This document package includes specifications for electric unit heaters and electric space heating equipment required for the renovation of Building 42 at the Defense Logistics Agency facility in Richmond, Virginia. The specifications call for suspended electric unit heaters with wall-mounted thermostats, as well as electric baseboard units and cabinet heaters. Key components of the unit heaters include nickel-chromium heating elements, refractory insulation, and galvanized steel propeller blades. The baseboard units and cabinet heaters must meet UL standards and include overheat protection controls. The specifications provide requirements for enclosures, wiring, disconnects, and testing to ensure proper installation and performance of the heating equipment. The related federal contract opportunity is solicitation number W9123620B0002 for the Building 42 renovation project managed by the U.S. Army Corps of Engineers Norfolk District.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COE-N - Repair Building 42 DLA 2130170

SECTION 23 82 46.00 40

ELECTRIC UNIT HEATERS

PART 1 GENERAL

Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS applies to work specified in this section.

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

UNDERWRITERS LABORATORIES (UL)

UL 1996 (2009; Reprint Jul 2016) UL Standard for Safety Electric Duct Heaters

1.2 SUBMITTALS

Submit the following in accordance with Section 01 33 00 SUBMITTAL

PROCEDURES:

SD-02 Shop Drawings

Fabrication Drawings

SD-03 Product Data

Performance Data

Electric Unit Heaters

Heating Element

Controls

Casings

Propellers and Motors

SD-08 Manufacturer's Instructions

Manufacturer's Instructions

PART 2 PRODUCTS

2.1 SYSTEM DESCRIPTION

Provide suspended electric unit heaters, and arrange for the discharge of air as indicated.

Provide electric unit heaters with at least the indicated capacity and ensure that they conform to the requirements specified herein. Ensure that the electric unit heaters are factory-prewired and ready for field

SECTION 23 82 46.00 40 Page 1 terminal connections.

Ensure products conform to the requirements of UL 1996 for electric unit heaters.

Submit performance data for electric heaters, including use life, test, system functional flows, safety features, and mechanical automated details.

2.2 COMPONENTS

2.2.1 Heating Element

Provide a heating element constructed of a resistance wire insulated by highly compacted refractory insulation protected by a sealed metallic-finned sheath. Provide component materials as follows:

a. Provide a resistance wire of not less than 20-helix wound alloy of approximately 80-percent nickel and 20-percent chromium.

b. Provide a refractory insulation of magnesium oxide with a resistance of not less than 50,000 ohms after exposure to an ambient temperature and humidity of 90 degrees F and 85 plus or minus 5-percent relative humidity, respectively, for not less than 24 hours.

c. Provide a sheathing consisting of aluminum fins cast around an internal steel sheath containing refractory insulation and resistance wire or carbon-steel fins permanently attached to a tubular carbon-steel sheath containing refractory insulation and resistance wire and with external surfaces porcelainized.

2.2.2 Controls

Provide wall-mounted thermostats complete with thermometer, mechanical high-limit stop, calibrated operator, and an adjustable heater to prevent override of space temperature with a range between 55 and 105 degrees F and a differential not exceeding 1.5 degrees F. Provide a thermostat rated for operation at 24 volts, 60 hertz. Provide transformers, wiring, and devices necessary to meet this requirement.

2.2.3 Propellers and Motors

Provide propellers with galvanized-steel blades statically and dynamically balanced to within 0.5 percent. Provide units with fan-inlet safety guards.

Ensure that propellers and motors are AMCA-certified for air performance and noise level.

Protect motors against damage by the heating element and resilient mount.

Ensure that propellers and motors conform to Section 26 60 13.00 40 LOW-VOLTAGE MOTORS for motors, except that load-matched and custom-designed motors may be used and be so identified on the shop drawings. For motors not so identified, conform to the requirements specified.

Subfractional and fractional custom-designed or applied motors may deviate from the preceding motor requirements as follows:

SECTION 23 82 46.00 40 Page 2

a. Shaded-pole motors rated less than 1/6 horsepower may be used for direct-drive service.

b. Permanent split-capacitor, split-phase, and capacitor-start motors rated 1/4 horsepower or less may be used for direct-drive service.

c. Split-phase and capacitor-start motors, rated 1/4 horsepower or less, may be used for belt-drive service.

d. Motor bearings may be the manufacturer's standard prelubricated sleeve type but provide the motor with antifriction thrust bearings, when specified. Ensure that the lubricant provisions are for extended service, requiring replenishment not more than twice per year of continuous operation.

Provide the manufacturer's standard motor identification plate.

Provide the manufacturer's standard motor speed and control.

PART 3 EXECUTION

3.1 INSTALLATION

Install unit heaters in accordance with the manufacturer's instructions at the mounting heights indicated.

3.1.1 Casings

Provide casings with smoothly contoured propeller orifice rings of at least 20-gage cold-rolled carbon steel. Provide a casing surface finish with phosphate pretreatment, prime coating, and baked-enamel finish.

3.1.2 Air Distribution

Provide horizontal units with adjustable single- or double-deflection louvers.

3.2 FIELD QUALITY CONTROL

Demonstrate in the presence of the Contracting Officer that the unit heaters operate satisfactorily.

Cycle unit heaters five times, from start to operating thermal conditions to off, to verify adequacy of construction, system controls, and component performance.

Conduct an operational test for a minimum of 6 hours.

-- End of Section --

SECTION 23 82 46.00 40 Page 3

SECTION 23 83 00.00 20

ELECTRIC SPACE HEATING EQUIPMENT

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;

TIA 17-3; TIA 17-4; TIA 17-5; TIA 17-6;

TIA 17-7; TIA 17-8; TIA 17-9; TIA 17-10;

TIA 17-11; TIA 17-12; TIA 17-13; TIA

17-14; TIA 17-15; TIA 17-16; TIA 17-17 )

National Electrical Code

UNDERWRITERS LABORATORIES (UL)

UL 1025 (1980; R 1990, Bul. 1991) Electric Air Heaters

UL 1042 (2009; Reprint Dec 2016) UL Standard for Safety Electric Baseboard Heating Equipment

1.2 GENERAL REQUIREMENTS

Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS, applies to this section, with the additions and modifications specified herein.

1.3 SUBMITTALS

Submit the following in accordance with Section 01 33 00 SUBMITTAL

PROCEDURES:

SD-02 Shop Drawings

Heater installation drawing

SD-03 Product Data

Electric unit and cabinet heaters

Electric baseboard units

Thermostat

Unit thermostat

SD-10 Operation and Maintenance Data

Electric unit and cabinet heaters, Data Package 5

SECTION 23 83 00.00 20 Page 1

Electric baseboard units, Data Package 5

Submit in accordance with Section 01 78 23 OPERATION AND

MAINTENANCE DATA.

PART 2 PRODUCTS

2.1 ELECTRIC UNIT AND CABINET HEATERS

UL 1025 ; wattage, voltage, phase, number of steps, Btu/hr and CFM as indicated. Provide control-circuit terminals and single source of power supply. Heaters 5 Kw and larger shall be 3-phase, with load balanced on each of the three phases. Limit leaving air temperature to 140 degrees F with entering air of 60 degrees F.

2.1.1 Enclosure

Minimum 20 gage steel.

2.1.2 Heating Element

Nickel chromium heating wire element, free from expansion noise and 60 Hz hum. Embed element in magnesium-oxide insulating refractory. Seal element in high-mass steel or corrosion-resisting metallic sheath with fins. Enclose element ends in terminal box. Provide not more than six fins per inch. Limit fin surface temperature 550 degrees F at any point during normal operation.

2.1.3 Controls

Include limit controls for overheat protection of heaters. For remote thermostatic operation, provide contactor rated for 100,000 duty cycles.

2.1.4 Wiring

Completely factory-prewired to terminal strips, ready to receive branch circuit and control connections for 140 degrees F copper wiring.

2.1.5 Thermostat

Provide tamper resistant space thermostat, adjustable without requiring removal of heater components. Thermostat operating range shall be approximately 50 degrees F to a maximum of 75 degrees F with operating differential of 3 degrees F or less.

2.1.6 Disconnect Means

Provide factory-installed safety disconnect switch in the housing or in an auxiliary matching control section with "off" position marking on the face plate.

2.2 ELECTRIC BASEBOARD UNITS

UL 1042 ; wattage, voltage, phase, Btu per houroutput indicated. Provide units complete with heating elements, mounting brackets, end closures, splice plates, interior and exterior corners and accessible wiring compartment. Limit outlet air temperature and enclosure surfaces to 200 degrees F under continuous operating conditions.

SECTION 23 83 00.00 20 Page 2

2.2.1 Enclosure

Fabricate from steel not less than 12 gage. Provide manufacturer's standard white finish. Locate terminal blocks for branch circuit conductor and control wiring connections as required. Wiring shall conform to NFPA 70 .

2.2.2 Accessories

Where continuous wall-to-wall installations are indicated, provide accessories; including corner fittings, fillers, splice plates, and end caps. Accessories shall have the same profile as the basic unit, and contain no sharp edges. Provide for expansion of enclosure.

2.2.3 Limit Control

Provide thermal overload and over voltage protection.

2.2.4 Disconnect Means

Provide factory-installed safety disconnect switch in the housing or in an auxiliary matching control section with "off" position marking on the face plate.

2.2.5 Unit Thermostat

Provide tamper resistant space tool adjustable thermostat, without requiring removal of cabinet parts. Thermostat, operating range shall be approximately 50 degrees F to a maximum of 75 degrees F with operating differential of 3 degrees F or less.

2.3 DISCONNECTS

Disconnect. UL listed. Enclosed non-fusible switch, rated 120 volt, 1 phase, NEMA Type 1 enclosure.

PART 3 EXECUTION

3.1 INSTALLATION

Install in conformance with the approved heater installation drawing, NFPA 70 , UL listing, and manufacturer's instructions, with necessary clearances for air circulation, maintenance, inspection, service testing and repair. Connect to electrical supply in accordance with Section

26 20 00 INTERIOR DISTRIBUTION SYSTEM.

3.1.1 Unit Heaters

Mount units plumb, square and level with ceiling and walls.

3.1.2 Cabinet Heaters

Where recessed mounting is indicated, seal entire recessed opening from exterior wall cavities, and provide a minimum 1/2-inch thick rigid fire resistant insulation on the wall behind the cabinet. Verify manufacturer's clearance requirements from electrical cords, drapes, and other furnishings.

SECTION 23 83 00.00 20 Page 3

3.1.3 Remote Thermostat

Mount remote room space thermostats 4 feet 6 inches above finished floor on wall or as indicated. Connect remote thermostats with conduit and wiring to heaters as indicated.

3.1.4 Baseboard Heaters

Verify manufacturer's clearance requirements from electrical cords, drapes, and other furnishings.

3.2 FIELD QUALITY CONTROL

Provide necessary personnel, instruments, and equipment to perform tests.

Notify the Contracting Officer 5 working days prior to scheduled testings and locations.

3.2.1 Field Inspection

Prior to initial operation, inspect installed equipment for conformance with drawings and specifications.

3.2.2 Insulation Resistance Tests

Test 600-volt wiring to verify that no short circuits or grounds exist.

Tests shall be made using an instrument which applies a voltage of approximately 500 volts and provides a direct reading of resistance in ohms.

3.2.3 Operational Tests

Test equipment circuits and devices to demonstrate proper operation.Test each item of control equipment not less than 5 times.

SECTION 23 83 00.00 20 Page 4

-- End of Section --

SECTION 23 83 00.00 20 Page 5

DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
ELECTRIC UNIT HEATERS
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
2.2 COMPONENTS
2.2.1 Heating Element
2.2.2 Controls
2.2.3 Propellers and Motors
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Casings
3.1.2 Air Distribution

3.2 FIELD QUALITY CONTROL

ELECTRIC SPACE HEATING EQUIPMENT
PART 1 GENERAL
1.1 REFERENCES
1.2 GENERAL REQUIREMENTS
1.3 SUBMITTALS
PART 2 PRODUCTS
2.1 ELECTRIC UNIT AND CABINET HEATERS
2.1.1 Enclosure
2.1.2 Heating Element
2.1.3 Controls
2.1.4 Wiring
2.1.5 Thermostat
2.1.6 Disconnect Means
2.2 ELECTRIC BASEBOARD UNITS
2.2.1 Enclosure
2.2.2 Accessories
2.2.3 Limit Control
2.2.4 Disconnect Means
2.2.5 Unit Thermostat

2.3 DISCONNECTS

PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Unit Heaters
3.1.2 Cabinet Heaters
3.1.3 Remote Thermostat
3.1.4 Baseboard Heaters
3.2 FIELD QUALITY CONTROL
3.2.1 Field Inspection
3.2.2 Insulation Resistance Tests
3.2.3 Operational Tests

File details come from the government source that posted it. Updated .