DWG B1789 EXHAUST SYSTEM.pdf
PDF 2 MB Posted
- Attached to
- B1789 Vehicle Exhaust System Repair
- Solicitation number
- W911SG24B0003
About this file
This document is a set of engineering drawings and specifications related to a federal construction solicitation for repairing the vehicle exhaust system at Building 1789 at White Sands Missile Range in New Mexico.
The solicitation, numbered W911SG-24-B-0003, is being issued by the Mission and Installation Contracting Command (MICC) at Fort Bliss, Texas on behalf of the Directorate of Public Works at White Sands Missile Range. The work includes demolishing the existing vehicle exhaust extraction system and installing a new system with a motor-fan assembly, flex hoses, ductwork, and controls. Key requirements are that the new system must provide airflow of at least 500 CFM and 850 CFM at the specified nozzles, and use components from the Plymovent manufacturer or equivalent. The contract will be a Firm-Fixed Price with a 90-day period of performance after the Notice to Proceed. The procurement is set aside for small businesses under NAICS code 238220 with a size standard of $19.0M. An organized site visit will be held for interested offerors.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGNED
CHIEF, ENGINEERING DIVISION
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
NTS
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-01789-2023-G-G1-01
COVER SHEET
AND INDEX
05/01/24
BWE
MONICA TORRES
JAMES NUNEZ
01 06
ROBERT LOPEZ III
ISSUED
FOR
CONSTRUCTION
BUILDING 1789
SHEET INDEX
DRAWING NUMBER TITLE
WS-1789-2023-G-GI-01 COVER SHEET/INDEX SHEET
WS-1789-2023-G-PL-02 B1789 PROJECT LOCATION
WS-1789-2023-G-100-03 B1789 GENERAL NOTES
WS-1789-2023-M-MD-04 B1789 EXHAUST SYSTEM DEMOLITION PLAN
WS-1789-2023-M-MH-05 B1789 EXHAUST SYSTEM REPAIR PLAN
WS-1789-2023-E-DT-06 B1789 EXHAUST SYSTEM ELECTRICAL
VEHICLE EXHAUST SYSTEM REPAIR
AutoCAD SHX Text
ARCH D
AutoCAD SHX Text
WHITE SANDS MISSILE RANGE, NEW MEXICO
AutoCAD SHX Text
DIRECTORATE OF PUBLIC WORKS
AutoCAD SHX Text
ENGINEERING DIVISION
AutoCAD SHX Text W
AutoCAD SHX Text H
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text B
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text T
AutoCAD SHX Text I
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text Y
LOCATION
CHIEF, ENGINEERING DIVISION
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
NTS
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-01789-2023-G-GI-02
B1789
PROJECT LOCATION
05/01/24
ARCH D
BWE
MONICA TORRES
JAMES NUNEZ
02 06
ROBERT LOPEZ III
PROJECT LOCATION B01789
32°22'41"N, 106°28'32"W
B01789 GSA SERVICE SHOP
ISSUED
FOR
CONSTRUCTION
CHIEF, ENGINEERING DIVISION
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
NTS
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-01789-2023-G-GI-03
B1789
VEHICLE EXHAUST SYSTEM
GENERAL NOTES
05/01/24
ARCH D
BWE
MONICA TORRES
JAMES NUNEZ
03 06
ROBERT LOPEZ III
ISS
UE
D
FO
R
CO
NS
TRU
CTI
ON
GENERAL NOTES-
1. CONTRACTOR PERSONNEL ACCESS TO EACH SITE REQUIRES APPROVAL FROM THE WSMR
SECURITY OFFICE AND COMPLY WITH THE REQUIREMENTS OF THE WHITE SANDS MISSILE
RANGE VISITOR/ACCESS CONTROL POLICY (04JUNE2021).
2. THE CONTRACTOR SHALL COORDINATE ALL ACTIVITIES WITH THE CONTRACTING OFFICER'S
REPRESENTATIVE (C.O.R.). NO CONSTRUCTION WORK SHALL BE ACCOMPLISHED WITHOUT AN
APPROVED CONSTRUCTION SCHEDULE. THE CONTRACTOR SHALL NOTIFY THE C.O.R. OF THE
SCHEDULED OUTAGES 72 HOURS IN ADVANCE.
3. CONTRACTOR SHALL COORDINATE ALL WORK WITH EXISTING CONDITIONS AND CONSTRUCTION
DRAWINGS. CONTRACTOR SHALL PROVIDE ALL EQUIPMENT, MATERIAL AND LABOR AS
REQUIRED FOR COMPLETE FUNCTIONAL SYSTEMS.
4. CONTRACTOR SHALL NOTIFY AND COORDINATE WITH C.O.R. FOR ANY FORKLIFT OR SCISSOR
LIFT USE AT THE SITE WHICH MIGHT BE NEEDED TO REMOVE/INSTALL EXHAUST SYSTEM
DUCTWORK, MOTOR-FAN ASSEMBLY OR COMPONENTS. CONTRACTOR SHALL BARRICADE
HAZARDOUS OPERATIONS AREAS.
5. ALL MATERIALS AND EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S
PUBLISHED RECOMMENDATIONS, CONTRACT DOCUMENTS, INDUSTRY STANDARDS AND ALL
FEDERAL, STATE AND LOCAL CODES AND AMENDMENTS AS ADOPTED BY THE GOVERNMENT FOR
SERVICE INTENDED BY THE CONTRACTING OFFICER (KO). THE INSTALL OF ALL MATERIALS AND
EQUIPMENT SHALL BE MADE BY EXPERIENCED AND LICENSED CRAFTSMAN IN A NEAT WORKMAN
LIKE MANNER, ALL MATERIALS, SUPERVISION, LABOR, TOOL, COST AND SERVICES NECESSARY
TO COMPLETELY INSTALL A FUNCTIONAL SYSTEM SHALL BE FURNISHED BY THE CONTRACTOR.
6. THE TERM "PROVIDE" USED IN THE DRAWINGS AND SCOPE OF WORK IMPLIES THE CONTRACTOR
IS TO FURNISH, TRANSPORT, INSTALL, CONNECT, WARRANT, AND START-UP, INCLUSIVELY.
7. THE DRAWINGS ARE DIAGRAMMATIC ONLY BUT SHALL BE FOLLOWED AS CLOSELY AS ACTUAL
CONSTRUCTION CONDITIONS AND WORK OF OTHER TRADES PERMIT. THE DIMENSIONS ARE FOR
REFERENCE AND THE CONTRACTOR SHALL FIELD VERIFY ALL NECESSARY DIMENSIONS
REQUIRED TO PERFORM THE SCOPE OF WORK.
8. CONTRACTOR SHALL REPORT DISCREPANCIES BETWEEN FIELD CONDITIONS AND NEW
CONSTRUCTION DRAWINGS TO THE KO IN WRITING BEFORE THE RFI DEADLINE DURING THE
SOLICITATION PHASE, PRIOR TO PROVIDING THEIR BID.
9. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING STRUCTURE, EQUIPMENT AND UTILITIES
WITHIN THE FACILITY TO ACCOMMODATE THE SYSTEM REPAIRS PRIOR TO THE START OF WORK.
10. CONTRACTOR SHALL PROTECT EXISTING STRUCTURE, EQUIPMENT AND UTILITIES WITHIN THE
FACILITY TO ENSURE NO DAMAGE DURING DEMOLITION AND NEW CONSTRUCTION. ANY DAMAGE
THAT IS DONE SHALL BE REPAIRED TO PRIOR CONDITION AND MATCH EXISTING.
11. UPON COMPLETION OF WORK, CONTRACTOR SHALL PROVIDE WITHIN 10 DAYS,
MANUFACTURER'S OPERATING & MAINTENANCE MANUAL FOR ALL EQUIPMENT INCLUDING
REPLACEMENT PARTS LIST PER SOW 8.8.
12. THE CONTRACTOR SHALL TRANSPORT AND DISPOSE OF ANY CONSTRUCTION WASTE AND
DEBRIS TO AN OFF-SITE SOLID WASTE COLLECTION CENTER THAT HAS BEEN PERMITTED, BY
THE JURISDICTION HAVING AUTHORITY TO ACCEPT AND DISPOSE OF CONSTRUCTION WASTE
AND DEBRIS.
13. WHILE PERFORMING WORK, THE CONTRACTOR SHALL ENSURE THAT PERSONNEL USE
PERSONAL PROTECTIVE EQUIPMENT (PPE) TO AVOID INJURY.
HAZARDOUS MATERIAL TESTING AND ABATEMENT
14. PRIOR TO PERFORMING WORK CONTRACTOR SHALL PERFORM HAZARDOUS BUILDING
MATERIALS SAMPLING OF ALL BUILDING MATERIALS THAT WILL BE DISTURBED IN AREAS
WORKED. TESTING SHALL BE PER SOW PART 10-HAZARDOUS BUILDING MATERIALS ABATEMENT,
CONTRACTOR SHALL FOLLOW GUIDELINES.
15. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ABATING ALL HAZARDOUS BUILDING MATERIALS
FOUND IN THE WORK AREA. ABATEMENT OF HAZARDOUS MATERIALS (INCLUDING ASBESTOS
CONTAINING MATERIAL (ACM), LEAD BASED PAINT (LBP), OR MOLD SHALL TAKE PLACE PRIOR TO
PERFORMING OTHER WORK OF THE PROJECT.
ELECTRICAL WORK
16. PRIOR TO PERFORMING WORK ENSURE THAT ELECTRICAL ENERGY SOURCES TO EFFECTED
SYSTEM HAS BEEN SECURED AND LOCKED OUT/TAGGED OUT (LOTO).
17. CERTIFIED ELECTRICIAN SHALL INSPECT EXISTING WIRING TYPE AND SIZE AND CIRCUIT
BREAKER RATING TO ENSURE THEY MEETS THE REQUIREMENTS FOR NEW MOTORS AND
CONTROLLERS PER NEC. FOR HIGHER RATED WIRING, THE ELECTRICIAN SHALL REMOVE
EXISTING WIRING TO THE EXTENT NEEDED AND INSTALL REQUIRED 600 VOLT, THHN COPPER
STRANDED ELECTRICAL CONDUCTOR. FOR HIGHER RATED CIRCUIT BREAKER, ELECTRICIAN
SHALL ENSURE THAT THE NEW CIRCUIT BREAKER DOES NOT UNBALANCE THE PANEL. ALL
ELECTRICAL POWER AND CONTROL WIRING SHALL BE ROUTED THROUGH EMT CONDUIT, USING
PROPER CONNECTION METHODS, J-BOXES, NIPPLES, ETC. ALL ELECTRICAL WORK SHALL BE
DONE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE (NEC) 70 AS REVISED.
MECHANICAL WORK
16. THE CONTRACTOR SHALL ENSURE THAT THE VEHICLE EXHAUST SYSTEM IS SIZED TO PRODUCE
A FLOWRATE OF NO LESS THAN 500 CFM AND 850 CFM AT SPECIFIED SYSTEM NOZZLES, WITH
ALL OTHER NOZZLES OPEN AND IN USE. THIS FLOWRATE SHALL BE DEMONSTRATED AND
TESTED FOR COMPLIANCE PRIOR TO FINAL SIGN-OFF AT PROJECT COMPLETION. THE
CONTRACTOR SHALL INCORPORATE SYSTEM DAMPERS AND CONTROLS TO ENSURE PROPER
FLOW DISTRIBUTION.
17. CONTRACTOR SHALL USE THE BASIS-OF-DESIGN FROM 'PLYMOVENT' MANUFACTURER IN ORDER
TO COMPLY WITH ALL THE EXHAUST SYSTEM REQUIREMENTS.
18. WHEN INSTALLING A NEW MOTOR-FAN ASSEMBLY, CAREFULLY DISCONNECT MOTOR AND FAN
ASSEMBLY, MOUNTING FRAME AND HOUSING FROM EXISTING DUCTWORK. DESIGNATED
DUCTWORK AND SUPPORTS MAY REMAIN IN PLACE IF SUITABLE FOR REUSE. THE NEW
MOTOR-FAN ASSEMBLY SHALL BE INSTALLED PER MANUFACTURERS RECOMMENDATIONS BY
LICENSED/CERTIFIED TECHNICIANS. THE UNIT WILL BE INSTALLED WITH VIBRATION ISOLATORS
PER MANUFACTURERS RECOMMENDATIONS.
19. LIGHT DUTY LOCK SEAM HVAC DUCT AND ELBOWS SHALL NOT BE USED IN THE EXHAUST
EXTRACTION SYSTEM DUCTWORK.
20. A SEALANT WILL BE APPLIED TO ALL WALL PENETRATIONS (EITHER DUCTWORK AND CONDUIT)
TO THE EXTERIOR WITH A SEALANT THAT MEETS OR EXCEEDS CHEMLINK HIGH PERFORMANCE
WALL AND BLOCK ADHESIVE.
21. ALL MECHANICAL WORK SHALL BE DONE IN ACCORDANCE WITH INTERNATIONAL MECHANICAL
CODE (IMC) AND SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION
(SMACNA) AS REVISED. NEW DUCTWORK AND ASSOCIATED FITTINGS WILL BE IN ACCORDANCE
WITH SMACNA AND CONFIGURED TO PROVIDE BEST FLOW CONDITIONS WITHIN THE DUCTWORK.
22. THE CONTRACTOR SHALL ENSURE THAT THE ENTIRE EXHAUST SYSTEM DUCTWORK (INTERIOR
AND EXTERIOR) IS FREE OF CONTAMINATION AND DEBRIS.
23. ALL RIGID METAL DUCTWORK SEAMS WILL BE SEALED WITH FLEXIBLE HIGH TEMPERATURE
SEALANT.
24.EXHAUST SYSTEM FLEXHOSES SHALL BE AN ABRASION AND CRUSH RESISTANT HOSE THAT IS
HIGHLY FLEXIBLE MADE FROM HIGH-QUALITY MATERIALS DESIGNED TO WITHSTAND HIGH
TEMPERATURES AS SPECIFIED.
PLAN VIEW
SECTION A-A
DESIGNED
CHIEF, ENGINEERING DIVISION
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
NTS
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-01789-2023-M-MD-04
B1789
VEHICLE EXHAUST SYSTEM
DEMOLITION
05/01/24
ARCH D
BWE
MONICA TORRES
JAMES NUNEZ
04 06
ROBERT LOPEZ III
ISS
UE
D
FO
R
CO
NS
TRU
CTI
ON
GENERAL NOTES-
1. THE EXHAUST SYSTEM DRAWING IS DIAGRAMMATIC ONLY AND DIMENSIONS AND GEOMETRY MAY VARY.
THE SYSTEM HAS A BLOWER ASSEMBLY, CONTROLLER, MULTIPLE FLEX HOSE DOWN DROPS AND A
NOZZLES. THE EXHAUST SYSTEM IS APPROXIMATELY 14 FEET ABOVE FINISH FLOOR.
2. THE CONTRACTOR SHALL ENSURE THAT PRIOR TO REMOVING ANY COMPONENT WHICH HAS
ELECTRICAL CONTROLS AND POWER, THE ELECTRICAL POWER SHALL BE TURNED OFF AND THE
BREAKERS WILL BE LOCKED OUT-TAGGED OUT (LOTO).
3. DURING DEMOLITION AND CONSTRUCTION THE CONTRACTOR SHALL TAKE PRECAUTIONS TO PROTECT AND NOT DISTURB ANY OTHER UTILITIES, EQUIPMENT, PIPING, AND INFRASTRUCTURE IN THE FACILITY.
4. THE CONTRACTOR WILL CAREFULLY DISCONNECT AND DEMOLISH THE VEHICLE EXHAUST EXTRACTION SYSTEM INCLUDING BLOWER MOTOR ASSEMBLY AND CONTROLLER, FLEX HOSES, DUCTWORK, HOSE
SUPPORT CABLES AND PULLEYS, MOUNTING BRACKETS AND HARDWARE. REMOVE WIRING AND
CONDUIT BACK TO EACH BLOWER MOTOR CONTROLLER. REMOVE WALL PENETRATION DUCTWORK,
UNBOLT AND DEMOLITION EACH BLOWER ASSEMBLY.
5. THE STEEL ANGLE SUPPORT STRUCTURE FOR THE BLOWER THAT IS BOLTED TO THE WALL WILL BE REUSED TO THE GREATEST EXTENT POSSIBLE. USE CARE SO THAT BOLTED CONNECTIONS OF THE
FRAME TO THE WALL ARE NOT DAMAGED.
6. THE CONTRACTOR WILL ENSURE THAT DURING CONSTRUCTION ANY WALL OPENINGS DUE TO
DEMOLITION ARE COVERED AND SECURED WITH TEMPORARY COVERS TO PROTECT AGAINST
INTRUSION AND INCLEMENT WEATHER.
7. THE CONTRACTOR SHALL TRANSPORT AND DISPOSE OF CONSTRUCTION WASTE AND DEBRIS TO AN OFF-SITE SOLID WASTE COLLECTION CENTER THAT HAS BEEN PERMITTED, BY THE JURISDICTION
HAVING AUTHORITY TO ACCEPT AND DISPOSE OF CONSTRUCTION WASTE AND DEBRIS.
AutoCAD SHX Text
ELECTRICAL PANELS
AutoCAD SHX Text
ROLL UP
AutoCAD SHX Text
BAY DOOR
AutoCAD SHX Text
ROOF
AutoCAD SHX Text 14'
AutoCAD SHX Text 16'-8"
AutoCAD SHX Text 59'-9"
AutoCAD SHX Text 39'-2"
AutoCAD SHX Text
CONCRETE APRON
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
MOTOR-FAN ASSEMBLY
AutoCAD SHX Text
EXHAUST STACK
AutoCAD SHX Text
METAL DUCTWORK
AutoCAD SHX Text
EXHAUST HOSE
AutoCAD SHX Text
AND NOZZLE
AutoCAD SHX Text
AND MOUNTING PLATE
AutoCAD SHX Text
(TYP. 3 PLACES)
AutoCAD SHX Text
SUSPENDED
AutoCAD SHX Text
CONCRETE FLOOR
AutoCAD SHX Text
METAL DUCTWORK
AutoCAD SHX Text
SUSPENDED
AutoCAD SHX Text
BLOWER ASSEMBLY
AutoCAD SHX Text
AND MOUNTING PLATE
AutoCAD SHX Text
EXHAUST HOSE
AutoCAD SHX Text
AND NOZZLE
AutoCAD SHX Text
(TYP. 3 PLACES)
AutoCAD SHX Text 15'-3"
AutoCAD SHX Text 14'-7"
AutoCAD SHX Text 14'-7"
AutoCAD SHX Text
ROLL UP
AutoCAD SHX Text
BAY DOOR
AutoCAD SHX Text
ROLL UP
AutoCAD SHX Text
BAY DOOR
AutoCAD SHX Text
ROLL UP
AutoCAD SHX Text
BAY DOOR
AutoCAD SHX Text
ALL-THREAD ROD
AutoCAD SHX Text
THRU BOLTS
AutoCAD SHX Text
& STL PLATE
AutoCAD SHX Text
ROOF FLASHING
AutoCAD SHX Text
ROOF JOIST
AutoCAD SHX Text 60" O.C.
AutoCAD SHX Text
MDP
AutoCAD SHX Text 240V/3Ø/100A
AutoCAD SHX Text
EXHAUST MOTOR DISCONNECT
240V/3Ø/30A
SECTION A-A
DESIGNED
CHIEF, ENGINEERING DIVISION
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
NTS
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-01789-2023-M-DT-05
B1789
VEHICLE EXHAUST SYSTEM
REPAIR PLAN
05/01/24
ARCH D
BWE
MONICA TORRES
JAMES NUNEZ
05 06
ROBERT LOPEZ III
ISS
UE
D
FO
R
CO
NS
TRU
CTI
ON
GENERAL NOTES-
1. PRIOR TO PERFORMING WORK ENSURE THAT ELECTRICAL POWER TO SYSTEM BEING WORKED HAS BEEN SECURED AND LOCKED OUT/TAGGED OUT
(LOTO).
2. EXHAUST EXTRACTOR SYSTEM COMPONENTS REFERENCED FROM 'PLYMOVENT' MANUFACTURER ARE USED AS THE BASIS-OF-DESIGN, OR
EQUIVALENT.
3. THE CONTRACTOR SHALL ENSURE THAT THE NEW MOTOR-FAN ASSEMBLY FOR THE VEHICLE EXHAUST SYSTEM IS SIZED TO PRODUCE A FLOW RATE OF NO LESS THAN 500 CFM AND 850 CFM AT THE SPECIFIED SYSTEM NOZZLES, WITH ALL OTHER NOZZLES OPEN AND IN USE, AND AT AN ALTITUDE OF 4200 FEET ABOVE SEA LEVEL. THESE FLOW RATES SHALL BE DEMONSTRATED AND TESTED FOR COMPLIANCE PRIOR TO FINAL SIGN-OFF AT PROJECT
COMPLETION.
4. THE CONTRACTOR SHALL INCORPORATE REQUIRED SYSTEM CONTROLS (MANUAL OR AUTOMATED BALANCER DAMPERS AND/OR VARIABLE MOTOR SPEED CONTROLS) AS REQUIRED TO ENSURE BALANCED FLOW AT ALL NOZZLES AS SPECIFIED. THE DUCT DESIGN SHALL BE SIZED TO HAVE AN
INTERNAL FLOW VELOCITY NO LESS THAN 2400 FPM.
5. THE CONTRACTOR SHALL SUPPLY HARDWARE, EQUIPMENT, CONDUIT, WIRING, CONTROLS, AS NECESSARY FOR THE COMPLETE INSTALLATION AND OPERATIONS OF THE NEW EXHAUST EXTRACTION SYSTEMS. EXISTING HARDWARE AND SUPPORTS MAY BE USED IF SUITABLE FOR REUSE AND ARE IN
GOOD CONDITION.
6. ALL MECHANICAL WORK SHALL BE DONE IN ACCORDANCE WITH INTERNATIONAL MECHANICAL CODE (IMC) AND SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION (SMACNA) AS REVISED. ALL DUCTWORK AND ASSOCIATED FITTINGS WILL BE IN ACCORDANCE WITH SMACNA AND CONFIGURED TO PROVIDE BEST FLOW CONDITIONS POSSIBLE. ALL WORK PERFORMED WILL BE DONE BY CERTIFIED LICENSED TECHNICIANS.
7. LIGHT DUTY LOCK SEAM HVAC DUCT AND ELBOWS SHALL NOT BE USED IN EXHAUST EXTRACTION SYSTEM DUCTWORK. ALL DUCTWORK WILL BE GALVANIZED CONFORM TO ASTM A653 G90. ELBOWS AND FITTINGS WILL BE DIE-STAMPED OR STITCH WELDED EQUIVALENT. MAIN BRANCH TEES WILL BE 45° LATERAL OR LATERAL REDUCING TYPE. ALL DUCT SEAMS WILL BE WELDED OR SEALED WITH FLEXIBLE HIGH TEMPERATURE SEALANT.
8. A SEALANT WILL BE APPLIED TO ALL DUCTWORK AND CONDUIT WALL PENETRATIONS TO THE EXTERIOR WITH A SEALANT THAT MEETS OR EXCEEDS
CHEMLINK HIGH PERFORMANCE WALL AND BLOCK ADHESIVE.
9. THE CONTRACTOR MAY MODIFY AND USE EXISTING STEEL FRAMEWORK AND COMPONENTS IF SUITABLE AND IN GOOD CONDITION FOR FAN-MOTOR ASSEMBLY AND HOSE REEL MOUNTING. ALL BARE STEEL WILL BE CLEANED, PRIMERED AND PAINTED WITH A FINISH COAT TO MATCH THE EXISTING.
10. EACH EXHAUSTER WILL HAVE A VERTICAL OUTLET EXHAUST STACK WITH RAIN CAP AND INTEGRAL DAMPER TO PROVIDE PROTECTION FROM RAIN AND OTHER INCLEMENT WEATHER. FLEX DUCT WILL BE INSTALLED BETWEEN THE BLOWER HOUSING AND THE RIGID DUCTWORK. VIBRATION ISOLATORS WILL BE USED TO ATTACH THE MOTOR-FAN ASSEMBLY TO THE MOUNTING FIXTURE TO REDUCE THE TRANSMISSION OF NOISE AND VIBRATION.
11. HOSE REELS WILL BE MOUNTED TO THE ROOF JOISTS USING THE METHOD ILLUSTRATED IN THE DETAIL, OR EQUIVALENT. NO HOLES SHALL BE DRILLED IN THE ROOF JOISTS. THE MOUNTING HEIGHT OF THE REELS WILL BE APPROXIMATELY 14' ABOVE FINISH FLOOR. STRUT CHANNEL BRACING WILL BE SECURED TO THE ROOF JOISTS USING BOLT CLAMPS OR EQUIVALENT. HOSE REELS WILL INCLUDE A RATCHET LOCK, LOCKING THE HOSE IN THE REQUIRED POSITION; AND HOSE STOP TO POSITION THE HOSE AT RETURN FOR ADEQUATE HEIGHT AND REACH.
12. NEW FLEX HOSES SHALL BE AN ABRASION AND CRUSH RESISTANT HOSE THAT IS HIGHLY FLEXIBLE. MADE FROM HIGH-QUALITY MATERIALS DESIGNED TO WITHSTAND CONTINUOUS TEMPERATURES UP TO 350°F FOR THE 6" DIAMETER AND 600°F FOR THE 8" DIAMETER.
13. ELECTRIC MOTORS SHALL BE TOTALLY ENCLOSED FAN COOLED (TEFC) CONTINUOUS DUTY RATED. THE FAN/MOTOR SHALL BE DIRECT DRIVE TYPE
AND HAVE BALL BEARINGS THAT ARE PERMANENTLY SEALED AND LUBRICATED.
14. ALL METAL COMPONENTS OF THE EXHAUST SYSTEM INCLUDING MOTOR HOUSING, REEL COMPONENTS AND MOUNTING FRAME, CONTROLLER ENCLOSURE WILL BE CONSTRUCTED OF GALVANIZED ZINC PLATED STEEL OR POWDER COAT PROTECTIVE FINISH TO PREVENT CORROSION AND
DETERIORATION OF THE BASE METAL FOR THE LIFE OF THE PRODUCT.
AutoCAD SHX Text
ROLL UP
AutoCAD SHX Text
BAY DOOR
AutoCAD SHX Text
BUILT-UP ROOF
AutoCAD SHX Text 14'-0"
AutoCAD SHX Text 16'-8"
AutoCAD SHX Text
MOTOR-FAN ASSY.
AutoCAD SHX Text
ROLL UP
AutoCAD SHX Text
BAY DOOR
AutoCAD SHX Text
ROLL UP
AutoCAD SHX Text
BAY DOOR
AutoCAD SHX Text
ROLL UP
AutoCAD SHX Text
BAY DOOR
AutoCAD SHX Text
CONCRETE APRON
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
SEE HOSE
AutoCAD SHX Text
REEL MOUNTING
AutoCAD SHX Text
DETAIL (TYP.)
AutoCAD SHX Text 9'-0"
AutoCAD SHX Text 9'-5"
AutoCAD SHX Text 6'-6"
AutoCAD SHX Text 22'-9"
AutoCAD SHX Text 6'-6"
AutoCAD SHX Text 4'-2"
AutoCAD SHX Text 7 8 9
AutoCAD SHX Text 3 4 5 6
AutoCAD SHX Text 7 8 9
AutoCAD SHX Text 3 4 5 6
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ELECTRICAL PANELS
AutoCAD SHX Text
MDP
AutoCAD SHX Text 240V/3Ø/100A
AutoCAD SHX Text
EXHAUST MOTOR DISCONNECT
AutoCAD SHX Text 240V/3Ø/30A
AutoCAD SHX Text
850 CFM ASSEMBLY
AutoCAD SHX Text
500 CFM ASSEMBLY
AutoCAD SHX Text
850 CFM ASSEMBLY
AutoCAD SHX Text
500 CFM ASSEMBLY
AutoCAD SHX Text
ROOF JOIST
AutoCAD SHX Text
%%UHOSE REEL MOUNTING
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
STRUT BEAM
AutoCAD SHX Text
ROOF JOIST
AutoCAD SHX Text
(2 EACH)
AutoCAD SHX Text
EXHAUST HOSE
AutoCAD SHX Text
HOSE REEL
AutoCAD SHX Text
& MOUNTING KIT
AutoCAD SHX Text
NOZZLE W/ DAMPER
AutoCAD SHX Text
STRUT BEAM
AutoCAD SHX Text
TO ROOF JOIST
AutoCAD SHX Text
SECURE REEL TO
AutoCAD SHX Text
STRUT BEAM
AutoCAD SHX Text
UNISTRUT BEAM
AutoCAD SHX Text
%%UEXHAUSTER MOUNTING
AutoCAD SHX Text
FLEX-DUCT
AutoCAD SHX Text
3' MIN.
AutoCAD SHX Text
NEW STACK
AutoCAD SHX Text
RAIN-CAP
AutoCAD SHX Text
ADAPTER
AutoCAD SHX Text
STACK
AutoCAD SHX Text
ASSEMBLY
AutoCAD SHX Text
MOTOR-FAN
AutoCAD SHX Text
MOUNTING
AutoCAD SHX Text
FRAME
AutoCAD SHX Text
VIBRATION
AutoCAD SHX Text
ISOLATORS
AutoCAD SHX Text
FLASHING
AutoCAD SHX Text
ROOF
AutoCAD SHX Text
ALL-THREAD
AutoCAD SHX Text
SUSPENSION ROD
AutoCAD SHX Text
ANCHOR BOLTS
AutoCAD SHX Text
MOUNTING FRAME
AutoCAD SHX Text
ITEM
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
PART/MODEL
AutoCAD SHX Text
EXHAUST EXTRACTION SYSTEM PARTS LIST
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PLYMOVENT
AutoCAD SHX Text
5 HP BLOWER ASSESMBLY, VARIABLE SPEED DIRECT DRIVE
AutoCAD SHX Text
QTY
AutoCAD SHX Text
AutoCAD SHX Text
MFR *
AutoCAD SHX Text
TEV-559
AutoCAD SHX Text
AutoCAD SHX Text
5" HOSE REEL, SPRING OPERATED, MANUAL
AutoCAD SHX Text
SER-850-125
AutoCAD SHX Text
AutoCAD SHX Text
PLYMOVENT
AutoCAD SHX Text
5"ØX33' FLEX HOSE
AutoCAD SHX Text
AutoCAD SHX Text
PLYMOVENT
AutoCAD SHX Text
AUTOMATIC SYSTEM CONTROLLER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PLYMOVENT
AutoCAD SHX Text
EG2 TYPE
AutoCAD SHX Text
OS-3
AutoCAD SHX Text
AutoCAD SHX Text
PLYMOVENT
AutoCAD SHX Text
5" NOZZLE W/ DAMPER AND CLAMP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REC TYPE
AutoCAD SHX Text
MOUNTING KIT
AutoCAD SHX Text
MAS-125
AutoCAD SHX Text
PLYMOVENT
AutoCAD SHX Text
* DENOTES MANUFACTURER PLYMOVENT AS THE DESIGN BASIS OR EQUIVALENT
AutoCAD SHX Text
8" HOSE REEL, SPRING OPERATED, MANUAL
AutoCAD SHX Text
SER-1050-200
AutoCAD SHX Text
AutoCAD SHX Text
PLYMOVENT
AutoCAD SHX Text
8"ØX33' FLEX HOSE, HIGH VOLUME-HIGH TEMP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PLYMOVENT
AutoCAD SHX Text
SNF2 TYPE
AutoCAD SHX Text
PLYMOVENT
AutoCAD SHX Text
8" NOZZLE W/ DAMPER
AutoCAD SHX Text
MEN TYPE
M
M
DESIGNED
CHIEF, ENGINEERING DIVISION
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
NTS
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-01789-2023-E-DT-06
B1789
VEHICLE EXHAUST SYSTEM
ELECTRICAL
05/01/24
ARCH D
BWE
MONICA TORRES
JAMES NUNEZ
06 06
ROBERT LOPEZ III
ISS
UE
D
FO
R
CO
NS
TRU
CTI
ON
GENERAL NOTES
1. PRIOR TO PERFORMING WORK ENSURE THAT ELECTRICAL ENERGY SOURCES TO EFFECTED SYSTEM
HAS BEEN SECURED AND LOCKED OUT/TAGGED OUT (LOTO).
2. ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE (NEC) 70 AS
REVISED.
3. GOVERNMENT SURVEYED THE MDPS AND WAS ABLE TO IDENTIFY ONLY A FEW CIRCUITS DUE TO BAD LABELS OR NONE AT ALL. THEREFORE, CONTRACTOR WILL NEED TO FIELD VERIFY AND TRACE THE
EXHAUST SYSTEM ELECTRICAL CIRCUITS AND ASSOCIATED CIRCUIT BREAKERS.
4. CERTIFIED ELECTRICIAN SHALL INSPECT EXISTING WIRING TYPE AND SIZE AND CIRCUIT BREAKER
RATING TO ENSURE THEY MEETS THE REQUIREMENTS FOR NEW MOTORS AND CONTROLLERS PER
NEC. FOR HIGHER RATED WIRING (IF NEEDED) THE ELECTRICIAN SHALL REMOVE EXISTING WIRING TO
THE EXTENT NEEDED AND INSTALL REQUIRED 600 VOLT, THHN COPPER STRANDED ELECTRICAL
CONDUCTOR. FOR HIGHER RATED CIRCUIT BREAKER, ELECTRICIAN SHALL ENSURE THAT THE NEW CIRCUIT BREAKER DOES NOT UNBALANCE THE PANEL. ALL ELECTRICAL POWER AND CONTROL WIRING
SHALL BE ROUTED THROUGH EMT CONDUIT, USING PROPER CONNECTION METHODS, J-BOXES,
NIPPLES, ETC.
5. DEMOLITION EXISTING 3 PHASE 208V CONTROLLER AND DEDICATED DISCONNECTS TO BLOWER ASSEMBLY. LABEL ALL CIRCUITS PRIOR TO TRANSFER TO NEW CONTROLLER AND DISCONNECTS. USE EXISTING WIRE FEED FROM DISTRIBUTION PANELS AND CONDUIT FOR NEW CONTROLLER IF SUITABLE.
6. NEW CONTROLLER WILL BE WALL MOUNTED AT OR NEAR THE LOCATION ILLUSTRATED IN THE DRAWING. THE NEW CONTROLLER SHALL BE BUILT AND SUPPLIED BY UL RECOGNIZED AN LISTED
EXHAUST SYSTEM MANUFACTURER.
7. INSTALL NEW EMT CONDUIT TO MATCH EXISTING OR PER MANUFACTURER RECOMMENDATIONS FROM
EXISTING CONDUIT UP TO NEW COMPONENTS AS NEEDED. USE PROPER CONNECTION METHODS
SUCH AS J-BOX, NIPPLES, ETC. FOR CONTINUATION OF CONDUIT AND SEAL PROPERLY. THE USE OF
FLEX CONDUIT IS ALLOWED ACCORDING PER NEC.
8. BLOWER ASSEMBLY SHALL HAVE AN ELECTRICAL NEMA DISCONNECT NEAR THE ELECTRIC MOTOR.
9. ALL GROUNDS FOR EQUIPMENT, BONDING AND NEUTRALS SHALL BE SIZED ACCORDING TO NEC
ARTICLE 250.
10. THE CONTRACTOR SHALL VERIFY THAT THE VEHICLE EXHAUST SYSTEM CONTROLS AND INTERLOCKS
ARE OPERATING CORRECTLY.
AutoCAD SHX Text 59'-9"
AutoCAD SHX Text 39'-2"
AutoCAD SHX Text
CONCRETE APRON
AutoCAD SHX Text
EXHAUST
AutoCAD SHX Text
DISCONNECT
AutoCAD SHX Text 240V, 3Ø
AutoCAD SHX Text
TO DEDICATED
AutoCAD SHX Text
MOTOR
AutoCAD SHX Text
ELECTRICAL PANELS
AutoCAD SHX Text
MDP
AutoCAD SHX Text 240V/3Ø/100A
AutoCAD SHX Text
EXHAUST MOTOR DISCONNECT
AutoCAD SHX Text 240V/3Ø/30A
AutoCAD SHX Text
NEW EXHAUSTER
AutoCAD SHX Text
CONTROLLER
AutoCAD SHX Text
FUSED DISCONNECT
AutoCAD SHX Text
MAIN
AutoCAD SHX Text
EXHAUSTER
AutoCAD SHX Text
FAN MOTOR
AutoCAD SHX Text
DISCONNECT
AutoCAD SHX Text
DISCONNECT
AutoCAD SHX Text
OS-3 CONTROLLER
AutoCAD SHX Text
NEW
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
NEW
AutoCAD SHX Text C1
AutoCAD SHX Text C3
AutoCAD SHX Text C4
AutoCAD SHX Text
OPTIONS
AutoCAD SHX Text
BUILDING POWER SUPPLY EXHAUSTER CONTROLS DIAGRAM DIAGRAMATIC ONLY
AutoCAD SHX Text 100A/240V/3Ø
AutoCAD SHX Text C2
AutoCAD SHX Text
MAIN
AutoCAD SHX Text
DISTRIBUTION
AutoCAD SHX Text
PANEL
AutoCAD SHX Text 30A/240V/3Ø
AutoCAD SHX Text
DISCONNECT
AutoCAD SHX Text
NEW
AutoCAD SHX Text C5
AutoCAD SHX Text
CIRC
AutoCAD SHX Text
TRIP
AutoCAD SHX Text
NO.
AutoCAD SHX Text
SERVICES
AutoCAD SHX Text A
AutoCAD SHX Text
SERVICES
AutoCAD SHX Text
TRIP
AutoCAD SHX Text
NO.
AutoCAD SHX Text
PANEL: 'A'
AutoCAD SHX Text
CIRC
AutoCAD SHX Text
PANEL COMPUTATION
AutoCAD SHX Text
CIRCUIT BREAKER INTERRUPT RATING: 25,000 AMPS
AutoCAD SHX Text
PHASES: 3 4 WIRE
AutoCAD SHX Text
VOLTAGE: 120/208
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text
NO.
AutoCAD SHX Text
AMPS
AutoCAD SHX Text
POLES
AutoCAD SHX Text
AMPS
AutoCAD SHX Text
POLES
AutoCAD SHX Text
NO.
AutoCAD SHX Text
CEILING LIGHTS
AutoCAD SHX Text X
AutoCAD SHX Text
RECEPT. WEST
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CEILING LIGHTS
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CEILING LIGHTS
AutoCAD SHX Text
HEATERS
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CEILING LIGHTS
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
WELDER
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CEILING LIGHTS
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CEILING LIGHTS
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
HEATER, RECEPT. EAST
AutoCAD SHX Text
COMPRESSER
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
RECEPT. NORTH
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
RECEPT. NORTH
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CEILING LIGHTS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FLOOD LIGHTS
AutoCAD SHX Text
EVAP. COOLER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
W. SIDE, EXT LIGHT
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
FUSE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
SERVICES
AutoCAD SHX Text A
AutoCAD SHX Text
PANEL: 'A-SIDE'
AutoCAD SHX Text
MANUAL DISCONNECT
AutoCAD SHX Text
MAX HP 7.5
AutoCAD SHX Text
PHASES: 3 4 WIRE
AutoCAD SHX Text
VOLTAGE: 240
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text
AMPS
AutoCAD SHX Text
POLES
AutoCAD SHX Text
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXHAUST MOTOR
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CFM *
AutoCAD SHX Text
ESP
AutoCAD SHX Text
RPM
AutoCAD SHX Text
HP
AutoCAD SHX Text
DRIVE
AutoCAD SHX Text
LOCATION
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
ELEC DATA
AutoCAD SHX Text
MFR
AutoCAD SHX Text
MODEL
AutoCAD SHX Text
EXHAUST FAN SCHEDULE (NEW)
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DIRECT
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
CENTRIFUGAL
AutoCAD SHX Text 4kW/208V/60/3
AutoCAD SHX Text
PLYMOVENT
AutoCAD SHX Text
TEV-559
* DENOTES PERFORMANCE REQUIREMENT AT 4200 FEET ABOVE SEA LEVEL
| Sheets and Views |
| B1789 EXHAUST SYSTEM 052024-COVER-INDEX SHEET |
| B1789 EXHAUST SYSTEM 052024-SITE LOCATIONS |
| B1789 EXHAUST SYSTEM 052024-GEN NOTES |
| B1789 EXHAUST SYSTEM 052024-1789 DEMO |
| B1789 EXHAUST SYSTEM 052024-1789 INSTALL |
| B1789 EXHAUST SYSTEM 052024-1789 ELEC |
File details come from the government source that posted it. Updated .