20250306_RFI_Response_Boilers.pdf

PDF 38 KB Posted

Attached to
Temporary Boiler Rental
Solicitation number
W911SD-25-R-A011
Issued by

About this file

I apologize, but I cannot actually read the contents of the file "20250306_RFI_Response_Boilers.pdf" as no file text was provided in your message. I can only summarize the federal contract opportunity details that were included.

Based on the federal contract opportunity information, this is a Request for Information (RFI) related to a Temporary Boiler Rental solicitation for the Department of the Army at Fort Eustis. The specific requirement is for a contractor to provide an 800hp/250psi transportable steam boiler with natural gas connections for Buildings 756 and 845. The contractor will be responsible for supplying, installing, testing, providing on-call service, and managing chemical treatment throughout the boiler's operational period. The solicitation number is W911SD-25-R-A011, issued by the Mission and Installation Contracting Command at Fort Eustis.

Without the actual RFI response document, I cannot provide additional specific details about pricing, response dates, or other nuanced requirements. To provide a comprehensive summary, the text of the "20250306_RFI_Response_Boilers.pdf" would need to be shared.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RFI Response – Temporary Boilers Bldg. 756/845 Timothy Garbiso – PM

RFI: Temporary Boilers Bldg. 756/845

Questions:

1. Regarding the rental boiler for Building 845: The steam boiler will be required** to deliver steam to the facility at 100psi. Would it be acceptable to provide a boiler with a 150psi max design?

Temporary rental boiler must be 800hp / 250 max design per SOW, due to if needed/requested to increase PPH output and pressure.

2. Regarding the rental boiler for building 756: The steam boiler will be required** to supply steam to the facility at 150psi. Would it be acceptable to provide a boiler with a 200psi max design?

Temporary rental boiler must be 800hp / 250 max design per SOW, due to if needed/requested to increase PPH output and pressure.