This document package includes specifications for electric unit heaters and electric space heating equipment required for the renovation of Building 42 at the Defense Logistics Agency facility in Richmond, Virginia. The specifications call for suspended electric unit heaters with wall-mounted thermostats, as well as electric baseboard units and cabinet heaters. Key components of the unit heaters include nickel-chromium heating elements, refractory insulation, and galvanized steel propeller blades. The baseboard units and cabinet heaters must meet UL standards and include overheat protection controls. The specifications provide requirements for enclosures, wiring, disconnects, and testing to ensure proper installation and performance of the heating equipment. The related federal contract opportunity is solicitation number W9123620B0002 for the Building 42 renovation project managed by the U.S. Army Corps of Engineers Norfolk District.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COE-N - Repair Building 42 DLA 2130170
SECTION 23 82 46.00 40
ELECTRIC UNIT HEATERS
PART 1 GENERAL
Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS applies to work specified in this section.
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
UNDERWRITERS LABORATORIES (UL)
UL 1996 (2009; Reprint Jul 2016) UL Standard for Safety Electric Duct Heaters
1.2 SUBMITTALS
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Fabrication Drawings
SD-03 Product Data
Performance Data
Electric Unit Heaters
Heating Element
Controls
Casings
Propellers and Motors
SD-08 Manufacturer's Instructions
Manufacturer's Instructions
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Provide suspended electric unit heaters, and arrange for the discharge of air as indicated.
Provide electric unit heaters with at least the indicated capacity and ensure that they conform to the requirements specified herein. Ensure that the electric unit heaters are factory-prewired and ready for field
SECTION 23 82 46.00 40 Page 1 terminal connections.
Ensure products conform to the requirements of UL 1996 for electric unit heaters.
Submit performance data for electric heaters, including use life, test, system functional flows, safety features, and mechanical automated details.
2.2 COMPONENTS
2.2.1 Heating Element
Provide a heating element constructed of a resistance wire insulated by highly compacted refractory insulation protected by a sealed metallic-finned sheath. Provide component materials as follows:
a. Provide a resistance wire of not less than 20-helix wound alloy of approximately 80-percent nickel and 20-percent chromium.
b. Provide a refractory insulation of magnesium oxide with a resistance of not less than 50,000 ohms after exposure to an ambient temperature and humidity of 90 degrees F and 85 plus or minus 5-percent relative humidity, respectively, for not less than 24 hours.
c. Provide a sheathing consisting of aluminum fins cast around an internal steel sheath containing refractory insulation and resistance wire or carbon-steel fins permanently attached to a tubular carbon-steel sheath containing refractory insulation and resistance wire and with external surfaces porcelainized.
2.2.2 Controls
Provide wall-mounted thermostats complete with thermometer, mechanical high-limit stop, calibrated operator, and an adjustable heater to prevent override of space temperature with a range between 55 and 105 degrees F and a differential not exceeding 1.5 degrees F. Provide a thermostat rated for operation at 24 volts, 60 hertz. Provide transformers, wiring, and devices necessary to meet this requirement.
2.2.3 Propellers and Motors
Provide propellers with galvanized-steel blades statically and dynamically balanced to within 0.5 percent. Provide units with fan-inlet safety guards.
Ensure that propellers and motors are AMCA-certified for air performance and noise level.
Protect motors against damage by the heating element and resilient mount.
Ensure that propellers and motors conform to Section 26 60 13.00 40 LOW-VOLTAGE MOTORS for motors, except that load-matched and custom-designed motors may be used and be so identified on the shop drawings. For motors not so identified, conform to the requirements specified.
Subfractional and fractional custom-designed or applied motors may deviate from the preceding motor requirements as follows:
SECTION 23 82 46.00 40 Page 2
a. Shaded-pole motors rated less than 1/6 horsepower may be used for direct-drive service.
b. Permanent split-capacitor, split-phase, and capacitor-start motors rated 1/4 horsepower or less may be used for direct-drive service.
c. Split-phase and capacitor-start motors, rated 1/4 horsepower or less, may be used for belt-drive service.
d. Motor bearings may be the manufacturer's standard prelubricated sleeve type but provide the motor with antifriction thrust bearings, when specified. Ensure that the lubricant provisions are for extended service, requiring replenishment not more than twice per year of continuous operation.
Provide the manufacturer's standard motor identification plate.
Provide the manufacturer's standard motor speed and control.
PART 3 EXECUTION
3.1 INSTALLATION
Install unit heaters in accordance with the manufacturer's instructions at the mounting heights indicated.
3.1.1 Casings
Provide casings with smoothly contoured propeller orifice rings of at least 20-gage cold-rolled carbon steel. Provide a casing surface finish with phosphate pretreatment, prime coating, and baked-enamel finish.
3.1.2 Air Distribution
Provide horizontal units with adjustable single- or double-deflection louvers.
3.2 FIELD QUALITY CONTROL
Demonstrate in the presence of the Contracting Officer that the unit heaters operate satisfactorily.
Cycle unit heaters five times, from start to operating thermal conditions to off, to verify adequacy of construction, system controls, and component performance.
Conduct an operational test for a minimum of 6 hours.
-- End of Section --
SECTION 23 82 46.00 40 Page 3
SECTION 23 83 00.00 20
ELECTRIC SPACE HEATING EQUIPMENT
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;
TIA 17-3; TIA 17-4; TIA 17-5; TIA 17-6;
TIA 17-7; TIA 17-8; TIA 17-9; TIA 17-10;
TIA 17-11; TIA 17-12; TIA 17-13; TIA
17-14; TIA 17-15; TIA 17-16; TIA 17-17 )
National Electrical Code
UNDERWRITERS LABORATORIES (UL)
UL 1025 (1980; R 1990, Bul. 1991) Electric Air Heaters
UL 1042 (2009; Reprint Dec 2016) UL Standard for Safety Electric Baseboard Heating Equipment
1.2 GENERAL REQUIREMENTS
Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS, applies to this section, with the additions and modifications specified herein.
1.3 SUBMITTALS
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Heater installation drawing
SD-03 Product Data
Electric unit and cabinet heaters
Electric baseboard units
Thermostat
Unit thermostat
SD-10 Operation and Maintenance Data
Electric unit and cabinet heaters, Data Package 5
SECTION 23 83 00.00 20 Page 1
Electric baseboard units, Data Package 5
Submit in accordance with Section 01 78 23 OPERATION AND
MAINTENANCE DATA.
PART 2 PRODUCTS
2.1 ELECTRIC UNIT AND CABINET HEATERS
UL 1025 ; wattage, voltage, phase, number of steps, Btu/hr and CFM as indicated. Provide control-circuit terminals and single source of power supply. Heaters 5 Kw and larger shall be 3-phase, with load balanced on each of the three phases. Limit leaving air temperature to 140 degrees F with entering air of 60 degrees F.
2.1.1 Enclosure
Minimum 20 gage steel.
2.1.2 Heating Element
Nickel chromium heating wire element, free from expansion noise and 60 Hz hum. Embed element in magnesium-oxide insulating refractory. Seal element in high-mass steel or corrosion-resisting metallic sheath with fins. Enclose element ends in terminal box. Provide not more than six fins per inch. Limit fin surface temperature 550 degrees F at any point during normal operation.
2.1.3 Controls
Include limit controls for overheat protection of heaters. For remote thermostatic operation, provide contactor rated for 100,000 duty cycles.
2.1.4 Wiring
Completely factory-prewired to terminal strips, ready to receive branch circuit and control connections for 140 degrees F copper wiring.
2.1.5 Thermostat
Provide tamper resistant space thermostat, adjustable without requiring removal of heater components. Thermostat operating range shall be approximately 50 degrees F to a maximum of 75 degrees F with operating differential of 3 degrees F or less.
2.1.6 Disconnect Means
Provide factory-installed safety disconnect switch in the housing or in an auxiliary matching control section with "off" position marking on the face plate.
2.2 ELECTRIC BASEBOARD UNITS
UL 1042 ; wattage, voltage, phase, Btu per houroutput indicated. Provide units complete with heating elements, mounting brackets, end closures, splice plates, interior and exterior corners and accessible wiring compartment. Limit outlet air temperature and enclosure surfaces to 200 degrees F under continuous operating conditions.
SECTION 23 83 00.00 20 Page 2
2.2.1 Enclosure
Fabricate from steel not less than 12 gage. Provide manufacturer's standard white finish. Locate terminal blocks for branch circuit conductor and control wiring connections as required. Wiring shall conform to NFPA 70 .
2.2.2 Accessories
Where continuous wall-to-wall installations are indicated, provide accessories; including corner fittings, fillers, splice plates, and end caps. Accessories shall have the same profile as the basic unit, and contain no sharp edges. Provide for expansion of enclosure.
2.2.3 Limit Control
Provide thermal overload and over voltage protection.
2.2.4 Disconnect Means
Provide factory-installed safety disconnect switch in the housing or in an auxiliary matching control section with "off" position marking on the face plate.
2.2.5 Unit Thermostat
Provide tamper resistant space tool adjustable thermostat, without requiring removal of cabinet parts. Thermostat, operating range shall be approximately 50 degrees F to a maximum of 75 degrees F with operating differential of 3 degrees F or less.
2.3 DISCONNECTS
Disconnect. UL listed. Enclosed non-fusible switch, rated 120 volt, 1 phase, NEMA Type 1 enclosure.
PART 3 EXECUTION
3.1 INSTALLATION
Install in conformance with the approved heater installation drawing, NFPA 70 , UL listing, and manufacturer's instructions, with necessary clearances for air circulation, maintenance, inspection, service testing and repair. Connect to electrical supply in accordance with Section
26 20 00 INTERIOR DISTRIBUTION SYSTEM.
3.1.1 Unit Heaters
Mount units plumb, square and level with ceiling and walls.
3.1.2 Cabinet Heaters
Where recessed mounting is indicated, seal entire recessed opening from exterior wall cavities, and provide a minimum 1/2-inch thick rigid fire resistant insulation on the wall behind the cabinet. Verify manufacturer's clearance requirements from electrical cords, drapes, and other furnishings.
SECTION 23 83 00.00 20 Page 3
3.1.3 Remote Thermostat
Mount remote room space thermostats 4 feet 6 inches above finished floor on wall or as indicated. Connect remote thermostats with conduit and wiring to heaters as indicated.
3.1.4 Baseboard Heaters
Verify manufacturer's clearance requirements from electrical cords, drapes, and other furnishings.
3.2 FIELD QUALITY CONTROL
Provide necessary personnel, instruments, and equipment to perform tests.
Notify the Contracting Officer 5 working days prior to scheduled testings and locations.
3.2.1 Field Inspection
Prior to initial operation, inspect installed equipment for conformance with drawings and specifications.
3.2.2 Insulation Resistance Tests
Test 600-volt wiring to verify that no short circuits or grounds exist.
Tests shall be made using an instrument which applies a voltage of approximately 500 volts and provides a direct reading of resistance in ohms.
3.2.3 Operational Tests
Test equipment circuits and devices to demonstrate proper operation.Test each item of control equipment not less than 5 times.
SECTION 23 83 00.00 20 Page 4
-- End of Section --
SECTION 23 83 00.00 20 Page 5
| DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) |
| ELECTRIC UNIT HEATERS |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 SUBMITTALS |
| PART 2 PRODUCTS |
| 2.1 SYSTEM DESCRIPTION |
| 2.2 COMPONENTS |
| 2.2.1 Heating Element |
| 2.2.2 Controls |
| 2.2.3 Propellers and Motors |
| PART 3 EXECUTION |
| 3.1 INSTALLATION |
| 3.1.1 Casings |
| 3.1.2 Air Distribution |
3.2 FIELD QUALITY CONTROL
| ELECTRIC SPACE HEATING EQUIPMENT |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 GENERAL REQUIREMENTS |
| 1.3 SUBMITTALS |
| PART 2 PRODUCTS |
| 2.1 ELECTRIC UNIT AND CABINET HEATERS |
| 2.1.1 Enclosure |
| 2.1.2 Heating Element |
| 2.1.3 Controls |
| 2.1.4 Wiring |
| 2.1.5 Thermostat |
| 2.1.6 Disconnect Means |
| 2.2 ELECTRIC BASEBOARD UNITS |
| 2.2.1 Enclosure |
| 2.2.2 Accessories |
| 2.2.3 Limit Control |
| 2.2.4 Disconnect Means |
| 2.2.5 Unit Thermostat |
2.3 DISCONNECTS
| PART 3 EXECUTION |
| 3.1 INSTALLATION |
| 3.1.1 Unit Heaters |
| 3.1.2 Cabinet Heaters |
| 3.1.3 Remote Thermostat |
| 3.1.4 Baseboard Heaters |
| 3.2 FIELD QUALITY CONTROL |
| 3.2.1 Field Inspection |
| 3.2.2 Insulation Resistance Tests |
| 3.2.3 Operational Tests |
File details come from the government source that posted it. Updated .