QUESTIONS AND ANSWERS
Please confirm the exhaust fan will be similar to a model AERN80LK(plan E1.0), and that it should be 80 cfm not the fan mentioned in spec section 23 34 23 – 2.01 mention a 150 cfm.
ANSWER: Government Response: 80 cfm exhaust fan shall be used.
After the walkthrough it was hard to determine if there was adequate exhaust ductwork and louvers in place. Please reference attached picture for what we found. It appears something may be wrong with the ducting of these exhaust fan units. Should new ducting be included in the scope of work? If so, should it go through ANSWER: Government Response: New exhaust fans shall vent through the roof not the soffit with new duct.