PWS Reference

Question
Answer
C.2.2 & C.2.3
The Salient Characteristics doc requires the heat exchanger to cool the exhaust gas to 100' F or lower, while the blower package is required to operate with an inlet temperature of up to 125' F.

Is this a typo?

This is not a typo. The heat exchanger should be able to cool the exhaust gas to 100 deg F or lower, while the blower should be able to operate with an inlet temperature of up to 125 deg F. This is so there is some safety margin in case something goes wrong with the heat exchanger.