This document consists of a set of Questions and Answers related to the Request for Information (RFI) for Solicitation W911SG24B0003 for the B1789 Vehicle Exhaust System Repair project. The key details are:

The solicitation is for a construction project to provide repairs to the vehicle exhaust system at the White Sands Missile Range in New Mexico. The contractor will be required to provide all labor, materials, equipment, and transportation necessary to complete the work. The contract will be a Firm-Fixed Price (FFP) with an anticipated delivery of 90 days after the Notice to Proceed. The procurement is set aside for 100% Small Business and the NAICS code is 238220. The magnitude of the contract is between $100,000 and $250,000. The questions and answers address topics such as asbestos testing, availability of the work area, electrical panel replacement, and other project-specific details. An organized site visit will be conducted as part of the solicitation process.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

W911SG24B0003 B1789 Vehicle Exhaust System Repair

RFIs and Answers

1) Are we providing a quote for testing of ACM?

Answer: Yes.

2) When are we going to get the pictures of the electrical panels?

Answer: Pictures are posted on SAM.gov.

3) Are we going to have the bay available for the entire task?

Answer: Yes.

4) If the areas are clear, are we going to have to wait for the modification to take place or are we going to be able to proceed while the modification of funds get revised?

Answer: If the test comes out negative for asbestos, the contractor will not have to wait for the modification to continue working. The modification will be provided at a later time shortly after notifying COR and MICC about the negative results.

5) Sheet 06 Drawing indicate to inspect existing circuit breaker and circuitry supplying the fan motor. As per the recent site visit, it was observed that the fan motors disconnect, and other loads were being served by the tapping of the main lugs in the Bldgs, Main

Disconnect. We suspect this was due to there being no available space in the existing

100Amp panel. Please advise if it is the intent to replace the existing electrical panel to add additional space for the new exhaust system circuit.

Answer: Yes, replace existing electrical panel.