20250306_RFI_Response_Boilers.pdf
PDF 38 KB Posted
- Attached to
- Temporary Boiler Rental
- Solicitation number
- W911SD-25-R-A011
About this file
I apologize, but I cannot actually read the contents of the file "20250306_RFI_Response_Boilers.pdf" as no file text was provided in your message. I can only summarize the federal contract opportunity details that were included.
Based on the federal contract opportunity information, this is a Request for Information (RFI) related to a Temporary Boiler Rental solicitation for the Department of the Army at Fort Eustis. The specific requirement is for a contractor to provide an 800hp/250psi transportable steam boiler with natural gas connections for Buildings 756 and 845. The contractor will be responsible for supplying, installing, testing, providing on-call service, and managing chemical treatment throughout the boiler's operational period. The solicitation number is W911SD-25-R-A011, issued by the Mission and Installation Contracting Command at Fort Eustis.
Without the actual RFI response document, I cannot provide additional specific details about pricing, response dates, or other nuanced requirements. To provide a comprehensive summary, the text of the "20250306_RFI_Response_Boilers.pdf" would need to be shared.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 20250306_Solicitation_Amendment_W911SD25RA0110001_SF 30.pdf | ||
| 20250221_Performance_Work_Statement.pdf | ||
| 20250227_Solicitation - W911SD25RA011.pdf | ||
| 20241223_Wage_Determination_15-4159.txt | TXT text file |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFI Response – Temporary Boilers Bldg. 756/845 Timothy Garbiso – PM
RFI: Temporary Boilers Bldg. 756/845
Questions:
1. Regarding the rental boiler for Building 845: The steam boiler will be required** to deliver steam to the facility at 100psi. Would it be acceptable to provide a boiler with a 150psi max design?
Temporary rental boiler must be 800hp / 250 max design per SOW, due to if needed/requested to increase PPH output and pressure.
2. Regarding the rental boiler for building 756: The steam boiler will be required** to supply steam to the facility at 150psi. Would it be acceptable to provide a boiler with a 200psi max design?
Temporary rental boiler must be 800hp / 250 max design per SOW, due to if needed/requested to increase PPH output and pressure.