A N
S I
D
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
M
R
D L
D
E F
E N
S
U P
P
Y
C
N
T E
R
R
I C
H M
O N
D
R
I C
H M
O N
D
V
A
B U
I L D
I N
G
T
R U
K
N
O P
Y
P R
O J E
T
M
B E
R
SHEET ID
F I L
E N
A M
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
O
US Army Corps of Engineers
C A
T E
G O
D
E
X X
X X
X X
X
U S
A
R M
Y
C
O R
P
F
E
N G
I N
E E
R S
N O
R F
O
I S
T R
I C
T
F
R O
R
E E
T
N O
R F
O L K
V
I R
G I N
I A
X X
X X
X X
X
X X
X
X X
X
X X
X X
X X
X
X X
X
X X
X
D E
P
T I O
N
R A
L E
I G
H
N
C
F
A X
L I C
E N
BCOES
NOT FOR CONSTRUCTION
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
G-001
C O
V E
R
S
H E
E T
R S
M B
M C
M C
G D
G N
PROJECT SITE
ELECTRICALSTRUCTURAL
US Army Corps of Engineers
NORFOLK DISTRICT
INDEX OF DRAWINGS
SHEET
NUMBER
TITLE
GENERAL
G-001 COVER SHEET, VICINITY MAP AND PROJECT LOCATION MAP
G-002 LEGENDS & ABBREVIATIONS
G-003 GENERAL CONSTRUCTION NOTES
VICINITY MAP
1" = 3,000'
LOCATION MAP
NTS
DLA DEFENSE
SUPPLY CENTER
STRUCTURAL
SD101 PARTIAL FLOOR PLAN AND EXTERIOR ELEVATION - DEMOLITION
SA101 FLOOR PLAN - NEW WORK
SA102 EXTERIOR ELEVATION AND BUILDING SECTION
SA103 DETAILS - NEW WORK
S-001 GENERAL NOTES, DESIGN DATA, SHEAR TAB SCHEDULE AND DETAILS
S-002 SPECIAL INSPECTIONS
S-101 FLOOR PLAN - NEW WORK
S-102 DETAILS
FIRE PROTECTION
F-001 FIRE PROTECTION SYMBOLS, ABBREVIATIONS AND NOTES
FX101 FIRE SPRINKLER PLAN
ELECTRICAL
E-001 ELECTRICAL SYMBOLS
EL101 FLOOR PLAN AND SECTION
FIRE PROTECTION
HAUL ROUTE MAP
CONTRACTOR
DELIVERY ROUTE
NOT TO SCALE
SUMMER
CONSULTANTS
I N C O R P O R A T E D
DLA DEFENSE SUPPLY CENTER RICHMOND, RICHMOND, VA
PN 469015, BUILDING 98 TRUCK CANOPY
BCOES
NAO FILE NO.: 871
SOLICITATION NO.: XXXXXX-XX-X-XXX
CONTRACT NO.: XXXXXX-XX-X-XXXX
ISSUE DATE: 28 MARCH 2019
VOLUME I
CONTRACTOR TRAILER
AND LAY DOWN AREA
S I
D
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
D
F
E N
P
P
N
T E
R
R
I C
H M
O N
D
R
I C
H M
O N
D
V
A
B U
I L D
I N
G
T
R U
N
O P
Y
P R
O J E
M
B E
R
SHEET ID
F I L
E N
A M
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
US Army Corps of Engineers
C A
T E
G O
D
E
X X
X X
X X
X
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
N O
R F
O
S
T R
I C
T
F
R O
R
E E
T
N O
R F
O L K
V
I R
G I N
I A
X X
X X
X X
X
X X
X
X X
X
X X
X X
X X
X
X X
X
X X
X
D E
P
T I O
N
R A
L E
I G
H
N
C
F
A X
L I C
E N
BCOES
NOT FOR CONSTRUCTION
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
DRAWING ABBREVIATIONS MATERIAL LEGEND
A ---------------------
A/E ARCHITECT/ENGINEER
ACC ACCESSIBLE
ACS AUTOMATIC CONTROL
SYSTEM
ACS DR ACCESS DOOR
ACS PNL ACCESS PANEL
ACT ACOUSTICAL CEILING
TILE
ADA AMERICANS WITH
DISABILITIES ACT
ADMIN ADMINISTRATION
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ALUM ALUMINUM
APPROX APPROXIMATE
AR AS REQUIRED
ARCH ARCHITECT
ASSY ASSEMBLY
ATC ACOUSTICAL TILE
CEILING
AVG AVERAGE
B ---------------------
BD BOARD
BDRY BOUNDARY
BHMA BUILDER'S HARDWARE
MANUFACTURER'S
ASSOCIATION
BLDG BUILDING
BLKG BLOCKING
BN BULLNOSE
BOS BOTTOM OF STEEL
BOT BOTTOM
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT-UP ROOFING
C ---------------------
CAV CAVITY
CBB CEMENTITIOUS (BACKER)
BOARD
CD CONSTRUCTION
DOCUMENTS
CEM PLAS CEMENT PLASTER
CER CERAMIC
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED
/CONTRACTOR INSTALLED CFE
CONTRACTOR FURNISHED
EQUIPMENT
CFLG COUNTERFLASHING
CFM CUBIC FEET PER MINUTE CFMF
COLD-FORMED METAL
FRAMING
CFS CUBIC FEET PER SECOND
CG CORNER GUARD
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLG DIFF CEILING DIFFUSER
CLG HT CEILING HEIGHT
CLRM CLASSROOM
CMU CONCRETE MASONRY UNIT
CDR CARD READER
CO CLEANOUT
COL COLUMN
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUE
COORD COORDINATE
CORR CORRIDOR
CPT CARPET
CT CERAMIC TILE
CTR CENTER
CU FT CUBIC FEET
D ---------------------
D DEPTH
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DRI DIRECTION
DIST DISTANCE
DOC DOCUMENT
DR DOOR
DS DOWNSPOUT
E ---------------------
EA EACH
EIFS EXTERIOR INSULATION
AND FINISH SYSTEM
EJ EXPANSION JOINT
ES EACH SIDE
EL ELEVATION
ELEV ELEVATOR
ENTR ENTRANCE
EQ EQUAL
EWC ELECTRIC WATER COOLER
EXP EXPOSED
EXT EXTERIOR
EXT EXTINGUISHER
F ---------------------
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR
PANEL
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF EL FINISH FLOOR ELEVATION
FGL FIBERGLASS
FIN FINISH
FIN FLR FINISH FLOOR
FIN GR FINISH GRADE
FIXT FIXTURE
FLG FLOORING
FLR FLOOR
FOC FACE OF CONCRETE
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUD
FR FIRE RESISTANT
FRG FIBER REINFORCED GYPSUM
FRMG FRAMING
FRP FIBERGLASS REINFORCED
PLASTIC
FRTW FIRE RETARDANT
TREATED WOOD
FS FEDERAL SPECIFICATION
FSTNR FASTENER
FT FEET
FTG FOOTING
FWC FABRIC WALLCOVERING
G ---------------------
G NATURAL GAS
GA GAGE/GUAGE
GALV GALVANIZED
GB GRAB BAR
GFCI GOVERNMENT FURNISHED
CONTRACTOR INSTALLED
GFGI GOVERNMENT FURNISHED
GOVERNMENT INSTALLED
GFRG GLASS-FIBER
REINFORCED GYPSUM
GLZ GLAZING
GMS GALVANIZED METAL STUD
GUT GUTTER
GYP BD GYPSUM BOARD
H --------------------
HB HOSE BIBB
HDPE HIGH DENSITY POLYETHYLENE
HDW HARDWARE
HDWD HARDWOOD
HEPA HIGH EFFICIENCY
PARTICULATE AIR (FILTER)
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HORIZ HORIZONTAL
HT HEIGHT
HYDR HYDRAULIC
I ---------------------
IBC INTERNATIONAL BUILDING
CODE
INSUL INSULATION
INT INTERIOR
ILO IN LIEU OF
J ---------------------
JAN JANITOR
K ---------------------
KPD KEYPAD
KIT KITCHEN
KPL KICKPLATE
L ---------------------
LAM LAMINATE
LAV LAVATORY
LBS POUND
LIB LIBRARY
LIN LINEAR
LOC LOCATION
LT LIGHT
LVR LOUVER
M ---------------------
MACH RM MACHINE ROOM
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MECH RM MECHANICAL ROOM
MFR MANUFACTURER
MIL STD MILITARY STANDARD
MIN MINIMUM, MINUTE
MISC MISCELLANEOUS
MO MASONRY OPENING
MOD MODIFY
MTG MOUNTING
MTL METAL
MWP MEMBRANE WATERPROOFING
N ---------------------
N NORTH
NA NOT APPLICABLE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
O -------------------
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OFF OFFICE
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OWSJ OPEN WEB STEEL JOIST
ORIG ORIGINAL
P --------------------
PA PUBLIC ADDRESS
PB PULL BOX
PBD PARTICLEBOARD
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FT
PERF PERFORATED
PERIM PERIMETER
PH PHASE
PL PROPERTY LINE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PLYWD PLYWOOD
PNL PANEL
PP PL PUSH/PULL PLATE
PR PAIR
PRCST PRECAST
PRKG PARKING
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
PTD PAPER TOWEL DISPENSER
PTDR PAPER TOWEL DISPENSER
AND RECEPTACLE
PTN PARTITION
PWR POWER
Q --------------------
QT QUARRY TILE
QTY QUANTITY
R --------------------
RB RESILIENT BASE
RBR RUBBER
RC REINFORCED CONCRETE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFERENCE
REQ REQUIRE
REQD REQUIRED
RESIL RESILIENT
REST RESTROOM
RF RESILIENT FLOORING
RFG ROOFING
RH ROOF HATCH
RHR RIGHT HAND REVERSE
RM ROOM
RO ROUGH OPENING
RV ROOF VENT
RVL REVEAL
S --------------------
SB SPLASH BLOCK
SCHED SCHEDULE
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SGL SINGLE
SHTHG SHEATHING
SHV SHELVING
SIM SIMILAR
SJ SCORED JOINT
SL SLOPE
SLNT SEALANT
SMK SMOKE
SMLS SEAMLESS
SP EL SPOT ELEVATION
SPEC SPECIFICATION
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SST STAINLESS STEEL
STD STANDARD
STL JST STEEL JOIST
STOR STORAGE
STRB/HRN STROBE/HORN
T --------------------
T TREAD
TC TERRA COTTA
TD TRENCH DRAIN
TEL TELEPHONE
TEMP TEMPORARY
TER TERRAZZO
THK THICKNESS
TN TRUE NORTH
TOP TOP OF PARAPET
TOPO TOPOGRAPHY
TOS TOP OF SLAB
ACCESSORY BY MARK
AFF
Elevation
A202
SIM
NORTH ARROW
SQUARE FOOTAGE
ROOM NUMBER
ROOM NAME
VIEW NUMBER
WALL TAG
WINDOW TAG
DOOR TAG
LEVEL
MARK
SHEET NUMBER
SIMILAR TAG
DETAIL LOCATED ON SHEET (MAY ALSO BE
REF. UNDER TITLE FOR MULTIPLE SHEETS)
SIMILAR TAG
ELEVATION RELATIVE TO
FINISHED FLOOR
BUILDING SECTION
99 SIM
A103
99 SIM
AE101
VIEW NUMBER
SHEET NUMBER
SIMILAR TAG
PLAN NORTH INDICATOR
TRUE NORTH
MATCHLINE 11/ AE-101.A1MATCH LINE
NUMBER ON
MATCHING SHEET
CONTINUATION SHEET
DETAIL LOCATED
ON SHEET
AE101
A
VIEW IDENTIFIER
ROOM TAG WITH SQUARE FOOTAGES*
DETAIL CALLOUT
CALLOUT - DETAILS
ELEVATION
MATCH LINE
SIM
SIMILAR TAG
SIM
B
A202
SIM
A202
______________VIEW NUMBER
SHEET NUMBER
SIMILAR TAG
WALL SECTION
99 SIM
AE101
VIEW NUMBER
SHEET NUMBER
SIMILAR TAG
DETAIL CALLOUT
GRID HEAD
VIEW NUMBER
SHEET NUMBER
SIMILAR TAG
BUILDING ELEVATION
VIEW NUMBER
EXTENT OF DETAIL
KEYED NOTE
REVISION NOTE
C
D
EARTH - COMPACTED
FILL
CONCRETE
BRICK - MASONRY
STEEL
PLYWOOD
RIGID INSULATION
BATT INSULATIONFINISHED WOOD
BLOCKING
CONTINUOUS WOOD
CONCRETE MASONRY
UNIT (PLAN)
CONCRETE MASONRY
UNIT (SECTION) GLASS MAT
SHEATHING
SPRAY-FOAM
INSULATION
SAND, FIREPROOFING,
MORTAR, GROUT,
PLASTER, DRYWALL
SYMBOLS LEGEND
A202
SIM
103A
A
1A
W1
ROOM NAME
100 SF
GB
CEILING TAG C1
FIRE EXTINGUISHER
CABINET
G-002
L E
G E
N D
B B
R E
V I A
T I O
N S
R S
M B
M C
M C
G D
G
SIM
S I
D
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
D
F
E N
P
P
N
T E
R
R
I C
H M
O N
D
R
I C
H M
O N
D
V
A
B U
I L D
I N
G
T
R U
N
O P
Y
P R
O J E
M
B E
R
SHEET ID
F I L
E N
A M
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
US Army Corps of Engineers
C A
T E
G O
D
E
X X
X X
X X
X
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
N O
R F
O
S
T R
I C
T
F
R O
R
E E
T
N O
R F
O L K
V
I R
G I N
I A
X X
X X
X X
X
X X
X
X X
X
X X
X X
X X
X
X X
X
X X
X
D E
P
T I O
N
R A
L E
I G
H
N
C
F
A X
L I C
E N
BCOES
NOT FOR CONSTRUCTION
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
G-003
G E
N E
R A
L
C
O N
S T
R U
C T
I O
N
N
O T
E S
R S
M B
M C
M C
G D
G
1 2
B
C
3 4 5 6 7 8 9 10 11 12 13
A N
S I
D
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
D
F
E N
P
P
N
T E
R
R
I C
H M
O N
D
R
I C
H M
O N
D
V
A
B U
I L D
I N
G
T
R U
N
O P
Y
P R
O J E
M
B E
R
SHEET ID
F I L
E N
A M
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
US Army Corps of Engineers
C A
T E
G O
D
E
X X
X X
X X
X
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
N O
R F
O
S
T R
I C
T
F
R O
R
E E
T
N O
R F
O L K
V
I R
G I N
I A
X X
X X
X X
X
X X
X
X X
X
X X
X X
X X
X
X X
X
X X
X
D E
P
T I O
N
R A
L E
I G
H
N
C
F
A X
L I C
E N
BCOES
NOT FOR CONSTRUCTION
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
PHASE I PHASE II
SD101
PARTIAL FLOOR PLAN - EXISTING
1/16" - 1'-0'
SD101
EXTERIOR ELEVATION -DEMOLITION
1/8" - 1'-0'
EXISTING GUTTER TO
REMAIN INTACT, TYP
EXISTING DOWNSPOUT TO BE
REMOVED. GUTTER OPENING
LOCATION TO BE REUSED, TYP
EXISTING CAST IRON DOWNSPOUT
RECEIVER TO UNDERGROUND STORM
DRAIN TO REMAIN INTACT, TYP
EXISTING RIBBON
WINDOW ASSEMBLIES
TO REMAIN INTACT, TYP
EXISTING CONDUIT TO
BE REMOVED, TYP.
SEE ELECTRICAL
EXISTING ROLL-UP
DOOR TO REMAIN
INTACT, TYP
EXISTING STAIR
WAREHOUSE FLOOR LEVEL
TO REMAIN INTACT, TYP
EXISTING WAREHOUSE
ADDITION (N.I.C.) TO
REMAIN INTACT, TYP
EXISTING DOWNSPOUT
@ THIS LOCATION TO
REMAIN INTACT
EXISTING WALL PACK
LIGHTING TO BE REMOVED,
TYP. SEE ELECTRICAL
EXISTING WALL PACK
LIGHTING TO REMAIN INTACT
@ MANDOORS, TYP. SEE
ELECTRICAL
REMOVE EXISTING
CMU AS REQ'D FOR
STRUCTURAL
STEEL
INSTALLATION
16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
199'-6"
199'-6"
16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
PHASE II PHASE I
EXISTING CMU AS OCCURS
BLDG
BLDG
BLDG
KEY PLAN
NTS
PROJECT LOCATION
GENERAL NOTES
1. EACH PROJECT PHASE IS TO BE COMPLETED
INDEPENDENTLY.
2. ACCESS TO THE BAYS NOT IN THE CURRENT
CONSTRUCTION PHASE MUST BE FULLY OPEN FOR
RECEIVING OPERATIONS.
BLDG 98 BLDG 60
SD101
P A
R T
I A
L
F
L O
A
N
A
N D
E X
T E
R I O
R
E
L E
V A
T I O
N
D
E M
O L I T
I O
N
R S
M B
M C
M C
S D
D
G N
SD101
B
C
D
E
F
G
H
J
K
L
3 4 5 6 7 8 9 10 11 12 13
A N
S I
D
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
D
F
E N
P
P
N
T E
R
R
I C
H M
O N
D
R
I C
H M
O N
D
V
A
B U
I L D
I N
G
T
R U
N
O P
Y
P R
O J E
M
B E
R
SHEET ID
F I L
E N
A M
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
US Army Corps of Engineers
C A
T E
G O
D
E
X X
X X
X X
X
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
N O
R F
O
S
T R
I C
T
F
R O
R
E E
T
N O
R F
O L K
V
I R
G I N
I A
X X
X X
X X
X
X X
X
X X
X
X X
X X
X X
X
X X
X
X X
X
D E
P
T I O
N
R A
L E
I G
H
N
C
F
A X
L I C
E N
BCOES
NOT FOR CONSTRUCTION
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
PHASE I PHASE II
TYP
SA101
FLOOR PLAN - NEW WORK
1/16" - 1'-0'
199'-6"
16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
NEW PRE-FINISHED STANDING
SEAM CANOPY. SEE GENERAL
NOTES FOR STANDARD FINISH
EXISTING OFFICE
EXIST STEEL
BARRICADE, BOLTED
TO FLOOR, TO
REMAIN INTACT
GENERAL NOTES
1. EACH PROJECT PHASE IS TO BE COMPLETED IN A
METHOD TO MAINTAIN DELIVERY ACCESS, AND
SHALL ENSURING A MINIMUM OF THREE BAYS WILL
HAVE UN-IMPEDED ACCESS AT ALL TIMES.
2. ACCESS TO THE BAYS NOT IN THE CURRENT
CONSTRUCTION PHASE MUST BE FULLY OPEN FOR
RECEIVING OPERATIONS.
3. CONTRACTOR SHALL INSTALL A DUST CONTROL
PARTITION, MEETING EM 385-1-1 AND NFPA 241,
FROM FLOOR TO CEILING, IN THE LOCATION
SHOWN OR AT THE DIRECTION OF THE
CONTRACTING OFFICER'S REPRESENTATIVE FOR
WORK IN THE IMMEDIATE WORK AREA.
4. CONTRACTOR SHALL INSTALL WARNING CONES,
FOR FORKLIFT TRAFFIC, AND MAINTAIN THE
SAFETY ZONE DURING THE ENTIRE PROJECT.
5. ALL NEW STANDING SEAM ROOF PANELS, TRIM
METAL, GUTTERS, DOWNSPOUTS, ETC. SHALL
MATCH THE STANDARD INSTALLATION COLOR, W/
"KYNAR" 500 FINISH (BENJAMIN MOORE, MANOR
BROWN, #345287), OR APPROVED EQUAL.
PHASE II DUST PARTITION (SEE GENERAL NOTE 3)PHASE I DUST PARTITION (SEE GENERAL NOTE 3)
WARNING CONES
(SEE GENERAL NOTE 4)
CONTRACTOR TO PROVIDE
ACCESS TO THE EXISTING
OFFICE THROUGHOUT THE
ENTIRETY OF THE PROJECT
145'-0"
SA102
SA102
SA103
SA101
F L O
A
N
N
W
R
K
R S
M B
M C
M C
S A
D
G N
BLDG
BLDG
BLDG
KEY PLAN
NTS
SA102
12345678910111213
ABCDEFGHJKL
A N
S I
D
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
M
D L
A
D
E F
E N
P
P L
Y
C
E N
T E
R
R
I C
H M
O N
D
R
I C
H M
O N
D
V
A
B U
I L
D I N
G
T
R U
N
O P
Y
P R
O J E
M
B E
R
SHEET ID
F I L E
N A
M E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
US Army Corps of Engineers
C A
T E
G O
D
E
X X
X X
X X
X
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
N O
R F
O L
K
D
I S
T R
I C
T
F
R O
R
E E
T
N O
R F
O L
K
V
I R
G I N
I A
X X
X X
X X
X
X X
X
X X
X
X X
X X
X X
X
X X
X
X X
X
D E
P
T I O
N
J O
N E
S
F
R A
N K
L
S
U I T
E
R A
L E
I G
H
N
C
F
A X
L I C
E N
BCOES
NOT FOR CONSTRUCTION
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
TYP
NEW CANOPY
12'-0"
TOP OF STEEL
0'-0"
FIN FLR
RIBBON WINDOWS
21'-3"
BOTTOM OF
EXISTING GUTTER TO
REMAIN INTACT, TYP
SA102
EXTERIOR ELEVATION - NEW WORK
1/8" - 1'-0'
SA102
BUILDING SECTION B-B
1/8" - 1'-0'
EXISTING GUTTER TO
REMAIN INTACT, TYP
INSTALL NEW DOWNSPOUT @ PREVIOUS
GUTTER OPENING LOCATIONS, TYP
EXISTING CAST IRON DOWNSPOUT
RECEIVER TO UNDERGROUND STORM
DRAIN TO REMAIN INTACT, TYP. SEE
GENERAL NOTE 1 FOR FURTHER INFO
EXISTING RIBBON
WINDOW ASSEMBLIES
TO REMAIN INTACT, TYP
NEW PRE-FINISHED
STANDING SEAM
CANOPY, TYP
EXISTING ROLL-UP
DOOR TO REMAIN
INTACT, TYP
EXISTING STAIR
WAREHOUSE FLOOR LEVEL
TO REMAIN INTACT, TYP
EXISTING WAREHOUSE
ADDITION (N.I.C.) TO
REMAIN INTACT, TYP
EXISTING DOWNSPOUT
@ THIS LOCATION TO
REMAIN INTACT, TYP
16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
199'-6"
PHASE II PHASE I
20'-6" 21'-6" 21'-6" 17'-10" 18'-0" 18'-0" 17'-10" 21'-6" 21'-6" 20'-6"
198'-8"
GENERAL NOTES:
1. THE CONTRACTOR SHALL CLEAN THE EXISTING STORM DRAIN
SYSTEM FROM THE DOWNSPOUT RECEIVER AT THE
BUILDING, AND OUT TO THE JUNCTION WITH THE MAIN STORM
DRAIN, APPROXIMATELY 60 FEET WEST OF THE FACILITY.
2. SEE GENERAL NOTES ON SHEET SA101 FOR FINISH COLOR
OF ALL NEW METAL.
SA103
SA102
E X
T E
R I O
R
E
L E
V A
T I O
N
A
B
I L
D I N
G
S
E C
T I O
N
N E
W
W
O R
K
R S
M B
M C
M C
S A
D
G N
SA103
GRIDGRID
N
S I
D
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
D
F
E N
P
P
N
T E
R
R
I C
H M
O N
D
R
I C
H M
O N
D
V
A
B U
I L D
I N
G
T
R U
N
O P
Y
P R
O J E
M
B E
R
SHEET ID
F I L
E N
A M
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
US Army Corps of Engineers
C A
T E
G O
D
E
X X
X X
X X
X
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
N O
R F
O
S
T R
I C
T
F
R O
R
E E
T
N O
R F
O L K
V
I R
G I N
I A
X X
X X
X X
X
X X
X
X X
X
X X
X X
X X
X
X X
X
X X
X
D E
P
T I O
N
R A
L E
I G
H
N
C
F
A X
L I C
E N
BCOES
NOT FOR CONSTRUCTION
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
SA103
CANOPY SECTION A - NEW WORK
3/8" - 1'-0'
EXISTING CONCRETE
STAIRS & METAL
HANDRAIL ASSEMBLY
NEW DOWNSPOUT, TYP
NEW GUTTER, TYP
NEW STANDING SEAM ROOF OVER
GALVANIZED METAL DECKING OVER
METAL CANOPY FRAMING, TYP
NEW DOWNSPOUT INSTALLED @
PREVIOUS LOCATIONS, TYP
EXISTING RIBBON WINDOWS TO
REMAIN INTACT, TYP
EXISTING GUTTER TO REMAIN
INTACT, TYP
12'-0"
TOP OF STEEL
0'-0"
FIN FLR
RIBBON WINDOWS
21'-3"
BOTTOM OF
SA103
CANOPY HEAD DETAIL
1 1/2" - 1'-0'
SA103
CANOPY EAVE DETAIL
1 1/2" - 1'-0'
NEW 1/2" BIRD NETTING TO MATCH
EXISTING NETTING @ OTHER
BUILDINGS ON THE SITE. INSTALL
VELCRO TYPE MAINTENANCE ACCESS
OPENINGS FOR SPRINKLER AND
ELECTRICAL SYSTEMS (SEE 4/SA103),
TYP BETWEEN ALL GRID SPACES, AND
INSTALLED ABOVE ALL RAIN LEADERS
AND DOWNSPOUTS
NEW METAL CANOPY FRAMING W/
STANDING SEAM ROOF, TYP
DOWNSPOUT BEYOND
EXISTING RIBBON WINDOW
SAWCUT MORTAR JOINT - PROVIDE REGLET
SILICONE SEALANT
ALUMINUM COUNTER FLASHING
TO MATCH CANOPY COLOR, TYP
Z-CLOSURE
GALVANIZED METAL DECKING
STANDING SEAM METAL ROOF
STANDING SEAM METAL ROOF
ROOF PANEL CLIPS
ALUMINUM DRIP EDGE
COLD FORMED METAL ROOF
FRAMING, SEE STRUCTURAL
ALUMINUM FASCIA - WRAP
AROUND
6" ALUMINUM GUTTER TO MATCH EXISTING
NEW 4"x6" ALUMINUM DOWNSPOUT
TO EXISTING DRAIN (TO MATCH
EXISTING) - HOLD TIGHT TO
CEILING. VERIFY ACTUAL SIZE OF
EXISTING DOWNSPOUTS
GALVANIZED METAL DECKING
FASTEN P.T. 2X
NAILER TO FRAMING
NEW 8X24 WF
NEW FRAMING AS REQ'D
NEW COLD FORMED METAL
FRAMING, SEE STRUCTURAL
EXISTING CAST IRON
DOWNSPOUT RECEIVER TO
UNDERGROUND STORM DRAIN
TO REMAIN INTACT, TYP
SA103
CANOPY SOFFIT ACCESS PLAN
1/4" - 1'-0'
NEW 1/2" BIRD NETTING TO MATCH
EXISTING NETTING @ OTHER
BUILDINGS ON THE SITE
NEW VELCRO TYPE MAINTENANCE
ACCESS OPENINGS FOR SPRINKLER
AND ELECTRICAL SYSTEMS, TYP
BETWEEN ALL GRID SPACES
FACE OF CANOPY
FACE OF BLDG
NEW BRACING ANGLES, SEE
STRUCTURAL, 1/S-101
NEW FRAMING,
SEE STRUCTURAL
GENERAL NOTES:
1. SEE GENERAL NOTES ON SHEET SA101 FOR FINISH COLOR
OF ALL NEW METAL.
~5
(2) ROWS OF NEW SNOW
GUARDS, ENTIRE
LENGTH OF CANOPY,
PER ROOF MFR, TYP
SA103
D E
T A
I
R
K
R S
M B
M C
M C
S A
D
G N
SA103
SA103
S I
D
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
D
F
E N
P
P
N
T E
R
R
I C
H M
O N
D
R
I C
H M
O N
D
V
A
B U
I L D
I N
G
T
R U
N
O P
Y
P R
O J E
M
B E
R
SHEET ID
F I L
E N
A M
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
US Army Corps of Engineers
C A
T E
G O
D
E
X X
X X
X X
X
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
N O
R F
O
S
T R
I C
T
F
R O
R
E E
T
N O
R F
O L K
V
I R
G I N
I A
X X
X X
X X
X
X X
X
X X
X
X X
X X
X X
X
X X
X
X X
X
D E
P
T I O
N
R A
L E
I G
H
N
C
F
A X
L I C
E N
BCOES
NOT FOR CONSTRUCTION
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
GENERAL
1. CONTRACTOR IS TO VERIFY DIMENSIONS AT THE SITE.
2. THERE SHALL BE NO DEVIATIONS FROM THESE CONSTRUCTION DOCUMENTS UNLESS
APPROVED BY THE CONTRACTING OFFICER. ANY DEVIATION FROM, ADDITION TO,
SUBSTITUTION FOR, OR MODIFICATION TO THE STRUCTURE OR ANY PART OF THE
STRUCTURE SHOWN ON THESE DRAWINGS SHALL BE SUBMITTED IN WRITING TO THE
CONTRACTING OFFICER FOR REVIEW. SHOP DRAWINGS THAT ARE SUBMITTED FOR
REVIEW DO NOT CONSTITUTE “IN-WRITING” UNLESS IT IS CLEARLY NOTED THAT SPECIFIC
CHANGES ARE BEING SUGGESTED.
EXISTING STRUCTURAL & EXISTING CONDITIONS
1. CONTRACTOR IS TO NOTIFY THE CONTRACTING OFFICER OF QUESTIONABLE EXISTING
STRUCTURAL COMPONENTS (MASONRY WALLS, STEEL BEAMS & LINTEL, EXPOSED
FOUNDATIONS, ETC.) AND FRAMING CONNECTIONS WHEN ENCOUNTERED.
2. GRIDLINES ARE SHOWN ON THE STRUCTURAL DRAWINGS AND THESE REFLECT
ASSUMED ARCHITECTURAL AND STRUCTURAL DIMENSIONS. IN MOST CASE, GRID LINES
COINCIDE WITH EXISTING COLUMN AND PILASTER CENTERLINES. IF ACTUAL FIELD
DIMENSIONS VARY, NOTIFY THE CONTRACTING OFFICER.
3. CONTRACTOR TO VERIFY EXACT LOCATION OF ALL EXISTING STRUCTURAL
COMPONENTS THAT WILL BE CONNECTED TO NEW FRAMING PRIOR TO STEEL
FABRICATION. IT IS THE CONTRACTOR’S RESPONSIBILITY TO VERIFY ALL EXISTING
DIMENSIONS AND COORDINATE THESE DIMENSIONS WITH THE STEEL FABRICATOR
PRIOR TO STEEL FABRICATION TO ENSURE ARCHITECTURAL AND STRUCTURAL DESIGN
CONCEPT. CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER OF
DISCREPANCIES.
4. CONTRACTOR IS TO FURNISH ENGINEER A PROPOSED SEQUENCE OF EXISTING
COMPONENT REMOVAL. METHODS OF SAW CUTTING, TEMPORARY SHORING AND
OTHER PERTINENT TASKS RELATING TO EXISTING COMPONENT REMOVAL IS TO BE
SUBMITTED TO THE THE CONTRACTING OFFICER FOR REVIEW AND TO VERIFY THAT
WORK IS IN GENERAL CONFORMANCE.
STRUCTURAL STEEL
1. STRUCTURAL STEEL IS TO CONFORM TO THE FOLLOWING ASTM SPECIFICATIONS, AND IS
TO BE FABRICATED AND ERECTED IN ACCORDANCE WITH THE LATEST EDITION OF THE
AISC SPECIFICATIONS.
1.a .....STEEL WIDE FLANGE SECTIONS............ASTM A992 OR ASTM A572 - GRADE 50
1.b .....MISCELLANEOUS STEEL SECTIONS......ASTM A36
2. ALL STEEL SHALL BE DOMESTICALLY (INCLUDING CANADA) MILLED AND FABRICATED.
3. CONNECTION BOLTS FOR STRUCTURAL STEEL MEMBERS SHALL CONFORM TO ASTM
A325 OR A490, UNLESS OTHERWISE NOTED. STRUCTURAL STEEL CONNECTIONS SHALL
BE DESIGNED BY THE CONTRACTOR IN ACCORDANCE WITH THE MINIMUM
REQUIREMENTS SPECIFIED IN THE DRAWINGS AND LRFD.
4. WELDING IS TO CONFORM TO THE REQUIREMENTS OF THE AMERICAN WELDING SOCIETY
AND THE AISC, AND IS TO BE PERFORMED ONLY BY CERTIFIED WELDERS.
5. STRUCTURAL STEEL, MISCELLANEOUS METAL, AND EMBEDS EXPOSED TO THE EXTERIOR
IS TO BE HOT DIP GALVANIZED AFTER FABRICATION, EXCEPT AS NOTED ON THE
DRAWINGS.
6. STRUCTURAL STEEL IS TO BE PREPARED AND PRIMED ACCORDING TO THE
SPECIFICATIONS. STRUCTURAL STEEL LOCATED IN CRAWL SPACES OR OTHERWISE
INACCESSIBLE AREAS ARE TO RECEIVE 2 COATS OF PRIMER.
COLD FORMED METAL FRAMING
1. METAL FRAMING IS TO CONFORM TO ASTM A446. MINIMUM YIELD STRENGTH IS TO BE
50,000 PSI, WITH 1 5/8” MINIMUM FLANGE WIDTH.
2. MEMBERS ARE TO BE FABRICATED IN ACCORDANCE WITH AISI SPECIFICATIONS FOR THE
DESIGN OF COLD-FORM STEEL STRUCTURAL MEMBERS, LATEST EDITION. MEMBERS
ARE TO BE GALVANIZED.
3. CONNECTIONS ARE TO BE SCREWED OR WELDED, WITH A MINIMUM OF 2 - #12 TEK
SCREWS OR 3/16 FILLET WELD AND USED AT EACH CONNECTION AS MINIMUM.
4. METAL FRAMING MEMBERS ARE TO BE CLOSED OFF AT BOTH ENDS WITH CONTINUOUS
METAL TRACK OF EQUIVALENT GAGE OR GREATER THICKNESS THAN METAL GAGE
MEMBERS.
5. CONTRACTOR IS TO PROVIDE DESIGN CALCULATIONS FOR REVIEW. CALCULATIONS ARE
TO BE PREPARED AND SEALED BY A LICENSED ENGINEER IN THE STATE OF VIRGINIA
AND ARE TO BE SUBMITTED TO THE THE CONTRACTING OFFICER FOR REVIEW AND TO
VERIFY THAT WORK IS IN GENERAL CONFORMANCE. REFER TO SPECIFICATION FOR
ADDITIONAL INFORMATION.
VERTICAL LOAD DESIGN DATA
CANOPY ROOF LIVE LOAD = 20 PSF
COLLATERAL DEAD LOAD = 10 PSF
GROUND SNOW LOAD (Pg) = 20 PSF
WIND DESIGN DATA
V (ULTIMATE) = 115 MPH
V (ASD) = 89 MPH
EXPOSURE CATEGORY = C
RISK CATEGORY = II
SEISMIC DESIGN DATA
SEISMIC IMPORTANCE FACTOR (Ie) = 1.0
SPECTRAL RESPONSE ACCELERATION (Ss) = 0.18
SPECTRAL RESPONSE ACCELERATION (S1) = 0.06
SITE CLASS = D (ASSUMED)
SPECTRAL RESPONSE COEFFICIENT (Sds) = 0.19
SPECTRAL RESPONSE COEFFICIENT (Sd1) = 0.10
SEISMIC DESIGN CATEGORY = B
BASIC SEISMIC RESISTING FORCE SYSTEM = NOT SPECIFICALLY DETAILED FOR SEISMIC DESIGN
ROOF (PSF)
AREA (SF)
10 100
ZONES
27.9
-25.2
41.9
-38.5
55.9
-75.5
27.9
-25.2
41.9
-38.5
41.9
-38.5
COMPONENETS & CLADDING TABLE (ULT.)
S-001
G E
N E
R A
L
N
O T
S
I G
N
D
A T
A
R S
M B
M C
M C
S D
G N
METAL ROOF DECK FASTENING SCHEDULE
LABEL SUPPORT
PATTERN
SIDE LAP
(#10 TEK
SCREWS)
TYPE & GAUGE
(GALV. ROOF
DECK)
32/4 - #12 TEK SCREWS
32/4 - #12 TEK SCREWS
32/4 - #12 TEK SCREWS
(4)
(3)
(2)
20 GAUGE - 1.5 B
20 GAUGE - 1.5 B
20 GAUGE - 1.5 B
ROOF ZONES DIAGRAM
3 3 a = 7'-0" a (TYP)
AISC - TABLE N5.6-1
INSPECTION TASKS PRIOR TO BOLTING
QUALITY
CONTROL
QUALITY
ASSURANCE
MANUFACTURER'S CERTIFICATIONS AVAILABLE FOR FASTNER MATERIALS
INSPECTION TASKS PRIOR TO BOLTING
PO
FASTENERS MARKED IN ACCORDANCE WITH ASTM REQUIREMENTS OO
CORRECT FASTENERS SELECTED FOR THE JOINT DETAIL (GRADE, TYPE, BOLT
LENGTH IF THREADS ARE TO BE EXCLUDED FROM SHEAR PLANE) OO
CORRECT BOLTING PROCEDURE SELECTED FOR JOINT DETAIL OO
CONNECTING ELEMENTS, INCLUDING THE APPROPRIATE FAYING SURFACE
CONDITION AND HOLE PREPARATION, IF SPECIFIED, MEET APPLICABLE
REQUIREMENTS
OPPRE-INSTALLATION VERIFICATION TESTING BY INSTALLATION PERSONNEL
OBSERVED AND DOCUMENTED FOR FASTENER ASSEMBLIES AND METHODS USED
OO
OOPROPER STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS AND OTHER
FASTENER COMPONENTS
1.
2.
OBSERVE (O): THE INSPECTOR SHALL OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE
DELAYED PENDING THESE INSPECTIONS.
PERFORM (P): THESE TASKS SHALL BE PERFORMED FOR EACH WELDED JOINT OR MEMBER.
AISC - TABLE N5.6-2
INSPECTION TASKS DURING BOLTING
CONTINUOUS PERIODIC
FASTENER ASSEMBLIES, OF SUITABLE CONDITION, PLACED IN ALL HOLES AND
WASHERS (IF REQUIRED) ARE POSITIONED AS REQUIRED
INSPECTION TASKS DURING BOLTING
FREQUENCY OF INSPECTION
X—
JOINT BROUGHT TO THE SNUG-TIGHT CONDITION PRIOR TO THE
PRETENSIONING OPERATION X—
FASTENER COMPONENT NOT TURNED BY THE WRENCH PREVENTED FROM
ROTATING X—
FASTENERS ARE PRETENSIONED IN ACCORDANCE WITH THE RCSC
SPECIFICATION, PROGRESSING SYSTEMATICALLY FROM MOST RIGID POINT
TOWARD THE FREE EDGES
X—
AISC - TABLE N5.6-3
INSPECTION TASKS AFTER BOLTING
CONTINUOUS PERIODIC
DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNECTIONS
INSPECTION TASKS AFTER BOLTING
FREQUENCY OF INSPECTION
—X
AISC - TABLE N5.4-1
INSPECTION TASKS PRIOR TO WELDING
QUALITY
CONTROL
QUALITY
ASSURANCE
WELDER QUALIFICATION RECORDS AND CONTINUITY RECORDS
INSPECTION TASKS PRIOR TO WELDING
O
MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLES AVAILABLE PP
MATERIAL INDENTIFICATION (TYPE/GRADE) OO
WELDER IDENTIFICATION SYSTEM {a] OO
FIT-UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY)
- JOINT PREPARATION
- DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL)
- CLEANLINESS (CONDITION OF STEEL SURFACES)
- TACKING (TACK WELD QUALITY AND LOCATION)
- BACKING TYPE AND FIT (IF APPLICABLE)
OO
CONFIGURATION AND FINISH OF ACCESS HOLES OO
FIT-UP OF FILLET WELDS
- DIMENSIONS (ALIGNMENT, GAPS AT ROOT)
- CLEANLINESS (CONDITION OF STEEL SURFACES)
- TACKING (TACK WELD QUALITY AND LOCATION)
OO
P
WPS AVAILABLE P P
FIT-UP OF CJP GROOVE WELDS OF HSS T-, Y- AND K-JOINTS WITHOUT BACKING
(INCLUDING JOINT GEOMETRY
- JOINT PREPARATIONS
- DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL)
- CLEANLINESS (CONDITION OF STEEL SURFACES)
- TACKING (TACK WELD QUALITY AND LOCATION)
- BACKING TYPE AND FIT (IF APPLICABLE)
P O
CHECKING WELDING EQUIPMENT O --
1.
2.
3.
[a] THE FABRICATOR OR ERECTOR, AS APPLICABLE, SHALL MAINTAIN A SYSTEM BY WHICH A WELDER WHO HAS WELDED A JOINT OF MEMBER CAN BE IDENTIFIED. STAMPS, IF USED, SHALL BE THE LOW-STRESS TYPE.
OBSERVE (O): THE INSPECTOR SHALL OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATION NEED NOT BE
DELAYED PENDING THESE INSPECTIONS.
PERFORM (P): THESE TASKS SHALL BE PERFORMED FOR EACH WELDED JOINT OR MEMBER.
WHEN A TASK IS NOTED TO BE PERFORMED BY BOTH QC AND QA IT IS PERMITTED TO COORDINATE THE INSPECTION FUNCTION BETWEEN THE QC INSPECTOR AND QA INSPECTOR SO THAT THE INSPECTION FUNCTION ARE PERFORMED BY ONLY ONE PARTY. WHEN THE QA RELIES UPON INSPECTION FUNCTIONS PERFORMED BY QC, THE APPROVAL OF THE ENGINEER OF RECORD AND THE AUTHORITY HAVING JURISDICTION.
AISC - TABLE N5.4-2
INSPECTION TASKS DURING WELDING
QUALITY
CONTROL
QUALITY
ASSURANCEINSPECTION TASKS DURING WELDING
CONTROL AND HANDLING OF WELDING CONSUMABLES
- PACKAGING
- EXPOSURE CONTROL
OO
NO WELDING OVER CRACKED TACK WELDS OO
ENVIRONMENTAL CONDITIONS
- WIND SPEED WITHIN LIMITS
- PRECIPITATION AND TEMPERATURE
OO
WPS FOLLOWED
- SETTINGS ON WELDING EQUIPMENT
- TRAVEL SPEED
- SELECTED WELDING MATERIALS
- SHIELDING GAS TYPE/FLOW RATE
- PREHEAT APPLIED
- INTERPASS TEMPERATURE MAINTAINED (MIN./MAX.)
- PROPER POSITION (F,V,H,OH)
OO
WELDING TECHNIQUES
- INTERPASS AND FINAL CLEANING
- EACH PASS WITHIN PROFILE LIMITATIONS
- EACH PASS MEETS QUALITY REQUIREMENTS
OO
PLACEMENT AND INSTALLATION OF STEEL HEADED STUD ANCHORS P P
1.
2.
OBSERVE (O): THE INSPECTOR SHALL OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE
DELAYED PENDING THESE INSPECTIONS.
PERFORM (P): THESE TASKS SHALL BE PERFORMED FOR EACH WELDED JOINT OR MEMBER.
AISC - TABLE N5.4-3
INSPECTION TASKS AFTER WELDING
QUALITY
CONTROL
QUALITY
ASSURANCE
WELDS CLEANED
INSPECTION TASKS AFTER WELDING
OO
SIZE, LENGTH, AND LOCATION OF WELDS PP
WELDS MEET VISUAL ACCEPTANCE CRITERIA
- CRACK PROHIBITION
- WELD/BASE-METAL FUSION
- CRATER CROSS SECTION
- WELD PROFILES
- WELD SIZE
- UNDERCUT
- POROSITY
PP
ARC STRIKES PP
k-AREA [a]
PPBACKING REMOVED AND WELD TABS REMOVED (IF REQUIRED)
PP
—OREPAIR ACTIVITIES
—PDOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OR MEMBER
WELD ACCESS HOLES IN ROLLED HEAVY SHAPES AND BUILT-UP HEAVY SHAPES [b] PP
NO PROHIBITED WELDS HAVE BEEN ADDED WITHOUT THE APPROVAL OF THE EOR OO
1.
2.
[a] WHEN WELDING OF DOUBLER PLATES, CONTINUITY PLATES OR STIFFENERS HAS BEEN PERFORMED IN THE K-AREA, VISUALLY INSPECT THE WEB K-AREA FOR CRACKS WITHIN 3 INCHES (75MM) OF THE WELD.
[b] AFTER ROLLED HEAVY SHAPES (SEE SECTION A3.1C) AND BUILT-UP HEAVY SHAPES (SEE SECTION a3.14D) ARE
WELDED, VISUALLY INSPECT THE WELD ACCESS HOLE FOR CRACKS.
OBSERVE (O): THE INSPECTOR SHALL OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE
DELAYED PENDING THESE INSPECTIONS.
PERFORM (P): THESE TASKS SHALL BE PERFORMED FOR EACH WELDED JOINT OR MEMBER.
SPECIAL INSPECTION NOTES:
1. THE CONTRACTING OFFICER IS NOT RESPONSIBLE FOR INSPECTIONS AND TESTINGS.
GENERAL CONTRACTOR TO CARRY IN THEIR CONTRACT.
2. GENERAL CONTRACTOR'S TESTING LABORATORY SHALL PROVIDE SPECIAL
INSPECTION SERVICES IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE
FOR THE FOLLOWING ITEMS LISTED ON THESE SHEETS. ONLY
TESTS ARE REQUIRED FOR THE APPLICABLE MATERIALS ON THE PROJECT.
A N
S I
D
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
D
F
E N
P
P
N
T E
R
R
I C
H M
O N
D
R
I C
H M
O N
D
V
A
B U
I L D
I N
G
T
R U
N
O P
Y
P R
O J E
M
B E
R
SHEET ID
F I L
E N
A M
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
US Army Corps of Engineers
C A
T E
G O
D
E
X X
X X
X X
X
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
N O
R F
O
S
T R
I C
T
F
R O
R
E E
T
N O
R F
O L K
V
I R
G I N
I A
X X
X X
X X
X
X X
X
X X
X
X X
X X
X X
X
X X
X
X X
X
D E
P
T I O
N
R A
L E
I G
H
N
C
F
A X
L I C
E N
BCOES
NOT FOR CONSTRUCTION
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
S-002
S P
E C
I A
L
I N
S P
E C
T I O
N S
R S
M B
M C
M C
S D
G
B
C
3 4 5 6 7 8 9 10 11 12 13
GRID
4 5
A N
S I
D
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
D
F
E N
P
P
N
T E
R
R
I C
H M
O N
D
R
I C
H M
O N
D
V
A
B U
I L D
I N
G
T
R U
N
O P
Y
P R
O J E
M
B E
R
SHEET ID
F I L
E N
A M
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
US Army Corps of Engineers
C A
T E
G O
D
E
X X
X X
X X
X
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
N O
R F
O
S
T R
I C
T
F
R O
R
E E
T
N O
R F
O L K
V
I R
G I N
I A
X X
X X
X X
X
X X
X
X X
X
X X
X X
X X
X
X X
X
X X
X
D E
P
T I O
N
R A
L E
I G
H
N
C
F
A X
L I C
E N
BCOES
NOT FOR CONSTRUCTION
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
PHASE I PHASE II
TYP
S-101
PARTIAL PLAN & STRUCTURAL GRID LAYOUT
1/16" - 1'-0'
199'-6"
16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
" 16'-7
OUTLINE OF NEW
CANOPY, TYP
S-101
CANOPY SECTION A - NEW WORK
3/8" - 1'-0'
EXISTING CONCRETE
STAIRS & METAL
HANDRAIL ASSEMBLY
BOTTOM W8X24 BEAM
@ EACH COLUMN, TYP
NEW 2L 5X5X3/8 KICKBACK ANGLES.
SLOPE TO MATCH EXISTING
CANOPIES ON SITE
EXISTING RIBBON WINDOWS TO
REMAIN INTACT, TYP
EXISTING GUTTER TO REMAIN
INTACT, TYP
12'-0"
TOP OF STEEL
0'-0"
FIN FLR
RIBBON WINDOWS
21'-3"
BOTTOM OF
NEW W8X24 FRAMED IN BETWEEN
BEAMS, SHEAR TAB CONNECTIONS
BETWEEN BEAMS, TYP
W8X24 BEAM FRAMED
INTO EXISTING
COLUMNS, TYP
EXISTING W12X40
COLUMN, TYP
NEW W8X24 FRAMED IN
BETWEEN BEAMS, SEE
DETAIL 1/S-102, AND SHEAR
TAB SCHEDULE, TYP
NEW 1 1/2", 20 GA, TYPE 'B', G-60
GALVANIZED METAL DECKING OVER COLD
FORM STEEL FRAMING. FASTEN TO THE
METAL FRAMING SYSTEM WITH #12 DP2
SELF DRILLING SCREWS. SEE S-001 FOR
FASTENING SCHEDULE
PL 12"x6"x3/4" THICK PLATE. FOR
KICKBACK ANGLE ATTACHMENT,
SEE DETAIL 4/S-102
PL 18"x6"x3/4" THICK PLATE W/ (8) 3/4"Ø
A325 BOLTS, BOLTED TO W8 CANOPY
BEAM W/ 3/8" THICK PLATE FOR
KICKBACK ANGLE ATTACHMENT, SEE
DETAIL 3/S-102
4'-5
BEAM OVER BEAM
CONNECTION
7'-1
BEAM OVER BEAM
CONNECTION
L4x4x1/4 BRACING ANGLE 1/4", SEE DETAIL 5/S-102 FOR
CONNECTION TO BEAM, TYP.
6" METAL STUD W/ TRACK @ TOP &
BOTTOM(MIN 20 GA) SPACED @ 24"
MAX C/C
EXISTING CMU
WALL, TYP
PL 12"X6"X3/4", TYP. SEE
DETAIL 2/S-102 AND SHEAR
TAB SCHEDULE
REPAIR ALL CUTOUTS IN CMU
WALL W/ POLYMER MODIFIED
MORTAR WHERE ACCESS TO
COLUMNS OCCURS, AND PAINT
TO MATCH EXISTING,TYP
S-101
PARTIAL CANOPY CANTILEVER SECTION @ WALL
1/2 - 1'-0'
EDGE OF NEW
CANOPY
EDGE OF NEW
CANOPY
S-101
PARTIAL CANOPY CANTILEVER SECTION @ EAVE
1/2 - 1'-0'
FACE OF NEW
CANOPY BEYOND, TYP
NEW W8X24 IN
FOREGROUND
NEW W8X24 FRAMED IN
BETWEEN BEAMS, SEE DETAIL
1/S-001, AND SHEAR TAB
SCHEDULE, TYP
BOTTOM W8X24 BEAM
@ EACH COLUMN, TYP
NEW W8X24 @
EDGE OF CANOPY
NEW W8X24 @
EDGE OF CANOPY
NEW W8X24 FRAMED IN
BETWEEN BEAMS, SEE DETAIL
1/S-001, AND SHEAR TAB
SCHEDULE, TYP
NEW W8X24
CANTILEVER BEAM
OPP
HAND
OPP
HAND
(4) 3/4"Ø A325
BOLTS, TYP
19'-0 3/4"±
TOP OF STEEL
EQ EQ EQ
3"
17'-3
" DIM TO MATCH EXIST
(FIELD VERIFY)
1/4
1/4
6" METAL STUD
BRACE, TYP
S-101
P A
R T
I A
L
S
T R
U C
T U
R A
L
P
L A
N
A N
D
S
E C
T I O
R
K
R S
M B
M C
M C
S D
G N
S-101
S-101
S-101
S-101
S-101
S I
D
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
D
F
E N
P
P
N
T E
R
R
I C
H M
O N
D
R
I C
H M
O N
D
V
A
B U
I L D
I N
G
T
R U
N
O P
Y
P R
O J E
M
B E
R
SHEET ID
F I L
E N
A M
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
US Army Corps of Engineers
C A
T E
G O
D
E
X X
X X
X X
X
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
N O
R F
O
S
T R
I C
T
F
R O
R
E E
T
N O
R F
O L K
V
I R
G I N
I A
X X
X X
X X
X
X X
X
X X
X
X X
X X
X X
X
X X
X
X X
X
D E
P
T I O
N
R A
L E
I G
H
N
C
F
A X
L I C
E N
BCOES
NOT FOR CONSTRUCTION
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
S-102
SHEAR TAB CONNECTION SCHEDULE
3/4" - 1'-0'
3/16
SNUG-TIGHTENED BOLTED
CONNECTION USING 3/4"Ø, A325
BOLTS, IN HORIZONTAL
SHORT-SLOTTED HOLES IN PLATE
COPE
SINGLE PLATE 3/8"
THICKNESS, TYP.
3" MAX 1 1/2" MIN. TYP.
S-102
NEW PLATE CONNECTION #1
3" - 1'-0'
6"
3/4" PL
S-102
NEW PLATE CONNECTION #2
3" - 1'-0'
3"
6"
1 2
1 2
13/16"Ø
3/8" THICK
PLATE WELDED
TO 3/4" PLATE
TOP
3" 9" 3"
18"
3/4" PLATE
3/4" PLATE
SIDE
FRONT
NOTES:
1. TYPICAL BEAM TO BEAM AND BEAM TO COLUMN CONNECTION.
2. SINGLE PLATE SHEAR CONNECTIONS PER AISC LRFD.
SHEAR TAB BEAM-GIRDER STANDARD CONNECTIONS
BEAM
SIZE
MIN. # OF
BOLTS
2W8
PLATE
THICKNESS
3/8
SIZE OF FILLET
WELD 'W'
3/16
CONNECTION
STRENGTH (LFRD)
24.5K
EXIST W12X40
AS OCCURS
1/4
1/4
3/8" SHEAR TAB
CENTERED ON
PLATE
18"
NEW KICKBACK
ANGLE, SEE 2/S-101
FRONT SIDE
3/8" THICK
PLATE WELDED
TO 3/4" PLATE
S-102
NEW PLATE CONNECTION #3
3" - 1'-0'
1 2
NEW KICKBACK
ANGLE, SEE 2/S-101
6"
3/4" PL
EXIST W12X40
AS OCCURS
1/4
NEW KICKBACK
ANGLES, SEE
2/S-101
3/4" PL
EXIST W12X40
AS OCCURS
19'-0 3/4"±
TOP OF STEEL
19'-0 3/4"±
TOP OF STEEL
3/8" THICK
PLATE WELDED
TO 3/4" PLATE
1 4
1/4
1/4
S-102
D E
T A
I L S
A N
D
S
E C
T I O
R
K
R S
M B
M C
M C
S D
G N
S-102
BRACING CONNECTION
3" - 1'-0'
3/8" PL
1/4
STEEL BRACING ANGLE
WELDED TO 3/8" PLATE,
SEE PLAN FOR ANGLE
SIZE
STEEL BEAM TYP.,
SEE PLAN
1'-8"
SYMBOLS
FP-001 FP-101
A135
DETAIL NUMBER:
1 - NUMBER INDICATES DETAIL.
FP-001 - SHEET NUMBER WHERE DETAIL IS REFERENCED.
FP-101 - SHEET NUMBER WHERE DETAIL IS DRAWN
COLUMN LINE NUMBER
NOTE REFERENCE NUMBER
ROOM NUMBER DESIGNATION
DRAWING REVISION NUMBER
ABBREVIATIONSGENERAL NOTES
1. PROVIDE AN EXTENSION TO THE EXISTING WET-PIPE SPRINKLER SYSTEM, AS INDICATED IN THE DRAWINGS, DESIGNED IN ACCORDANCE WITH UFC 3-600-01, CHANGE2 DATED 25 MARCH 2018 AND NFPA 13, 2016.THE EXISTING SYSTEM WAS HYDRAULICALLY DESIGNED AND THE HYDRAULICALLY MOST REMOTE AREA IS OUTSIDE OF THE AREA OF WORK.
HYDRAULICALLY DESIGN THE WET-PIPE SPRINKLER EXTENSION IN ACCORDANCE WITH UFC 3-600-01 SECTION 9-6.4.
2. FOLLOW THE PHASING PLAN INDICATED ON THE A SHEETS.
3. ALL DRAWING INFORMATION IS DIAGRAMMATIC IN NATURE AND SHALL BE CONFIRMED.
4. THE EXISTING SPRINKLER SYSTEM IS IN SERVICE, AND WILL REMAIN IN SERVICE UNTIL FINAL CONNECTIONS ARE READY TO BE
MADE. AFTER CONNECTION, FILL AND TEST THE NEW AND EXISTING SYSTEM.
5. MODIFY THE EXISTING WET-PIPE SPRINKLER SYSTEM TO PROTECT THE AREA UNDER THE CANOPY. PROVIDE DRY BARREL EXTENDED COVERAGE SIDEWALL HEADS SUITABLE FOR ANGLED MOUNTING. BASIS OF DESIGN: VIKING VK-25X3 OR VK-27X3.
6. CONDUCT A HYDRANT WATER FLOW TEST PER NFPA 291 2019 EDITION.
7. THE FIRE ALARM SYSTEM IS EXISTING, AND IS NOT MODIFIED AS A RESULT OF THIS PROJECT.
8. SEPARATE THE AREA OF WORK FROM THE OCCUPIED BUILDING PORTION. SEE SHEET SA101 FOR BARRIER SEPARATION.
0.20 GPM/SF
ORDINARY
SPRINKLER DESIGN CRITERIA
OUTSIDE HOSE STREAM ALLOWANCE:
REMOTE AREA: 2500 SF
250 GPM
DISCHARGE DENSITY:
OCCUPANCY HAZARD:
SUMMER CONSULTANTS
FLOW TEST DATA
TEST DATE:
FLOW TEST BY:
LOCATION:
TOTAL FLOW:
RESIDUAL PRESSURE:
STATIC PRESSURE:
FLOW HYDRANT 45, RESIDUAL 44
17 OCT 2018
65 PSI
1250 GPM
40.5 PSI
3-1/2" DIAMETER PRESSURE GAUGE
WITH ISOLATION VALVE
LIMIT OF DEMOLITION
DOUBLE CHECK BACKFLOW
POINT OF CONNECTION
OS&Y VALVE
CHECK VALVE
FIRE DEPARTMENT CONNECTION
SP SPRINKLER PIPING
PREVENTOR ASSEMBLY
EXISTING SPRINKLER
## SPRINKLER AND FIRE ALARM ZONE NAME
SPRINKLER TEMPERATURE: ORDINARY
MINIMUM K-FACTOR: 8.0
ADDRESSABLE INPUT MODULE
ADDRESSABLE OUTPUT MODULE
VALVE TAMPER SWITCH
WATER FLOW SWITCH
DRY PIPE RISER
FLOW METER
VALVE
HYDRAULIC CALCULATION MODE
AC
AFF
AHU
AHJ
AI
AS
BM
BFC
C
CLOS
CKT
CMU
CONC
CRM
DN
DHWT
EG
ELEV
EOL
EP
EQUIP
EX/(E)
FA
FL
FLS
FT
GYP
HDR
HV
IDC
IN
LAT
MCC
MECH
NAC
NAP
NFPA
NO
NTS
RM
SP
ST
TC
TELE
TYP
UON
W
ZN
AIR CONDITION
ABOVE FINISHED FLOOR
AIR HANDLING UNIT
AUTHORITY HAVING JURISDICTION
ADDRESSABLE INTERFACE
ASPIRATING
BEAM
BELOW FINISHED CEILING
CEILING
CLOSET
CIRCUIT
CONCRETE MASONRY UNIT
CONCRETE
CENTRIFUGAL REFRIGERATION MACHINE
DOWN
DOMESTIC HOT WATER TANK
EQUIPMENT GROUND
ELEVATOR
END OF LINE SUPERVISION DEVICE
ELECTRIC-PNEUMATIC SWITCH
EQUIPMENT
EXISTING
FIRE ALARM
FLOOR
FLOOR SINK
FEET
GYPSUM BOARD
HEADER
HEATING VENTILATING
INITIATING DEVICE CIRCUIT
INCH
LAY-IN ACOUSTICAL TILE
MOTOR CONTROL CENTER
MECHANICAL
NOTIFICATION APPLIANCE CIRCUIT
NOTIFICATION APPLIANCE PANEL
NATIONAL FIRE PROTECTION ASSOCIATION
NUMBER
NOT TO SCALE
ROOM
SPRINKLER
STAIR
TERMINAL CABINET
TELEPHONE
TYPICAL
UNLESS OTHERWISE NOTED
WATER
ZONE
FDC FIRE DEPARTMENT CONNECTION
FPC FIRE PUMP CONNECTION
NEW UPRIGHT SPRINKLER
BUTTERFLY VALVE
EXISTING SIDEWALL SPRINKLER
NEW PENDANT SPRINKLER
(E)
(ETR)
EXISTING PIPING
EXISTING TO REMAIN PIPING ON DEMOLITION DRAWINGS
AIM
AOM
TS
WF
NORMALLY OPEN
NORMALLY CLOSED
CHECK
SCALE
USED
FLOW - G.P.M.
PR
ES
SU
RE
P.
S.
I.
WATER SUPPLY GRAPH NO. _____, N 1.85
105 PSI
1950 GPM
96 PSI
NO PUMP PUMP ON
100300
103400
106500
109600
112700
115800
118900
1211000
1241100
1271200
1301300
1331400
1361500
1391600
1421700 1451800
1481900
1512000
1542100
1572200
1602300
1632400
200 399
203 499
206 599
209 699
212 799 215 899
218 999
221 1099
224 1199
227 1299
230 1399
2331499
2361599
2391699
242 1799
245 1899
248 1999
251 2099
254 2199
2572299
260 2399
263 2499
PUMP RUNNING
PUMP SECURED
ORIGINAL SYSTEM CURVE
Dx
Dx1060
Dx
Dx
Dx
Dx
Dx
Dx
Dx
SYSTEM EXTENSION CURVE
HYDRAULIC CALCULATION AREA
RESIDUAL HYDRANT 44
FLOW HYDRANT 45
HYDRAULIC NODE DIAGRAM
MAXIMUM SPACING 20 FT
NOT TO SCALE
WATER FLOW TEST DEMAND VS SUPPLY GRAPH
NOT TO SCALE
FI
LE
N
AM
E:
OU
RE
F:
PL
OT
D
AT
E:
3/2
7/2
9 1 2:2
7:4 6 P
M
1.1
2-
F
-0
.D W
G
A N
S I
D
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
M
D L
A
D
E F
E N
P
P L
Y
C
E N
T E
R
R
I C
H M
O N
D
R
I C
H M
O N
D
V
A
B U
I L
D I N
G
T
R U
N
O P
Y
P R
O J E
M
B E
R
SHEET ID
F I L E
N A
M E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
US Army Corps of Engineers
C A
T E
G O
D
E
X X
X X
X X
X
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
N O
R F
O L
K
D
I S
T R
I C
T
F
R O
R
E E
T
N O
R F
O L
K
V
I R
G I N
I A
X X
X X
X X
X
X X
X
X X
X
X X
X X
X X
X
X X
X
X X
X
D E
P
T I O
N
J O
N E
S
F
R A
N K
L
S
U I T
E
R A
L E
I G
H
N
C
F
A X
L I C
E N
BCOES
NOT FOR CONSTRUCTION
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
F I R
E
P
R O
T E
C T
I O
N
S
Y M
B O
L S
F-001
A B
B R
I V
I A
T I O
N S
N
O T
E S
CO
LL
AT
CO
LL
AT
PA
TE
RS
ON
(E) 6"FIRE
(E)FDC
(E) BACKFLOW TEST HEADER
(E)RISER VALVE BELOW FLOOR
(E) ISOLATION VALVE
E
F
I R
E
T
Y P
112 115 118 121 124 127 130 133 136 139
142 145 148 151 154 157 160 163
D x
D x
D x
D x
D x
D x
D x
D x
D x
1"DRAIN
(E) 6" FIRE (E) 3" FIRE
1.5" FIRE
SIDEWALL DRY
SPRINKLER ASSEMBLY
1" DRAIN HEADER
A N
S I
D
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
M
D L
A
D
E F
E N
P
P L
Y
C
E N
T E
R
R
I C
H M
O N
D
R
I C
H M
O N
D
V
A
B U
I L
D I N
G
T
R U
N
O P
Y
P R
O J E
M
B E
R
SHEET ID
F I L E
N A
M E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
US Army Corps of Engineers
C A
T E
G O
D
E
X X
X X
X X
X
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
N O
R F
O L
K
D
I S
T R
I C
T
F
R O
R
E E
T
N O
R F
O L
K
V
I R
G I N
I A
X X
X X
X X
X
X X
X
X X
X
X X
X X
X X
X
X X
X
X X
X
D E
P
T I O
N
J O
N E
S
F
R A
N K
L
S
U I T
E
R A
L E
I G
H
N
C
F
A X
L I C
E N
BCOES
NOT FOR CONSTRUCTION
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
FLOOR PLAN - NEW WORK
1/8" = 1'-0"
CANOPY SECTION - NEW WORK
3/8" = 1'-0"
NOTES
1. CORE DRILL CMU WALL AT ANGLE TO MATCH
NEW CANOPY. PROVIDE DRY SIDEWALL
SPRINKLER ASSEMBLY OF SUFFICIENT
LENGTH.
2. COORDINATE SPRINKLER LOCATIONS TO
CLEAR CANOPY STRUCTURE.
FX101
F I R
E
S
P R
I N
K L
A
N
CO
LL
AT
CO
LL
AT
PA
TE
RS
ON
FX101 FX101
FX101 FX101
FX101
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 6'
AutoCAD SHX Text 2'
AutoCAD SHX Text
FIRE SPRINKLER PLAN
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
J
DN
UP
Ø
SYMBOLS
A135 1,3,5
#10
#10
1,3,5
A135
#10 A135 1,3,5
E-001 E-101
A135
A AMPERES.
AF FRAME SIZE IN AMPERES.
AFF ABOVE FINISHED FLOOR.
AT TRIP SIZE IN AMPERES.
AWG AMERICAN WIRE GAUGE.
BLDG. BUILDING.
C/B CIRCUIT BREAKER.
EMT ELECTRICAL METALLIC TUBING.
FA FIRE ALARM.
FACP FIRE ALARM CONTROL PANEL.
FCU FAN COIL UNIT.
FLA FULL LOAD AMPERES.
FVNR FULL VOLTAGE NON-REVERSING.
GFI GROUND FAULT INTERRUPTER.
GRD. GROUND CONDUCTOR.
HOA HAND-OFF-AUTOMATIC SELECTOR SWITCH.
KAIC THOUSAND AMPERE INTERRUPTING CAPACITY.
KW KILO-WATTS.
M.L.O. MAIN LUGS ONLY.
N.C. NORMALLY CLOSED.
N.E.C. NATIONAL ELECTRICAL CODE.
NEMA NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION.
NFSS NON-FUSED SAFETY SWITCH.
N.O. NORMALLY OPEN. NUMBER OF POLES.
P NUMBER OF PHASES.
PH. RIGID GALVANIZED STEEL.
SRC SERVER RACK CLUSTER.
U.L. UNDERWRITER'S LABORATORIES.
V VOLTAGE.
WP WEATHERPROOF, OR NEMA 3R ENCLOSURE.
DETAIL NUMBER:
- NUMBER INDICATES DETAIL.
- SHEET NUMBER WHERE DETAIL IS REFERENCED.
- SHEET NUMBER WHERE DETAIL IS DRAWN.
COLUMN LINE NUMBER.
NOTE REFERENCE NUMBER.
ROOM NUMBER DESIGNATION.
DRAWING REVISION NUMBER.
CONDUIT UP.
CONDUIT DOWN.
DELTA CONFIGURATION.
WYE GROUNDING CONFIGURATION.
PHASE.
BRANCH CIRCUIT CONDUIT AND CONDUCTORS RUN EXPOSED.
SIZE IN ACCORDANCE WITH N.E.C. RACEWAY SHALL BE
MINIMUM 1/2" CONDUIT, AND WIRE SHALL BE MINIMUM SIZE #12
AWG COPPER, UNLESS OTHER SIZES ARE SPECIFICALLY NOTED.
HOME RUN TO PANEL.
NUMBER OF ARROWS INDICATE THE NUMBER OF
CIRCUITS.
NUMBER OF SLASH MARKS INDICATE THE NUMBER OF
CONDUCTORS IN RACEWAY. NO SLASH MARKS INDICATE
2 CIRCUIT CONDUCTORS PLUS A GROUND CONDUCTOR.
GREEN GROUND CONDUCTOR RUN IN RACEWAY.
PANEL NAME TO WHICH CIRCUITS RUN.
CIRCUIT BREAKERS IN PANEL SERVING THESE CIRCUITS.
WIRE SIZE IN AWG. SIZE NOT SHOWN INDICATES #12
AWG.
BRANCH CIRCUIT CONDUIT AND CONDUCTORS RUN CONCEALED
IN WALLS AND CEILING, ALL OTHER CHARACTERISTICS SAME AS
SHOWN ABOVE.
JUNCTION BOX, 4" SQUARE x 2-1/8" DEEP GALVANIZED PRESSED
STEEL, RECESS MOUNTED AT 18" ABOVE FINISHED FLOOR, WITH
BLANK COVER PLATE.
E-101
E-001
ABBREVIATIONS
FI
LE
N
AM
E:
OU
RE
F:
PL
OT
D
AT
E:
3/2
7/2
9 3 :08
:07 P
M
2.0
2-
E
-0
.D W
G
A N
S I
D
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
M
D L
A
D
E F
E N
P
P L
Y
C
E N
T E
R
R
I C
H M
O N
D
R
I C
H M
O N
D
V
A
B U
I L
D I N
G
T
R U
N
O P
Y
P R
O J E
M
B E
R
SHEET ID
F I L E
N A
M E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
US Army Corps of Engineers
C A
T E
G O
D
E
X X
X X
X X
X
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
N O
R F
O L
K
D
I S
T R
I C
T
F
R O
R
E E
T
N O
R F
O L
K
V
I R
G I N
I A
X X
X X
X X
X
X X
X
X X
X
X X
X X
X X
X
X X
X
X X
X
D E
P
T I O
N
J O
N E
S
F
R A
N K
L
S
U I T
E
R A
L E
I G
H
N
C
F
A X
L I C
E N
BCOES
NOT FOR CONSTRUCTION
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
E L
E C
T R
I C
M
B O
L S
E-001
CO
LL
AT
CO
LL
AT
ST
EW
AR
T
1 1 1 1 1 3
4 4
C
C
T
V
2 2 2 22
C
C
T
V
A N
S I
D
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
M
D L
A
D
E F
E N
P
P L
Y
C
E N
T E
R
R
I C
H M
O N
D
R
I C
H M
O N
D
V
A
B U
I L
D I N
G
T
R U
N
O P
Y
P R
O J E
M
B E
R
SHEET ID
F I L E
N A
M E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
A
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
US Army Corps of Engineers
C A
T E
G O
D
E
X X
X X
X X
X
U S
A
R M
Y
C
O R
E
N G
I N
E E
R S
N O
R F
O L
K
D
I S
T R
I C
T
F
R O
R
E E
T
N O
R F
O L
K
V
I R
G I N
I A
X X
X X
X X
X
X X
X
X X
X
X X
X X
X X
X
X X
X
X X
X
D E
P
T I O
N
J O
N E
S
F
R A
N K
L
S
U I T
E
R A
L E
I G
H
N
C
F
A X
L I C
E N
BCOES
NOT FOR CONSTRUCTION
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
FLOOR PLAN - NEW WORK
CANOPY ELEVATION - NEW WORK
NOTES
1. CAREFULLY REMOVE AND STORE EXISTING LED
LIGHT FIXTURE FOR REUSE. REMOVE EXISTING
CONDUIT AND CONDUCTORS COMPLETE.
2. UPON COMPLETION OF CANOPY WORK, INSTALL
STORED LIGHT FIXTURE APPROXIMATELY 24"
BELOW PREVIOUS MOUNTING HEIGHT. PROVIDE
CONDUIT AND CONDUCTORS AND CONNECT TO
OPERATE AS BEFORE.
3. PROVIDE CAST ALUMINUM JUNCTION BOX AND
GASKETED COVER. INTERCEPT EXISTING
CONDUIT SYSTEM.
4. PROVIDE TEMPORARY TYPE UF FEEDER,
2-#12+#12G, TO MAINTAIN REMAINING LIGHTS IN
SERVICE DURING CONSTRUCTION OF CANOPY.
ROUTE UP TO AND ACROSS ROOF. AT
COMPLETION OF CANOPY WORK, REMOVE
TEMPORARY FEEDER.
5. EXISTING CAMERA. RELOCATE VERTICALLY UP
OR DOWN 10 FEET TO A LOCATION DIRECTED BY
THE CONTRACTING OFFICER. PROVIDE
JUNCTION BOX, CONDUIT AND CONDUCTORS TO
OPERATE AS BEFORE.
EL101
F L
O O
R
P
L A
N
A
C
T I O
N
CO
LL
AT
CO
LL
AT
ST
EW
AR
T
EL101 EL101
EL101 EL101
1/8" = 1'-0"
1/8" = 1'-0"
TO/FROM REMAINING
EXISTING FIXTURES
TO/FROM REMAINING
EXISTING FIXTURES
EL101
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
FLOOR PLAN AND SECTION
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
16'
| G-001,COVER SHEET |
| G-002,LEGENDS & ABBREVIATIONS |
| G-003,GENERAL CONSTRUCTION NOTES |
| SD101,PARTIAL FLOOR PLAN AND EXTERIOR ELEVATION - DEMOLITION |
| SA101,FLOOR PLAN - NEW WORK |
| SA102,EXTERIOR ELEVATION AND BUILDING SECTION NEW WORK |
| SA103,DETAILS - NEW WORK |
| S-001,GENERAL NOTES AND DESIGN DATA |
| S-002,SPECIAL INSPECTIONS |
| S-101,PARTIAL STRUCTURAL PLAN AND SECTIONS - NEW WORK |
| S-102,DETAILS AND SECTIONS - NEW WORK |
| F-001,FIRE PROTECTION SYMBOLS, ABBRIVIATIONS, NOTES |
| FX101,FIRE SPRINKLER PLAN |
| E-001,ELECTRICAL SYMBOLS |
| EL101,FLOOR PLAN AND SECTION |