SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

SECTION 00100 - BIDDING SCHEDULE/INSTRUCTIONS TO BIDDERS

The following have been modified:

CONTRACTOR Q&A

Q1. Will razor wire be required on any temporary or altered fencing? (none shown on plan set, just barbed wire shown)

A1. Temporary fence can either be 8’ in height or 6’ with 3 strands of barbed wire.

Q2. What are the security requirements/measures that will be required for maintaining the secure fencing perimeter? (only afterhours, during, etc.)

A2. Keep the construction gate closed as much as possible.

Q3. Can a work trailer & restrooms be placed in the parking lot?

A3. Yes, it can also be placed inside the security fence.

Q4. On Page S101, it shows the existing security window next to the ramp in the existing building being removed (shown with dotted lines). If the existing security window is removed are we to save? Or install at vestibule 101 new location?

A4. The existing security window is not to be removed. A new security window, as per specifications, is required.

(End of Summary of Changes) image1.wmf