W911SD-16-B-0002-0003_ELEVATOR_RFI'S.doc
DOC document 118 KB Posted
- Attached to
- Remove & Replace Elevator
- Solicitation number
- W911SD-16-B-0002
About this file
Amendment 3 --answers to RFI's
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Abstract_for_Elevator_Bldg._745_at_WP_SF_1409rw.pdf | ||
| W911SD-16-B-0002-0003_ELEVATORS_CONFORMED_COPY.doc | DOC document | |
| W911SD-16-B-0002-0002_ELEVATORS.doc | DOC document | |
| W911SD-16-B-0002-0001_ELEVATORS.doc | DOC document | |
| W911SD-16-B-0002.docx | DOCX document | |
| TE__2_Elevator_Layout_Floor_Plan.pdf | ||
| TE__1_Elevator_Details_Drawing.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION SF 30 - BLOCK 14 CONTINUATION PAGE (SF 30)
The following have been added by full text:
RESPONSES TO RFI
W911SD-16-B-0002 ELEVATOR REPLACEMENT BUILDING 745 WASHINGTON HALL
Questions and answers (RFI)
Questions Company #1
1. Is the project tax exempt?
No—there are no tax exempt documents available
2. Do you require the new sump pump to be an OIL MINDER SUMP?
No
3. The specifications call for Drilling of the existing pit. Can you clarify that the elevator company has made no provisions for encountering rock when re-drilling? It would be very difficult to provide a fair and accurate price for drilling into rock.
Upon investigation if re-drilling is required we will look into alternate possibilities.
4. Please clarify if a certified welder is required?
Yes welders should have proper certification to work and must follow the proper safety procedures.
5. Do you require full height barricades with a lockable door?
Yes
6. Specifications call for a 4,000Lb elevator, but all information on existing elevator shows 3,000lb's - please clarify.
Please use the existing elevator information 3,000 lbs.
7. Is the existing machine room door code compliant or does it need to be replaced with new code compliant self-closing, self-locking, fire rated door?
The existing machine room door is code compliant.
8. Do you require a new drop ceiling put in the machine room or box out piping and other items not related to the elevator?
No
9. Do you require new HVAC in the machine room to meet the ASME code for microprocessor controllers?
No new HVAC is required for the machine room but the controller components must have integrated AC.
10. Do you require any fire alarm upgrades?
No.
11. Is the existing elevator connected to the generator?
No.
12. Do you require new lighting outside of each hoistway entrance?
Need clarification. If the question concerns building lights the answer is no. We will accept another question to clarify this issue if needed.
13. Please confirm the existing hoistway sills are in good condition and do not warrant replacement.
No.
14. Do you require new mainline disconnects?
Yes.
15. Do you require new 110V emergency cab light disconnects?
Yes.
16. Do you require a new car top railing?
Yes.
17. There is an escape hatch at the top of the hoistway, do you require this to be sealed off, locked and covered up?
No.
18. Do you require new piping from the pumping unit to the hydraulic cylinder? If so, please confirm that all piping is accessible above the ceiling.
Yes. All piping are accessible.
Company # 2 questions
#1- Are original building plans available that indicate an existing steel casing is in place or not in place?
No plan available. There are no known plans available.
2#- To eliminate the expensive re-drilling possibility, can we use either standard or in-ground telescoping or hole-less jack assemblies?
Upon investigation if re-drilling is required we will look into alternate possibilities.
#3- Is the fire panel and other devices up to current code? Is fire alarm system upgrade part of this renovation?
They are up to code. No fire alarm upgrades will be required.
#4- Is parking available. Is on-site storage available?
There is no parking available in central area. Staging area to be determined. Parking issues will be coordinated with the COR, yet do not plan on parking any personal vehicles and or contractor owned vehicles in the immediate vicinity. Parking at West Point is very limited and especially with the Central Area .
#5- Re-drilling the hole, if necessary, will be very expensive and intrusive. The cost of re-drilling is not based on depth in feet, but by the number of days on site. The travel, set up, and tear down are major factors as is hazardous waste disposal, etc. Combined with the actual drilling, the expense could exceed $65k. Has this been factored into the government estimate.
Refer to #2.
#6- When do you want our crew on site?
Contract will state the start and completion dates and working hours. A pre-construction /kickoff meeting will be scheduled after award of the contract and all dates will be reviewed. Due to the delay in the solicitation closing, the completion date will be changed in the contract.
#7- Does the project have any additional work beyond what is listed in the Statement of Work outlined in the elevator section?
We don’t anticipate any additional work being done.
The questions and answers as shown above are replies to questions received. If you feel that we have missed and or omitted your question, Please contact David Ariosto and copy Rick Williams with your issue and we will resolve the issue.
SECTION 00 10 00 - SOLICITATION
The following Delivery Schedule item for CLIN 0001 has been changed from:
| DELIVERY DATE |
| QUANTITY |
| SHIP TO ADDRESS |
| DODAAC |
POP 29-JUL-2016 TO
31-OCT-2016
| N/A |
| SEE SCHEDULE |
SEE SCHEDULE
US MILITARY ACADEMY
WEST POINT NY 10996
FOB: Destination
W16BCU
To:
| DELIVERY DATE |
| QUANTITY |
| SHIP TO ADDRESS |
| DODAAC |
POP 29-JUL-2016 TO
30-NOV-2016
| N/A |
| SEE SCHEDULE |
SEE SCHEDULE
US MILITARY ACADEMY
WEST POINT NY 10996
FOB: Destination
W16BCU
SECTION 01 00 00 - GENERAL REQUIREMENTS
The following have been modified:
STATEMENT OF WORK
Statement OF WORK (SOW)
ELEVATOR REPLACEMENT
The statement of work (SOW) for this project involves the replacement of Elevator 5B in Building 745-A, Washington Hall, of the United States Military Academy (USMA), West Point, New York.
The elevator that requires this work is one of two that service this buildings kitchen area. The kitchen provides dining services to over 4,000 Cadets & over 12,000 meals are prepared and served from this area on a daily basis. All work performed shall be done without any interruption of this service.
1.0. THE FOLLOWING ITEMS ARE TO BE REMOVED AND REPLACED WITH NEW.
A. Motor Room:
1. New power unit and valves
2. New Hydraulic piping muffler and isolation
3. New hydraulic and automatic freight door controllers
4. New fluorescent lighting and GFCI outlet
5. Painting
B. Hoistway:
1. Align rails, clean and paint: Replace if needed
2. Patch holes in Hoistway
3. New conduit and wiring
4. Replace covers and guards
5. New oil retrieval system
C. Entrance/Landings
1. New powered hoistway doors
2. New pushbutton stations, access switches
D. Car enclosure:
1. New Stainless Steel cab enclosure
2. New Powered gates
3. New car pushbutton station
E. Pit:
1. Clean pit
2. New Jack Unit and Piston
3. New spring buffers
4. New rupture valve
5. Drilling of existing pit, as necessary
6. New sump pump, piping and electrical outlet
7. New stop switch, lighting, GFI receptacle, etc.
F. Other: Any old equipment not listed above shall be replaced with new.
1.01 REMOVAL OF RUBBISH AND EXISTING EQUIPMENT
A. On a scheduled basis, the Contractor shall remove from the job site all rubbish generated in performing work specified in the Contract Documents.
B. Any component of the existing elevator that is not reused under the scope of work specified in the Contract Documents shall become property of the Contractor and, as such, shall be removed from the premises at the Contractors sole expense.
C. The Contractor agrees to dispose of the aforementioned equipment and rubbish in accordance with any and all applicable Federal, State, and municipal environmental regulations. The Contractor further accepts all liability that may result from handling and/or disposing of such material.
1. 02 QUALITY ASSURANCE
A. The approved elevator component manufacturers is:
1. Canton Elevator Products (Hydraulic Equipment), or approved equal
B. Additional approved equipment manufacturers:
1. Controllers:
a. GAL-Galaxy - or approved equal
b. Motion Controller Engineering - or approved equal
2. Fixtures:
a. GAL-Galaxy - or approved equal
3. Door Operator and Equipment:
a. Peelle - or approved equal
4. Autodial Telephone:
a. GAL-Galaxy - or approved equal
5. Roller Guides:
a. Hollister Whitney- or approved equal
6. Car Top Inspection Station:
a. GAL-Galaxy - or approved equal
7. Cab Manufacturer:
a. Peelle- or approved equal
1.03 STANDARDS
Except as modified by governing codes and by this Division, the work shall comply with provisions of the latest editions of the following:
A. ASME A17.1 (2013 Edition with Supplements): The American Society of Mechanical Engineers - Safety Code for Elevators and Escalators including Supplements.
B. International Building Code (2015 Edition)
C. United States Occupational Safety and Health Standards (OSHA)
D. NFPA 70- National Electrical Code (2014 Edition)
E. NFPA 72- National Fire Alarm Code (2016 Edition)
1. 04 SUBMISSION, SAMPLES, CUTS AND DRAWINGS
A. The Shop Drawings shall show material type and gauge, general dimensions, methods of attachment, location and size of reinforcements and openings, and a general arrangement of components. Approval thereof shall not relieve the Contractor of compliance with the specification, unless the attention of the USMA West Point is called to the non-complying features in writing.
The Drawings submitted shall be as follows:
1. Elevator layout; including Machine Room, Plan View, and Elevation, which shall be plotted from a computer aided design package and drawn to scale. Hand drawn submissions will not be accepted. Show all adjoining and related structures including shaft steel and or concrete beams, columns, column lines, etc. To include pit, casing, sump pump and pit equipment.
2. Elevator Car enclosure details and layout.
3. Hoistway entrance door details complete.
4. Fixture Drawings.
5. Car frame and car platform construction details and layout complete.
6. Machine isolation foundation fastening details and hydraulic oil line isolation fastening details (include manufacturer's data of all isolation equipment used).
B. Sample submissions (as requested by the USMA, West Point) shall include:
1. Cab or fixture material and finishes.
2. Braille plates and jamb designation.
3. Push-buttons, position indicators, emergency lighting fixture
C. At completion of the work of the contract, the Contractor shall submit to the USMA, West Point, six (6) copies of an Operation Maintenance and Parts Manual and six (6) complete sets of as-built. These shall be reviewed, and if approved, shall become the property of the USMA, West Point. Include at a minimum:
1. Legible schematic wiring diagrams including all changes made during installation.
2. Description of operation of elevator system installed.
3. Power unit including pump motor, valve, etc.
4. Car guide rollers and assemblies.
5. Controller and selector: Including parts information on relays, printed circuit boards, reverse phase relays, switches, lamps, electrical cables, monitors, modems, diagnostic hardware, diagnostic software and overload protection devices.
6. Door assemblies: Including hangers, rollers, door motor, door operator, door clutch assembly, door closers, door drive arms, related hardware, sheaves, door guides, interlocks and safety door edge.
7. Signal equipment: Including car station, hall stations, position indicators, direction indicators, fire service panel, smoke detectors, key switches and pushbutton assemblies.
8. Solid state starter.
9. Car top inspection station, limit switches, solid state leveling control units, leveling switches and alarm bell.
10. Pit equipment: pit stop switch, sump pump, oil retrieval system etc.
1.05 ACCEPTANCE DEMONSTRATION AND PERFORMANCE TEST
A. Demonstrate to the USMA, West Point or the USMA, West Point’s designated representative, the operation of the elevator system. Demonstration shall include:
1. Installation compliance with specifications and inspected by an independent QEI certified individual who shall issue a certificate indicating that the elevator has passed all requirements in accordance with the code checklist and is approved for use.
2. Contract speed, capacity, and floor-to-floor performance compliance with specifications.
3. Stopping accuracy and car ride compliance with specifications.
4. Operation of signal fixtures, operation of supervisory or dispatching system and fireman's service operation.
5. Upon completion of installation and before final acceptance, conduct a running speed test with full design load to verify compliance with performance requirements including Items 2, 3 and 4. An independent Q.E.I. Inspector, hired by the contractor will witness the test as outlined in A17.1 and sign off and certify that the elevator is safe for public use and provide a certificate for operation.
6. Operating Instructions: Provide instructions to the USMA West Point personnel, including safety procedures, proper operation of the equipment and routine maintenance procedures.
1.06 TERMS AND DEFINITIONS
The terms used herein are defined as follows:
A. “Owner" shall be the USMA, West Point.
B. "Contractor” shall mean the person, firm or corporation named in the Contract Documents who will execute the Work. It shall include all his employees, subcontractors, suppliers and Contractors.
C. “Provide" shall mean to supply, install and connect up complete and ready for safe and regular operation the particular work in accordance to the code check list.
D. “Install" shall mean to erect, mount and connect complete with related accessories.
E. “Furnish" or “Supply" shall mean to purchase, procure, acquire and deliver complete with related accessories.
F. "Notice to Proceed" shall mean a written document from the USMA West Point allowing the Contractor to commence only that portion of the Work stated in the written document.
G. “Work" shall mean the services, materials, labor and all other equipment required for complete and proper installation by the Contractor.
H. "Best", “first-class" or similar terms as applied to materials, products and workmanship shall mean that, in the Owner's opinion, there are no superior qualities of materials or products on the market, and there is no better class of workmanship.
I. “Concealed" shall mean in masonry or other construction, installed in furred spaces, within double partitions or hung ceilings, in trenches, in crawl spaces or in enclosures.
J. “Exposed" shall mean not installed underground or "concealed" as defined above.
1.07 PERMITS
A. The Contractor shall file all necessary plans and application with the local building department or other authorities having jurisdiction and obtain the required permits and approvals.
B. The Contractor shall submit to the Owner a copy of the permit application, elevator specs,permit and print of elevator drawings as submitted and approved by the authority having jurisdiction.
C. Upon completion of the work, and prior to final payments, tests may be made by the Owner of all materials and appliances installed hereunder. The Contractor shall furnish all labor, materials and test equipment required for such tests.
1. Should the tests show that any of the materials, appliances or workmanship are not first class or not in compliance with the Specifications, the Contractor, on written notice from the Owner, shall remove same and promptly replace them with other materials and appliances in conformity with the Specifications.
D. The Contractor shall perform all tests required by the USMA West Point, or other authorities having jurisdiction in the presence of the Owner and an authorized inspector to obtain Final Certificate of Inspection prior to turnover of the elevators to the Owner. All testing to be performed by Independent QEI Inspector.
1.08 PROTECTION
Protect all items against dirt and damage. The Contractor shall be held fully responsible for all damage until final acceptance. Any equipment or property of the Owner damaged by this Contractor or his employees' shall be restored to its original condition or replaced without cost to the Owner.
1.09 STORAGE
A. The USMA West Point will designate a suitable area where the Contractor may store equipment until the work is completed. All equipment shall be stored at the sole risk of the Contractor.
B. If the Contractor utilizes a construction trailer or similar structure, he shall provide his own lock and key, but a duplicate key shall be furnished to the Project Superintendent. The assigned storage area shall be left clear and unencumbered of material or debris and shall be left in a broom-clean condition at the completion of the workday. An approved type “Fire Extinguisher” shall be provided and installed on a wall for each staging area assigned to the Contractor.
1.10 WARRANTY
The elevator contractor shall guarantee the materials and workmanship of the apparatus furnished under these specifications and shall make good any defects which may develop within one (1) year from the date of completion. The warranty shall not include items affected by ordinary wear and tear or vandalism or improper or insufficient maintenance by others or abuse, misuse, or neglect or any other cause beyond the elevator contractor's control.
1.11 MAINTENANCE
A. Furnish full protective maintenance on the equipment described herein for a period of one (1) year from the date of final acceptance of the entire installation. The maintenance shall include monthly examinations, adjustments and lubrication of all equipment. The maintenance shall include a detailed check list of monthly services that conforms to manufacturers recommended maintenance procedures and A17.1 code requirements (Section 8.6). Also repair or replace any parts of equipment whenever this is required during the maintenance period and shall use only genuine standard parts produced by the manufacturer of the equipment installed.
The elevator contractor shall notify the USMA West Point prior to working on the equipment installed under this contract. The elevator contractor shall upon each visit record in detail work performed, parts and or material replaced or repaired in the elevator machine room log book and submit a copy of the same and receive a signature from the Owner's Representative after each visit.
Note: It is the responsibility of the elevator maintenance contractor to respond to any emergency regarding any elevators. In the event that someone is trapped in an elevator that is under contracted maintenance, the contractor will respond to free the passengers as soon as possible, to minimize the inconvenience to users. In any case, response time shall be no later than one (1) hour.
The contractor shall be responsible to service, maintain and record all elevator emergency circuits, (including the fire capture, related equipment and sensors) as part of the regular elevator maintenance contract.
B. All maintenance procedures and contracts shall be in accordance with the USMA West Point's requirements and shall be based on the Owner's form of maintenance contract. Contractor to fill out USMA’s preventative Maintenance Spreadsheet section on conveyance.
C. All work under the maintenance provisions shall be performed by competent personnel under the supervision and in the direct employ of the Contractor and 24- hour emergency call back service shall be available at all times and be included in the cost of the contract.
D. Provide interim maintenance on all units completed and put to service prior to the overall project completion.
E. Full protective maintenance requirements (at a Minimum):
1. Regularly and systematically examine, adjust, lubricate, clean and when conditions warrant repair or replace the following items and all other mechanical or electrical equipment.
2. Hydraulic power unit and accessories: pump, motor, valves, operating valves, pulleys, drive belts, flexible hydraulic hose and fitting assemblies, oil tank, muffler, strainer, sound isolating coupling, plunger, packing gland, scavenger system, piping and other components.
3. Motor, motor drives, motor windings, rotating element, commutator, field coil, brushes, brush holders and bearings, rotors, stators, slip rings.
4. Controller, Selector and Dispatching Equipment: all components including all relays, solid state components, resistors, condensers, transformers, contacts, leads, dashpots, computer devices, selector switches, mechanical or electrical driving equipment, coils, magnet frames, contact switch assemblies, springs, solenoids, resistance grids, hoistway vanes, magnets and inductors.
5. Hoistway door interlocks or locks and contacts, hoistway door hangers and tracks, bottom door gibs, cams, rollers, and auxiliary door closing devices for power operated doors. Chains, tracks, cams, interlocks, sheaves for vertical bi-folding doors.
6. Hoistway limit switches, slowdown switches, leveling switches and associated cams, vanes, and electronic components.
7. Guide shoes including rollers or replaceable gibs.
8. Power operated doors, door operators/actuators, door protective devices, car door hangers, tracks and car door contacts for both side slide and vertical bifolding doors.
9. Traveling cables.
10. Elevator control wiring in hoistway and machine room.
11. Car safety mechanism and Load weighing equipment.
12. Buffers.
13. All car and hoistway operating fixtures including hall lanterns, main lobby fixtures, car operating panels, car position indicator, car fans, electric door operators, proximity devices, safety edge, photo eyes, door reflectors and Starters' Panels.
14. The guide rails shall be kept free of rust. Where roller guides are used, rails shall be kept dry and properly lubricated when sliding guides are used. Renew guide shoe rollers and gibs as required to insure smooth and satisfactory operation.
15. Examine, and make necessary adjustments or repair to the following accessory equipment including relamping of signal equipment: corridor lanterns, car and corridor position indicators, car stations, traffic director station, electric door operators, interlocks, door hangers, safety edge, and autodial telephone systems.
16. Lighting: Contractor shall be responsible to relamp all lighting fixtures in the pit, machine room, and hoistway (including cab lighting), as required.
17. Cleaning: Contractor shall, during the course of all examinations, remove and discard immediately, all accumulated dirt and debris from the pit areas. Prior to the expiration of the one-year new product service anniversary date of this Contract, the Contractor shall thoroughly clean down the entire hoistway including all equipment, door tracks, saddles, ledges, separation beams, etc. of all accumulated dirt, grease, dust and debris. Pits shall be cleaned on a monthly basis.
18. Examine regularly and systematically all safety devices, and conduct an annual no load test prior to the expiration of the new product service.
19. Maintain all elevator equipment in hoistways, machine rooms, and pits in a clean, orderly condition, free of dirt, dust and debris.
20. Furnish lubricants compounded specifically for elevator usage.
21. Contractor shall not be required to make renewals or repairs necessitated by reason of negligence or misuse of the equipment or by reason of any other cause beyond the contractor’s control except ordinary wear and tear unless the contractor receives just compensation.
22. All work is to be performed during regular working hours of regular working days. Emergency calls shall be answered at all hours of the day or night.
23. The Contractor shall check the group dispatching systems (if applicable) and make necessary tests to insure that all circuits and time settings are properly adjusted, and that the system performs as designed and installed.
24. Contractor shall perform the required mandated inspections and tests as required per local jurisdictions during the term of the included one (1) year maintenance contract.
PART 2- DESCRIPTION
2.01 DESCRIPTION OF ELEVATOR SYSTEM
A.
BASE BID- ELEVATOR "5B" (BUILDING 745):
1. Quantity:
One (1) Conventional Drill Hole Hydraulic Elevator
2. Type:
Freight (Designated for Class "C-A" Loading)
3. Capacity:
3,000 lbs. ( Changed 3 August per RFI)
4. Speed:
45 FPM
5. Travel:
12'- 5"
6. Number of Landings:
3 - Basement, Loading Dock & Kitchen
7. Number of Openings:
Front: 2 @ Basement & Kitchen Floor
Rear: 1 @ Loading Dock Only
8. Operation:
Manual operation
9. Special Operation:
F.E.R. Service- Phase I
10. Control:
AC for Hydraulic
11. Platform Size:
Approx. 7' - 7" Wide x 5' - 3" Deep (Contractor to verify)
12. Buffers:
Spring
13. Car Enclosures:
Rigidized Stainless Steel
14. Landing Doors:
7' - 2" Wide x 8' - 0" High (Contractor to verify)
15. Door Operation:
Motorized Powered Bi-Parting Freight
16. Machine Location:
Remote (Approx. 75' - 0" at Basement)
17. Comm. Equipment:
Autodial Telephone
18. Power Supply:
Existing 208V
19. Fixtures:
Vandal Resistant Stainless Steel
20. Power Unit Type:
Submersible, 80 Starts per Hour
2.02 POWER UNIT (NEW)
A. The power unit shall be compactly and neatly designed with all components combined in a self-contained unit and with all adjustment features accessible. It shall include (at a minimum) a constant displacement rotary screw-type, pump motor designed for oil hydraulic elevator service, oil reservoir (minimum 10-gallon reserve) with an oil-level indicator, control valve, tank strainer in the suction line, integral pressure gauge and blowout proof muffler to reduce pulsations that may occur in the system. The pump and motor shall be submersible type. The power unit shall be tested and adjusted at the factory by operating a test elevator loaded to conform to the elevator specified herein. The power unit shall be located in the machine room.
B. The motor shall be designed for 80 starts per hour.
2.03 POWER UNIT ISOLATION (NEW)
A. The power unit shall be mounted on vibration sound dampeners designed to isolate the unit from the building structure. Sound and vibration isolation pads shall be installed between the motor/pump assembly and the power unit structure and between the power unit and the machine room floor.
1. Provide neoprene vibration isolator pads as manufactured by Mason Industries. (Model WSW or approved equal)
2. All wiring connections to the power unit shall be flexible conduit, minimum 36" long, and installed slack.
2.04 VALVES (NEW)
A control valve including safety check valve, up direction valve with high pressure relief including up leveling and soft stop features, lowering valve including down leveling and manual leveling feature shall be mounted in a compact unit assembly. Control valves shall be solenoid operated and designed to open and close gradually to give smooth control. All valves shall be readily accessible for adjustment. The valve shall be equipped with a “no pressure sensing device" which will disable the piston from dropping if the car is blocked for any reason.
2.05 JACK UNITS (NEW)
A. Design and construct the jack unit in accordance with the applicable requirements of the ASME Code. It shall be of sufficient size to lift the gross load at the rated speed to the height specified and shall be factory tested to ensure adequate strength and freedom from leakage. No brittle material, such as grey cast iron, shall be used in the jack construction.
B. The jack unit shall consist of the following parts: a plunger of heavy seamless steel tubing accurately turned and polished; a stop ring electrically welded to the plunger to positively prevent the plunger leaving its cylinder; an internal bronze, phenolic or babbitt-lined guide bearing, packing or seal of suitable design and quality, a drip ring around cylinder top and a cylinder made of steel pipe and provided with a pipe connection and air bleeder.
C. For in ground jacks, provide cylinder with a factory applied extruded coating or two (2) layers of tape coat designed for corrosion prevention. Tape coat shall be "scotch wrap".
D. Remove the existing jack unit and PVC liner and replace it with a new jack unit and PVC liner. Provide new steel mounting channels for jack assembly.
2.06 JACK HOLE (TO BE CLEANED OUT AND REUSED)
A. Re-drill hole to proper size, if needed. Provide an additional Schedule 80 fully enclosed PVC Liner of minimum diameter four inches greater than the hydraulic cylinder diameter Include a water stop ring to be cast into the pit floor. If re-drilling the jack hole is required there will be an additive bid item $/foot (estimated at 5 feet).
B. All spoils shall be removed from site by the elevator contractor.
2.07 PACKING GLAND AND OIL RETRIEVAL SYSTEM (NEW)
A. A steel packing gland with phenolic guide bearing, wiper ring and packing especially designed for hydraulic elevator service shall be provided. An oil retrieval system shall be furnished to return oil leakage back to the storage tank.
1.
Provide an automatic motorized pump oil retrieval system for the elevators.
The pump shall have adequate discharge pressure to pump retrieval oil to a remote machine room as shown on the drawings. The pump shall include a screen strainer and be self-priming, self-lubricating and float activated. The sealed unit shall be manufactured by Wagner or Leland Industries. Include automatic shut off provisions in the event of water accumulation in the pit.
2.08 PIPING (NEW)
A.
Provide and install new schedule 80 piping from the power unit to the jack unit. All piping shall be supported at intervals not exceeding 10’- 0" and on each section of pipe.
B.
Provide a pipe rupture value as close as possible to the pipe inlet into the cylinder.
2.09 HYDRAULIC MUFFLER AND ISOLATION COUPLINGS (NEW)
A.
A muffler shall be provided in the oil line near the power unit. The muffler shall be designed to reduce pulsation and noise which may be present in the flow of the hydraulic fluid.
Provide two-sound isolation couplings in the oil line. The couplings shall incorporate neoprene seals and gaskets to limit the transmission of vibrations.
2.
In the event of remote machine room, all piping between the machine room and hoistway shall be supported at intervals not exceeding 10' - 0" utilizing vibration isolation hangers on the pipe stand. The pipe shall be covered with pre-molded fiberglass insulation with a smooth plastic cover.
3.
When the hydraulic pipe penetrates a wall or slab, it shall be sleeved with steel sleeves to provide a minimum of 1" annular gap between the sleeve and the pipe.
2.10 CONTROLLER AND OPERATION (NEW)
A.
The elevator controller shall utilize a generic, non-proprietary microprocessor based logic system and shall comply with ANSI/ASME 17.1, 2013 Edition. Safety code for elevators. The system shall provide comprehensive means to access the computer memory for elevator diagnostic purposes without need for any external devices, and shall have permanent indicators to indicate important elevator statuses as an integral part of the controller. Systems that require hook up of external devices for troubleshooting are not acceptable. The system shall include a self-contained air conditioning unit.
B.
The control system shall provide comprehensive means of accessing the computer memory for elevator diagnostic purposes. It shall have permanent indicators for important elevator statuses as an integral part of the controller.
C.
Failure of any single magnetically operated switch, contactor, or relay to release in the intended manner; the failure of any static control device, speed measuring circuit, or speed pattern generating circuit to operate as intended; the occurrence of a single accidental ground or short circuit; shall not permit the car to start or run if any hoistway door or gate interlock is unlocked or if any hoistway door or car door or gate contact is not in the made position. Furthermore, while on car top inspection or hoistway access operation, failure of any single magnetically operated switch, contactor or relay to release in the intended manner; the failure of any static control device to operate as intended; or the occurrence of a single accidental ground, shall not permit the car to move even with the hoistway door locks and car door contacts in the closed or made position.
D.
Dedicated permanent status indicators shall be provided on the controller to indicate when the safety string is open, when each door lock is open, when the elevator is operating at high speed, when the elevator is on independent service, when the elevator is on fire service, when the elevator out of service timer has elapsed, and when the elevator has failed to successfully complete its intended movement. In addition, a means shall be provided to display other special or error conditions that are detected by the microprocessor.
E.
An out of service timer shall be provided to take the car out of service if the car is delayed in leaving the landing while there are calls existing in the system.
F.
Car and hall call registration and lamp acknowledgment shall be by means of a single wire per call, in addition to the ground and the power bus. Systems that register the call with one wire and light the call acknowledgment lamp with a separate wire are not acceptable.
G.
Fire Phase I emergency recall operation, alternate level Phase I emergency recall operation shall be provided according to applicable local codes.
H.
A relay panel inspection switch and an up/down switch shall be provided in the controller to place the elevator on inspection operation and allow the user to move the car in the hoistway. The car top inspection switch shall render the relay panel inspection switch inoperative.
I.
Hoistway Access Key switch operation at the terminal landings are to gain access to the top of the car from the top landing and to gain access to the pit from the bottom landing.
J.
The elevator shall not require the functioning or presence of the microprocessor to operate on car top inspection or hoistway access operation to provide a reliable means of moving the car if the microprocessor fails.
K.
A phase quality monitor shall be provided that monitors high or low voltage, phase loss, phase imbalance or phase reversal. The monitor shall be manual reset type.
L.
A motor limit timer function shall be provided which, in case of the pump motor being energized longer than a predetermined time, shall cause the car to descend to the lowest landing and park, open the doors automatically and then close them. Car calls shall be canceled and the car taken out of service automatically. Operation may be restored by cycling the main line disconnect switch or putting the car on access or inspection operation. Door reopening devices shall remain operative.
M.
A valve limit timer shall be provided which shall automatically cut off current to the down valve solenoids if they have been energized longer than a predetermined time. The car calls shall then be canceled and the car taken out of service automatically. Operation may be restored by cycling the main line disconnect switch or putting the car on access or inspection operation. Door reopening devices shall remain operative.
N.
A selector switch shall be provided on the controller to select high or low speed during access or inspection operation as long as contract speed does not exceed 150 feet per minute.
O.
Viscosity control shall cause the car to accomplish the following operation. A temperature sensor shall be provided to determine if the oil is too cold, and if there are no calls registered, the car shall go to the bottom landing and, as long as the doors are closed, the pump motor shall run without the valve coils energized to circulate and heat the oil to the desired temperature. In the event that the temperature sensor fails,a timer shall prevent continuous running of the pump motor. Provide means to disable this feature.
P.
Provide PLC controllers as manufactured by Elevator Systems, Inc. or C&L Controls or approved equal.
2.11 OPERATIONS
A.
Manual elevator with powered doors and gates
2.12 FREIGHT DOOR CONTROLLER
A.
Control panels shall be furnished to electrically energize door and gate motors. Controllers shall be mounted within the machine room.
B.
Power doors and gates shall be arranged to open automatically as the elevator arrives at a floor and to close by momentary pressure push button operation.
C.
Power operated doors shall be provided with Sequence Operation between door and gate and with a reopening device on the gate. The landing doors and car gates are set so that in closing, the car gate shall be closed at least two-thirds of its travel before the landing door can start to close.
D.
The power operators and electric controls shall be designed to prevent electrical overload should an obstruction prevent the landing doors or car gate from moving with power applied. After removing the obstruction, the equipment shall be capable of being returned to service immediately.
E.
Power equipment design shall allow immediate emergency manual operation of the landing doors and car gates without disconnecting the power equipment.
F.
System shall be provided with automatic sequential closing with all associate codes mandated safety signaling provisions (including but not limited to bell and strobe light actuation upon initiating of closing sequence). This feature shall allow the doors to close automatically after an adjustable pre-determined time period. (The adjustable door dwell time shall be adjustable from 0 to 3 minutes in increments of 15 seconds.) Provide key switches in the car station to enable/disable this feature, the strobe and the bell. (Note emergency recall will initiate sequential closing without delay.)
2.13 FIRE EMERGENCY OPERATION (NEW)
A.
Phase I - Emergency Recall Operation shall be provided in accordance with ASME A17.1 and local codes.
B.
The car operating station shall be provided with an indicator light warning buzzer, each of which shall become activated whenever Phase I Operation is engaged. The warning buzzer shall cease to function once the car has completed the recall sequence and is positioned at the designated recall landing. The indicator light shall remain illuminated as long as Phase I Operation is activated.
C.
A three (3) position key-operated switch shall be provided on the designated recall landing per local law to manually activate Phase I Operation. When activated, Phase I Operation shall be arranged so that in order to reset normal service, the car must first be returned to the designated recall landing, after which the Phase I key-switch must be turned to the "OFF" position.
2.14 REDUCED CURRENT STARTING (NEW)
A Reduced current starting shall be furnished which shall limit both the initial starting current and peak current drawn by the motor.
Provide Wye-Delta reduced voltage starting systems.
2.15 LOW OIL CONTROL (NEW)
A In the event of a low oil condition, a low oil control feature shall be provided designed to automatically cause an up traveling car to descend to the lowest terminal landing to permit passengers to egress. The doors shall then automatically close and all control buttons, except the "Door Open” button in the car operating panel, shall be made ineffective. The oil reservoir should be refilled before the elevator is returned to service The low oil control may be utilized as part of the Automatic Lowering Feature as specified herein.
2.16 PLATFORM (NEW)
A The platform shall be steel construction (structural steel members). The floor is to be constructed of two (2) layers of 3/4" marine-grade plywood. The underside of the platform shall be properly fireproofed with 26 gauge galvanized steel metal in a maximum of two (2) sections. Provide a layer of unitized 14 gauge stainless steel between the two layers of plywood. Refer to cab section for finished flooring.
B.
The hydraulic elevators manufacturer’s standard bolster vibration isolation system may be used. Rubber vibration isolation pad shall be a minimum of 1" thick in a hardness to suit the application.
2.17 CAR GUIDE SHOES
A The car frame shall have roller-guide shoes attached at the upper and lower portion of the stiles. These roller-guide shoes shall be adjustable, spring loaded type with adjustable mounting base, rigidly bolted to the top and bottom of each side of the car frame.
1.
Rollers for the car shall be a minimum of 6" diameter and shall be as manufactured by Hollister Whitney.
2.18 BUFFERS (NEW)
A.
Spring type buffers shall be provided in the elevator pit.
2.19 DOOR EDGE PROTECTIVE DEVICE
A.
Provided with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person. The device shall be capable of completing these operations without required contact for an obstruction passing through the opening. The device shall be a non-reflective through beam system with a minimum of forty sensors per edge. It shall have a maximum sensor spacing of 1.8" or less. It shall incorporate a microprocessor controlled fail-safe system. It shall be capable of self-adjustment to compensate for varying environmental conditions.
2.20 FREIGHT ELEVATOR DOORS AND GATES (NEW)
A.
Provide counterbalanced, vertical slide and bi-parting freight elevator door and track assembly at each open landing entrance and where shown on the contract drawings. Provide one vertical slide-up counterweighted car gate at each entrance on the car as required.
Doors and gates shall comply with the latest edition of the ANSI/ASME A17.1 Code for Elevators (Section 3.13).
B.
The doors shall be stainless steel as manufactured by Peele or approved equal and shall bear a 1 ½ hr. UL "B" label. The top edge of each lower door panel shall have a Truckable Sill designed to meet the ANSI/ASME A17.1 code requirements for the loading/class specified (Section 3.16). The lower edge of the upper panel shall be equipped with a Resilient Astragal. An automatic stay-closed device (dual-side tension latching) shall be provided to minimize separation of the panel edges when closed. The vertical edges of the door frame shall have shoe angles with solid precision grooved shoes, hinged fire lintel on the upper panel of each pass type door and shall have one (1) vision panel per landing door assembly. Doors shall be constructed of steel with angle framing and shall present a flush appearance to the room side.
C.
Rails/guides shall be steel and have adjustable trucking sill stops. Door sections shall be connected to each other with suitable roller chain running over grooved ball bearing sheaves. Connection to the upper panel with malleable iron connectors and to the lower panel with cold rolled square rods with adjustable connectors. All material shall have one coat factory applied rust inhibitive shop primer.
D.
Each landing door assembly shall be equipped with an approved interlock. Each interlock within type limitations shall bear a UL label.
E.
Each door shall be electrically operated with two motorized two-speed door operators mounted on either side of the door assembly (if applicable). Door travel shall be determined by direct drive limit switch actuation, motor speed controlled to minimize slam or rebound, and designed to insure full opening and full closing. An operating mechanisms shall be entirely within the elevator shaft. The equipment shall permit immediate emergency manual operation. (Pull chain stations at each opening.)* Each landing door shall be provided with manufacturer’s standard weather stripping.
F.
Car gates shall be counterweighted, vertical slide-up two-section as required. The entire gate assembly shall be constructed of stainless steel with channel steel frame and channel stiffeners on vertical centers. Each gate shall be provided with a vision panel, shoe angles, guide shoes, guide rails, suitable roller chains arranged to insure balanced vertical motion with adjustable connectors, ball bearing sprockets for manual operated gates, ball bearing sheaves for power operated gates positively guided counterweight and an approved electric contact.
G.
Each gate shall be electrically operated by a motorized two-speed gate operator. Gate travel shall be determined by direct drive limit switch actuation, motor speed controlled to minimize slam or rebound, and designed to insure full opening and full closing. The equipment shall permit immediate emergency manual operation.
H.
Provide an infra-red beam type reopening device that will stop and reopen the car gate and hoistway door automatically if the door becomes obstructed by an object or person. The device shall be capable of completing these operations without required contact for an obstruction passing through the opening.
I.
Provide new stainless steel, non-slid sills at loading dock level. Scrape, patch and paint existing sills at basement and kitchen levels.
2.21 EMERGENCY EXIT CONTACTS (NEW)
A.
Top emergency exit shall be provided with electric contacts to prevent the operation of the car and sound an alarm when the exit door is opened. Means shall be provided to secure the escape hatch from the car top to ensure it may only be opened from the top of the car by authorized personnel.
2.22 INSPECTOR'S OPERATING STATION (NEW)
A.
An inspector's operating station shall be provided on top of the elevator car consisting of "Up", "Down" and "Safety" constant pressure buttons, incandescent light with guard, 110 Volt G.F.I. work outlet and an emergency stop switch.
1.
Provide an additional light with guard and G.F.I. Work outlet mounted to the bottom of the car and located towards the front for easy access.
2.
Provide audible and visual indicators to identify activation of Phase 1 Firemen's Service.
2.23 PIT EMERGENCY STOP SWITCH (NEW)
A.
An emergency stop switch shall be provided in the elevator pit, designed to cut off current supply to motor and "down" direction valves and bring the car to rest independent of the regular operating devices.
1.
Locate the pit stop switch (s) in accordance with A17.1 code requirements
(Section 3.26).
2.
Switch shall be capable of being pad locked in the "off" (stop) position.
2.24 ALARM BELL (NEW)
A.
An electric signal bell shall be provided on the car top. This bell shall be connected to the alarm button in the car operating panel and shall be powered by its own battery pack in the event of a power failure.
2.25 CAR OPERATING PANEL (NEW- MAIN AND AUXILIARY)
A.
Stainless steel car operating panels shall be furnished in the car containing illuminating buttons for each landing, emergency car light with flush lens, door open and close buttons, autodial telephone, emergency stop switch, fireman's service indicator light and audible signal, alarm button and keyswitches for out-of service and light.
1.
The autodial telephone unit shall be concealed behind the faceplate. Provide a perforated hold pattern in the faceplate for speakers and microphone voice transmission.
2.
Provide as manufactured by PTL, Inc or approved equal.
3.
Provide door open/door close buttons.
2.26 ILLUMINATED CALL AND CAR BUTTON
A.
Call registration lights shall be provided in each push-button unit. When a button is pressed, it shall illuminate, signaling to the waiting passenger that the call has been registered. Each button shall remain illuminated until the call has been answered.
1.
Provide PTL Centurion VR (vandal resistant) or approved equal.
2.27 HALL CALL STATIONS
A.
Provide faceplates with beveled edges and tamper proof fasteners in a # 4 brushed stainless finish.
B.
Provide fireman's service Phase I keyswitch with engraved instructions at the main egress level or as directed by the local authorities.
C.
Provide PTL Manufacturing Centurion VR (vandal resistant) fixtures or approved equal.
D.
Hall station at loading dock shall be NEMA 4 rated.
2.28 HOISTWAY ACCESS SWITCHES
A.
Provide a hoistway access keyswitch type Medeco R63C at the top and bottom terminal floors for each elevator.
2.29 ELECTRIC WIRING (ALL DESIGNED FOR EXTERNAL APPLICATION)
A.
It shall be the responsibility of the Contractor to furnish and install complete, insulated wiring to connect all parts of the equipment. Wiring, conduit, fittings and installation shall be in accordance with exterior application, and comply with therequirements of the National Electric Code. Conduit and fittings shall be of the rigidized type with water tight fittings.
B.
Insulated wiring shall have a flame retarding and moisture resisting outer cover and shall run in concealed galvanized metal conduit, metallic tubing or wire ducts.
1.
Flexible liquid-tight shall be permitted for short runs only (less than 36").
C.
Traveling cables between car and hoistway shall have a flame retarding and moisture resisting outer cover. They shall be flexible and suitably suspended to relieve strains in the individual conductors. The traveling cable shall also include:
1.
A minimum of 10% spare conductors (ends to be left accessible to facilitate connections at a later date).
2.
Wiring as required for the auto-dial telephone and firemen’s communication
(as required per local code).
3.
Six (6) pairs of 18 gauge shielded cables, (terminating on terminal strips in the controller and in the car operating station).
4.
Traveling cable to include coaxial camera cable for future connection.
2.30 TERMINAL STOPPING DEVICES (NEW NEMA 4)
A.
Provide new upper and lower normal terminal stopping devices arranged to automatically stop the car from any speed attained in normal operation within the top and bottom overtravel, independent of the operating devices, final terminal stopping device and buffers.
B.
Final terminal stopping devices shall be through bolted to the rails.
C.
Covers for all stopping devices (normal, slowdown and final) shall be provided with internal parts. Opening on limit switches shall face down.
2.31 PERFORMANCE
A.
For Hydraulic Elevators, speed to be within 3% of rated speed in the up direction and 5% in the down direction under any load.
B.
Leveling to be within 1/8" of the Hoistway Sill level.
C.
Maximum 400 psi working pressure. (For Hydraulic Elevators)
2.32 CAR ENCLOSURE
A.
Shell- 14 gauge textured stainless steel (5WL pattern) for walls and
12 gauge reinforced stainless steel sheet metal for canopy. Apply sound deadening mastic to rear of shell.
B.
Flooring - 1/8" stainless steel diamond plate with all seams and edges caulked with clear construction silicone.
C.
Fronts - Strike post, front return and transom shall be 14 gauge stainless steel with a No. 4 finish. Reinforce strike post with formed stainless steel channel backing.
D.
Gates- Stainless steel mill finish.
E.
Lighting/Ceiling - Recessed fluorescent fixtures in the ceiling. Ceiling fixtures shall be provided with a stainless steel frame and "security type" lexan lens.
F.
Handrail(s) - Handrail and…