAULT CIRCUIT INTERRUPTER

AC ABOVE COUNTER

WP WEATHER PROOF (SHALL ALSO HAVE GFCI)

IG ISOLATED GROUND

LETTER DESIGNATIONS ON

RECEPTACLES INDICATE

DIFFERENT TYPES AS FOLLOWS:

SG

DRAWOUT CIRCUIT BREAKER

AUTOMATIC TRANSFER SWITCHATS

ATS AUTOMATIC TRANSFER SWITCH

SG SWITCHGEAR

GEN GENERATOR

SWITCHBOARDSG

DPW DIRECTORATE OF PUBLIC WORKS

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

File Path:

Plot Date:

M A

R K

D E

S C

R

IP

T

IO

N

D:\Desktop\Projects\Dugway Proving Grounds - UT\B4156\BIM\B4156_Electrical_New.rvt

24-Apr-24 11:03:27

E-001

E L E

C T

R

IC

A L L

E G

E N

D A

N D

A B

B R

E V

IA

T

IO

N

S

D U

G W

A Y

P R

O V

IN

G

G R

O U

N D

U

T A

H

S A

C R

A M

E N

T O

D

IS

T R

IC

T

J

S T

R E

E T

S A

C R

A M

E N

T O

C

A

D Z

A W

A L

IC

H

D Z

A W

A L

IC

H s J L O

R E

N Z

O O

R T

IZ

A

P R

W -X

X -X

-X X

X X

W -X

X -X

-X X

X X

S P

E C

N O

D E

S

IG

N F

IL

E

N O

C O

R R

E C

T E

D F

IN

A

L

B U

IL

D

IN

G

E L E

C T

R

IC

A L U

P G

R A

D E

P N

-2

-0

Ex

Ex

E x

E x

E x

E x

E x

E x

E x

E x

E x

E x E x

Ex Ex

E x

Ex Ex Ex Ex Ex Ex

Ex Ex Ex Ex

Ex

E x

E x

E x

E x

E x

E x

E x

E x

E x

E x

XXXXX

X X X X X X

X X X X

X X X X X X X X X X X X X X

X

X

X X

X X

X X

X X

X X

X

X

X

XXXXXXXXXXXXX

X X X X X X X X X X X X X

X

X

X X

X X

X X

X X

X X

X

X

X

XXXXXXXXX

X

X

X X X X

CP CP CP CP

C P

FO FO FO

FO

FO

FO

FO

FO

SSx SSx SSx

W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W

W W

W W

W

W W

W W

W

W W

W W

W W

W W

W W

W W

W W

W W

W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W

W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W

W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

WWWWWW

W W W W W W W

E x

E x

N

SO

LI

C

IT

AT

IO

N N

O

D

ES

IG

N

ED

B

Y:

D

ES

C R

IP

TI

O N

A

M

AR

K

SI

ZE

SU

BM

IT

TE

D B

Y:

D

AT

E

C O

N

TR

AC

T

N O

C

H

EC

KE

D

B Y:

D R

AW

N

B Y:

IS

SU

E D

AT

E:

SHEET ID

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

US Army Corps of Engineers

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SP

EC

N O

D

ES

IG

N

F

IL

E N

O

D U

G W

AY

P

R O

VI

N

G G

R O

U N

D , U

TA

H

BU

IL

D

IN

G

EL

EC

TR

IC

AL

U

PG

R

AD

E

PN

SA

C

R

AM

EN

TO

D

IS

TR

IC

T

J

S

TR

EE

T

SA

C

R

AM

EN

TO

, C A

AP

R

IL

W

8-

XX

-X

-X

XX

X

W

8-

XX

-X

-X

XX

X

1-

-0

D

C O

R R

EC

TE

D F

IN

AL

ED101

EL

EC

TR

IC

AL

D

EM

O

LI

TI

O N

P

LA

N

D . Z

AW

AL

IC

H

D . Z

AW

AL

IC

H

- J.

O

R

TI

Z

LEGEND

TELECOMMUNICATIONS (E)

ELECTRIC (E)

SANITARY SEWER (E)

STORM DRAIN (E)

WATER SERVICE (E)

FENCE LINE (E)

DITTO AREA - COMBINED CHEMICAL TEST FACILITY

FO

SSx

W W

CP

Ex

ACCESS

GATE

BUILDING

BUILDING

4T H

ST

R

EE

T

C

STREET

R O

TH

EN

BE

R

G

BL

D G

GENERAL NOTES:

1. REFER TO E-001 FOR ACRONYMS AND SYMBOLS.

2. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS.

3. CONTRACTOR SHALL EXCAVATE AROUND EXISTING UTILITIES AND

CONTRACTOR SHALL REPAIR ANY DAMAGED UTILITIES.

4. THE EXISTENCE AND LOCATION OF UNDERGROUND UTILITIES,

APPURTENANCES AND STRUCTURES SHOWN ARE BASED ON

AVAILABLE RECORDS. THE CONTRACTOR SHALL BE RESPONSIBLE

FOR VERIFYING THE LOCATION, SIZE AND DEPTH OF ALL EXISTING

UTILITIES PRIOR TO STARTING ANY UTILITY WORK AND SHALL

PROTECT ALL SUCH UTILITIES AT ALL TIMES, UNLESS OTHERWISE

INDICATED. EXISTING UTILITIES, WHETHER SHOWN ON THE

DRAWINGS OR NOT, WHICH HAVE BEEN DAMAGED AS A RESULT

OF THE CONSTRUCTION WORK SHALL BE RESTORED NEW AS

ORIGINALLY DESIGNED, OR AS APPROVED BY THE COR, AT THE

CONTRACTOR'S EXPENSE.

KEY NOTES:

1. CONTRACTOR SHALL DEMOLISH EXISTING 2000KVA SECONDARY

UNIT SUBSTATION AND ASSOCIATED EQUIPMENT.

2. CONTRACTOR SHALL REMOVE EXISTING SECONDARY

CONDUCTORS AND MODIFY EXISTING DUCTBANK AS DIRECTED BY

KEYED NOTE 6 ON SHEET ES-101. REFER TO KEYED NOTES 5 AND

6 ON SHEET E-101 FOR ADDITIONAL INFORMATION.

3. CONTRACTOR SHALL DEMOLISH EXISTING 1000KW GENERATOR.

DEMOLITION SHALL INCLUDE EXISTING POWER, CONTROL,

BATTERY CHARGER CIRCUITS AND ANY OTHER ASSOCIATED

EQUIPMENT.

4. ASSUMED DUCTBANK ROUTE, CONTRACTOR TO VERIFY.

CONTRACTOR SHALL REMOVE 15kV CABLES. EXISTING DUCTS

SHALL BE CUT AT GRADE SURFACE AND SEALED WITH

CONCRETE.

5. UNLESS DIRECTED OTHERWISE, CONTRACTOR SHALL HAUL AWAY

ALL HAZARDOUS AND NON-HAZARDOUS MATERIAL THAT SHALL BE

DEMOLISHED AND SHALL TRANSPORT OFF BASE/POST AND

DISCARD AT A LOCATION THAT MEETS STATE AND FEDERAL

LANDFILL DISPOSAL RESTRICTIONS.

6. REFER TO SHEET ED102 FOR UPGRADE REQUIREMENTS TO

INTERIOR MAIN SWITCHBOARD, ATS WITH BYPASS/ISOLATION AND

DISTRIBUTION BUSDUCT AND FEEDERS.

7. CONTRACTOR SHALL DEMOLISH RISER CONDUIT, CABLES, AND

CABLE TERMINATORS AND BARE CONDUCTORS TO LOAD SIDE OF

FUSED CUTOUTS.

ATS

SB

GEN

EXISTING ROUTE.

EXISTING ROUTE.

file:///C:/Documents%20and%20Settings/griswold/Desktop/DPG%20Documentation/MHE2.dwg file:///C:/Documents%20and%20Settings/griswold/Desktop/DPG%20Documentation/MHE2.dwg file:///C:/Documents%20and%20Settings/griswold/Desktop/DPG%20Documentation/MHE2.dwg of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

File Path:

Plot Date:

M A

R K

D E

S C

R

IP

T

IO

N

D:\Desktop\Projects\Dugway Proving Grounds - UT\B4156\BIM\B4156_Electrical_New.rvt

24-Apr-24 11:03:32

ED102

D E

M O

L

IT

IO

N

P L A

N

D U

G W

A Y

P R

O V

IN

G

G R

O U

N D

U

T A

H

S A

C R

A M

E N

T O

D

IS

T R

IC

T

J

S T

R E

E T

S A

C R

A M

E N

T O

C

A

R L E

O N

R L E

O N

J P

A D

IL

L A

G P

A D

IL

L A

A

P R

W -X

X -X

-X X

X X

W -X

X -X

-X X

X X

S P

E C

N O

D E

S

IG

N F

IL

E

N O

C O

R R

E C

T E

D F

IN

A

L

B U

IL

D

IN

G

E L E

C T

R

IC

A L U

P G

R A

D E

P N

-2

-0

1/8" = 1'-0"ED102

1 DEMOLITION PLAN

KEY NOTES:

1. CONTRACTOR SHALL DEMOLISH EXISTING 3000 AMP, 3-PHASE, 4-WIRE, 480/277V

SWITCHBOARD. CONTRACTOR SHALL NOT DEMOLISH UNTIL THE NEW SWITCHGEAR HAS

BEEN APPROVED, IS ON SITE AND IS READY TO BE INSTALLED. CONTRACTOR SHALL

ENSURE THAT THE EXISTING GROUNDING ELECTRODE SYSTEM CAN BE REUSED, AND IF

NOT THEN PROVIDE NEW GROUNDING PER NFPA 70 ARTICLE 250.

2. CONTRACTOR SHALL DEMOLISH EXISTING 2000 AMP 4-POLE AUTOMATIC TRANSFER

SWITCH WITH BYPASS ISOLATION SWITCH.

3. CONTRACTOR SHALL DEMOLISH EXISTING 1000 KW, 0.8 PF, 480/277V GENERATOR.

DEMOLITION SHALL INCLUDE EXISTING POWER, CONTROL, BATTERY CHARGER

CIRCUITS AND ANY OTHER ASSOCIATED EQUIPMENT.

4. FOR REFERENCE INFORMATION ONLY. EXISTING 2000 AMP BUSWAY ROUTING TO

EXISTING MCC EQUIPMENT.

5. CONTRACTOR SHALL TEST EXISTING BUSWAY/BUSTDUCT TO VERIFY THAT IT MAY BE

REUSED. CONTRACTOR SHALL PROTECT EXISTING BUSWAY/BUSDUCT. CONTRACTOR

SHALL MODIFY EXISTING BUSWAY/BUSDUCT AS REQUIRED.

6. FOR CONTINUATION REFER TO SHEET ED-101.

7. CONTRACTOR SHALL FIELD VERIFY TERMINATION OF BUSDUCT AND SHALL MAINTAIN

BUSDUCT WHILE DEMOLITION IS DONE.

8. REFER TO KEYED NOTES 5 AND 6 ON SHEET E-101 FOR ADDITIONAL INFORMATION.

GENERAL NOTES:

1. REFER TO SHEET E-001 FOR ACRONYMS AND SYMBOLS.

2. CONTRACTOR SHALL FEILD VERIFY EXISTING CONDITIONS.

3. UNLESS DIRECTED OTHERWISE, CONTRACTOR SHALL HAUL AWAY ALL HAZARDOUS AND

NON-HAZARDOUS DEMOLISHED MATERIAL/EQUIPMENT AND SHALL TRANSPORT OFF

BASE/POST AND DISCARD AT A LOCATION THAT MEETS STATE AND FEDERAL LANDFILL

DISPOSAL RESTRICTIONS.

0 8'4' 16'

PLAN NORTH

ATS

SB

SB

SB

SB

Ex

E x

E x

E x

E x

E x

E x

E x

E x

E x

E x E x

Ex Ex

E x

Ex Ex Ex Ex Ex Ex

Ex Ex Ex Ex

Ex

E x

E x

E x

E x

E x

E x

E x

E x

E x

E x

XXXXX

X X X X X X

X X X X

X X X X X X X X X X X X X X

X

X

X X

X X

X X

X X

X X

X

X

X

XXXXXXXXXXXXX

X X X X X X X X X X X X X

X

X

X X

X X

X X

X X

X X

X

X

X

XXXXXXXXX

X

X

X X X X

CP CP CP CP

C P

FO FO FO

FO

FO

FO

FO

FO

SSx SSx SSx

W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W

W W

W W

W

W W

W W

W

W W

W W

W W

W W

W W

W W

W W

W W

W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W

W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W

W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

W W

WWWWWW

W W W W W W W

E

E

E

ES

x

N

SO

LI

C

IT

AT

IO

N N

O

D

ES

IG

N

ED

B

Y:

D

ES

C R

IP

TI

O N

A

M

AR

K

SI

ZE

SU

BM

IT

TE

D B

Y:

D

AT

E

C O

N

TR

AC

T

N O

C

H

EC

KE

D

B Y:

D R

AW

N

B Y:

IS

SU

E D

AT

E:

SHEET ID

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

US Army Corps of Engineers

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SP

EC

N O

D

ES

IG

N

F

IL

E N

O

D U

G W

AY

P

R O

VI

N

G G

R O

U N

D , U

TA

H

BU

IL

D

IN

G

EL

EC

TR

IC

AL

U

PG

R

AD

E

PN

SA

C

R

AM

EN

TO

D

IS

TR

IC

T

J

S

TR

EE

T

SA

C

R

AM

EN

TO

, C A

AP

R

IL

W

8-

XX

-X

-X

XX

X

W

8-

XX

-X

-X

XX

X

1-

-0

D

C O

R R

EC

TE

D F

IN

AL

ES101

EL

EC

TR

IC

AL

S

IT

E

PL

AN

D . Z

AW

AL

IC

H

D . Z

AW

AL

IC

H

- J.

O

R

TI

Z

LEGEND

ELECTRIC UNDERGROUND PRIMARY (N)

ELECTRIC UNDERGROUND SECONDARY (N)

TELECOMMUNICATIONS (E)

ELECTRIC (E)

SANITARY SEWER (E)

STORM DRAIN (E)

WATER SERVICE (E)

FENCE LINE (E)

E

DITTO AREA - COMBINED CHEMICAL TEST FACILITY

FO

SSx

W W

CP

Ex

ACCESS

GATE

BUILDING

BUILDING

4T H

ST

R

EE

T

C

STREET

R O

TH

EN

BE

R

G

BL

D G

GENERAL NOTES:

1. REFER TO E-101 FOR ACRONYMS AND SYMBOLS.

2. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS.

3. THE EXISTENCE AND LOCATION OF UNDERGROUND UTILITIES,

APPURTENANCES AND STRUCTURES SHOWN ARE BASED ON

AVAILABLE RECORDS. THE CONTRACTOR SHALL BE

RESPONSIBLE FOR VERIFYING THE LOCATION, SIZE AND DEPTH

OF ALL EXISTING UTILITIES PRIOR TO STARTING ANY UTILITY

WORK AND SHALL PROTECT ALL SUCH UTILITIES AT ALL TIMES,

UNLESS OTHERWISE INDICATED. EXISTING UTILITIES, WHETHER

SHOWN ON THE DRAWINGS OR NOT, WHICH HAVE BEEN

DAMAGED AS A RESULT OF THE CONSTRUCTION WORK SHALL BE

RESTORED NEW AS ORIGINALLY DESIGNED, OR AS APPROVED BY

THE COR, AT THE CONTRACTOR'S EXPENSE.

KEY NOTES:

1. CONTRACTOR SHALL INSTALL NEW 2000KVA SECONDARY UNIT

SUBSTATION TRANSFORMER WITH A 1200A LOAD INTERRUPTER

SWITCH. AIR TERMINAL CHAMBER SHALL BE USED FOR

SECONDARY DISTRIBUTION. NEW 2000KVA SECONDARY UNIT

SUBSTATION TRANSFORMER SHALL USE LESS FLAMMABLE OIL

PER NEC 450.23 AND HAVE A MINIMUM SEPARATION OF 5' FROM

NONCOMBUSTIBLE MATERIAL WALL.

2. CONTRACTOR SHALL PROVIDE NEW 2000kW/2500kVA STANDBY

GENERATOR AND LOCATE IT IN THE SAME LOCATION AS EXISTING

GENERATOR. REFER TO KEYED NOTES 5 AND 6 ON SHEET E-101

FOR ADDITIONAL INFORMATION.

3. REFER TO SHEET E-101 FOR LOCATION OF SERVICE ENTRANCE

SWITCHGEAR, ATS AND GENERATOR.

4. REFER TO SHEET E-501 FOR PRIMARY DUCTBANK AND

SECONDARY DUCTBANK DETAIL.

5. REFER TO SHEET E-501 FOR SECONDARY UNIT SUBSTATION

TRANSFORMER DETAIL.

6. CONTRACTOR SHALL TRENCH FROM SECONDARY OF NEW

SECONDARY SUBSTATION TRANSFORMER TO PROVIDE NEW 12 X

4" CONCRETE ENCASED DUCTBANK AND CONNECT TO MODIFIED

EXISTING 12 X 4" SERVICE ENTRANCE DUCTBANK THAT

PRESENTLY ENTERS FACILITY AND TERMINATES AT EXISTING

SWITCHBOARD MAIN DISCONNECT. SAWCUT EXISTING CONCRETE

OF EXISTING DEMOLISHED 2000kVA TRANSFORMER AND BREAK

EXISTING CONCRETE ENCASED OF 12 X 4" SERVICE DUCTS TO

EXPOSE SUFFICIENT LENGTH OF DUCTS TO MODIFY AND

TERMINATE WITH NEW COUPLINGS TO NEW 12 X 4" DUCTS. CLEAN

AND MANDREL ALL DUCTS PRIOR TO ENCASING IN NEW

CONCRETE. EXERCISE CARE WHEN CROSSING EXISTING ABOVE

GRADE OR BURIED WATER PIPES. PROVIDE 12" SEPARATION

BETWEEN WATER LINE AND TOP CONCRETE ENVELOPE.

7. CONTRACTOR SHALL PROVIDE NEW 5" SCHEDULE 80 RISER

CONDUIT, 3 - 4/0 15KV EPR, 133% MV-105 CABLES AND CABLE

TERMINATORS AND #2 ASCR BARE CONDUCTORS TO LOAD SIDE

OF 200A FUSED CUTOUTS. REFER TO SHEET E-502 FOR DETAIL. ATS

SG

GEN

EXISTING ROUTE TO BE REUSED.

ESx file:///C:/Documents%20and%20Settings/griswold/Desktop/DPG%20Documentation/MHE2.dwg file:///C:/Documents%20and%20Settings/griswold/Desktop/DPG%20Documentation/MHE2.dwg

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

File Path:

Plot Date:

M A

R K

D E

S C

R

IP

T

IO

N

D:\Desktop\Projects\Dugway Proving Grounds - UT\B4156\BIM\B4156_Electrical_New.rvt

24-Apr-24 11:03:28

E-101

P O

W E

R P

L A

N

D U

G W

A Y

P R

O V

IN

G

G R

O U

N D

U

T A

H

S A

C R

A M

E N

T O

D

IS

T R

IC

T

J

S T

R E

E T

S A

C R

A M

E N

T O

C

A

D Z

A W

A L

IC

H

D Z

A W

A L

IC

H

J O

R T

IZ

A

P R

W -X

X -X

-X X

X X

W -X

X -X

-X X

X X

S P

E C

N O

D E

S

IG

N F

IL

E

N O

C O

R R

E C

T E

D F

IN

A

L

B U

IL

D

IN

G

E L E

C T

R

IC

A L U

P G

R A

D E

P N

-2

-0

1/8" = 1'-0"E-101

1 POWER PLAN

KEY NOTES:

1. CONTRACTOR SHALL PROVIDE NEW 3000 AMP, 3-PHASE, 4-WIRE, 480/277V SWITCHGEAR.

CONTRACTOR SHALL SELECT SWITCHGEAR WITH SAME/SIMILAR FOOTPRINT, SAME

LOCATION OF MAIN BREAKER AND OTHER BREAKERS TO MAINTAIN SAME DISTRIBUTION.

2. CONTRACTOR SHALL REFEED EQUIPMENT THAT WAS FED FROM DEMOLISHED 3000 AMP

SWITCHBOARD. REFER TO SHEET E-601 AND E-602.

3. CONTRACTOR SHALL PROVIDE NEW 3000 AMP 4-POLE AUTOMATIC TRANSFER SWITCH

WITH BYPASS ISOLATION. NEW ATS SHALL MAINTAIN THE SAME FOOTPRINT OR

SMALLER AND THE SAME DISTRIBUTION AS THE EXISTING AUTOMATIC TRANSFER

SWITCH.

4. CONTRACTOR SHALL REFEED NEW AUTOMATIC TRANSFER SWITCH TO NEW 3000A

BREAKER AT NEW SWITCHGEAR, TO NEW 2000 KW GENERATOR AND TO EQUIPMENT

THAT WAS FED FROM EXISTING 3000 AMP AUTOMATIC TRANSFER SWITCH. REFER TO

SHEET E-601 AND E-602.

5. CONTRACTOR SHALL PROVIDE NEW STANDBY 2000 KW, 2500KVA, 0.8 PF, 480/277V

GENERATOR. NEW GENERATOR SHALL MAINTAIN THE SAME FOOTPRINT AND THE SAME

DISTRIBUTION AS THE EXISTING GENERATOR AS TO REUSE EXITSING PAD,

DISTRIBUTION AND ENCLOSURE. NEW GENERATOR SHALL HAVE MAIN BREAKER AND

START/STOP CONTROL CABINET IN SAME LOCATION AS EXISTING IN ORDER TO REUSE

EXISTING CONDUITS. THE OVERALL GENERATOR AND ENCLOSURE FOOTPRINTS SHALL

MATCH EXISTING. CONTRACTOR SHALL PROVIDE SAME NUMBER OF NEW PARALLEL

SETS OF POWER CABLES, AS EXISTING, FROM THE GENERATOR TO MAIN BREAKER OF

THE ATS, PER NFPA 70, CONTROL WIRING AND BATTERY CHARGER CIRCUITS, PER

MANUFACTURER'S REQUIREMENTS. CONTRACTOR SHALL RECONNECT FUEL LINE

CONNECTION TO EXISTING DAY FUEL TANK, AND MODIFY AS REQUIRED TO RE-CONNECT

TO NEW GENERATOR. MANDREL AND CLEAN EXISTING CONDUITS PRIOR TO REUSING

THEM.

6. CONTRACTOR SHALL REFEED NEW GENERATOR TO NEW AUTOMATIC TRANSFER

SWITCH AND TO THE EQUIPMENT THAT WAS FED FROM DEMOLISHED 1000 KW

GENERATOR. REFER TO SHEET E-601 AND E-602.

7. FOR EXTERIOR ELECTRICAL PLAN REFER TO SHEET ES-101.

8. FOR REFERENCE INFORMATION ONLY. EXISTING 2000 AMP BUSWAY ROUTING TO

EXISTING MCC EQUIPMENT.

9. CONTRACTOR SHALL TEST EXISTING BUSWAY/BUSTDUCT TO VERIFY THAT IT MAY BE

REUSED. CONTRACTOR SHALL PROTECT EXISTING BUSWAY/BUSDUCT AND TEST

BUSWAY/BUSTDUCT BEFORE TERMINATION ON NEW EQUIPMENT. CONTRACTOR SHALL

MODIFY EXISTING BUSWAY/BUSDUCT AS REQUIRED. CONTRACTOR SHALL PROVIDE

NEW BUSWAY/BUSDUCT THAT IS CERTIFIED TO BE COMPATIBLE TO EXISTING

BUSWAY/BUSDUCT (VOLTAGE, SHORT CIRCUIT, AMPERAGE, ETC...) IF REQUIRED.

10. CONTRACTOR SHALL FIELD VERIFY TERMINATION OF BUSDUCT AND SHALL TERMINATE

EXISTING BUSDUCT TO EXISTING SWITCHBOARD AND NEW SWITCHGEAR.

3 1

GENERAL NOTES:

1. REFER TO SHEET E-001 FOR ACRONYMS AND SYMBOLS.

2. CONTRACTOR SHALL FEILD VERIFY EXISTING CONDITIONS.

3. CONTRACTOR SHALL PROVIDE NEW SWITCHGEAR AND ATS WHICH SHALL BE FROM

THE SAME MANUFACTURER AND SHALL BE 100% COMPATIBLE WITH EXISTING

BUSWAY/BUSDUCT.

0 8'4' 16'

PLAN NORTH

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

File Path:

Plot Date:

M A

R K

D E

S C

R

IP

T

IO

N

D:\Desktop\Projects\Dugway Proving Grounds - UT\B4156\BIM\B4156_Electrical_New.rvt

24-Apr-24 11:03:28

E-102

P H

A S

IN

G

D U

G W

A Y

P R

O V

IN

G

G R

O U

N D

U

T A

H

S A

C R

A M

E N

T O

D

IS

T R

IC

T

J

S T

R E

E T

S A

C R

A M

E N

T O

C

A

D Z

A W

A L

IC

H

D Z

A W

A L

IC

H

J O

R T

IZ

A

P R

W -X

X -X

-X X

X X

W -X

X -X

-X X

X X

S P

E C

N O

D E

S

IG

N F

IL

E

N O

C O

R R

E C

T E

D F

IN

A

L

B U

IL

D

IN

G

E L E

C T

R

IC

A L U

P G

R A

D E

P N

-2

-0

GENERAL NOTES:

1. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS.

2. NORMAL OPERATING HOURS ARE 0700 TO 1730 MONDAY THROUGH THURSDAY. MECHANICAL EQUIPMENT OPERATES 24/7/365.

3. CONTRACTOR SHALL PHASE DEMOLITION OF EXISTING EQUIPMENT TO MINIMIZE OUTAGES.

4. CONTRACTOR TO PROVIDE ALL TEMPORARY POWER SIZED NOT ONLY FOR HVAC AND OTHER MECHANICAL SYSTEMS BUT THE NORMAL FACILITY LOADS.

5. CONTRACTOR SHALL DETERMINE THE EXISTING LOAD BY PROVIDING A RECORDING OVER AMMETER OR POWER METER OVER A 30 DAY PERIOD, PER NEC SECTION 220.87. TEMPORARY GENERATOR SHALL

BE CAPABLE OF CARRYING MAXIMUM LOAD MEASURED BY RECORDING DATA.

6. CONTRACTOR SHALL COORDINATE WITH COR, DPW AND THE USER TO SCHEDULE OUTAGES. SCHEDULED OUTAGE SHALL BE AT LEAST 4 WEEKS IN ADVANCE.

7. CONTRACTOR SHALL PLAN POWER RESTORATION TO EACH DOWNSTREAM PANLEBOARD WHEN UTILITY IS RESTORED TO LIMIT INRUSH CURRENTS THAT CAN DAMAGE HVAC CIRCUIT BOARDS.

8. CONTRACTOR SHALL PROVIDE NEW SWITCHGEAR AND ATS WHICH SHALL BE FROM THE SAME MANUFACTURER AND SHALL BE 100% COMPATIBLE WITH EXISTING BUSWAY/BUSDUCT.

ATS AND GENERATOR PHASING NOTES:

1. EXISTING 1000KW, 0.8 PF, 480Y/277V GENERATOR SHALL BE DEMOLISHED. GENERATOR SHALL BE REPLACED WITH A 2000KW, 0.8 PF, 480Y/277V GENERATOR AND IT SHALL BE PLACED IN THE SAME LOCATION TO REUSE EXISTING CONDUITS AND FUEL ROUTING TO EQUIPMENT AND TO NEW 3000A, 4-POLE AUTOMATIC

TRANSFER SWITCH (ATS) BYPASS ISOLATION SWITCH.

2. EXISTING 2000A, 4-POLE AUTOMATIC TRANSFER SWITCH (ATS) BYPASS ISOLATION SWITCH SHALL BE DEMOLSIHED AND REPLACED WITH A 3000A, 4-POLE AUTOMATIC TRANSFER SWITCH (ATS) BYPASS ISOLATION SWITCH, NEW AUTOMATIC TRANSFER SWITCH (ATS) BYPASS ISOLATION SWITCH SHALL BE PLACED IN THE SAME LOCATION AS EXISTING TO REUSE EXISTING CONDUIT AND BUSDUCT. DURING THE REPLACEMENT OF THE GENERATOR REUSE EXISTING CONDUIT AND PROPERLY TERMINATE FEEDS.

3. NEW 3000A, 4-POLE AUTOMATIC TRANSFER SWITCH (ATS) BYPASS ISOLATION SWITCH SHALL REFEED EXISTING EQUIPMENT FED FROM EXISTING 2000A, 4-POLE AUTOMATIC TRANSFER SWITCH (ATS) BYPASS ISOLATION SWITCH, BY REUSING EXISTING BUSDUCTS AND CONDUITS. NEW 3000A SHALL HAVE SAME/SIMILAR

FOOTPRINT SO THAT EXISTING CONDUIT AND BUSDUCT CAN BE REUSED.

4. DEMOLITION OF BOTH GENERATOR AND ATS SHALL LEAVE EXISTING MECHANICAL EQUIPMENT WITHOUT POWER. CONTRACTOR SHALL PROVIDE TEMPORARY POWER TO THE CRITICAL HVAC LOADS DURING THIS OUTAGE. EXISTING GENERATOR SHALL BE DEMOLISHED AND REPLACED FIRST TO MINIMIZE OUTAGES.

COORDINATE OUTAGE WITH DIRECTORATE OF PUBLIC WORKS (DPW), COR AND USER TO MINIMIZE OUTAGE. PERFORM GENERATOR FIELD TESTING PER SPECIFICATION 26 32 15.00 10. PERFORM ALL SAFTEY, LOAD BANK TESTING, AND FUNCTIONAL TESTING.

TRANSFORMER AND SWITCHGEAR PHASING NOTES:

1. NEW PRIMARY DUCTBANK SHALL BE ROUTED TO NEW TRANSFORMER LOCATION AS SHOWN ON ES-101. EXISTING RISER POLE WITH NEW RISER SHALL BE REUSED TO PROVIDE PRIMARY FEED TO NEW 2000KVA, 12470-480Y/277V SECONDARY UNIT SUBSTATION TRANSFORMER. EXISTING FEED TO EXISTING TRANSFORMER

SHALL BE COORDINATED WITH USER BEFORE DEMOLITION TO MINIMIZE OUTAGES.

2. NEW 2000KVA, 12470-480Y/277V SECONDARY UNIT SUBSTATION TRANSFORMER AND 1200A LOAD INTERRUPTER SWITCH SHALL BE PLACED AT NEW LOCATION AS SHOWN ON SHEET ES-101.

3. EXISTING 2000KVA SECONDARY UNIT SUBSTATION, IS SURROUNDED BY MECHANICAL EQUIPMENT PIPES. CONTRACTOR SHALL DEMOLISH SECONDARY UNIT SUBSTATION WITHOUT DAMAGING EXISTING MECHANICAL PIPES.

4. STANDBY GENERATOR SHALL BE DEMOLISHED AND REPLACED FIRST, THE AUTOMATIC TRANSFER SWITCH WITH BYPASS ISOLATION SWITCH WILL BE DEMOLISHED AND REPLACED NEXT, AND THEN THE EXISTING 3000A SWITCHBOARD SHALL BE DEMOLISHED DURING THE SAME TIME THAT THE EXISTING 2000 KVA

SECONDARY UNIT SUBSTATION IS DEMOLISHED.

5. EXISTING 3000A, 3-PHASE, 4-WIRE, 480/277V SWITCHBOARD SHALL BE DEMOLISHED AND REPLACED WITH A NEW 3000A, 3-PHASE, 4-WIRE, 480/277V SWITCHGEAR. NEW 3000A SWITCHGEAR SHALL BE LOCATED IN THE SAME LOCATION AS EXISTING SWITCHBOARD.

6. NEW SECONDARY DUCTBANK SHALL ROUTE DUCT AROUND HVAC EQUIPMENT AND RECONNECT TO EXISTING SECONDARY DUCTBANK TO RECONNECT TO NEW 3000A SWITCHGEAR. SEE SHEET ES-101 FOR REFERENCE.

7. NEW 3000A, 3-PHASE, 4-WIRE, 480/277V SWITCHGEAR SHALL USE THE EXISTING CONDUIT AND BUSDUCT TO FEED EQUIPMENT FED FROM EXISTING SWITCHBOARD.

8. NEW GENERATOR AND AUTOMATIC TRANSFER SWITCH WITH BYPASS ISOLATION SWITCH SHALL BE USED TO MAINTAIN POWER TO MECHANICAL EQUIPMENT DURING THE TIME THAT THE TRANSFORMER AND SWITCHBOARD ARE DOWN.

9. CONTRACTOR SHALL COORDINATE WITH USER TO MINIMIZE OUTAGES. OUTAGES ARE ACCEPTABLE ON HOLIDAYS AND WEEKENDS.

10. CONTRACTOR SHALL PROVIDE TEMPORARY POWER AND DISTRIBUTION.

INSTRUMENT INSTRUMENT

MAIN

FEEDER

FEEDER FEEDER

3200 AF

3200 AF

800 AF 800 AF

CABLE

COMPARTMENT

24.00 INCHES

24.00 INCHES

30.00 INCHES

44.00 INCHES

B F

C G

D H

A E

INSTRUMENT INSTRUMENT

FEEDER

FEEDER

FEEDER FEEDER

1600 AF

2000 AF

800 AF 800 AF

CABLE

COMPARTMENT

24.00 INCHES

24.00 INCHES

30.00 INCHES

44.00 INCHES

B F

C G

D H

A E

3000 AT

3000 AT

WATTHOUR METER

AMP METER

VOLT METER

SPD

2000 AT

1000 AT

400 AT

BUS BUS BUS BUS BUS BUS

BREAKER BREAKER BREAKERCABLE

CONDUIT

AREA

CABLE

CONDUIT

AREA

CABLE

CONDUIT

AREA

24.00

INCHES

24.00

INCHES

48.00 INCHES

24.00

INCHES

24.00

INCHES

30.00

INCHES

54.00 INCHES 68.00 INCHES

44.00 INCHES

40.20 INCHES

20.00 INCHES

17.50 INCHES

20.50

INCHES

26.50

INCHES

40.50 INCHES

FRONT

.0

IN

C H

E S

MOUNTED ON ELEVATED CONCRETE PAD

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

File Path:

Plot Date:

M A

R K

D E

S C

R

IP

T

IO

N

D:\Desktop\Projects\Dugway Proving Grounds - UT\B4156\BIM\B4156_Electrical_New.rvt

24-Apr-24 11:03:29

E-401

S W

IT

C

H G

E A

R L

A Y

O U

T

D U

G W

A Y

P R

O V

IN

G

G R

O U

N D

U

T A

H

S A

C R

A M

E N

T O

D

IS

T R

IC

T

J

S T

R E

E T

S A

C R

A M

E N

T O

C

A

J D e s ig n e r

J D ra w e r

/s J O

H N

R P

A R

R

IS

H

P E

J C h e c k e r

A

P R

W -X

X -X

-X X

X X

W -X

X -X

-X X

X X

S P

E C

N O

D E

S

IG

N F

IL

E

N O

C O

R R

E C

T E

D F

IN

A

L

B U

IL

D

IN

G

E L E

C T

R

IC

A L U

P G

R A

D E

P N

-2

-0

6" = 1'-0"E-401

1 SWITCHGEAR CONFIGURATION LAYOUT

NOT TO SCALE

FINISHED GRADE

MIN.

36"

3"3"3"

3"

3"

3"

3"

CONCRETE

ENCASEMENT

4" 4" 4"

4" 4" 4"

CONCRETE ENCASED:

SECONDARY DUCTBANK

E-504

SPARE

3"

4" 4" 4"

12"

WARNING MARKER

PULL ROPE

CONCRETE ENCASED DUCT MAIN

PRIMARY DUCTBANK

CONDUIT (TYP)

5" PVC TYPE EB

ENCASEMENT

CONCRETE

FINISHED GRADE

MIN.

36"

3"

3"

3"

3"3"

12"

WARNING MARKER

NOT TO SCALE

E-504

5" 5"

CONDUIT (TYP)

4" PVC TYPE EB

PULL ROPE

SPARE

4"

4"

4"

3"

90% COMPACTED

BACKFILL UNDER

UN-PAVED AREAS

AND 95% UNDER

PAVED AREAS

90% COMPACTED

BACKFILL UNDER

UN-PAVED AREAS

AND 95% UNDER

PAVED AREAS

PRIMARY

SWITCH

TRANSFORMER

PRIMARY

FEED

SECONDARY

FEED

65" 12"12"

PLAN

AIR

TERMINAL

CHAMBER

85"

30"

MIN.

CONCRETE PAD TO

EXTERND 1' OUTSIDE

EQUIPMENT ON ALL

SIDES

GROUND

3/4" x 10' COPPER

GROUND ROD, NO.

AS REQUIRED

BARE COPPER GROUND

RING PER NEC 250.

NOTES:

CONTRACTOR SHALL VERIFY DIMENSIONS OF ACTUAL EQUIPMENT TO BE SUPPLIED AND SHALL ADJUST SIZE OF CONCRETE PAD AS NECESSARY.

CONTRACTOR SHALL ADJUST LOCATION OF BOLLARDS AS NECESSARY TO ENSURE A MINIMUM OF 10 FT CLEAR WORKSPACE IN FRONT OF PAD-MOUNTED EQUIPMENT FOR HOT STICK WORK .

INCOMING

SWITCHING &

PROTECTIVE

DEVICES

8" THICK CONCRETE PAD

REINFORCED WITH 6X6-

W2.9XW2.9 WIRE MESH

(4" ABOVE GRADE)

GRAVEL FILL

MEDIUM

VOLTAGE CABLE

TERMINATION

6" WELL-COMPACTED

SUBGRADE

INCOMING

PRIMARY

CONDUITS

OUTGOING

SECONDARY

CONDUITS

TRANSFORMER

SECTION

6" DIA. X 5'

CONCRETE FILLED

GUARD POST,

GALV. STEEL (TYP.

OF 4)

LOW VOLTAGE

CABLE

TERMINATION

Min. 3'

PLACE GROUND RING A

MINIMUM OF 30" DEEP

AND 3' FROM EDGE OF

PAD

4/0 BARE COPPER CONDUCTOR, AT

LEAST 20 FT IN LENGTH.

6" CLEARANCE

FROM THE SIDE

PANEL TO THE

SIDE OF

DUCTBANK.

6" CLEARANCE FROM THE

SIDE PANEL TO THE SIDE OF

DUCTBANK.

36" MIN.

EXOTHERMIC WELDS

TO BOLLARDS.

GROUNDING TEST

WELL. SEE SHEET

E-502 FOR DETAIL.

12" MINIMUM

DEPTH TO TOPS

OF GROUND

RODS.

PROVIDE SEPARATE

INSULATED

GROUNDING

CONDUCTOR

CONNECTED TO A

GROUNDING

ELECTRODE LOCATED

AT A DISTANCE OF NOT

LESS THAN 20' FROM

SURGE ARRESTOR

GROUNDING

ELECTRODE, IN

ACCORDANCE WITH

NESC (IEEE C2)

MIN. 3'

MIN. 3'

CONCRETE

ENCASED

M

IN

MIN. 12"

M

IN

(TYP. OF 4)

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

File Path:

Plot Date:

M A

R K

D E

S C

R

IP

T

IO

N

D:\Desktop\Projects\Dugway Proving Grounds - UT\B4156\BIM\B4156_Electrical_New.rvt

24-Apr-24 11:03:30

E-501

D E

T A

IL

S

D U

G W

A Y

P R

O V

IN

G

G R

O U

N D

U

T A

H

S A

C R

A M

E N

T O

D

IS

T R

IC

T

J

S T

R E

E T

S A

C R

A M

E N

T O

C

A

D Z

A W

A L

IC

H

D Z

A W

A L

IC

H s J L O

R E

N Z

O O

R T

IZ

A

P R

W -X

X -X

-X X

X X

W -X

X -X

-X X

X X

S P

E C

N O

D E

S

IG

N F

IL

E

N O

C O

R R

E C

T E

D F

IN

A

L

B U

IL

D

IN

G

E L E

C T

R

IC

A L U

P G

R A

D E

P N

-2

-0

GENERAL NOTES:

1. PROVIDE PULLWIRE IN ALL SPARE AND EMPTY CONDUITS. CAP AND

LABEL AT BOTH ENDS.

2. PROVIDE 2/0 BARE COPPER AS A GROUND/COUNTERPOISE, AT

SUBSTATION AND SWITCHES, BOND TO THE GROUND SYSTEM UNDER

PAD.

3. PLACE A PERMANENT TRACER TAPE 12" BELOW SURFACE GRADE,

CENTERED OVER THE DUCT BANK.

4. DUCTBANK DEPTH SHALL BE A MINIMUM OF 36", IN CASE OF CROSSING

WATER PIPE AN ADDITIONAL 1 FOOT VERITCAL SEPERATION IS

REQUIRED.

5. REFER TO CIVIL DETAILS FOR CONDUITS INSTALLED IN ROADS.

6. PROVIDE SHORING OR 1 1/2:1 CUT BACK SLOPES IF EXCAVATING TO A

DEPTH GRATER THAN 48 INCHES.

NOT TO SCALEE-501

3 SECONDARY UNIT SUBSTATION DETAIL

(E) POLE

TYP. (N)

ARRESTER,

SURGE

NEW 3-#4/0, 15KV

CABLE IN 5" GALV.

RIGID

STEEL CONDUIT

NEW CABLE

TERMINATOR,

(TYP.)

EXISTING OVERHEAD DISTRIBUTION SYSTEM

NEW STIRRUP AND

HOT

LINE CLAMP (TYP OF

3)

EXISTING 15KV, 150E

FUSED

CUTOUT, NEW FUSES

AT 200 AMPS

SEAL END OF

RISER

WITH DUCT SEAL

SURGE

ARRESTER

GROUND IN

MOLDING

NEW EQUIPMENT

GROUND IN

MOLDING

3'-0"

USE ADDITIONAL

GROUND ROD AS

REQUIRED

(TYP.) PER SPEC.

33 71 01

SURGE ARRESTOR GROUND

IN MOULDING

FINISHED GRADE

THERMOWELD

CONNECTION (TYP.)

MIN.

EQUIPMENT GROUND IN

MOULDING

CONNECT TO GROUNDING

BUSHING AT EACH END (TYP.)

1/2" RIGID STEEL CONDUIT

(TYP.)

#6 BARE COPPER (TYP.)

3'-0"

MIN.

"1

10'-0" MIN. 10'-0" MIN.

M

IN

3/4" X 10'-0"

GROUND ROD

(TYP.)

CLASS I MAIN SIZED

LIGHTNING

PROTECTION SYSTEM

CONDUCTOR, BARE

COPPER.

1/4" THICK GALV. STEEL COVER

FINISH GRADE

PVC TUBE 1" WALL

GRAVEL-FILL TO

WITHIN 12" OF TOP

OF WELL.

BOLTED COPPER BYPASS

GROUND ROD CONNECTION

13"

2'-6" 2'-0"

MIN.

12"

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

File Path:

Plot Date:

M A

R K

D E

S C

R

IP

T

IO

N

D:\Desktop\Projects\Dugway Proving Grounds - UT\B4156\BIM\B4156_Electrical_New.rvt

24-Apr-24 11:03:30

E-502

D E

T A

IL

S

D U

G W

A Y

P R

O V

IN

G

G R

O U

N D

U

T A

H

S A

C R

A M

E N

T O

D

IS

T R

IC

T

J

S T

R E

E T

S A

C R

A M

E N

T O

C

A

D Z

A W

A L

IC

H

D Z

A W

A L

IC

H s J L O

R E

N Z

O O

R T

IZ

A

P R

W -X

X -X

-X X

X X

W -X

X -X

-X X

X X

S P

E C

N O

D E

S

IG

N F

IL

E

N O

C O

R R

E C

T E

D F

IN

A

L

B U

IL

D

IN

G

E L E

C T

R

IC

A L U

P G

R A

D E

P N

-2

-0

NOT TO SCALEE-502

1 RISER POLE DETAIL

NOTES:

1. CONTRACTOR SHALL PROVIDE A NEW GROUNDING FOR RISER POLE, AS ILLUSTRATED BY GROUNDING ABOVE.

NOT TO SCALEE-502

2 GROUNDING TEST WELL

GENERATOR

AUTOMATIC TRANSFER

SWITCH

N

N

N

SEPARATELY DERIVED

GROUND PER NEC 250.30

NG

G

N

3 PHASE

3 WIRE

G

SECONDARY

WINDING

SERVICE TRANSFORMER

SEE TRANSFORMER PAD DETAIL FOR

FURTHER GROUNDING INFORMATION

N

N

N

G

N

G

ISOLATED

NEUTRAL

BAR. SEE NOTE 4.

G

G

G

G N

G N

GROUNDING ELECTRODE CONDUCTOR (COPPER) NEC TABLE 250.66.

MAIN BONDING

JUMPER PER

NEC

250.28 SIZE PER

NEC

TABLE 250.66.

COLD WATER PIPE NEC

250.52, 250.68(c)

STRUCTURAL BUILDING

FRAME NEC 250.52,

250.68(c).

GROUND ROD OR OTHER

MADE ELECTRODE NEC

250.52, 250.53.

ISOLATED

NEUTRAL

BAR. SEE NOTE 4.

INTERSYSTEM BONDING TERMINATION BAR, EXTERNAL

BUT ADJACENT TO SERVICE EQUIPMENT, PER NEC 250.94.

TELECOMMUNICATIONS MAIN GROUNDING BAR

SYSTEM BONDING JUMPER

PER NEC TABLE 250.66

(#6 MINIMUM).

CONTRACTOR SHALL

RECONNECT TO

EXISTING EQUIPMENT

CONTRACTOR SHALL

RECONNECT TO

EXISTING EQUIPMENT

N

NOTES:

1. ALL EQUIPMENT GROUNDING WIRES FOR RECEPTACLE BRANCH CIRCUITS SHALL BE SIZED PER

NEC TABLE 250.122. MULTIPLE BRANCH CIRCUIT HOMERUNS SHALL USE ONLY ONE EQUIPMENT

GROUND WIRE.

2. SIZE EQUIPMENT GROUNDING WIRES FOR FEEDER CIRCUITS PER NEC TABLE 250.122.

3. SIZE PER NEC 250.28 AND TABLE 250.66.

4. SERVICE CONDUCTOR GROUNDING IS SHOWN IN ACCORDANCE WITH NEC 250.24.

5. TYPICAL RECEPTACLE WITH EQUIPMENT GROUNDING CONDUCTOR, GROUND PER NEC 406.4.

6. EQUIPMENT BONDING JUMPER PER NEC 408.40 AND SIZED PER TABLE 250.122.

7. GROUND TERMINAL BAR, NEC 408.40.

NOTE 1.

NOTE 5.

NOTE 2.

NOTE 6.

NOTE 7.

NOTE 6.

NOTE 3.

SERVICE ENTRANCE

SWITCHGEAR

8. CONTACTOR SHALL INSTALL NEW GROUNDING SYSTEM, AS DETAILED, FOR NEW ELECTRICAL

EQUIPMENT. CONTRACTOR SHALL LOCATE FACILITY GROUNDING SYSTEM AND NEW GROUNDING

SYSTEMS SHALL BE BONDED TO EXISTING FACILITY GROUNDING SYSTEM PER NEC 250.

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

File Path:

Plot Date:

M A

R K

D E

S C

R

IP

T

IO

N

D:\Desktop\Projects\Dugway Proving Grounds - UT\B4156\BIM\B4156_Electrical_New.rvt

24-Apr-24 11:03:31

E-503

G R

O U

N D

IN

G

S Y

S T

E M

D

IA

G R

A M

D U

G W

A Y

P R

O V

IN

G

G R

O U

N D

U

T A

H

S A

C R

A M

E N

T O

D

IS

T R

IC

T

J

S T

R E

E T

S A

C R

A M

E N

T O

C

A

D Z

A W

A L

IC

H

D Z

A W

A L

IC

H s J L O

R E

N Z

O O

R T

IZ

A

P R

W -X

X -X

-X X

X X

W -X

X -X

-X X

X X

S P

E C

N O

D E

S

IG

N F

IL

E

N O

C O

R R

E C

T E

D F

IN

A

L

B U

IL

D

IN

G

E L E

C T

R

IC

A L U

P G

R A

D E

P N

-2

-0

NOT TO SCALEE-503

1 GROUNDING SYSTEM DETAIL

LEG

2000 A 3P

G

A SS

SSV

WM

3000A MAIN

CIRCUIT BREAKER

WITH GROUND

FAULT PROTECTION

AND CURRENT

LIMITING FUSES

DRAWOUT TYPE

AMP METER

WATTHOUR METER

VOLT METER

2000 A 3P

400 A 3P

1000 A 3P

FUSIBLE PANELBOARD 'HDP' 277/480V 3

PHASE 4 WIRE 1200A MAIN BUS

3000 AMP BOLTED PRESSURE SWITCH

W/3 - 3000A FUSES; 200,000 AIC

LOAD CENTER UNIT SUBSTATION

2000 KVA, OIL FILLED

12470 - 277/480Y

3 PHASE 4 WIRE, 5.75% Z

1200A - 15 KV FUSED INTERRUPTER SWITCH

W/3 - 150E FUSES

(3) #350 KCMIL AWG 15 KV-SHLD.

EPR 1 #1/0 THW GND.

5" GRC.

15 KV FUSED INTERRUPTER SWITCH W/150E FUSE

15 KV SURGE ARRESTER

2000A BY-PASS/

ISOLATION

TRANSFER

SWITCH

WITH NEUTRAL THROUGHOUT

3 #6 - 1"C

GENERATOR SET:

1000 KW @ 0.8 P.F.

277/480V Y 3 PHASE

4 WIRE IN

ENCLOSURE.

PANEL 'HBDP'

277/480V

3 PHASE 4 WIRE

14,000 AIC

11 SETS (4 # 500 KCMIL - 4" C.)

POWER DISTRIBUTION PANELBOARD 'MDP'

277/480V, 3 PHASE 4 WIRE

3000A MAIN BUS. 42,000AIC

EXISTING OVERHEAD DISTRIBUTION SYSTEM 7200/12470

400A 400A 400A

400A 400A 400A

EMCC 5 EMCC 3 EMCC 1

EMCC 6 EMCC 4 EMCC 2

LEA

45,000AIC TYP.

CONSTRUCTED FOR BACK TO BACK MOUNTING TYP.

(3) 4 - #400, 3"C

4 - #500 XHHW,

3-1/2"C

2000 A

3000 A 3P

'SWBD MDP'

277/480V 3 PHASE

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

File Path:

Plot Date:

M A

R K

D E

S C

R

IP

T

IO

N

D:\Desktop\Projects\Dugway Proving Grounds - UT\B4156\BIM\B4156_Electrical_New.rvt

24-Apr-24 11:03:31

E-601

O N

E -L

IN

E

D

IA

G R

A M

E X

IS

T

IN

G

D U

G W

A Y

P R

O V

IN

G

G R

O U

N D

U

T A

H

S A

C R

A M

E N

T O

D

IS

T R

IC

T

J

S T

R E

E T

S A

C R

A M

E N

T O

C

A

D Z

A W

A L

IC

H

D Z

A W

A L

IC

H s J L O

R E

N Z

O O

R T

IZ

A

P R

W -X

X -X

-X X

X X

W -X

X -X

-X X

X X

S P

E C

N O

D E

S

IG

N F

IL

E

N O

C O

R R

E C

T E

D F

IN

A

L

B U

IL

D

IN

G

E L E

C T

R

IC

A L U

P G

R A

D E

P N

-2

-0

KEY NOTES:

1. CONTRACTOR SHALL DEMOLISH.

2. CONTRACTOR SHALL REPLACE CONDUCTORS. CONDUIT TO

REMAIN.

3. CONTRACTOR SHALL PROTECT AND REUSE BUSDUCT/BUSWAY

DURING CONSTRUCTION.

4. NEW SWITCHGEAR AND ATS SHALL BE OF THE SAME

MANUFACTURER AND SHALL BE 100 PERCENT COMPATIBLE WITH

EXISTING BUSDUCT. EXISTING FEEDER CABLE/BUSDUCT SHALL BE

REUSED, CONTRACTOR SHALL MEGGER EXISTING CABLING PER

SPECIFICATION 26 20 00 BEFORE TERMINATION AT NEW

EQUIPMENT. IF CABLE/BUSDUCT INSULATION ON ANY PARALLEL

SET FAILS, THEN CONTRACTOR SHALL REPLACE WITH NEW SET OF

CABLES/BUSDUCT ONE CONDUIT AT A TIME. ANY MODIFICATION TO

EXTEND EXISTING BUSDUCT/BUSWAY SHALL BE CERTIFIED BY

BUSDUCT/BUSWAY MANUFACTURER'S REPRESENTATIVE.

5. CONTRACTOR SHALL MAINTAIN FUSED CUTOUTS, BUT 150A FUSES

SHALL BE REMOVED. SEE SHEET E-602 FOR FUSE THAT SHALL

REPLACE EXISTING.

6. CONDUITS MUST BE CUT AND MODIFIED TO RECEIVE THE NEW

CONDUITS.

7. PANEL HBDP IS LOCATED IN BUILDING 4153 RM 220. CONTRACTOR

SHALL PROVIDE TEMPORARY POWER TO THIS PANEL AND OTHER

CRITICAL PANELS WHILE SWITCHBOARD IS REPLACED.

GENERAL NOTES:

1. REFER TO SHEET E-001 FOR ACRONYMS AND SYMBOLS.

2. CONTRACTOR SHALL FEILD VERIFY EXISTING CONDITIONS.

LEG

3000 A 3P

G

A SS

SSV

WM

3000A MAIN

CIRCUIT BREAKER

WITH GROUND

FAULT PROTECTION

DRAWOUT TYPE

AMP METER

WATTHOUR METER

VOLT METER

2000 A 3P

400 A 3P

1000 A 3P

FUSIBLE PANELBOARD 'HDP' 277/480V 3

PHASE 4 WIRE 1200A MAIN BUS

SECONDARY UNIT SUBSTATION TRANSFORMER

2000 KVA, OIL FILLED

12470 - 277/480Y

3 PHASE 4 WIRE, 5.75% Z

1200A - 15 KV FUSED INTERRUPTER SWITCH

W/3 - 200A FUSES

(3) #4/0 KCMIL ALUMINUM 15 KV-SHLD.

(1) #2 GND.

5" C.

15 KV FUSED INTERRUPTER SWITCH W/200A FUSES

15 KV SURGE ARRESTER

3000A, 4-POLE

BY-PASS/

ISOLATION

TRANSFER

SWITCH

WITH NEUTRAL THROUGHOUT

4 #6

1 #10 GND

1"C

NEW GENERATOR

SET:

2000 KW @ 0.8 P.F.

480Y/277V, 3 PHASE

4-WIRE IN EATHER

HOUSING. GROUND

GENERATOR NEUTRAL

IN ACCORDANCE WITH

NEC 250.

PANEL 'HBDP'

277/480V

3 PHASE 4 WIRE

14,000 AIC

8 SETS ((4) #500 KCMIL COPPER, (1) #400 GND -

4" C.)

NEW SWITCHGEAR

277/480V, 3 PHASE 4 WIRE

3000A MAIN BUS. 50,000AIC

EXISTING OVERHEAD DISTRIBUTION SYSTEM 7200/12470

400A 400A 400A

400A 400A 400A

EMCC 5 EMCC 3 EMCC 1

EMCC 6 EMCC 4 EMCC 2

LEA

45,000AIC TYP.

CONSTRUCTED FOR BACK TO BACK MOUNTING TYP.

3 SETS (4 - #400,

1 - #2/0 GND

3"C)

4 - #500 XHHW,

#3 GND

3 1/2" C

2000A

BUSWAY

3000 A 3P

'SWBD MDP'

277/480V 3 PHASE

SPD

2000A

BUSWAY

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

File Path:

Plot Date:

M A

R K

D E

S C

R

IP

T

IO

N

D:\Desktop\Projects\Dugway Proving Grounds - UT\B4156\BIM\B4156_Electrical_New.rvt

24-Apr-24 11:03:32

E-602

O N

E -L

IN

E

D

IA

G R

A M

N E

W

D U

G W

A Y

P R

O V

IN

G

G R

O U

N D

U

T A

H

S A

C R

A M

E N

T O

D

IS

T R

IC

T

J

S T

R E

E T

S A

C R

A M

E N

T O

C

A

D Z

A W

A L

IC

H

D Z

A W

A L

IC

H s J L O

R E

N Z

O O

R T

IZ

A

P R

W -X

X -X

-X X

X X

W -X

X -X

-X X

X X

S P

E C

N O

D E

S

IG

N F

IL

E

N O

C O

R R

E C

T E

D F

IN

A

L

B U

IL

D

IN

G

E L E

C T

R

IC

A L U

P G

R A

D E

P N

-2

-0

KEY NOTES:

1. DRAWOUT TYPE CIRCUIT BREAKER WITH GROUND FAULT PROTECTION. 400

AMP CIRCUIT BREAKER DOES NOT REQUIRE GROUND FAULT PROTECTION.

2. UNLESS DIRECTED OTHERWISE, CONTRACTOR SHALL REUSE EXISTING

FEEDER PARALLEL CONDUITS AND/OR BUSDUCT CONNECTED TO EXISTING

ELECTRICAL EQUIPMENT FROM NEW ATS WITH BYPASS/ISOLATION,

SWITCHGEAR DISTRIBUTION BREAKERS AND GENERATOR MAIN BREAKER AND

POWER AND CONTROL CIRCUITS.

3. CONTRACTOR SHALL VERIFY EXISTING CONDITION AND DISTRIBUTION.

4. EXISTING BUSWAY TO REMAIN, CONTRACTOR SHALL RECONNECT EXISTING

BUSWAY TO NEW EQUIPMENT.

5. CONTRACTOR SHALL USE EXISTING SMART METER IN ACCORDANCE WITH

SPECIFICATION 26 27 13.

6. NEW SWITCHGEAR AND ATS SHALL BE OF THE SAME MANUFACTURER AND

SHALL BE 100 PERCENT COMPATIBLE WITH EXISTING BUSDUCT. EXISTING

FEEDER CABLE/BUSDUCT SHALL BE REUSED, CONTRACTOR SHALL MEGGER

EXISTING CABLING PER SPECIFICATION 26 20 00 BEFORE TERMINATION AT

NEW EQUIPMENT. IF CABLE/BUSDUCT INSULATION ON ANY PARALLEL SET

FAILS, THEN CONTRACTOR SHALL REPLACE WITH NEW SET OF

CABLES/BUSDUCT ONE CONDUIT AT A TIME. ANY MODIFICATION TO EXTEND

EXISTING BUSDUCT/BUSWAY SHALL BE CERTIFIED BY BUSDUCT/BUSWAY

MANUFACTURER'S REPRESENTATIVE.

7. PANEL HBDP IS LOCATED IN BUILDING 4153 RM 220.

GENERAL NOTES:

1. REFER TO SHEET E-001 FOR ACRONYMS AND SYMBOLS.

2. CONTRACTOR SHALL FEILD VERIFY EXISTING CONDITIONS.

1 11

2 2 2 2

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

File Path:

Plot Date:

M A

R K

D E

S C

R

IP

T

IO

N

D:\Desktop\Projects\Dugway Proving Grounds - UT\B4156\BIM\B4156_Electrical_New.rvt

24-Apr-24 11:03:32

E-603

P A

N E

L S

C H

E D

U L E

S

D U

G W

A Y

P R

O V

IN

G

G R

O U

N D

U

T A

H

S A

C R

A M

E N

T O

D

IS

T R

IC

T

J

S T

R E

E T

S A

C R

A M

E N

T O

C

A

D Z

A W

A L

IC

H

D Z

A W

A L

IC

H

/s J L O

R E

N Z

O O

R T

IZ

A

P R

W -X

X -X

-X X

X X

W -X

X -X

-X X

X X

S P

E C

N O

D E

S

IG

N F

IL

E

N O

C O

R R

E C

T E

D F

IN

A

L

B U

IL

D

IN

G

E L E

C T

R

IC

A L U

P G

R A

D E

P N

-2

-0

Notes:

Total Est. Demand: 0 A

Total Conn.: 0 A

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 0 A

Total Conn. Load: 0 VA

8 SPACE 3 -- -- --

7 SPARE 3 400 A 400 A 0 VA

6 SPARE 3 3000 A 3000 A 0 VA

5 SPD 3 0 A 0 A 0 VA

4 2000A BUSWAY FOR EMCC 3 2000 A 2000 A 0 VA

3 HBDP 3 400 A 400 A 0 VA

2 SWBD MDP 3 3000 A 3000 A 0 VA

1 HDP 3 1200 A 1000 A 0 VA

CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks

Notes:

Enclosure: MCB Rating: 3000 A

Mounting: FLOOR MOUNTED Wires: 4 Mains Rating: 3000 A

Supply From: BY-PASS/ISOLATION... Phases: 3 Mains Type: MAIN BREAKER

Location: Volts: 480/277 Wye A.I.C. Rating: 50k AIC

Switchgear: NEW...

G-001 - COVER SHEET
G-002 - HAUL ROUTE
E-001 - ELETRICAL LEGEND AND ABBREVIATIONS
ED101 - ELECTRICAL DEMOLITION PLAN
ED102 - DEMOLITION PLAN
ES101 - ELECTRICAL SITE PLAN
E-101 - POWER PLAN
E-102 - PHASING
E-401 - SWITCHGEAR LAYOUT
E-501 - DETAILS
E-502 - DETAILS
E-503 - GROUNDING SYSTEM DIAGRAM
E-601 - ONE-LINE DIAGRAM EXISTING
E-602 - ONE-LINE DIAGRAM NEW
E-603 -PANEL SCHEDULES