WHITE SANDS MISSILE RANGE, NEW MEXICO

ENGINEERING DIVISION

DIRECTORATE OF PUBLIC WORKS

DRAWING NUMBER

REVISIONS

DESCRIPTION

SHEET

CHIEF DESIGN BRANCH

CHIEF, ENGINEERING DIVISION

APPROVED

DATE SCALE

CHECKED

PROJECT MANAGER

RECOMMENDED

SUBMITTED

DESIGNED BY Cesar M. Limon

DRAWN CML

NUMBER DATE

OF

PLATE

APPROVEDBY

PROJECT DESCRIPTION

COVERSHEET / INDEX SHEET

S

ENGINEERING DIVISION

REPLACE AND REWIRE ELECTRICAL PANELS AND RELOCATE DRY TYPE

DIRECTORATE OF PUBLIC WORKS

WHITE SANDS MISSILE RANGE, NEW MEXICO

DESIGN BRANCH

T

C

I

R

A

E

M

A

F

O

E

C

A

L

P

H

T

R I

B

I

H

W

S

D

N

A

S

E

R

E

L

I

S

S

IM

Y

T

I

V

E

G

I

T

C

A

E

C

A

P

S

N

A

E

L

I

S

S

I M

TRANSFORMER AT DRY SITE BUILDING 22886

DRAWING # TITLE

WS-22886-2018-G-GI-01 COVERSHEET / INDEX SHEET

WS-22886-2018-E-EP-02 FLOOR PLAN FOR BUILDING 22886

WS-22886-2018-E-EP-03 EXISTING PANEL "MDP-2

WS-22886-2018-E-EP-04 EXISTING PANEL "P/1" WITH EQUIPMENT

WS-22886-2018-E-EP-05

SUB PANEL P/1 EXISTING

WS-22886-2018-E-EP-06

MAIN PANEL "MDP-2" EXISTING

WS-22886-2018-E-EP-07

MAIN PANEL "MDP-3" EXISTING AND NEW CONTACTORS FOR EXHAUST FANS AND EVAP COOLERS

WS-22886-2018-E-EP-08

EXISTING SUB PANELS "PP", "LA", AND "L" LAYOUT

WS-22886-2018-E-EP-09

EXISTING SUB PANEL "PP"

WS-22886-2018-E-EP-10 SUB PANEL "L" EXISTING AND NEW

WS-22886-2018-E-EP-11 SUB PANEL "LA" EXISTING AND NEW

WS-22886-2018-E-EP-12

EXISTING AND NEW 112.5 KVA DRY TYPE TRANSFORMER

WS-22886-2018-E-EP-13

GENERAL NOTES

WS-22886-2018-E-EP-14

GENERAL NOTES

WS-22886-2018-E-EP-15

GENERAL NOTES

WS-22886-2018-E-EP-16

GENERAL NOTES

WS-22886-2018-E-EP-17

AREA OF WORK RODENT DROPPINGS REMEDIATION

G1

I

S

S

U

E

D

T

O

C

O

N

S

T

R

U

C

T

I

O

N

Sam E. Morris

Rafael H. Acosta

Howard Guion

WS-22886-2018-G-GI-01

PROJECT DESCRIPTION

FLOOR PLAN FOR BUILDING 22886

WHITE SANDS MISSILE RANGE, NEW MEXICO

ENGINEERING DIVISION

DIRECTORATE OF PUBLIC WORKS

DRAWING NUMBER

REVISIONS

DESCRIPTION

SHEET

CHIEF DESIGN BRANCH

CHIEF, ENGINEERING DIVISION

APPROVED

DATE SCALE

CHECKED

PROJECT MANAGER

RECOMMENDED

SUBMITTED

DESIGNED BY Cesar M. Limon

DRAWN CML

NUMBER DATE

OF

PLATE

APPROVEDBY

MECHANICAL ROOM

POWER

PANEL

"P/1"

POWER

PANEL

"MDP-2"

PANEL

"PP"

EXISTING

112.5

KVA

TRANSFORMER

KITCHEN

AREA

BAY

AREA

PANEL

"L"

PANEL

"LA"

POWER PANEL

"MDP-3"

N

W

S

E

ELECTRICAL

ROOM

EXISTING 500 KVA

PADOUNT

TRANSFORMER

MAIN ENTRANCE

OFFICE

SPACE

NEW CONDUIT FOR SECONDARY

(MOUNTED ON WALL)

3-#4 / 0

AWG-2

"C

(UNDERGROUND)

3-#350

MCM-3"C

(UNDERGROUND)

4-#3 / 0

AWG-3"C

(EXISTING)

AREA OF WORK FOR

RODENT DROPPING

REMEDIATION

TERMINAL

COMPARTMENT

BUILDING 22886 FLOOR PLAN

E2

NEW SAFETY

DISCONNECT SWITCH

RELOCATION AND

NEW 112.5 KVA

TRANSFORMER

PULL BOX

NEW CONDUIT FOR PRIMARY

(MOUNTED ON WALL)

I

S

S

U

E

D

T

O

C

O

N

S

T

R

U

C

T

I

O

N

Sam E. Morris

Rafael H. Acosta

Howard Guion

WS-22886-2018-E-EP-02

75 KVA

TRANSFORMER

3-#1 AWG-1 1/2" C

(UNDERGROUND)

PROJECT DESCRIPTION

EXISTING PANEL "MDP-2

WHITE SANDS MISSILE RANGE, NEW MEXICO

ENGINEERING DIVISION

DIRECTORATE OF PUBLIC WORKS

DRAWING NUMBER

REVISIONS

DESCRIPTION

SHEET

CHIEF DESIGN BRANCH

CHIEF, ENGINEERING DIVISION

APPROVED

DATE SCALE

CHECKED

PROJECT MANAGER

RECOMMENDED

SUBMITTED

DESIGNED BY Cesar M. Limon

DRAWN CML

NUMBER DATE

OF

PLATE

APPROVEDBY

WITH EQUIPMENT

EXISTING EQUIPMENT

LAYOUT-MAIN PANEL

"MPD-2"

MAIN DISTRIBUTION

PANEL "MDP-2"

480 V 3 PHASE

PACKAGED CHILLER

UNIT

30 HP 30 HP 5 HP

HP

5 HP 15 HP

FAN

MOTOR

F-6

HP

HP

WATER

PUMP

WP-2

HOT

WATER

PUMP

HP-5

CHILLED

WATER

PUMP

CHP-5

MULTIZONE

UNIT MOTOR

MZ-3

75 KVA

TRANSFORMER

480 V DELTA PRIMARY

208 / 120 V

4- WYE SECONDARY

WALL MOUNT

4"X6"X3' WIRING TROUGH

200A

3P + SN

CIRCUIT

BREAKER

NEMA 1

ENCLOSURE

CLASS 3d

70A

3P + SN

CIRCUIT

BREAKER

NEMA 1

ENCLOSURE

CLASS 2d

1 KVA, 1 PHASE

480-120 V

DRY TYPE

TRANSFORMER,

WALL MOUNTED

30A-120V.

1P + SN

FUSIBLE

SAFETY

SWITCH

FUSE 10A

2-#12 AWG-1/2" C

2-#12 AWG-1/2" C

3-#1AWG-1 1/2" C

4-300 MCM-3" C

4-#4 AWG-1 1/2" C

4-#3/0 AWG

-2 1/2" C

2-#12 AWG-1/2" C

1-#2 BSD

TO GROUND

ROD

500 KVA, 7200/12,470-

240 / 480 V, 3 PHASE

TRANSFORMER

CONNECT 12,470 V

UNGROUNDED WYE

PRIMARY-480 V

DELTA

SECONDARY

3-#4/0 AWG-

2 1/2" C

1-#1/0 C-1" C

TO GROUND

ROD

120 V, 1 PHASE

CONTROL CKT

1-#8 BSD

CU.

3-#12 AWG-

1/2" C

3-#1 AWG-2" C

3-#12 AWG-1/2" C

CABLE TROUGH

3-#6 AWG-

1" C

4-#12 AWG-3/4" C

WIRING

CABINETS

WIRING

CABINET

SAFETY

DISCONNECT

SWITCH

WIRING

CABINETS

SAFETY

DISCONNECT

SWITCHES

E3

I

S

S

U

E

D

T

O

C

O

N

S

T

R

U

C

T

I

O

N

Sam E. Morris

Rafael H. Acosta

WS-22886-2018-E-EP-03

EXISTING SUB PANEL "P/1" WITH

WHITE SANDS MISSILE RANGE, NEW MEXICO

ENGINEERING DIVISION

DIRECTORATE OF PUBLIC WORKS

DRAWING NUMBER

REVISIONS

DESCRIPTION

SHEET

CHIEF DESIGN BRANCH

CHIEF, ENGINEERING DIVISION

APPROVED

DATE SCALE

CHECKED

PROJECT MANAGER

RECOMMENDED

SUBMITTED

DESIGNED BY Cesar M. Limon

DRAWN CML

NUMBER DATE

OF

PLATE

APPROVEDBY

EQUIPMENT

POWER PANEL "P1"

208 / 120V

3 PHASE

75 KVA

TRANSFORMER

480 V DELTA PRIMARY

208 / 120 V

4- WYE SECONDARY

3-#1 AWG-1 1/2" C

#2 BSD COPPER

4-#300 MCM-3" C

500 KVA

TRANSFORMER

EXISTING EQUIPMENT

LAYOUT-POWER

PANEL "P/1"

10 HP

3-#12 AWG-1/2" C

HP

HP

HP

FAN MOTOR

MULTIZONE UNIT

MOTOR MZ-1

CHILLED WATER

PUMP CHP-3

HOT WATER

PUMP HP-3

T

1-#8 AWG-

" C

P

H A

S E

C O

N T

R O

L C

I R

C U

I T

2-#12 AWG-1/2" C

PUMP HOUSE

30 HP 30 HP 5 HP

3-#1/0 AWG-2" C

3-#12 AWG-1/2" C

3-#6 AWG-

1" C

COMPRESSOR MOTORS

CONDENSOR FAN

MOTOR

4-#12 AWG-

3/4" C

J BOX

4" SQ

M

PUMP MOTOR WP-3

1-#8 AWG-

" C

TO CW PIPE

1 1/2 KVA

DRY TYPE

TRANSFORMER

1 PHASE, 480-120 V

HTR.

EH-1

S

Y

3-#12 AWG-1/2" C

2-#12 AWG-1/2" C

WIRING

CABINETS

WIRING

CABINET

WIRING

CABINET

1 KVA, 1 PHASE,

480V-120V, DRY TYPE

TRANSFORMER, WALL

MOUNTED

WIRING

CABINET

SAFETY

DISCONNECT

SWITCHES

WIRING

CABINETS

CABLE TROUGH

E4

I

S

S

U

E

D

T

O

C

O

N

S

T

R

U

C

T

I

O

N

Sam E. Morris

Rafael H. Acosta

WS-22886-2018-E-EP-04

SUB PANEL P/1 EXISTING AND NEW

WHITE SANDS MISSILE RANGE, NEW MEXICO

ENGINEERING DIVISION

DIRECTORATE OF PUBLIC WORKS

DRAWING NUMBER

REVISIONS

DESCRIPTION

SHEET

CHIEF DESIGN BRANCH

CHIEF, ENGINEERING DIVISION

APPROVED

DATE SCALE

CHECKED

PROJECT MANAGER

RECOMMENDED

SUBMITTED

DESIGNED BY Cesar M. Limon

DRAWN CML

NUMBER DATE

OF

PLATE

APPROVEDBY

GENERAL NOTES:

1) SUB PANEL DIMENSIONS

LENGTH: 38 INCHES

WIDTH: 32 ¼ INCHES

DEPTH: 9 ½ INCHES

2) MECHANICAL ROOM PANEL "P/1" FOUR CONDUCTOR WIRE FEED FROM WALLMOUNT

TRANSFORMER 75 KVA 480 V DELTA TO 208 / 120 V WYE 3 PHASE WALL MOUNTED DRY TYPE

TRANSFORMER IS 300 MCM THHN RATED AT 600 V. THE 75 KVA DRY TYPE WALL MOUNTED

TRANSFORMER IS FED FROM 500 KVA PADMOUNT TRANSFORMER. SEE SHEET 4-

WS-22886-2018-E-EP-04.

EXISTING SUB PANEL "P/1"

E5

I

S

S

U

E

D

T

O

C

O

N

S

T

R

U

C

T

I

O

N

Sam E. Morris

Rafael H. Acosta

Howard Guion

WS-22886-2018-E-EP-05

120 / 208 V WYE 3 PHASE 4 W SURFACE MOUNTED 200 AMP 3 POLE BREAKER CLASS 3a

CKT. NO. POLES

TRIP (AMPS)

SERVICES A B C CKT. NO. POLES

TRIP (AMPS)

SERVICES

3 150

PACKAGED AIR

COOLED UNIT CH-3

2 3 40

FAN MOTOR

F-4 10 HP

3 150 " 4 3 40 "

3 150 " 6 3 40 "

3 30

MULTIZONE UNIT

MOTOR MZ-1

8 3 40

CHILLED

WATER PUMP

CHP-3 1

HP

3 30 " 10 3 40 "

3 30 " 12 3 40 "

3 15

HOT WATER PUMP

HP-3

HP

14 3 15 SPARE

3 15 " 16 3 15 "

17 3

15 " 18 3 15 "

19 2

CONTROL POWER

TRANSFORMER 1

KVA

20 3 20 PUMP HOUSE

2 15 " 22 3 20 "

24 3 20 "

MAIN PANEL "MDP-2" EXISTING AND NEW

WHITE SANDS MISSILE RANGE, NEW MEXICO

ENGINEERING DIVISION

DIRECTORATE OF PUBLIC WORKS

DRAWING NUMBER

REVISIONS

DESCRIPTION

SHEET

CHIEF DESIGN BRANCH

CHIEF, ENGINEERING DIVISION

APPROVED

DATE SCALE

CHECKED

PROJECT MANAGER

RECOMMENDED

SUBMITTED

DESIGNED BY Cesar M. Limon

DRAWN CML

NUMBER DATE

OF

PLATE

APPROVEDBY

1) EXISTING PANEL DIMENSIONS:

LENGTH: 74 ¼ INCHES

WIDTH: 38 ¼ INCHES

DEPTHepth: 10 INCHES

2) MECHANICAL ROOM PANEL "MDP-2" FOUR CONDUCTOR WIRE FEED FROM

PADMOUNT TRANSFORMER (SAME TRANSFORMER FEEDS PANEL "MDP-3" SHEET

2-WS-22886-2018-E-EP-02 IN ELECTRICAL ROOM) 500 KVA SOUTH OF THE BUILDING,

ARE 4/0 AWG THHN RATED AT 600 VOLTS. SEE SHEET 3-WS-22886-2018-E-EP-03.

GENERAL NOTES:

EXISTING MAIN PANEL "MDP/2"

WITH DISCONNECT SAFETY SWITCHES

E6

I

S

S

U

E

D

T

O

C

O

N

S

T

R

U

C

T

I

O

N

Sam E. Morris

Rafael H. Acosta

Howard Guion

WS-22886-2018-E-EP-06

480 V 3 PHASE 4 W SURFACE MOUNTED 500 AMP 3 POLE BREAKER MAIN BREAKER CLASS 5a

CKT. NO. POLES

TRIP (AMPS)

SERVICES A B C CKT. NO. POLES

TRIP (AMPS)

SERVICES

3 150

PACKAGED AIR

COOLED CHILLER

UNIT

2 3 125

75 KVA DRY TYPE

TRANSFORMER

(ISOLATED TECH

POWER)

3 150 " 4 3 125 "

3 150 " 6 3 125 "

3 125

75 KVA DRY TYPE

TRANSFORMER

(LIGHTS & MISC.

POWER)

8 3 40 FAN MOTOR

3 125 " 10 3 40 "

3 125 " 12 3 40 "

3 20

MULTIZONE UNIT

MOTOR

14 3 15

CHILLED WATER

PUMP MOTOR

CHP-5 1

HP

3 20 " 16 3 15 "

17 3

20 " 18 3 15 "

19 3

HOT WATER PUMP

MOTOR HP-5

HP 20 3 20

WATER PUMP

MOTOR HP-2 1

HP

3 15 " 22 3 20 "

3 15 " 24 3 20 "

3 15 SPARE 24 2 15

CONTROL POWER

TRANSFORMER

1KVA

3 15 " 26 2 15 "

3 15 " 28

3 15

SPACE ONLY FOR

FUTURE BREAKER

31 3

15 " 32

33 3

15 " 34

MAIN PANEL "MDP-3" EXISTING AND NEW

WHITE SANDS MISSILE RANGE, NEW MEXICO

ENGINEERING DIVISION

DIRECTORATE OF PUBLIC WORKS

DRAWING NUMBER

REVISIONS

DESCRIPTION

SHEET

CHIEF DESIGN BRANCH

CHIEF, ENGINEERING DIVISION

APPROVED

DATE SCALE

CHECKED

PROJECT MANAGER

RECOMMENDED

SUBMITTED

DESIGNED BY Cesar M. Limon

DRAWN CML

NUMBER DATE

OF

PLATE

APPROVEDBY

1) EXISTING PANEL DIMENSIONS:

LENGTH: 68 INCHES

WIDTH: 38 INCHES

DEPTH: 9 INCHES

2) ELECTRICAL ROOM PANEL "MDP-3" FOUR CONDUCTOR WIRE FEED FROM PADMOUNT

TRANSFORMER (SAME TRANSFORMER FEEDS PANEL "MDP-3" SHEET

2-WS-22886-2018-E-EP-02 IN ELECTRICAL ROOM) 500 KVA SOUTH OF THE BUILDING,

ARE 4/0 AWG THHN RATED AT 600 VOLTS. SEE SHEET 7-WS-22886-2018-E-EP-07.

3) INSTALL 4 CONTACTORS FOR EXHAUST FANS AND 4 CONTACTORS FOR EVAP COOLERS

TO THE NEW PANEL "MDP-3" PANEL AND EACH EXHAUST FAN AND EVAP COOLER SHALL

HAVE ITS OWN BREAKER SIZED APPROPRIATELY.

GENERAL NOTES:

EXISTING MAIN PANEL "MDP/3"

STARTERS FOR EXHAUST FANS AND

E7

I

S

S

U

E

D

T

O

C

O

N

S

T

R

U

C

T

I

O

N

Sam E. Morris

Rafael H. Acosta

Howard Guion

WS-22886-2018-E-EP-07

480 V 3 PHASE 4 W FLUSH MOUNTED 600 AMP 3 POLE BREAKER MAIN BREAKER CLASS 5a

CKT. NO. POLES

TRIP (AMPS)

SERVICES A B C CKT. NO. POLES

TRIP (AMPS)

SERVICES

SPARE 2 3 175

112.5 KVA DRY

TYPE

TRANSFORMER

" 4 3 125 "

" 6 3 125 "

SPARE 8 50 SPARE

" 10 50 "

" 12 50 "

3 70 BORE SITE 14 3 50

AIR

COMPRESSOR

3 70 " 16 3 50 "

17 3

70 " 18 3 50 "

19 2

OVERHEAD DOOR,

NORTH SIDE

20 3 15

OVERHEAD

DOOR, SOUTH

SIDE

2 15 " 22 3 15 "

3 15 " 24 3 15 "

3 15 EXHAUST FANS 26 3 15

EVAPORATIVE

COOLER

3 15 " 28 3 15 "

15 " 30 3 15 "

SPARE

SPARE

" 34

" 36

EVAP COOLERS

EXISTING SUB PANELS "PP", "LA", AND "L"

WHITE SANDS MISSILE RANGE, NEW MEXICO

ENGINEERING DIVISION

DIRECTORATE OF PUBLIC WORKS

DRAWING NUMBER

REVISIONS

DESCRIPTION

SHEET

CHIEF DESIGN BRANCH

CHIEF, ENGINEERING DIVISION

APPROVED

DATE SCALE

CHECKED

PROJECT MANAGER

RECOMMENDED

SUBMITTED

DESIGNED BY Cesar M. Limon

DRAWN CML

NUMBER DATE

OF

PLATE

APPROVEDBY

MAIN DISTRIBUTION

PANEL "MDP-3"

480 V 3 PHASE

2 CU IN

" C

TO BLDG

GROUND ROD

3-#12 AWG-

3/4" C

2-SETS OF 3-350 MCM

IN 3" CONDUIT TO

EXISTING 500 KVA

TRANSFORMER

15 HP 1 HP 1 HP

1 HP 1 HP 1 HP

LIGHTING

PANEL

"LA"

3 P

208 / 120 V

LIGHTING

CONTACTOR

CONTROL

POWER OUTLET

PANEL

"PP"

3 P

208 / 120 V

3 PHASE

X-FMR

112.5 KVA

LIGHTING

PANEL

"L"

3 PHASE

208 / 120 V

4-#4 CU AWG-1 1/4" C

OR 4-#2 AL-1

" C

4-#8 AWG-1" C

4-#4 CU AWG-1 1/4" C

OR 4-#2 AL AWG-1

" C

3-#500 MCM & 1-#4 / 0

AWG CU-3 1/2" C

OR

3-#700 MCM & 1-#300

MCM AL-4" C

4-#3 /0 AWG CU -2 1/2" C

OR

4-#250 MCM AL-4" C

30 HP 30 HP 5 HP

5-TON

CRANE

MPD 3-1

3-#12 AWG-

3/4" C

HP

3-#12 AWG-3/4" C

3-#12 AWG-3/4" C

HP

HP

HP

HP

HP

DOOR

OPERATOR

DOOR

OPERATOR

EXHAUST

FAN

EXHAUST

FAN

EXHAUST

FAN

EXHAUST

FAN

EVAP

COOLER

EVAP

COOLER

EVAP

COOLER

EVAP

COOLER

EVAP

COOLER

AIR

CONDITIONER

EXISTING EQUIPMENT LAYOUT-POWER

OUTLET PANEL "PP", "LA", AND "L"

LAYOUT

WIRING

CABINET

WIRING

CABINETS

SAFETY DISCONNECT

SWITCHES

SAFETY DISCONNECT

SWITCHES

WIRING

CABINETS

WIRING

CABINETS

WIRING

CABINET

WIRING

CABINET

WIRING

CABINETS

CABLE TROUGH

E8

I

S

S

U

E

D

T

O

C

O

N

S

T

R

U

C

T

I

O

N

Sam E. Morris

Rafael H. Acosta

WS-22886-2018-E-EP-08

EXISTING SUB PANEL "PP"

WHITE SANDS MISSILE RANGE, NEW MEXICO

ENGINEERING DIVISION

DIRECTORATE OF PUBLIC WORKS

DRAWING NUMBER

REVISIONS

DESCRIPTION

SHEET

CHIEF DESIGN BRANCH

CHIEF, ENGINEERING DIVISION

APPROVED

DATE SCALE

CHECKED

PROJECT MANAGER

RECOMMENDED

SUBMITTED

DESIGNED BY Cesar M. Limon

DRAWN CML

NUMBER DATE

OF

PLATE

APPROVEDBY

1) EXISTING PANEL DIMENSIONS:

LENGTH: 68 ½ INCHES

WIDTH: 38 INCHES

DEPTH: 6 INCHES

2) FOUR CONDUCTOR COMES FROM 480 V 112 KVA DRY TYPE

TRANSFORMER THAT IS FED FROM PANEL “MPD-3” BREAKER

#1 IS 3/0 AWG CONDUCTORS THHN RATED AT 600 V AND THE

SECONDARY OF THE TRANSFORMER FEEDS 4-#4 / 0 AWG TO

PANEL "PP". SEE SHEET 7-WS-22886-2018-E-EP-08.

EXISTING SUB PANEL "PP"

GENERAL NOTES:

E9

I

S

S

U

E

D

T

O

C

O

N

S

T

R

U

C

T

I

O

N

Sam E. Morris

Rafael H. Acosta

Howard Guion

WS-22886-2018-E-EP-09

208 / 120 V, 3 PHASE, FLUSH MOUNTED, PHASE 4 W 400 AMP M.L.O FLUSH

CKT. NO. POLES

TRIP (AMPS)

SERVICES A B C CKT. NO. POLES

TRIP (AMPS)

SERVICES

3 225 2-200 AMP RECP. 2 3 225 2-200 AMP RECP.

3 225 " 4 3 225 "

3 225 " 6 3 225 "

1 30 RECEP. HIGH BAY 8 1 30 RECEP. HIGH BAY

1 30 RECEP. HIGH BAY 10 1 30 RECEP. HIGH BAY

1 30

RECEP. TEST

SHOP

12 1 30 RECEP. HIGH BAY

1 20

RECP. FLOOR

OUTLETS

14 1 20

RECP. FLOOR

OUTLETS

1 20

RECP. FLOOR

OUTLETS

16 1 20 RECP. HIGH BAY

17 1

RECEP. TEST

SHOP

18 1 20 RECP. HIGH BAY

19 1

20 RECP. HIGH BAY 20 1 20

RECEP. TEST

SHOP

1 15 RECP. HIGH BAY 22 1 15 6-UNIT HEATERS

1 15

4 EVAP PUMP

MOTORS

24 3 70 PANEL "LA"

3 50 PANEL "L" 26 3 70

3 50 " 28 3 70

3 50 " 30 1 50 SPARE

1 20 SPARE 32

WHITE SANDS MISSILE RANGE, NEW MEXICO

ENGINEERING DIVISION

DIRECTORATE OF PUBLIC WORKS

DRAWING NUMBER

REVISIONS

DESCRIPTION

SHEET

CHIEF DESIGN BRANCH

CHIEF, ENGINEERING DIVISION

APPROVED

DATE SCALE

CHECKED

PROJECT MANAGER

RECOMMENDED

SUBMITTED

DESIGNED BY Cesar M. Limon

DRAWN CML

NUMBER DATE

OF

PLATE

APPROVEDBY

EXISTING MAIN PANEL "L"

1) SUB PANEL DIMENSIONS

LENGTH: 24 INCHES

WIDTH: 16 ¼ INCHES

DEPTH: 5 INCHES

2) TMDE ROOM-PANEL LL. EXISTING PANEL "LL" ALONG WITH 4 FEEDER CONDUCTORS FROM PANEL "PP" BREAKER #23. SEE SHEET

7-WS-22886-2018-E-EP-07 .

GENERAL NOTES:

SUB PANEL "L" EXISTING AND NEW

E10

I

S

S

U

E

D

T

O

C

O

N

S

T

R

U

C

T

I

O

N

Sam E. Morris

Rafael H. Acosta

Howard Guion

208 / 120 V, 3 PHASE, FLUSH MOUNTED, 4 W 100 Amp M.L.O Flush

CKT. NO. POLES

TRIP (AMPS)

SERVICES A B C CKT. NO. POLES

TRIP (AMPS)

SERVICES

1 20

LIGHTS TEST

SHOP

2 1 20

LIGHTS TEST

SHOP

1 20

LIGHTS TEST

SHOP

4 1 20

LIGHTS TEST

SHOP

1 20

LIGHTS TEST

SHOP

6 1 20

LIGHTS TEST

SHOP

1 20

LIGHTS OVER

WORKBENCHES &

EXTERIOR

8 1 20 EXTERIOR FLOODS

1 20 SPARE 10 1 20 SPARE

1 20

SPARE

12 1 20 SPARE

13 1

SPARE

14 1 20

SPARE

15 1

SPARE

16 SPACE

SPACE 18 SPACE

WS-22886-2018-E-EP-10

WHITE SANDS MISSILE RANGE, NEW MEXICO

ENGINEERING DIVISION

DIRECTORATE OF PUBLIC WORKS

DRAWING NUMBER

REVISIONS

DESCRIPTION

SHEET

CHIEF DESIGN BRANCH

CHIEF, ENGINEERING DIVISION

APPROVED

DATE SCALE

CHECKED

PROJECT MANAGER

RECOMMENDED

SUBMITTED

DESIGNED BY Cesar M. Limon

DRAWN CML

NUMBER DATE

OF

PLATE

APPROVEDBY

EXISTING SUB PANEL "LA"

1) SUB PANEL DIMENSIONS

LENGTH: 24 INCHES

WIDTH: 16 ¼ INCHES

DEPTH: 5 INCHES

2) TMDE ROOM-PANEL LA. EXISTING PANEL "LA" ALONG WITH 4 FEEDER CONDUCTORS FROM PANEL "PP" BREAKER #22, LIGHTING CONTACTOR.

SEE SHEET 7-WS-22886-2018-E-EP-07 .

GENERAL NOTES:

SUB PANEL "LA" EXISTING AND NEW

E11

I

S

S

U

E

D

T

O

C

O

N

S

T

R

U

C

T

I

O

N

Sam E. Morris

Rafael H. Acosta

Howard Guion

WS-22886-2018-E-EP-11

208 / 120 V, 3 PHASE, FLUSH MOUNTED, PHASE 4 W 100 AMP M.L.O FLUSH

CKT. NO. POLES

TRIP (AMPS)

SERVICES A B C CKT. NO. POLES

TRIP (AMPS)

SERVICES

1 20 LIGHTS HIGH BAY 2 1 20 LIGHTS HIGH BAY

1 20 LIGHTS HIGH BAY 4 1 20 LIGHTS HIGH BAY

1 20 LIGHTS HIGH BAY 6 1 20 LIGHTS HIGH BAY

1 20

LIGHTS OVER

WORKBENCHES &

EXTERIOR

8 1 20 EXTERIOR FLOODS

1 20 SPARE 10 1 20 SPARE

SPACE 12 SPACE

EXISTING AND NEW 112.5 KVA DRY

WHITE SANDS MISSILE RANGE, NEW MEXICO

ENGINEERING DIVISION

DIRECTORATE OF PUBLIC WORKS

DRAWING NUMBER

REVISIONS

DESCRIPTION

SHEET

CHIEF DESIGN BRANCH

CHIEF, ENGINEERING DIVISION

APPROVED

DATE SCALE

CHECKED

PROJECT MANAGER

RECOMMENDED

SUBMITTED

DESIGNED BY Cesar M. Limon

DRAWN CML

NUMBER DATE

OF

PLATE

APPROVEDBY

DRY TYPE THREE PHASE TRANSFORMER SHALL BE REPLACED AND RELOCATED TO THE EAST SIDE OF THE BUILDING WHERE IT IS THE ELECTRICAL ROOM (SEE SHEET 2). THE TRANSFORMER AND FUSE DISCONNECT SAFETY SWITCH TO PROTECT THE SECONDARY BASED ON NEC 2017 CODE TABLE 240.21 C 6 TO SIZE FUSE SHALL BE NEMA 1. EXISTING TRANSFORMER IS FED FROM PANEL "MPD-3" FROM BREAKER #1 OF 175 AMPS LOCATED IN THE STORAGE ROOM (SEE SHEET 2-WS-22886-2018-E-EP-02). CONTRACTOR SHALL REMOVE EXISTING 112.5 KVA TRANSFORMER LOCATED IN THE KITCHEN AND ALONG WITH 3 /0 AWG CONDUCTORS FROM PANEL "MPD-3" BREAKER #1 AND FROM THE SECONDARY OF THE TRANSFORMER THAT FEEDS PANEL "PP" 400 AMP MAIN BREAKER WITH 350 MCM CONDUCTORS. CONTRACTOR SHALL INSTALL NEW DRY TYPE TRANSFORMER IN THE ELECTRICAL ROOM ALONG WITH LEVELING IT AND ANCHORED TO CONCRETE FLOOR TO SATISFY SEISMIC IEEE 693-RECOMMENDED PRACTICE FOR SEISMIC DESIGN (SEE SHEET 2) AND WIDEN THE DOOR TO THE ELECTRICAL ROOM TO BRING IN NEW DRY TYPE TRANSFORMER AS NEEDED. GROUT ELECTRICAL EQUIPMENT INSTALLED ON CONCRETE FOUNDATIONS IN PLACE TO PROVIDE FULL AND EVEN BEARING. CONTRACTOR SHALL USE EXISTING CONDUIT 3" TO FEED FROM THE NEW 112.5 KVA TRANSFORMER SECONDARY CONDUCTORS 3-350 MCM THHN RATED AT 600 V AT THE ELECTRICAL ROOM TO NEW PANEL "PP" MAIN BREAKER. NEW RIGID CONDUIT SHALL BE INSTALLED FOR THE NEW TRANSFORMER TO PRIMARY 3-1

AWG TO TERMINATE TO PANEL "MPD-3" BREAKER #1 (SEE SHEET 2-

WS-22886-2018-E-EP-02)

AT THE ELECTRICAL ROOM

TRANSFORMER AND FUSE DISCONNECT

SWITCH FOR SECONDARY SOLID BARE COPPER WITH PROPER COPPER CLAMPS. THE AREA WHERE OLD TRANSFORMER IS TO BE REMOVED, CONTRACTOR SHALL COVER AND GROUT TO MATCH EXISTING WALL AND WHERE THEY WILL RUN NEW CONDUIT AND IF DOOR IS NEEDED TO BE WIDEN AT THE ELECTRICAL ROOM, CONTRACTOR SHALL REMOVE AND INSTALL DOOR ALONG WITH REPAIRING ANY DAMAGES TO THE EXISTING WALL CLOSE TO THE DOOR.

1) EXISTING FEDERAL PACIFIC TRANSFORMER

480 V DELTA TO 208 / 120 V WYE

FREQUENCY: 60 Hz

IMPEDANCE: 4.05 %

112.5 KVA

PRIMARY CURRENT: 135 AMPS

SECONDARY CURRENT: 312 AMPS

LENGTH: 40 ½ INCHES

WIDTH: 31 INCHES

WEIGHT: 720 IBS

GENERAL NOTES:

TYPE TRANSFORMER

E12

I

S

S

U

E

D

T

O

C

O

N

S

T

R

U

C

T

I

O

N

Sam E. Morris

Rafael H. Acosta

Howard Guion

WS-22886-2018-E-EP-12

NEW TRANSFORMER DIMENSIONS

HEIGHT: 35.47 INCHES

HEIGHT: 31.90 INCHES

DEPTH: 26.88 INCHES

WEIGHT: 938 IBS

CONTRACTORS RESPONSIBILITY:

CONTRACTOR SHALL VERIFY AND LABEL EACH CIRCUIT ALONG WITH THE CONDUCTORS

SHOWN IN DRAWINGS OF THE EXISTING PANELS ARE WORKING PROPERLY PRIOR TO

REMOVING AND NOTIFY GOVERNMENT OF THE DEVICES THAT ARE NOT WORKING AND

WILL NOT BE RESPONSIBLE FOR THOSE DEVICES. THE EXISTING CONDUCTORS SHALL NOT

BE REMOVED BUT TRANSFERRED TO THE NEW PANEL AND TERMINATED TO THE CORRECT

BREAKER SIZE. EXISTING FEEDER CONDUCTORS SHALL BE REMOVED AND NEW ONES SHALL

BE SIZED AND INSTALLED TO MEET THE EXISTING LOADS THAT SHALL HAVE STRANDED COPPER, 600 V, THHN, AND TERMINATED TO PANELS PP,L, LA, MDP 2, MDP 3, P/1, LIGHTING CONTACTOR, AND DRY TYPE TRANSFORMER SHOWN IN THE DRAWINGS. EXISTING GROUND WIRES SHALL BE

REMOVED FROM EACH OF THE PANELS, LIGHTING CONTACTOR, AND DRY TYPE TRANSFORMER.

NEW GROUND COPPER WIRE WITH ASSOCIATED GROUNDING HARDWARE SHALL BE INSTALLED AND

TERMINATED TO EXISTING GROUND RODS. EACH PANEL AND SUBPANEL WILL HAVE A MAIN BREAKER

SIZED BY THE CONTRACTOR FOR THE AMOUNT OF BREAKERS ON IT. EXISTING CONDUIT THAT IS

EMBEDDED IN THE FLOOR AND IN THE EXISTING WALLS WILL BE USED BUT NEW CONDUIT SHALL

BE RAN FOR THE RELOCATION OF THE DRY TYPE TRANSFORMER. IF THE EXISTING CONDUIT IS TOO SHORT

FOR NEW PANELS, CONTRACTOR SHALL ADD GALVANIZED RIGID CONDUIT AS NEEDED TO THE EXISTING CONDUIT.

LABLE CIRCUITS IN THE NEW PANEL TO THE DEVICE IT GOES TO. ONCE EACH PANEL IS INSTALLED INDIVIDUALLY

THE CONTRACTOR WITH THE GOVERNMENT WILL RESET EACH BREAKER AND TEST THE DEVICES ARE WORKING

CORRECTLY.

112.5 KVA TRANSFORMER SECONDARY PROTECTION:

240 V, 3 PHASE, 3 POLE NEMA 1 SAFETY DISCONNECT

SWITCH HEAVY DUTY (FUSIBLE)

SERVICES VOLTAGES AMPERAGE FUSE

DRY TYPE

TRANSFORMER

SECONDARY 208 400 400

GENERAL NOTES

WHITE SANDS MISSILE RANGE, NEW MEXICO

ENGINEERING DIVISION

DIRECTORATE OF PUBLIC WORKS

DRAWING NUMBER

REVISIONS

DESCRIPTION

SHEET

CHIEF DESIGN BRANCH

CHIEF, ENGINEERING DIVISION

APPROVED

DATE SCALE

CHECKED

PROJECT MANAGER

RECOMMENDED

SUBMITTED

DESIGNED BY Cesar M. Limon

DRAWN CML

NUMBER DATE

OF

PLATE

APPROVEDBY

CONTRACTOR SHALL PROVIDE A JOB HAZARD ANALYSIS THAT SHALL BE REVIEWED AND APPROVED BY THE CONTRACTOR'S CQC AND SAFETY OFFICER. JOB HAZARD ANALYSIS (JHA) SHALL BE PREPARED TO IDENTIFY ALL HAZARDS SPECIFIC TO WORK TO BE PERFORMED. ANALYSIS

MUST INCLUDE ELECTRICAL SHOCK AND ARC FLASH HAZARD CONSIDERATIONS.

GOVERNMENT AND CONTRACTOR SHALL DO A PRE-CONSTRUCTION BRIEFING PRIOR TO PERFORMING THE CLEARANCE TO DE-ENERGIZE

THE PANELS AND DRY TYPE TRANS FORMER.

CONTRACTOR AND IT'S CQC AND SAFETY OFFICER SHALL PERFORM THE CLEARANCE AND FOLLOW THE JHA IN DOING A LOCKOUT TAG OUT.

CONTRACTOR SHALL WORK THE PANEL DE-ENERGIZED. A CLEARANCE IS TO BE PLACED BY CUTTING POWER FROM THE FEEDER INTO THE PANEL AND PLACING A CLEARANCE ON THE BREAKER THAT FEEDS THE PANEL. CONTRACTOR SHALL TRIP THE BREAKER AND PLACE A LOCKOUT AND TAG OUT TAG. SAFETY OFFICER AND CONTRACTOR'S CQC SHALL BE THERE TO WITNESS THE CLEARANCE PERFORM.

CONTRACTOR WILL THEN VERIFY IF THE PANEL IS DE-ENERGIZED. CONTRACTOR SHALL THEN VERIFY AND CHECK TO SEE THAT THE PANEL IS

DE-ENERGIZED WITH THE PRESENCE OF THE CONTRACTOR CQC AND SAFETY OFFICER.

INSTALLATION:

COMPLY WITH NFPA 70 NATIONAL FIRE PROTECTION ASSOCIATION AND IEEE C2 NATIONAL ELECTRICAL SAFETY CODE.

A. INSTALL WIRING WITHOUT EXCEEDING ALLOWABLE PULLING TENSIONS AND SIDEWALL PRESSURES

RECOMMENDED BY CABLE MANUFACTURER.

B. CONDUIT INSTALLATION:

1) DO NOT PULL WIRE INTO CONDUITS UNTIL THEY HAVE BEEN CLEANED AND ARE FREE FROM OBSTRUCTIONS AND SHARP CORNERS.

2) DRAW A CLEAN, DRY, TIGHT-FITTING RAG THROUGH CONDUIT IMMEDIATELY BEFORE INSTALLING WIRES.

3) INSTALL WIRES TO PREVENT CUTS OR ABRASIONS IN INSULATION OR PROTECTIVE COVERING, OR KINKS IN WIRE INSULATION.

4) BLOCK CABLE OPENING IN SLEEVES UNDER EQUIPMENT OR PASSING THROUGH BLOCK OUTS WITH SILICONE-FOAM, FIRE

RETARDANT TYPE MATERIAL IN ACCORDANCE WITH NFPA 70.

5) LUBRICANT:

a. USE ONLY AS AID PULLING.

b. SOAPSTONE OR OTHER SUITABLE MATERIAL NOT INJURIOUS TO CABLE SHEATH.

6) PULL ALL PHASES AND GROUNDS IN ONE CONDUIT.

7) PULL WIRES BY PULL STRING, OR USE TENSION METER OR RELEASE MECHANISM ON WIRE PULLING EQUIPMENT TO ENSURE PULLING

TENSION REMAINS BELOW TENSILE STRENGTH OF THE CONDUCTOR.

8) ALL CONDUCTORS THAT ARE TO BE INSTALLED FOR THE FEEDERS FOR THE NEW

PANELS AND TRANSFORMER SHALL BE MANUFACTURED NO MORE THAN 24

MONTHS PRIOR TO NOTICE TO PROCEED FROM CONTRACTING OFFICER (KO).

INSTALLATION OF ELECTRICAL EQUIPMENT INCLUDES:

1. LEVELING AND GROUTING CHANNEL BASES.

DRILLING HOLES, FURNISHING HARDWARE, AND ASSEMBLING COMPONENTS TO EACH

OTHER.

2. FURNISHING MATERIALS FOR AND MAKING ALL CONNECTIONS CORRECTLY IN

ACCORDANCE WITH WIRING DIAGRAMS.

3. LABELING WIRES AND TAGGING WIRES AND CABLES AT EACH END.

GROUT ELECTRICAL EQUIPMENT INSTALLED ON CONCRETE FOUNDATIONS IN PLACE TO

PROVIDE FULL AND EVEN BEARING. REPAIR DAMAGED PAINTED SURFACES OF EQUIPMENT TO

MATCH ORIGINAL FINISH. GOVERNMENT WILL INSPECT EQUIPMENT DURING CONSTRUCTION.

CONTRACTOR SHALL INDENTIFY AND TRACE EACH CIRCUIT. CONTRACTOR SHALL VERIFY WIRE SIZES LISTED IN TABLES FOR EACH PANEL AND TRANSFORMER IN ACCORDANCE WITH NFPA 70 BASED ON

90 DEGREES C CONDUCTOR TEMPERATURE THHN CONDUCTOR TEMPERTURE AND SIZES NO. 10

AWG OR LARGER. IN EVENT OF CONFILCT WITH NFPA 70 AND MINIMUM CONDUCTOR SIZE, USE

LARGER CONDUCTOR. UL LISTED AND LABELED ON OUTER SURFACE IN ACCORDANCE WITH

NFPA 70. JACKET COVERING FOR CONDUCTOR WIRE: PVC (POLYVINYL CHLORIDE) TYPE FLAME

RETARDENT. AS EACH CIRICUIT IS IDENTIFIED, THE CONTRACTOR SHALL INSTALL NEW CONDUCTOR BASED ON NEC TABLE 310.16 OF 90 DEGREES CELSIUS THHN STRANDED CONDUCTOR FOR DRY AND DAMP LOCATIONS. THE NEC 2017 STATES THAT NO MORE THAN 3% DROP AT THE SOURCE, AND 5%

DROP AT THE LOAD WILL USUALLY "PROVIDE REASONABLY EFFICIENCY OF OPERATION". WIRE

SIZING, AND VOLTAGE DROP IS IMPORTANT FOR ENERGY CONSUMPTION. EACH CIRCUIT SHALL

HAVE THE PROPER CONDUCTOR SIZE (NEC 2017 TABLE 310.16), INSULATION (NFPA 79 2015

SECTION 12.3.1.), PROPER CONNECTION OF THE TERMINALS, AND PROPER OVERCURRENT

PROTECTION NEC 2017 CODE STANDARD AMPERE RATING 240.6. THE FEEDER CONDUCTOR

AMPACITY MUST NOT BE LESS THAN THAT OF THE SERVICE CONDUCTORS. NEC 2017 ELECTRICIAN

CONDUCTOR IDENTIFICATION COLOR INSIDE THE PANEL 208 / 120 V WYE THREE PHASE

CONDUCTOR: A PHASE-BLACK, B PHASE-RED, C PHASE-BLUE, AND NEUTRAL-WHITE. NEC 2017

ELECTRICIAN'S CONDUCTOR IDENTIFICATION COLOR INSIDE THE PANEL 480 V DELTA-THREE

PHASE-COLOR: A PHASE-BROWN, B PHASE-ORANGE, C PHASE-YELLOW, AND NEUTRAL-WHITE. ALL

CONDUCTOR'S SHALL HAVE FLAME-RETARDANT PROPERTIES AND TEMPERATURE LIMITS AND

CHARACTERISTICS AS LISTED ON NPFA 79 2015 SECTION 12.3.1.

a) CONDUCTOR MARKERS:

· WHITE

· SELF-LAMINATING VINYL TYPE OR HEAT SHRINK TYPE.

· MARKED WITH CONDUCTOR DESIGNATION.

· COMPUTER GENERATED LETTERING.

(CONTINUED ON SHEET 14)

GENERAL NOTES:

E13

I

S

S

U

E

D

T

O

C

O

N

S

T

R

U

C

T

I

O

N

Sam E. Morris

Rafael H. Acosta

WS-22886-2018-E-EP-13

WHITE SANDS MISSILE RANGE, NEW MEXICO

ENGINEERING DIVISION

DIRECTORATE OF PUBLIC WORKS

DRAWING NUMBER

REVISIONS

DESCRIPTION

SHEET

CHIEF DESIGN BRANCH

CHIEF, ENGINEERING DIVISION

APPROVED

DATE SCALE

CHECKED

PROJECT MANAGER

RECOMMENDED

SUBMITTED

DESIGNED BY Cesar M. Limon

DRAWN CML

NUMBER DATE

OF

PLATE

APPROVEDBY

1) IF MORE THAN 3 CURRENT-CARRYING CONDUCTORS ARE IN THE SAME RACEWAY OR

CABLE, THE AMPACITY TABLES LISTED IN THE NEC 2017 MUST BE REDUCED USING TABLE

310.15 (B) (2) (a) AMBIENT TEMPERATURE CORRECTION.

2) IF THERE ARE FOUR OR MORE CURRENT- CARRYING POWER CONDUCTORS ARE IN THE

SAME RACEWAY LONGER THAN 24 INCHES, NEC 2017 TABLE 310.15 (B) (a), AMPACITY OF

EACH CONDUCTOR MUST BE REDUCED.

3) INSTALL THE FEED WIRED FROM THE AC SOURCE. INSTALL THE OUTPUT WIRES. REFER

TO WIRE SIZING CHART TO SELECT THE CORRECT WIRE SIZE NEC 2017 TABLE 310.16.

4) ALL ELECTRICAL CONNECTIONS MUST BE PROPERLY TORQUED TO PREVENT EXCESSIVE

HEAT BUILDUP CAUSED BY A LOOSE CONNECTION OR DAMAGE OF THE CONDUCTOR All

CAUSED BY OVERHEATING. TOO LOOSE A CONNECTION OR TOO TIGHT A CONNECTION

CAN CAUSE PROBLEMS. CIRCUIT BREAKER TERMINALS DIFFER FROM SWITCH AND AND

RECEPTACLE TERMINALS IN THE TIGHTENING TORQUE.

a) TERMINAL CONNECTORS:

1. HEAVY-DUTY, PRE INSULATED, PRESSURE-CRIMP TYPE WITH RING TONGUES.

2. TIN-PLATED COPPER.

3. SERRATED INNER BARREL.

4. 600-VOLT-RATED VOLT-RATED NYLON INSULATION.

5. INSULATION SUPPORT SLEEVE FOR VIBRATION RESISTANCE.

6. UL LISTED.

7. COMPATIBLE WITH CONDUCTOR SIZE AND TYPE OF CABLE FOR WHICH IT

USED..

5) ALL GROUND CONDUCTORS IN A BUILDING SHALL BE INSTALLED IN ACCORDANCE WITH

IEC 60364 ELECTRICAL INSTALLATIONS FOR BUILDINGS Buildings (INTERNATIONAL

ELECTRO TECHNICAL COMMISSION).

6) NEC 2017 ARTICLE 215.6, FEEDER CIRCUITS MUST INCLUDE OR PROVIDE AN EQUIPMENT

GROUNDING CONDUCTOR OF A TYPE LISTED IN 250.118, AND IT MUST TERMINATE IN A

MANNER SO THAT THE BRANCH CIRCUIT EQUIPMENT GROUND CONDUCTORS CAN BE

CONNECTED TO IT, AND INSTALLED IN ACCORDANCE WITH 250.134.

THE EQUIPMENT GROUNDING CONDUCTORS OF THE WIRE TYPE MUST BE SIZED NOT

SMALLER THAN SHOWN IN TABLE 250.122 (NEC 2017), BASED ON THE RATING OF THE

CIRCUIT OVERCURRENT DEVICE; HOWEVER, THE CIRCUIT EQUIPMENT GROUNDING

CONDUCTOR ISN'T REQUIRED TO BE LARGER THAN THE CIRCUIT CONDUCTORS.

GROUNDING ON THE LINE SIDE OF THE SERVICE SHALL BE DONE ACCORDANCE WTH

TABLE 250366 OF THE NEC 2107. CONNECTORS FOR GROUND CABLES, INCLUDING

FITTINGS, LUGS, BOLTS, NUTS, AND WASHERS: COPPER ALLOY. MAKE CONNECTIONS

WITH NEW EQUIPMENT TO EXISTING GROUNDING SYSTEM. ALL GROUND CONNECTION

BETWEEN EQUIPMENT AND MISCELLANEOUS METAL WORK, AND GROUND PLATES

OF THE GROUNDING SYSTEM WHETHER OR NOT SUCH GROUNDING CONNECTIONS

ARE INDICATED ON DRAWINGS. NUMBER OF GROUNDING CONNECTIONS FOR

EQUIPMENT MAY BE ONE, TWO, OR MORE IN SOME CASES. REMOVE PAINT, ENAMEL,

SCALE, OIL, GREASE, OR OTHER FOREIGN NONCONDUCTIVE MATERIAL FROM POINT

OF CONTACT ON METAL SURFACES BEFORE MAKING GROUND CONNECTIONS. REPAIR

DAMAGED OR REMOVED PAINT OR GALVANIZING MATERIAL ON METAL FINISHES.

a) RUN TO EACH SERVICE DISCONNECTING MEANS.

b) BONDED TO SERVICE DISCONNECTING MEANS ENCLOSURE.

c) ROUTED WITH PHASE CONDUCTORS.

d) SIZED NO SMALLER THAN GROUNDING ELECTRODE CONDUCTOR.

e) SIZED AT LEAST 12 12 PERCENT OF AREA OF CONDUCTORS WHERE LARGE THAN

GIVEN IN NEC 2017 TABLE 250.66.

f) BASED ON EQUIVALENT AREA OF UNGROUNDED PARALLEL SERVICE -ENTRANCE

CONDUCTORS.

g) SIZED IN ACCORDANCE WITH MINIMUM REQUIREMENTS OF NEC 2017 TABLE 220.61.

h) GROUND CABLE:

1) ANNELEAD BARE-COOPER:

a) ASTM B8, CLASS B.

b) SOLID WIRES USED IN FORMING THE COPPER CABLE: ASTM B3.

1) CONCENTRIC STRANDED.

2) SIZES:

a) MAJOR EQUIPMENT: SUB PANELS “P/1”, "PP", "L", "LA" , MAIN

PANEL “MDP-2”, "MDP 3", DRY TYPE TRANSFORMER, AND LIGHTING

CONTACTOR . i) CABLE CONNECTORS:

1) WELDED, BOLTED SOLDELESS OR COMPRESSION TYPE.

2) CURRENT-CARRYING CAPACITY: EQUAL TO CABLE WITH WHICH THEY ARE USED.

3) CONNECTORS FOR GROUND CABLES, INCLUDING FITTINGS, LUGS, BOLTS, NUTS, AND

WASHERS: COPPER ALLOY..

4) BOLTED SOLDERLESS OR COMPRESSION TYPE CONNECTORS: IEEE 837 Standard for Qualifying Permanent Conductors.

1) WIRING SHALL BE DONE PROFESSIONALLY, NEATLY, AND ORGANIZED ALONG

WITH LABELING EACH OF THE BRANCH CIRCUITS. IDENTIFICATION OF

CONDUCTORS SHALL BE DONE AS STATED IN NFPA 79 ELECTRICAL STANDARD

FOR INDUSTRIAL MACHINERY SECTION 13.2. OVERCURRENT PROTECTION

SIZING . FEEDER OVERCURRENT DEVICES MUST HAVE A RATING OF NOT LESS THAN

125 PERCENT OF THE CONTINUOUS LOADS, PLUS 100 PERCENT OF THE

NON-CONTINUOUS LOADS.

2) EACH PANEL SHALL HAVE THE PROPER MARKING AND SAFETY SIGNS AS STATED ON

NFPA 79 SECTION 16.2 SAFETY SIGNS FOR ELECTRICAL ENCLOSURES. PANEL SHALL

DISPLACE OUTSIDE LABELS ON THE DOOR OF THE PANEL WITH THE VOLTAGE 208 /

120 V WYE AND 480 V DELTA, DANGER, AND ARC FLASH WARNING SIGNS.

CONDUIT:

A) FITTINGS REQUIRED TO COMPLETE ELECTRICAL CONDUIT SYSTEMS.

INCLUDES CAPS, CONNECTORS, COUPLINGS (EXCLUDING EXPANSION AND

EXPANSION-DEFLECTION COUPLINGS), NIPPLES, REDUCERS, ELBOWS, PIPE,

PLUGS LOCKNUTS, BOND NUTS, BUSHINGS, SEALS (EXCLUDING WALL

PENETRATION AND ANY OTHER FITTINGS.)

B) DEVICES REQUIRED TO COMPLETE ELECTRICAL CONDUIT SYSTEMS AND TO

FASTEN, CLAMP, ATTACH, AND SUPPORT EACH CONDUIT IN PLACE.

1) INCLUDES THREADED JOINT COMPOUND; PROTECTIVE SEALANT; MATERIALS

FOR SEALING ENDS OF CONDUITS TERMINATING AT OUTDOOR BOXES, PANEL

BOARDS OR CABINETS; SUPPORTS AND CLAMPS.

2) COMPLETE WITH BOLTS, WASHERS, AND NUTS.

A) JUNCTION BOX, JUNCTION BOX EXTENSIONS, AND JUNCTION BOX COVERS:

STEEL, OR ZINC COATED.

B) EXPANSION COUPLINGS:

1) FURNISH FOR LONGITUDINAL MOVEMENT ONLY.

(CONTINUED ON SHEET 15)

GENERAL NOTES:

GENERAL NOTES

E14

I

S

S

U

E

D

T

O

C

O

N

S

T

R

U

C

T

I

O

N

Sam E. Morris

Rafael H. Acosta

WS-22886-2018-E-EP-14

WHITE SANDS MISSILE RANGE, NEW MEXICO

ENGINEERING DIVISION

DIRECTORATE OF PUBLIC WORKS

DRAWING NUMBER

REVISIONS

DESCRIPTION

SHEET

CHIEF DESIGN BRANCH

CHIEF, ENGINEERING DIVISION

APPROVED

DATE SCALE

CHECKED

PROJECT MANAGER

RECOMMENDED

SUBMITTED

DESIGNED BY Cesar M. Limon

DRAWN CML

NUMBER DATE

OF

PLATE

APPROVEDBY

2. ZINC COATED WATERTIGHT TYPE.

3. CAPABLE OF AT LEAST 4-INCH EXPANSION/CONTRACTION.

4. EXPANSION COUPLINGS FOR PLASTIC CONDUIT SHALL EXPAND AT LEAST 4 INCHES FOR EACH

100 FEET OF RUN AND FOR EACH 100 DEGREES F TEMPERATURE CHANGE.

A. EXPANSION-DEFLECTION COUPLINGS:

1. FURNISH FOR MOVEMENT IN ANY DIRECTION.

2. WATERTIGHT.

3. DEFLECTION AND EXPANSION: 3/4-INCH, MINIMUM.

4. ANGULAR MISALIGNMENT: 30 DEGREES, MINIMUM.

F. CONDUIT WALL/FLOOR PENETRATION SEALS:

1. ELASTOMERIC MATERIAL TO PREVENT LIQUID OR LIQUID AND GAS SEEPAGE.

2. DUST TIGHT.

3. FIRE RETARDANT.

H. REMOVE BURRS AND SHARP CORNERS AT ENDS OF METAL CONDUIT.

I. COAT MALE THREADS OF RIGID METAL CONDUIT JOINTS WITH SUITABLE GRAPHITE OR ZINC SEALING

MATERIAL BEFORE MAKING JOINTS.

J. TIGHTEN CONDUIT JOINTS SECURELY TO ENSURE ELECTRICAL CONTINUITY AND TO PREVENT ENTRANCE OF

MOISTURE OR FOREIGN MATERIAL.

K. INSTALL BUSHINGS OR CHASE-TYPE NIPPLES ON ENDS OF CONDUIT TO PROTECT INSULATION OF

INSULATED CONDUCTORS FROM ABRASION.

L. INSTALL LOCKNUTS AND BOND NUTS TO PROVIDE TIGHT GROUND CONNECTIONS BETWEEN CONDUIT AND

BOXES, PANEL BOARDS, AND CABINETS.

M. SEAL ENDS OF CONDUITS THAT TERMINATE AT BOXES, OR CABINETS WITH SEALING MATERIAL OR SEALING BUSHINGS TO PREVENT AIR CIRCULATION THROUGH CONDUITS INTO BOXES, CABINETS. INSTALL SEALS

IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.

N. TIGHTEN CONDUIT TO ELECTRICAL EQUIPMENT MOUNTED ON TUBULAR METAL STRUCTURES SECURELY AND SUPPORT RIGIDLY IN PLACE BY CONDUIT CLAMPS, HEX HEAD NUTS, AND THREADED 3/8-INCH STUD

FASTENERS DRIVEN BY POWER-ACTUATED TOOLS.

O. INSTALL EXPANSION COUPLINGS WHERE EXPOSED OR EMBEDDED CONDUITS CROSS EXPANSION OR CONTRACTION JOINTS. INSTALL EXPANSION COUPLINGS AND EXPANSION AND EXPANSION-DEFELECTION COUPLINGS IN

ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.

P. DRILL HOLES AS NEEDED IN CONCRETE FOR INSTALLATION OF CONDUIT THRU WALLS, FLOOR, OR CEILING. GROUT CONDUIT IN PLACE IN ACCORDANCE NO SHRINK GROUT. CONTRACTOR SHALL SUBMIT APPROVAL DATA (MANUFACTURER'S PRODUCT DATA) AND INSTRUCTIONS (MANUFACTURER'S SURFACE PREPARATION, MIXING, INSTALLATION, AND CURING INSTRUCTIONS).

CLEAN AND PREPARE BASE CONCRETE SURFACE TO WHICH GROUT WILL BE BONDED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.

1. ROUGHEN SURFACE.

2. REMOVE DIRT, LAITANCE, LOOSE OR DEFECTIVE CONCRETE, COATINGS, AND OTHER FOREIGN

MATERIAL.

3. WASH WITH WATER.

4. LUBRICATE CONCRETE SURFACE BY WASHING WITH WATER IMMEDIATELY BEFORE PLACING

GROUT WHEN DELAY OCCURS BETWEEN WASHING SURFACE AND PLACING GROUT.

5. REMOVE FREE WATER.

a) GROUT MIXTURE: ASTM C 1107 and PRE-MIXED, NONMETALLIC, COMMERCIAL GROUT MIXTURE.

b) WATER: CLEAN POTABLE WATER AS RECOMMENDED BY GROUT MANUFACTURER.

PLACE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS TO COMPLETELY FILL SPACE TO BE GROUTED. CURE EXPOSED GROUT SURFACES BY METHODS RECOMMENDED BY GROUT MANUFACTURER. DO NOT APPLY LOADS TO GROUT BEFORE 72 HOURS AFTER PLACEMENT. APPLY LOADS TO GROUT AFTER GROUT HAS ATTAINED A MINIMUM COMPRESSIVE STRENGTH OF 3,000 POUNDS PER

SQUARE INCH.

CHECK THAT ALL THREE PHASES ARE CORRECT (A, B, AND C). THE METER READING ON THE PHASING TESTER SHOULD

READ ZERO BETWEEN PHASE 1 AND PHASE A. THE CONTRACTOR'S CQC SHALL VERIFY WITH CONTRACTOR THAT EACH CIRCUIT THAT POWERS THAT PIECE OF EQUIPMENT TURNS ON AND WILL RUN WITHOUT TRIPPING THE CIRCUIT BREAKER.

GENERAL NOTES:

GENERAL NOTES

E17

I

S

S

U

E

D

T

O

C

O

N

S

T

R

U

C

T

I

O

N

Sam E. Morris

Rafael H. Acosta

Howard Guion

WS-22886-2018-E-EP-15

Additional Submittals

1) PROOF OF FEEDER CONDUCTORS FOR PANELS AND DRY TYPE

TRANSFORMER (THHN) TO HAVE BEEN MANUFACTURED WITHIN 24

MONTHS.

WHITE SANDS MISSILE RANGE, NEW MEXICO

ENGINEERING DIVISION

DIRECTORATE OF PUBLIC WORKS

DRAWING NUMBER

REVISIONS

DESCRIPTION

SHEET

CHIEF DESIGN BRANCH

CHIEF, ENGINEERING DIVISION

APPROVED

DATE SCALE

CHECKED

PROJECT MANAGER

RECOMMENDED

SUBMITTED

DESIGNED BY Cesar M. Limon

DRAWN CML

NUMBER DATE

OF

PLATE

APPROVEDBY

EXISTING 500 KVA PAD

MOUNTED

TRANSFORMER

COMPARTMENT

DOOR

CONDUIT AND ELECTRICAL

CABLE

AREAS CONTAMINATED WITH

RODENT DROPPINGS

IMPERMEABLE DROP CLOTH

CONTAINMENT AREA

TERMINAL

COMPARTMENT

5' 0" MIN.

5' 0" MIN.

5' 0" MIN.

LAYOUT: EXISTING 500 KVA PAD MOUNTED TRANSFORMER

LOCATION OF RODENT DROPPINGS AND CONTAINMENT

AREA LAYOUT

RODENT DROPPING REMEDIATION NOTES:

1. See the Rodent Droppings Remediation specification for all requirements. Specification to be provided as a separate attachment.

2. The Contractor shall ensure that the Government provides a copy of the specification before submitting a cost proposal.

3. Ensure electrical power is turned off before working on the transformer. Ensure lockout/tagout procedures have been implemented before the start of any work.

4. The Decontamination area is not shown because the contractor shall determine the specific location for the decontamination area.

The decontamination area shall be adjacent and connected to the containment area and shall be of sufficient size to allow the entry/exit of workers, equipment, and supplies; and to allow the decontamination of workers, equipment, and waste.

BUILDING 22886

LOCATION OF WORK

RODENT DROPPINGS REMEDIATION

WS-22886-2018-H-16

E16

I

S

S

U

E

D

T

O

C

O

N

S

T

R

U

C

T

I

O

N

Sheets and Views
B22886 AC Panel Replacement Revision_2-Title Sheet
B22886 AC Panel Replacement Revision_2-Sheet 2
B22886 AC Panel Replacement Revision_2-Sheet 3
B22886 AC Panel Replacement Revision_2-Sheet 4
B22886 AC Panel Replacement Revision_2-Sheet 5
B22886 AC Panel Replacement Revision_2-Sheet 6
B22886 AC Panel Replacement Revision_2-Sheet 7
B22886 AC Panel Replacement Revision_2-Sheet 8
B22886 AC Panel Replacement Revision_2-Sheet 9
B22886 AC Panel Replacement Revision_2-Sheet 10
B22886 AC Panel Replacement Revision_2-Sheet 11
B22886 AC Panel Replacement Revision_2-Sheet 12
B22886 AC Panel Replacement Revision_2-Sheet 13
B22886 AC Panel Replacement Revision_2-Sheet 14
B22886 AC Panel Replacement Revision_2-Sheet 15
Sheet 1.pdf
Sheets and Views
B22886 AC Panel Replacement Revision-Title Sheet
Sheet 2.pdf
Sheets and Views
B22886 AC Panel Replacement Revision-Sheet 2
Sheet 3.pdf
Sheets and Views
B22886 AC Panel Replacement Revision-Sheet 3
Sheet 7.pdf
Sheets and Views
B22886 AC Panel Replacement Revision-Sheet 6 (2)

File details come from the government source that posted it.