E L E
IS
U R
C O
V E
R S
H E
T of Engineers
US Army Corps
SOLICITATION NO.:
CONTRACT NO.:
ISSUE DATE:
AND APPROVAL OF ALL DRAWINGS LISTED ON THE INDEX SHEET.
SIGNATURES AFFIXED BELOW INDICATE OFFICIAL RECOMMENDATION
SUBMITTED BY:
SECTION CHIEF
APPROVAL RECOMMENDED BY:
BRANCH CHIEF
APPROVED BY:
CONSTRUCTION DIVISION
CHIEF, ENGINEERING AND
DATE
DATE
DATE
THEIR EMPLOYMENT AS REQUIRED BY ER 1110-1-8152.
APPEAR ON THESE PROJECT DOCUMENTS WITHIN THE SCOPE OF
DESIGNATIONS OF U.S. ARMY CORPS OF ENGINEERS INDIVIDUALS
THIS SHEET. THE INITIALS OR SIGNATURES AND REGISTRATION
U.S. ARMY CORPS OF ENGINEERS AND THE A/E FIRMS IDENTIFIED ON
THIS PROJECT WAS DESIGNED BY THE PITTSBURGH DISTRICT OF THE
Pittsburgh District
W911WN-16-T-8005
OHIO RIVER BASIN
DASHIELDS LOCKS AND DAM
ALLEGHENY COUNTY, PENNSYLVANIA
G-0054
R T
Y S
Z K
IE
W
IC
Z
APRIL 2016
HVAC SYSTEM REPLACEMENT - SERVICE BUILDING
C L
IC
H T
Y
/s/ JEANINE HOEY P.E.
/s/ STEPHEN R. STOLTZ P.E.
/s/ JOHN. E. NITES P.E.
14 APRIL 2016
14 APRIL 2016
14 APRIL 2016
/s J
O H
N E
N
IT
E S P .E
S O
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N M
A R
K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
SHEET ID
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
®of Engineers
US Army Corps
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
L D
A
G -0
.d g n
-A
P R -2
:3
IP
P
W P :d m s \L
D A
G -0
.d g n h e c n e rl
A
S H
IE
L D
S L
O C
K S A
N D D
A M
P
IT
T S
B U
R G
H D
IS
T R
IC
T
L
IB
E R
T Y A
V E
P
IT
T S
B U
R G
H P
A
O H
IO
R
IV
E R B
A S
IN
H V
A C S
Y S
T E
M R
E P
L A
C E
M E
N T S
E R
V
IC
E B
U
IL
D
IN
G W
W N -1
-T -8
CERTIFIED FINAL DOCUMENTS
A
P R
IL
L E
IS
U
G-0055
L E
IS
U R
E
R T
Y S
Z K
IE
W
IC
Z
C O
N T
R A
C T R
E F
E R
E N
C E D
R A
W
IN
G I
N D
E X
S Y
M B
O L S
A B
B R
E
IV
A T
IO
N S
A N
D G
E N
E R
A L N
O T
E S
DETERMINED.
INSULATION WHERE REQUIRED. THE EXACT LOCATIONS SHALL BE FIELD
PIPE WITH FLEXIBLE CAULKING. SIZE THE DRILL TO ACCOUNT FOR PIPE
CORE DRILL EXTERIOR WALL PENETRATIONS AND SEAL AROUND THE12.
REMOVAL OF PIPING OR EQUIPMENT SHALL BE PATCHED TO MATCH EXISTING.
ANY PORTION OF WALL, FLOOR, AND CEILING DAMAGED DURING11.
CEILING GRID AND LIGHTS.
COORDINATE DIFFUSER AND GRILLE LOCATION WITH EXISTING DROP10.
ROUTE DUCTWORK ABOVE DROP CEILING EXCEPT WHERE INDICATED.9.
HEATER SEE EQUIPMENT SCHEDULE ON M-6004.
FOR REQUIREMENTS OF FURNACE, AIR CONDITIONING UNIT, AND INFRARED 8.
A SLIGHT POSITIVE PRESSURE.
BALANCE SYSTEM TO AIR FLOWS SHOWN WITH OFFICE UNDER7.
IN ELECTRICAL/MECHANICAL ROOM AND GARAGE.
SUPPLY DUCTWORK SHALL BE INSULATED WITH R-5 INSULATION IN6.
SMACNA REQUIREMENTS.
DUCT TO BE GALVANIZED STEEL AND INSTALLED IN ACCORDANCE WITH5.
TERMINATION DISTANCES.
REFER TO MANUFACTURERS INSTRUCTIONS FOR FLUE AND VENT4.
COORDINATE THE FINAL THERMOSTAT LOCATIONS WITH LOCK MASTER.3.
AND SEALED AS PER NFPA 54 AND MANUFACTURER'S RECOMMENDATIONS.
FLUE AND VENT PIPING SHALL BE FLASHED, COUNTER FLASHED,2.
AND SHALL UTILIZE EXISTING HOT WATER HEATING SYSTEM PENETRATIONS.
PIPE ROUTING TO BE COORDINATED WITH EXISTING BUILDING LAYOUT1.
GENERAL NOTES:
T
HOT WATER PIPING FLOW
ELECTRIC VALVE
MANUAL BALANCING DAMPER
MOTORIZED DAMPER
PIPE ELBOW
PIPE TEE
PIPE ELBOW DOWN
DEMOLISH
THERMOSTAT
TURNING VANES
STANDARD BRANCH FOR SUPPLY AND RETURN
WALL SUPPLY GRILLE OR DIFFUSER
CEILING RETURN GRILLE
RETURN DUCT (UP & DOWN)
SUPPLY DUCT (UP & DOWN)
INDEX DRAWINGSREFERENCE
NAMEFILE TITLEDRAWING
O-LDA-0/2.4 DRAWINGS CONTRACT -INDEX
O-LDA-70/1.1 PLANS FLOOR SECOND AND FIRST - BUILDING SERVICE WALLLAND
O-LDA-70/2.1 ELEVATIONS - BUILDING SERVICE WALLLAND
O-LDA-70/3.1 DETAILS AND ELEVATIONS - BUILDING SERVICE WALLLAND
O-LDA-70/4 DETAILS AND SECTIONS - BUILDING SERVICE WALLLAND
O-LDA-70/5.1 DETAILS AND SECTIONS - BUILDING SERVICE WALLLAND
O-LDA-70/6.1 SECTIONS - BUILDING SERVICE WALLLAND
O-LDA-70/7 LEVEL UPPER AT PLAN ROOF - BUILDING SERVICE WALLLAND
O-LDA-70/8 DETAILS AND PLAN FRAMING - BUILDING SERVICE WALLLAND
O-LDA-70/9.1 DETAILS AND FLOOR, GARAGE RAMP, - BUILDING SERVICE WALLLAND
O-LDA-70/10.1 SECTIONS AND REINFORCEMENT WALL - BUILDING SERVICE WALLLAND
O-LDA-70/11 DETAILS AND PLAN HEATING - BUILDING SERVICE WALLLAND
O-LDA-70/12.1 DETAILS AND PLAN PLUMBING - BUILDING SERVICE WALLLAND
INDEX DRAWINGSCONTRACT
NAMEFILE
SHEET
TITLEDRAWING
NO.ID
GENERAL
LDA_100_G-0054 G-0054 COVERSHEET
LDA_100_G-0055 G-0055 NOTES GENERAL & ABBREVIATIONS, SYMBOLS, INDEX, DRAWING REFERENCE &CONTRACT
LDA_100_G-0056 G-0056 LIMITS WORKCONTRACTOR
DEMOLITIONMECHANICAL
LDA_770_MD1001 MD1001 PLANS DEMOLITION BUILDING SERVICE - WALLLAND
MECHANICAL
LDA_770_M-1002 M-1002 PLANS BUILDING SERVICE - WALLLAND
LDA_770_M-3003 M-3003 SECTIONS BUILDING SERVICE - WALLLAND
LDA_770_M-6004 M-6004 SCHEDULES HVAC - WALLLAND
ELECTRICAL
LDA_770_E-1060 E-1060 PLAN BUILDING SERVICE - WALLLAND
ABBREVIATIONS
AMPA, AMPERE
AC CONDITIONINGAIR
ACU UNIT CONDITIONINGAIR
AFUE EFFICIENCY UTILIZATION FUELANNUAL
AHU UNIT HANDLINGAIR
AIH HOUSING INTAKEAIR
APPROX. APPROXIMATELY
AWG GAUGE WIREAMERICAN
BTU UNIT THERMALBRITISH
C CONDUIT
CFM MINUTE PER FEETCUBIC
CMU UNIT MASONRYCONCRETE
COP PREFORMANCE OFCOEFFICIENT
CU UNITCONDENSING
DB BULBDRY
DIA DIAMETER
DWG DRAWING
EER RATIO EFFICIENCYENERGY
EF FANEXHAUST
ELEC ELECTRICAL
EX EXISTING
F FAHRENHEIT
FAF FURANCE AIRFORCED
GRDG, GROUND
GAL GALLON
GALV GALVANIZED
HP HORSEPOWER
HR HOUR
HVAC CONDITIONING AIR & VENTILATION,HEATING,
HZ HERTZ
IN INCH
IRH HEATER RADIANTINFRARED
LAT TEMPERATURE AIRLEAVING
LP PETROLEUMLIQUID
MAT TEMPERATURE AIRMIXED
MBH HOUR PER BTU'STHOUSAND
MECH MECHANICAL
NFPA ASSOCIATION PROTECTION FIRENATIONAL
OA AIROUTSIDE
OP BLADEOPPOSED
P POLE
PH PHASE
RA AIRRETURN
RG GRILLERETURN
SA AIRSUPPLY
SCH SCHEDULE
SD DIFFUSERSUPPLY
SEER RATIO EFFICIENCY ENERGYSEASONAL
SG GRILLESUPPLY
SMACNA
ASSOCIATIONNATIONAL
CONTRACTORS CONDITIONING AIR AND METALSHEET
FTSQ FEET/FOOTSQUARE
STA STATION
STD STANDARD
TYP TYPICAL
UH HEATERUNIT
V VOLTS
VFD DRIVE FREQUENCYVARIABLE
VOIP PROTOCOL INTERNET OVERVOICE
W WATTS
WC COLUMNWATER
WB BULBWET
/s J
O H
N E
N
IT
E S P .E
S O
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N M
A R
K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
SHEET ID
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
®of Engineers
US Army Corps
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
A
G -0
.d g n
-A
P R -2
:3
IP
P
W P :d m s \L
D A
G -0
.d g n h e c n
S H
IE
L D
S L
O C
K S A
N D D
A M
P
IT
T S
B U
R G
H D
IS
T R
IC
T
L
IB
E R
T Y A
V E
P
IT
T S
B U
R G
H P
A
O H
IO
R
IV
E R B
A S
IN
H V
A C S
Y S
T E
M R
E P
L A
C E
M E
N T S
E R
V
IC
E B
U
IL
D
IN
G W
W N -1
-T -8
CERTIFIED FINAL DOCUMENTS
A
P R
IL
SYMBOLS:
BUILDING
LAND WALL SERVICE
STEEL DECKING
CONTRACTOR WORK LIMITS
120'0 60'
SCALE: 1"=60'
ESPLANADE
C R
O S
S O
V E
R
O V
E R
C R
O S
S
RIVER WALL
MIDDLE WALL
UPPER GUARD WALL LOWER GUARD WALL
UPPER GUIDE WALL
LAND WALL
D A
M
FLOW
FLOW
S T
A
.3
A
S T
A
.8
A
LOWER GUIDE WALL
LOWER GUARD WALL
S T
A
.2
B
M A
T
H
IN
E
B
L O
W
M A
T
H
E
O V
E
S T
A
.2
A
S T
A
.9
B
S T
A
.3
L
IC
H T
Y
E L E
IS
U
G-0056
S T
A
.0
A
S T
A
.0
A
S T
A
.0
B
S T
A
.4
T
Y S
Z K
IE
W
IC
Z
N
SCALE: 1"=60'
CONTRACTOR WORK LIMITS
C O
N T
R A
C T
O R W
O R
K L
IM
IT
S
/s J
O H
N E
N
IT
E S P .E
S O
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N M
A R
K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
SHEET ID
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
®of Engineers
US Army Corps
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
A
G -0
.d g n
-A
P R -2
:3
IP
P
W P :d m s \L
D A
G -0
.d g n h e c n
S H
IE
L D
S L
O C
K S A
N D D
A M
P
IT
T S
B U
R G
H D
IS
T R
IC
T
L
IB
E R
T Y A
V E
P
IT
T S
B U
R G
H P
A
O H
IO
R
IV
E R B
A S
IN
H V
A C S
Y S
T E
M R
E P
L A
C E
M E
N T S
E R
V
IC
E B
U
IL
D
IN
G W
W N -1
-T -8
CERTIFIED FINAL DOCUMENTS
A
P R
IL
ROOM
LOCKER
WOMEN'S
EF-2
EF-3
EF-1
EXISTING 3‚" X 10" DUCT (TYP)
WALL CAP (TYP)
ƒ"
1•" ƒ" ƒ"
1‚"
1•" ƒ" ƒ"
1‚"
1•"
1" 1‚"
WATER PIPING (TYP)
REMOVE EXISTING HOT
LOCATIONS)
(TYP FOR 6
ELECTRIC VALVES
REMOVE EXISTING
AND ASSOCIATED DUCTWORK
REMOVE EXISTING UH-5
DUCTWORK
UH-4 AND ASSOCIATED
REMOVE EXISTING
DUCTWORK
UH-3 AND ASSOCIATED
REMOVE EXISTING
HEATER (TYP)
REMOVE EXISTING BASEBOARD
EXISTING WALKWAY
CORRIDOR
THERMOSTAT
REMOVE EXISTING
THERMOSTAT
REMOVE EXISTING
THERMOSTAT
REMOVE EXISTING
EXISTING BOILER
REMOVE AND SALVAGE
L
IC
H T
Y
E L E
IS
U
MD1001
A
N D W
A L L S
E R
V
IC
E B
U
IL
D
IN
G
FIRST FLOOR
SECOND FLOOR
0 4' 8' 12'
SCALE: ‰"=1'
WORKSHOP
MEN'S LOCKER
OFFICE
MASTERS
LOCKER
RESTROOM
OFFICE
ROOM
MECH
ELEC/
T
TT
EF-4
D E
M O
L
IT
IO
N P
L A
N
SCALE: ‰"=1'-0"
HVAC - LAND WALL SERVICE BUILDING DEMOLITION PLAN
UH-2
EXISTING
REMOVE
UH-1
EXISTING
REMOVE
UNIT AND BASEBOARD HEATERS.
REMOVE THERMOSTATS ASSOCIATED WITH EXISTING2.
ASSOCIATED WITH THE HOT WATER HEATING SYSTEM.
DEMOLISH ALL HOT WATER PIPING AND EQUIPMENT1.
NOTES:
T
T
J L
O W
E
N
M E
C H
A N
IC
A L
/s J
O H
N E
N
IT
E S P .E
S O
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N M
A R
K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
SHEET ID
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
®of Engineers
US Army Corps
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
A
M D
.d g n
-A
P R -2
:3
IP
P
W P :d m s \L
D A
M D
.d g n h e c n
S H
IE
L D
S L
O C
K S A
N D D
A M
P
IT
T S
B U
R G
H D
IS
T R
IC
T
L
IB
E R
T Y A
V E
P
IT
T S
B U
R G
H P
A
O H
IO
R
IV
E R B
A S
IN
H V
A C S
Y S
T E
M R
E P
L A
C E
M E
N T S
E R
V
IC
E B
U
IL
D
IN
G W
W N -1
-T -8
CERTIFIED FINAL DOCUMENTS
A
P R
IL
30'-0"±
PROPANE TANK
NEW 500 GALLON
CORRIDOR
ROOM
ELEC/MECH
14"X10"
ROOF
NEW FLUE UP THROUGH
HEATER
TO INFRARED
NEW THERMOSTAT
12"X8"
20 CFM
SD-1
185 CFM
SG-1
(TYP 2)
180 CFM
RG-2
CFM
RG-3
200 CFM
SD-2
120 CFM
SD-1
120 CFM
RG-2
(TYP 2)
240 CFM
RG-3
(TYP 2)
240 CFM
SG-2
305 CFM
SD-3
305 CFM
SD-3
305 CFM
RG-3
130 CFM
SG-1
20 CFM
SD-1
130 CFM
RG-2
305 CFM
RG-3
6'-0" ABOVE GRADE
EXISTING STEEL DECKING
OF CONCRETE GUTTER
PIPING ALONG WALL
RUN HORIZONTAL GAS
FROM ELEVATED RAMP
SUPPORT PIPING WITH PIPE HANGERS
20 CFM
RG-1
14"X10" DOWN
18"X10" DOWN
20"X16"
12"X8" DOWN
CONCRETE GUTTER
DOWN TO
DECKING HEIGHT
PIPE DROP FROM
EXISTING WALKWAY
NEW MOTORIZED DAMPER
TO FURNACE
NEW THERMOSTAT
10"X8"
NEW FURNACE
EXISTING WALKWAY ON SECOND FLOOR
HEATER
NEW INFRARED
18"X10" UP
14"X10" UP
GARAGE STORAGE SHELF
ROUTE DUCT ABOVE
10"X8"
10"X6"
FROM ELEC/MECH ROOM
FOR NEW DUCTWORK
CREATE OPENING IN CMU
20 CFM
RG-1
180 CFM
SG-1
PIPE
NEW •" SCH 40 STEEL
STEEL PIPE
NEW •" SCH 40
VENT DETAIL M-3003.
THROUGH ROOF SEE RADIANT HEATER
NEW AC UNIT
WALL
PIPES TO
REFRIGERANT
SECURE NEW
ROUTE PIPE UP TO ELEVATED RAMP
12"X8" UP
L
IC
H T
Y
E L E
IS
U
M-1002
A
N D W
A L L S
E R
V
IC
E B
U
IL
D
IN
G
FIRST FLOOR
SECOND FLOOR
WORKSHOPROOM
MEN'S LOCKER
OFFICE
MASTERS
LOCKER
RESTROOM
OFFICE
P L
A N
S
A M-3003
12"X10"
10"X10" x
X
12"X8"
14"X10"
X
14"X10" 10"X10"
T
T
10"X10"
ROOM
LOCKER
WOMEN'S
SCALE: ‰"=1'-0"
HVAC - LAND WALL SERVICE BUILDING PLANS
ROOM
STORAGE
OFFICE
ROOM
CONFERENCE
ROOM
BREAK
10"X8"
10"X8"
J L
O W
E
M
IN
N
REFERENCE SCHEDULE ON M-6004.6.
DUCT AS REQUIRED.
PROVIDE LINTEL OR STRUCTURALLY REINFORCED5.
SYSTEM.
PENETRATIONS USED FOR HOT WATER HEATING
GAS PIPING SHALL BE ROUTED THROUGH EXISTING4.
FIELD DETERMINED.
CONDUIT AND PIPING. EXACT LOCATIONS SHALL BE
COORDINATE WALL PENETRATIONS WITH EXISTING3.
WALL.
ROUTE DUCT UP THROUGH VOIP ROOM ALONG2.
OF PLYWOOD FLOOR.
ROUTE DUCT RISER THROUGH EXISTING SECTION1.
NOTES:
B M-3003
M E
C H
A N
IC
A L
/s J
O H
N E
N
IT
E S P .E
S O
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N M
A R
K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
SHEET ID
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
®of Engineers
US Army Corps
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
A
M -1
.d g n
-A
P R -2
:3
IP
P
W P :d m s \L
D A
M -1
.d g n h e c n
S H
IE
L D
S L
O C
K S A
N D D
A M
P
IT
T S
B U
R G
H D
IS
T R
IC
T
L
IB
E R
T Y A
V E
P
IT
T S
B U
R G
H P
A
O H
IO
R
IV
E R B
A S
IN
H V
A C S
Y S
T E
M R
E P
L A
C E
M E
N T S
E R
V
IC
E B
U
IL
D
IN
G W
W N -1
-T -8
CERTIFIED FINAL DOCUMENTS
A
P R
IL
VENT CAP
ROOF
NEW REFRIGERANT LINES
EXISTING HOT WATER HEATER
NEW INDOOR COOLING COIL 185 CFM
SG-1
(TYP 2)
240 CFM
RG-3
12"X8"
(TYP 2)
240 CFM
SG-2
ROOM
MECHANICAL
ELECTRICAL/
20"X16"
MOTORIZED DAMPER
NEW FURANCE
LOUVER/DAMPER
NEW COMBINATION
NEW AC UNIT
NEW PIPE PENETRATION
PAD
CONCRETE
WATER HEATER
EXISTING HOT
NEW FURNACE
COIL
NEW INDOOR COOLING
DUCT
NEW SUPPLY
(TYP 2)
240 CFM
SG-2
14"X10"
NEW RETURN DUCT
FLASHING
L
IC
H T
Y
E L E
IS
U
N D W
A L L S
E R
V
IC
E B
U
IL
D
M-1002
SECTION
SCALE: …"=1'-0"
S E
C T
IO
N S
A M-1002
SECTION
SCALE: …"=1'-0"
0 2' 4' 6'
SCALE: …"=1'
ROOM
MECHANICAL
ELECTRICAL/
CORRIDOR
OFFICE
LOCK MASTERS
OFFICE
LOCK MASTERS
X
18"X16"
12"X8"
X
X
18"X16"
X
SCALE: NONE
RADIANT HEATER VENT DETAIL
SHALL NOT BE LESS THAN 1 SQ FT.
AND EQUIPPED WITH INSECT SCREEN. FREE AREA
NEW INTAKE LOUVER/DAMPER SHALL BE MOTORIZED2.
NFPA 54 & MANUFACTURERS RECOMMENDATIONS.
COUNTER FLASHED, & SEALED AS PER
FLUE & VENT PIPING SHALL BE FLASHED1.
NOTES:
INTAKE
J L
O W
E
18"X16"
M E
C H
A N
IC
A L
/s J
O H
N E
N
IT
E S P .E
S O
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N M
A R
K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
SHEET ID
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
®of Engineers
US Army Corps
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
A
M -3
.d g n
-A
P R -2
:3
IP
P
W P :d m s \L
D A
M -3
.d g n h e c n
S H
IE
L D
S L
O C
K S A
N D D
A M
P
IT
T S
B U
R G
H D
IS
T R
IC
T
L
IB
E R
T Y A
V E
P
IT
T S
B U
R G
H P
A
O H
IO
R
IV
E R B
A S
IN
H V
A C S
Y S
T E
M R
E P
L A
C E
M E
N T S
E R
V
IC
E B
U
IL
D
IN
G W
W N -1
-T -8
CERTIFIED FINAL DOCUMENTS
A
P R
IL
L
IC
H T
Y
E L E
IS
U
M-6004
UNIT SHALL BE COMPATIBLE WITH LP GAS.3.
HIGH AND LOW FIRE CONTROL OPTION.
UNIT SHALL HAVE A TWO STAGE MODULATING INPUT WITH2.
HEIGHTS AND PITCH.
FOLLOW MANUFACTURERS RECOMMENDATIONS FOR MOUNTING1.
NOTES:
DIFFUSERS AND GRILLES SHALL BE STEEL.2.
WITHOUT SPECIAL TOOLS FROM THE BOTTOM OF THE DIFFUSER.
PROVIDE ADJUSTABLE DAMPER FOR SUPPLY DIFFUSER/GRILLE. DAMPER SHALL BE ADJUSTABLE1.
NOTES:
J L
O W
E
PROVIDE A 7-DAY PROGRAMMABLE THERMOSTAT.5.
SHALL SHUT DOWN FURNACE FAN UPON DETECTION OF SMOKE.
PROVIDE SMOKE DETECTOR ON RETURN PLENUM. SYSTEM4.
UNOCCUPIED MODE.
CONTROLS SHALL CLOSE DAMPER WHEN THE UNIT IS IN
CONNECT EXISTING OUTSIDE AIR DAMPER TO FURNACE CONTROLS.3.
LAT = COIL LEAVING AIR TEMPERATURE.
MAT = MIXED AIR TEMPERATURE ENTERING COIL;2.
AND SHALL BE OF THE SAME MANUFACTURER
FURNACE SHALL BE COMPATIBLE WITH THE AIR CONDITIONING UNIT1.
NOTES:
M E
C H
A N
C A
L
H V
A C S
C H
E D
U L E
S
SCHEDULE FURNACE(FAF) AIRFORCED
LOADCOOLING MAT LAT LOADHEATING ELECTRICAL FAN AIROUTDOOR
NAME
BTU/HR
TON
BTU/HR
AFUE V PH HZ
CFM WCIN
CFM
TOTAL SENSIBLE DW/WB DW/WB NET AIRFLOW PRESSURE
FAF-1 55,000 38,000 5 76/63 54/54 85,000 95% 120 1 60 2,000 0.50 475
SCHEDULE GRILLE &DIFFUSER
NAME RANGECFM SIZE TYPE MODEL REMARKS
SD-1 10-74 6"x4" LAY-IN WAY TWODIFFUSER, SERIES 250 TITUS TOSIMILAR
SD-2 75-199 10"x6" LAY-IN WAY TWODIFFUSER, SERIES 250 TITUS TOSIMILAR
SD-3 200-325 10"x10" LAY-IN WAY TWODIFFUSER, SERIES 250 TITUS TOSIMILAR
SG-1 75-199 8"x6" LAY-IN DEFLECTION DOUBLEGRILLE, SERIES 300/350 TITUS TOSIMILAR
SG-2 200-325 12"x6" LAY-IN DEFLECTION DOUBLEGRILLE, SERIES 300/350 TITUS TOSIMILAR
RG-1 10-74 6"x6" LAY-IN GRILLE SERIES 300/350 TITUS TOSIMILAR
RG-2 75-199 10"x6" LAY-IN GRILLE SERIES 300/350 TITUS TOSIMILAR
RG-3 200-325 12"x8" LAY-IN GRILLE SERIES 300/350 TITUS TOSIMILAR
SCHEDULE (IRH) HEATER RADIANTINFRARED
NAME OUTPUT
HEATING
ELECTRICAL
REMARKS
BTU/HR V PH HZ
IRH-1 40,000 120 1 60 LTU RAY SPACE TOSIMILAR
/s J
O H
N E
N
IT
E S P .E
S O
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N M
A R
K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
SHEET ID
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
®of Engineers
US Army Corps
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
A
M -6
.d g n
-A
P R -2
:3
IP
P
W P :d m s \L
D A
M -6
.d g n h e c n
S H
IE
L D
S L
O C
K S A
N D D
A M
P
IT
T S
B U
R G
H D
IS
T R
IC
T
L
IB
E R
T Y A
V E
P
IT
T S
B U
R G
H P
A
O H
IO
R
IV
E R B
A S
IN
H V
A C S
Y S
T E
M R
E P
L A
C E
M E
N T S
E R
V
IC
E B
U
IL
D
IN
G W
W N -1
-T -8
CERTIFIED FINAL DOCUMENTS
A
P R
IL
REFRIGERANT UTILIZED SHALL BE R-410A.4.
PROVIDE NEW KILL SWITCH FOR AIR CONDITIONING UNIT.3.
2.
AND SHALL BE OF THE SAME MANUFACTURER.
AC UNIT SHALL BE COMPATIBLE WITH THE FURNACE1.
NOTES:
SCHEDULE (ACU) UNIT CONDITIONINGAIR
NAME TON
ELECTRICAL
SEER EER
V PH HZ
AC-1 5 208 3 60 13.0 11.0
EXISTING WALKWAY ON SECOND FLOOR
EXISTING LIGHTING PANEL G
NEMA 3R
30A, 240V, 3P, NON-FUSED,
HEAVY DUTY SAFETY SWITCH
2 #12, #12 GRD, EXISTING CONDUIT
3#12, #12 GRD, ƒ" C 2#12, #12 GRD, ƒ"C
LIGHTING PANEL G
20A CIRCUIT BREAKER IN
FURNACE WILL USE EXISTING
NEW AC UNIT
NEW INFRARED HEATER
LIGHTING PANEL
EXISTING 208/120VAC GARAGE
M
M
IL
L E
R
E L E
IS
U
E-1060
A
N D W
A L L S
E R
V
IC
E B
U
IL
D
IN
G
FIRST FLOOR
WORKSHOP
MEN'S LOCKER
P L
A N
ROOM
LOCKER
WOMEN'S
ROOM
STORAGE
SCALE: ‰"=1'-0"
HVAC - LAND WALL SERVICE BUILDING PLAN
E L E
C T
R
IC
A L
CORRIDOR
ROOM
MECH
ELEC/
FOR SQUARE D NQOD PANEL
WILL NEED NEW SINGLE POLE 20A CIRCUIT BREAKER
BREAKER FOR A SQUARE D NQOD PANEL. HEATER
CONDENSER WILL NEED NEW 3 POLE, 20A CIRCUIT1.
NOTES:
J
O S
T R
O S
K Y
N
/s J
O H
N E
N
IT
E S P .E
S O
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N M
A R
K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
SHEET ID
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
®of Engineers
US Army Corps
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
A E -1
.d g n
-A
P R -2
:4
IP
P
W P :d m s \L
D A E -1
.d g n h e c n
S H
IE
L D
S L
O C
K S A
N D D
A M
P
IT
T S
B U
R G
H D
IS
T R
IC
T
L
IB
E R
T Y A
V E
P
IT
T S
B U
R G
H P
A
O H
IO
R
IV
E R B
A S
IN
H V
A C S
Y S
T E
M R
E P
L A
C E
M E
N T S
E R
V
IC
E B
U
IL
D
IN
G W
W N -1
-T -8
CERTIFIED FINAL DOCUMENTS
A
P R
IL
| LDA_100_G-0054 |
| LDA_100_G-0055 |
| LDA_204_G-0056 |
| LDA_770_MD1001 |
| LDA_770_M-1002 |
| LDA_770_M-3003 |
| LDA_770_M-6004 |
| LDA_770_E-1060 |
| Reference Drawings |
| O-LDA_0-2.4 |
| O-LDA_70-1.1 |
| O-LDA_70-2.1 |
| O-LDA_70-3.1 |
| O-LDA_70-4 |
| O-LDA_70-5.1 |
| O-LDA_70-6.1 |
| O-LDA_70-7 |
| O-LDA_70-8 |
| O-LDA_70-9.1 |
| O-LDA_70-10.1 |
| O-LDA_70-11 |
| O-LDA_70-12.1 |
File details come from the government source that posted it. Updated .