The following pages are an excerpt from the Draft 01 10 10
Specifications.
This document is for information only and subject to change.
GBSD - MISSION INTERGRATION FACILITY W91238-18-D-0019
HILL AIR FORCE BASE, UTAH
01 10 10 - 62
GENERAL
Project Scope
This request for proposal (RFP) provides for the design and construction of the Ground- Based Strategic Deterrent Mission Integration
Facility (GBSD MIF) and adjacent parking garage at Hill Air Force Base.
Reference PART 12 for Parking Garage criteria. The overall design goal for the facilities is to provide a contemporary, functional, and visually appealing complex that is a source of pride for users and Hill AFB. The project scope is limited to a maximum area of 140,000 square feet per the
DOD 1391 requirements. The schematic drawings represent a conceptual design of 139,926 gross square feet. It is the intent of this RFP that the
DBT shall construct a facility that incorporates all of the requirements stated herein up to and as close to the 1391 area limitation without exceeding such limitation. Once all functional area requirements represented in the RFP are met, floor plan efficiencies resulting in excess square footage, but below the 140,000 gross square foot limitation, shall be allocated to the inclusion of the following bonus program areas (in order of priority-first being highest priority):
Increase Auditorium seating to 700-person capacity-area as required.
Include a space for a 20-seat café-style dining area-for hot and cold sandwiches, soups and beverages-area as required.
Fitness area-not to exceed 750 square feet.
Though not shown on the documents, all building construction including, but not limited to foundation, structure, walls, floors, ceilings, doors, hardware, finishes, power, communications, plumbing, all other utilities, and FF&E, fees, and associated supervision sand management shall be included to accommodate the above bonus program areas. All costs to accommodate the above bonus program areas shall be included in the overall project costs. Excess square feet shall not be assigned to excessive areas of circulation or unusable space.
Calculations of the gross areas for the overall structure shall be in accordance with UFC 3-101-01 Architecture.
The concept drawings and supporting narrative requires an
ICD/ICS-705-1 compliant administrative facility constructed in three stories above grade. It will provide the necessary facilities and the required security measures for personnel to perform work in a controlled environment, in accordance with the GBSD Security Classification Guide.
Site modifications include a paved drop-off drive on the west (main entrance) side of the building, fenced loading area, trash/recycling receptacle storage area and the demolition of an existing Recreational
Vehicle (RV) lot, to be reconstructed at a location off-site.
The MIF will generally be comprised of private and open office areas, auditorium, laboratories, conference rooms, computer labs, server rooms and support spaces, secure spaces, storage areas, shipping/receiving dock area, breakrooms, restrooms, and mechanical/electrical support spaces and a separate parking garage containing approximately 700 vehicle spaces.
The office areas will be dominated by open plan workstations configured for a collaborative work environment. User functional priorities include
01 10 10 - 63 security, contiguous secure areas, flexible work environments and small meeting space for collaborative work. Special purpose space includes teamwork areas, conference rooms, and laboratories.
The building height above grade shall accommodate the view angle required for aircraft communication as indicated in diagrams provided in
PART 3 SITE WORK, except for antennae approved by the user. The finish floor of any programmed space shall not be constructed below ground level.
The concept drawings have been developed with the users to optimize operational building organization and they generally illustrate the functional needs, adjacencies, and relationships required in the facility. The primary adjacencies shall be maintained, unless the DBT recommends changes to the Owner and the Contracting Officer approves such changes.
The requirements specified in this PART 4-ARCHITECTURAL DESIGN and the Room Data Sheets are complementary and shall be incorporated into the proposal. Programmed net square footage allotted to mechanical, electrical, communications, and equipment rooms, or other similar building support spaces is a preliminary estimate of required space. The DBT shall provide the Owner with appropriately sized and dispersed accessible building support spaces, with code-compliant or manufacturer-specific equipment clearances for each such room. Roof-mounted equipment, where provided, shall be readily accessible through an internal roof hatch, with ladder access. All interior support spaces shall be appropriately shaped to allow access and ease of maintenance of equipment, with critical consideration given to removal and replacement of equipment or components without demolition of constructed elements or disruption of building users or functions. Irregular or oddly shaped spaces are discouraged and are not considered an efficient shape that is usable for enclosed or open office, storage or building support spaces.
All materials and equipment used for construction shall be new and free from defects. The finish materials and colors selected for the project shall be in accordance with the Hill Architectural Compatibility
Plan (ACP)as applicable.
Project Goals and Objectives
This facility should incorporate or foster the following:
Flexible and adaptable work environments.
Balance of individual and teamwork spaces.
Consistent amenities and support spaces.
Sense of identity.
Secure space planning.
User control and comfort in the environment.
Agile and future-proof IT infrastructure.
Environmental stewardship.
Architectural Compatibility and Context: The aesthetic approach for the design character for the MIF Complex shall be to create a cohesive architectural vocabulary that echoes elements of the contemporary style of adjacent structures on the base, but all features or elements shall be
01 10 10 - 64 compatible with the goals and objectives of the Architectural Compatibility
Plan for Hill Air Force Base. Concept drawings have been provided as the basis of design in the Appendix for the proposed facility. Any revisions to the plans shall be reviewed and approved by the Contracting Officer and the GBSD MIF representatives.
Exterior Design Objectives: The design of the building shall enhance the visual environment of the surrounding area. Exterior materials, roof forms, and detailing shall comply with the provisions of this RFP. Use durable, low-maintenance materials. Configure building massing and use exterior elements such as entry elements and material detailing to provide human scale. The overall appearance and aesthetic expression of the complex is of paramount importance to the Owner. The exterior envelope and massing shall be of simple and modern design that exemplifies the importance of a research facility. Simplicity in design will reduce the complexity of long-term maintenance and cost. The exterior building design guidance is conceptual; the DBT shall finalize all elements of the design, including exact dimensions. In completing the design, the
DBT will be allowed some latitude in manipulating the plans to improve functional layout, to accommodate structural, mechanical, electrical and other systems, and to allow for the implementation of sustainable design strategies and design/aesthetic expression. Both the MIF and the parking garage shall share the same color palette and material selection, as well as utilitarian structures such as screen walls, trash/recycling or mechanical/electrical enclosures or other outbuildings.
Interior Design Objectives: The interiors of the Complex shall be designed to reflect the mission of those who are engaged in the facilities, while arranging spaces in an efficient and functional manner.
The DBT shall provide a turn-key Comprehensive Interior Design (CID) package for the facility to include all building finishes and furnishings, including exterior finishes per UFC 3-120-10 requirements.
Refer to Interior Design Section 4.6 for additional information.
For functional purposes, the following spaces shall be column-free: Auditorium, conference rooms, computer labs, and all other spaces in which columns or other structural elements would impede sightlines or the efficient layout of furniture.
The main entrance lobby shall be designed in a manner providing clear delineation of non-secure and secure sides of the entry sequence. The lobby area configuration should provide the flexibility to allow appropriate public access to areas such as the auditorium, or Command area. The ability to restrict public access past the front entry, except for authorized personnel, is required.
Finishes and materials shall be utilized to define and identify the hierarchy of spaces and rankings located throughout the facility. Provide circulation schemes allowing for easy way-finding. Use durable materials and furnishings that can be easily maintained and replaced. Use interior surfaces that are easy to clean, but durable to repeated cleaning, and light in color. Project an atmosphere which is inviting and introduces color palettes associated with the region and mission of the facilities. Where feasible, arrange spaces to allow rearrangement of the furniture layout.
01 10 10 - 65
Coordinate interior finish materials, insulation and composite woods, as well as furnishings selections, with UFC 1-200-02.
This document provides basic finish requirements and defines levels of hierarchy for spaces throughout the complex. The
Proposer shall develop a comprehensive finish and color palette for approval by the Owner, including exterior and interior accent colors and finishes. Finishes submitted shall include all wall, ceiling and floor finishes as well as finishes for doors, hardware, door frames and window frames. The SID package shall include finishes for toilet partitions, lavatories, millwork, casework, window stools and shades. Refer to Section 4.6D -
Finishes for a general listing and criteria of interior finishes.
The DBT shall adhere to the minimum level of quality set forth in this document. All building finishes, both exterior and interior, shall be included in the SID package. Room specific finish levels are identified on the Room Data Spreadsheet.
Antiterrorism/Force Protection
The building and site shall be designed to incorporate minimum construction standards in accordance with UFC 4-010-01, DoD Minimum
Antiterrorism Standards for Buildings, including structure, storefront, windows, entrance layout, exterior doors and roof. The facility shall be designed to meet the minimum construction standards in accordance with UFC
4-010-01 for the actual standoff distances provided by the final site layout. For additional information, see PART 3 - SITE WORK and PART 5 -
STRUCTURAL DESIGN.
Security Considerations
For the most secure spaces, Intelligence Community Directive
(ICD) 705 requires that all Sensitive Spaces must comply with uniform physical and technical security requirements. The Sensitive Space must be planned, programmed, designed, and constructed per ICD 705 requirements and shall be DIA accredited by the Accrediting Official (AO). Working closely with the supporting command, designated Site Security Manager (SSM), and the Certified TEMPEST Technical Authority (CTTA) the requirements will be determined for each Sensitive Space. Per ICS 705-1, a Construction
Security Plan (CSP) will be developed by the SSM and approved by the AO to address the required physical security measures. The CSP will provide initial guidance to the design team for the required physical security measures.
Electronic Security Systems (ESS) encompass the facility's Access
Control (ACS), Intrusion Detection (IDS), and Closed-Circuit Television
(CCTV) systems.
Access control is required at each exterior door, each exterior entrance door, each access control point, and at the primary entrance of the Sensitive Space. An Intrusion Detection System (IDS) is required within the facility’s-controlled area. IDS devices are required at each exterior mechanical/electrical room door, exterior entrance doors, the
Sensitive Space entrance, emergency exits, and all windows below 18 feet.
Motion sensors will be required for all first-floor spaces having windows.
CCTV is required at each mechanical/electrical equipment room exterior door, employee entrances, primary Sensitive Space entrance
(secret/controlled), all controlled hallways/spaces, and the entire building perimeter. Design coordination with the SSM for the ESS specific requirements of the facility will be necessary.
01 10 10 - 66
Life Safety
A Qualified Fire Protection Engineer (QFPE) shall prepare and submit a complete life safety analysis documenting compliance with building and life safety codes and references as part of each phase of design and the final design package. This facility shall be designed to meet or exceed the minimum construction and life safety standards as required by
UFC 3-600-1. Occupancy separations shall be per the International Building
Code.
Fire Safety
Minimum allowable construction type, per UFC 3-600-1 shall be
Type IIB, non-combustible. However, the actual construction type shall be determined and proposed by the Proposers based on a full code analysis.
Each facility shall be of noncombustible construction and the interior of the facilities shall be fully sprinklered.
Accessibility and Barrier Free Design
This facility shall be required to be fully accessible incorporating barrier-free design in accordance with the requirements of the Architectural Barriers Act design guidelines (ABA). All building entrances, stairs, elevators, restrooms, fixtures, room or space door clearances, counters, FFE, signage, systems, and all other building elements shall be accessible according to these guidelines.
Energy Conscious Design
Passive solar design shall be incorporated to the greatest extent possible where it is not in conflict with other provisions of this RFP.
Strategies include, but not limited to, building orientation, roof color, building color, fenestration orientation, window glazing, and window shading. Maximizing daylighting throughout the complex is encouraged.
Reference SECTION 01 10 12 for Sustainable Design requirements.
Thermal, Vapor and Air Control
Thermal insulation shall be provided in accordance with the
Mechanical Section of this RFP. Perimeter rigid insulation shall be provided for all foundation walls of heated spaces. A vapor barrier shall be provided on the warm side of exterior walls, roofs and floors over unheated spaces. No loose or granular fill insulation will be permitted.
Sustainable Design Requirements
Refer to SECTION 01 10 12 for Sustainable Design requirements.
FUNCTIONAL AND PROGRAMMATIC REQUIREMENTS
External General Considerations and Features
Personnel will access the site by Government owned vehicles, privately owned vehicles, bicycles, motorcycles, and by walking from offsite. Paved vehicular access and maneuvering space and pedestrian paths shall be provided between the MIF and the parking garage, and the site perimeter.
A VIP drop-off shall be incorporated into the vehicular access to the MIF building at the main entrance. The drop-off shall be operational only with the manual removal of security bollards at the perimeter of the drop off-driveway. The main entrance shall be covered to provide shade or cover for inclement weather.
01 10 10 - 67
In close proximity to the front entrance of the MIF building and in direct view of the entry, one flagpole shall be provided. A minimum 5-foot wide concrete walkway leading from the main entry shall access the flagpole display and encircle the installation. The pole shall be a minimum 30 feet in height. The flag shall be lighted for nighttime illumination. All lighting shall be Dark Sky Compliant and oriented such that it shall not interfere with aircraft or airfield operations areas.
An area in front of the MIF building shall be reserved for a static display (such as aircraft or similar hardware) at the discretion of the Owner. A paved pedestrian path shall extend to all such areas with power provided and site lighting as appropriate to the display.
Provide an at-grade entrance with dock lift at the loading dock area to assist in unloading trucks for service deliveries and trash/recyclables removal. See Section 4.4.6.
Additional requirements for the above site features are provided in PART 3 - SITE WORK.
Internal General Considerations and Features
This project will house MIF personnel and contract staff.
Portions of the facility will be secure. Refer to the Room Data Sheets in the Appendix for spaces required to meet specific security criteria.
BUILDING SYSTEMS, MATERIALS, AND EQUIPMENT
General
The proposed building systems, materials, and equipment shall be in accordance with the requirements of this RFP. The intent of this RFP is to allow Proposers flexibility to design and construct this facility in an economical manner without sacrificing good engineering practices, quality materials and systems, architectural detailing, and ease of maintenance.
All buildings, structures, fencing, barriers, site furniture and screen walls shall exhibit in its appearance and detailing, a cohesive campus of consistent high quality and functionality, reflecting a common color pallet and exterior material selection. No criteria contained in this RFP shall be construed to indicate that lower quality or builder’s grade components, materials, or finishes are acceptable.
Building Structure and Exterior Wall Construction
The following paragraphs provide a general description of acceptable and unacceptable construction, but it is not all inclusive of all details and criteria necessary for a high-performance building.
Acceptable exterior wall construction may be considered as alternative exterior wall systems or materials to supplement the required exterior wall construction to meet the requirements of the ACP.
Acceptable exterior wall construction:
Concrete
Cast-in-place concrete may be used for any structural or architectural element; however, any exposed-to-view concrete shall be limited in scope unless integrally colored and cast in forms with liners that provide a smooth finish. All such concrete shall not exceed more than 5% of the surface area of the MIF building. Exposed board formed concrete shall be limited to no more than 2.5% of the