A01_-_Salient_Characteristics.docx

DOCX document 27 KB Posted

Attached to
Kohler Generators Federal contract opportunity
Solicitation number
W911QX-18-T-0070
Issued by
Department of the Army Materiel Command Army Contracting Command Aberdeen Proving Ground

About this file

Salient Characteristics

View the file

Other files for this federal contract opportunity

Other files attached to Kohler Generators, newest first.
File Type Posted
C01_-_Synopsis_of_Award.docx DOCX document
A02_-_Combination_Synopsis-Solicitation_for_Commercial_Purchases.docx DOCX document
A02_-_Provisions_and_Clauses_Full-Text_Attachment_(for_Combo_Synopsis-Solicitation).doc DOC document
A03_-_Redacted_Brand_Name_Simplified_Acquisition_Sole_Source.pdf PDF
A07_-_Evaluation_Criteria_(LPTA).docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salient Characteristics

The Army Research Laboratory requires the brand name Kohler generators below:

Generator #1 – Quantity: one (1) Kohler model: 400REOZJ

· Killowatt (KW): 400

· 120/208 Radiator

· 60 Hertz

· Fuel: Diesel

· Underwriters Laboratories (UL) 2200 Listed

· DEC-3000 Digital Generator Set Controller with digital display of voltage, amperes, frequency, accumulated run time, oil pressure and water pressure, rotary/push button selection, integral voltage regulation with +/-0.5% regulation, integral generator protection, Modbus communication

· Kohler factory outdoor weather housing equipped with locking doors with enclosed insulated critical silencer, tailpipe and rain cap

· 1135-gallon sub-base fuel tank UL 142 Listed double-wall construction equipped with fuel level gauge, low level alarm, and fuel-in-rupture-basin-alarm.

· Engine block heater

· Electronic isochronous governor

· Certified Test Report

· Factory 0.8 Power Factor Test

· Form C dry contacts

· Flexible fuel connections

· 800amp circuit breaker

· 800amp circuit breaker

· Battery rack and cables

· Remote annunciator

· Kohler battery charger, 10amp float type, with alarms

· Steel skid base with end caps and lube oil drain extension

· Lube oil and antifreeze

· Operations and Maintenance manual on CD-ROM

Generator #2 – Quantity: two (2) Kohler model: 175REOZT4

· KW: 154, 154, 106

· Voltage: 277/480, 120/208, 120/240, 120/240

· 60 Hertz

· Fuel: Diesel

· UL 2200 Listed

· EPA Tier 4 Final

· Dec 3500 Microprocessor control panel equipped with voltmeter, ammeter, frequency meter, running time meter, LCD display panel, engine gauges including lube oil pressure, battery voltage, fuel level, emergency stop button, integral generator protection and Modbus communication

· Kohler factory sound-attenuated weather housing equipped with locking doors with enclosed insulated critical silencer, tailpipe and rain cap mounted on dual axle trailer with 2 5/16 inch ball hitch coupler, running lights, electric brake system with battery back-up breakaway system, rear stabilizer jack, & electrical power panel w/ camlock connectors. Reduces noise level to be approximately 71 decibles (dB) @ 23 feet.

· 244-gallon (24 hour) sub-base fuel tank with fuel level gauge, fuel fill with lockable cap, and emergency vents.

· Voltage selector switch, three position lockable, wired for 277/480 3-phase, 120/208 3-phase, and 120/240 1-phase

· Cold weather package w/ engine block heater

· Flexible fuel connections

· Adjustable trip main line circuit breaker

· Battery rack and cables

· Remote annunciator

· Kohler battery charger, 6amp

· Water separator fuel filter

· Lube oil and antifreeze

· One (1) Kohler Series Rated Open Transition Automatic Transfer Switch, Model KSS-AMTA-0260S Amps: 260, Voltage: 480, Pole: 3, Wire: 4, Enclosure: NE