This document is a comprehensive set of appendices (C-G) detailing fire suppression systems inspection, testing, and maintenance (IT&M) requirements for Watervliet Arsenal. The file covers multiple fire protection system types including dry pipe, wet pipe, fire pump, standpipe, and pre-action systems across various building locations. The document specifies detailed maintenance tasks for each system type, with frequency schedules for base year and two option years, aligned with National Fire Protection Association (NFPA) Fire Protection Code standards.

The solicitation (W911PT25Q0073) is a total small business set-aside contract issued by the Department of the Army Materiel Command Contracting Command Detroit Arsenal for fire suppression IT&M services. The appendices outline specific inspection requirements for 28 dry pipe systems, 38 wet pipe systems, 5 fire pump systems, 5 standpipe systems, and 5 pre-action systems. Each system's documentation includes location, quantity, size, manufacturer, approximate coverage area, and required maintenance tasks such as valve inspections, flow tests, internal pipe inspections, and hydrostatic testing at specified intervals (annually, every 3 years, every 5 years).

View the file

Other files for this federal contract opportunity

Other files attached to Fire Suppression IT&M at Watervliet Arsenal, newest first.
File Type Posted
W911PT25Q0073 0003 - Amendment.pdf PDF
W911PT25Q0073 0002 - Amendment.pdf PDF
Hydrant Map.pdf PDF
W911PT25Q0073 0001 - Amendment.pdf PDF
W911PT25Q0073 - Solicitation.pdf PDF
SOW (2).docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Appendix C

Chapters 4 (General Requirements), 5 (Sprinkler Systems) and 12 (Valves, Valve Components, and Trim) of the National Fire Protection Association (NFPA) Fire Protection Code (FPC) 25 (Standard for the Inspection, Testing and Maintenance of Water-Based Fire Protection Systems), latest Edition.

BldgLocationQuantitySizeManufacturerApprox. Coverage (SF)Air Leakage Test5 Year Pipe InternalsFDC Hydro and Inspection
10North End Basement14 InchFirematic Viking202420242024
21East End, Basement Level16 InchFirematic16,700 (Basement, 1st Floor)Due 2025Due 20252024
22South East Basement14 InchSRI10,250 (Attic and Appartatus Bays)Due 2025Due 2025Due 2025
24North End, Ground Floor14 InchGem11,800 (Basement, 1st Floor, 2nd Floor, Attic)2024Due 20252024
38Center Sprinkler Room26 InchVictaulic18,000202420242024
40-1Security, Backroom26 InchFirematic14,800 (1st Floor, 2nd Floor, Attic)2024Due 2025Due 2025
40-2Center, Sprinkler Room Under Stairs26 InchFirematic56,800 (1st Floor, 2nd Floor, Attic)2024Due 2025Due 2025
40-2Center, Sprinkler Room Under Stairs14 InchViking2024Due 2025Due 2025
40-3Southeast, Sprinkler Room36 InchFirematic52,200 (1st Floor, 2nd Floor, Attic)2024Due 2025Due 2025
40-4Health Clinic, Ladies Room14 InchFirematic43,500 (1st Floor, Attic of 40-4, and 1st Floor, Attic of most of 40-5)2024Due 20252024
41East Side, Utility Room14 InchSRI4,000 (Attic Space)Due 2025Due 2025Due 2025
108South End, Backroom18 inchSRI2,400Due 2026Due 2026Due 2026
116Northeast Corner16 InchReliable (Deluge Type)2,700X20242024
120East Side, North and South26 InchGlobe96,600 (1st Floor, Mezzanine, 2nd Floor, 3rd Floor)Scheduled for replacementScheduled for replacementScheduled for replacement
124First Floor, South Side Corner Mech Room16 InchFirematic18,600 (1st Floor, 2nd Floor, Rafters above 2nd Floor)202420242024
130Center, East Side, Exterior Door16 InchFirematic30,9002024Due 2025Due 2025
135Center, East Side16 InchFirematic41,300 (Only Some Bays)20242024Due 2025
137Make Up Air Unit13 InchVictaulicFor MAUDue 2027Due 2030Due 2030
145Northeast, Northwest, Southeast, and Southwest46 InchFirematic113,5002024Due 2025Due 2025
Total28

&"Times New Roman,Bold"APPENDIX C: Dry Pipe Systems &"Times New Roman,Regular"Building Locations

Appendix C-2

FrequencyComponentTasks
Base Year, Option Year 1, and Option Year 21. Control Valves (locked or supervised)1. Verify valve position.
2. Waterflow Alarm Devices1. Operate to verify initiation and receipt of alarm. 2. Verify alarm test valve alignment and tamper switch (if supervised).
3. Dry Pipe Alarm Valve and Trim1. Trip test. 2. Visually inspect exterior of valves, gauges, trim alignment. 3. Verify valve pressure and legibility of hydraulic nameplate.
4. Main Drain1. Conduct main drain test to verify supply (valve position).
5. Fire Department Connection1. Verify accessibility and condition. 2. If caps removed or missing, check for obstructions.
6. Dry Pipe Alarm Valve Enclosure Heating1. Verify operability at beginning of heating season (for constant cold areas annually).
7. Low Temperature Alarm1. Verify initiation and receipt of alarm at beginning of heating season.
8. Low Point Drains1. Drain all low points to remove condensation prior to cold season.
9. Entire SystemVisually check: 1. Pipe hangers. 2. Heads for obstruction. 3. Piping for leaks. 4. Riser condition. 5. Sprinkler spares.
Option Year 2 (Only)1. Control Valves/Quick Opening Devices1. Full flow trip test. 2. Trip valve to verify operability. 3. Inspect internal condition before resetting and clean valve seat. 4. Check priming water level (before and after trip test).
Option Year 1 (Only)1. Control Valves1. Operate valve through entire travel to verify function. 2. Lubricate valve stem.
2. Quick Opening Devices1. Test to verify operability.
3. Low Air Pressure Alarm1. Test to verify initiation and receipt of supervisory alarm.
4. Automatic Air Pressure Maintenance Devices1. Inspect to verify proper operation.
Base year1. Strainers1. Internal inspection and cleaning to verify condition.
Every 3 Years2. Dry Side Piping1. 3 year air leakage test.
Every 5 Years1. Internal Piping1. Internal inspection to verify condition of piping.
2. FDC1. Internal inspection to verify condition of FDC, check valve and piping. Hydrostatically test FDC at 150 psi for 2 HRs.

&"Times New Roman,Bold"APPENDIX C: Dry Pipe Systems &"Times New Roman,Regular"Dry Pipe Automatic Sprinkler Systems Inspection, Testing, and Maintenance Tasks

Appendix D Chapters 4 (General Requirements), 5 (Sprinkler Systems), and 12 (Valves, Valve Components, and Trim) of the National Fire Protection Association (NFPA) Fire Protection Code (FPC) 25 (Standard for the Inspection, Testing and Maintenance of Water-Based Fire Protection Systems), latest Edition

BuildingLocationQuantitySizeManufacturerApprox. Coverage (SF)5 Year Pipe InternalsHydro and Inspect FDC
10North End Basement1
6 InchFirematic Viking66,900 (Basement, 1st Floor, 2nd Floor, Attic)20242024
15Center West, In Break Room – Note: Asbestos tile location diagram18 InchViking (Alarm Valve)23,00020242024
20First Floor, Locker Room16 InchAmerican3,200 (Two Bays Bottom Floor)Due 2025Hydro only. Inspection Due 2025
21East End, Basement Level14 InchRasco3,300Due 20252024
22Southeast Basement14 InchSRI6,250Due 2025Due 2025
25First Floor, East Center Column F-014 InchCentral (Alarm Check)28,800 (Some Bays First Floor, Some Bays Second Floor)20242024
35South Mechanical Room28 InchGem, Model A63,000 (35 Annex only, Most of First Floor, Most of Second Floor)Due 2025Due 2025
40-5Southwest Corner16 InchSRI13,800 ( Main Fl. and attic)Due 2025Due 2025
40-6North Center Rm. 6-10824 InchSRI18,375 (Main Fl. and attic)Due 2025Due 2025
41East Utility Rm.14 InchSRI4,000 (Main floor)Due 2025Due 2025
44Basement, Mechanical Room26 InchVictaulic62,000 (First Floor, Second Floor)20242024
110South West, Crane Repair Office18 InchViking16,900 (Only Some Bays, includes Dry Pre-Action System Over Substation)Due 2026Due 2026
110North Wall14 InchCentral17,900 (Only Some Bays, and Butler Bldg)Due 2026Due 2026
110Southwest Mech. Rm., Nortwest Mech. Rm., A-26, A-39, A-9, A-52, B-25, E-38, A-65106 InchVictaulic (Firelock)196,000Due 2026Due 2026
110B 58/5912.5 InchUnknownDue 2026Due 2026
112Ground Floor, East Wall14 InchViking (Alarm Valve)3,400 (Some First Floor, All Second Floor)20242024
114West Wall16 InchVictaulic3,50020242024
115North Vestibule Closet South Mechanical Room Note: Asbestos Tile location Diagram26 InchStar48,00020242024
123Northeast Cage14 InchReliable (Alarm Valve)850020242024
125West End of Building16 InchViking (Alarm Valve)39,500 (Offices, Common Space, Vestibule, Clean room, and Manufacturing space)20242024
125West End of Building16 InchViking (Alarm Valve)27,300 (Offices, Common Spaces, Bathrooms, and Mechanical Rooms)20242024
125West End of Building16 InchVictaulic (FireLock)35,00020242024
126North Center16 InchSRI6,100Due 2025Due 2025
126North Center12 InchSRI1,175Due 2025Due 2025
137Paint Booth16 InchVictaulicDue 2030Due 2030
153East Side of Building14 Inch15,00020242024
Total38

&"Times New Roman,Bold"APPENDIX D: Wet Pipe Systems &"Times New Roman,Regular"Building Locations&"Times New Roman,Bold"

Appendix D-2

FrequencyComponentTasks
Base Year, Option Yr 1, and Option Yr 21. Control Valves (locked or supervised)1. Verify valve position.
2. Waterflow Alarm Devices1. Operate to verify initiation and receipt of alarm. 2. Verify alarm test valve alignment and tamper switch (if supervised).
3. Alarm Valve and Trim1. Visually check exterior of valves, gauges, trim alignment. 2. Verify valve pressure and legibility of hydraulic nameplate.
4. Main Drain1. Conduct main drain test to verify supply (valve position)
5. Fire Department Connection1. Verify accessibility and condition 2. If caps removed or missing, check for obstructions.
6. Entire SystemVisually check: 1. Pipe hangers. 2. Heads for obstruction. 3. Piping for leaks. 4. Riser condition. 5. Sprinkler spares. 6. Area susceptible to freezing.
Option Year 1 (only)1. Control Valves1. Operate valve through entire travel to verify function. 2. Lubricate valves and stems to ensure operability.
Base Year1. Alarm Valve1. Clean and inspect internally to verify condition.
2. Anti-freeze Loops1. Confirm correct solution mixture
Every 5 Years1. Internal Piping1. Internal inspection to verify condition of piping.
2. FDC1. Internal inspection to verify condition of FDC, check valve and piping. 2. Hydrostatically test FDC at 150 psi for 2 HRs.

&"Times New Roman,Bold"APPENDIX E: Wet Pipe Systems &"Times New Roman,Regular"Wet Pipe Automatic Sprinkler Systems Inspection, Testing, and Maintenance Tasks

Appendix E FIRE PUMP SUPPRESSION (IAW) NFPA FPC 25, Chapters 8 (Fire Pumps) and 12 (Valves, Valve Components, and Trim), latest edition. Requires written report of inspection on contractor standard form.

BuildingLocationQuantitySizeManufacturerApprox. Coverage (SF)
35Mezzanine Deck Inside Mechanical Room11000 GPMFairbanks MorseNot Applicable
110Northwest and Southwest Mechanical Rooms.2750 GPMPattersonNot Applicable
116Inside Manhole Next To Building *Confined Space Entry Permit Required11000 GPMAllis ChalmersNot Applicable
137East Mechanical Room11,000 GPMFiretrolNot Applicable
Total5

&"Times New Roman,Bold"APPENDIX E: Fire Pump Systems &"Times New Roman,Regular"Building Locations

Appendix E-2

FrequencyComponentTasks
Base Year and Option Year 21. Control Valve1. Operate and lubricate valves to ensure operability.
2. Controllers1. Calibrate pressure switches. 2. Exercise circuit breakers and switches to verify operability. 3. Inspect fuses.
3. Pumps1. Check coupling alignment to ensure shaft aligned. 2. Check pump shaft end play. 3. Lubricate bearings. 4. Lubricate couplings. 5. Lubricate right-angle drives.
4. Fuel (Engine-Driven Pumps)1. Sample fuel to verify quality.
5. Relief Valves1. Calibrate valves.
6. Emergency Power Supply1. Test to verify availability and capacity for pump motor.
Base Year, Option Year 1, Option Year 21. Pump1. Conduct flow test to verify pump output.

&"Times New Roman,Bold"APPENDIX E: Fire Pump Systems &"Times New Roman,Regular"Fire Pump Inspection, Testing, and Maintenance Tasks

Appendix F Chapter 6 (Standpipe and Hose Systems) of the National Fire Protection Association (NFPA) Fire Protection Code (FPC) 25 (Standard for the Inspection, Testing and Maintenance of Water-Based Fire Protection Systems), latest Edition.

BuildingQuantitySizeManufacturerApprox. Coverage (SF)Year Flushed
2514 InchNot ApplicableVertical - East Stairwell, 2 Floors2025
11024 InchNot ApplicableHorizontal – 1,244 LF each2024
13524 InchNot ApplicableHorizontal – 605 LF each2025
5

&"Times New Roman,Bold"APPENDIX F: Stand Pipe Systems &"Times New Roman,Regular"Building Locations

Appendix F-2

FrequencyComponentTasks
Base Year, Option Year 1, and Option Year 21. Hose Connection and Pressure Reducing Valves1. Inspect for damage, leaking, missing caps, and obstruction.
2. Entire SystemVisually check: 1. Pipe hangers. 2. Connections for obstruction. 3. Piping for leaks. 4. Riser condition.
Option Year 1 (only)1. Piping1. Inspect for damage and pipe supports.
Option Year 1 (only)1. Standpipe1. Air test to ensure integrity.
Option Year 21. Standpipe1. Flush standpipe.

&"Times New Roman,Bold"APPENDIX F: Stand Pipe Systems &"Times New Roman,Regular"Standpipe Systems Inspection, Testing, and Maintenance Tasks

Appendix G Chapters 4 (General Requirements) and 5 (Sprinkler Systems), and 12 (Valves, Valve Components, and Trim) of the National Fire Protection Association (NFPA) Fire Protection Code (FPC) 25 (Standard for the Inspection, Testing and Maintenance of Water-Based Fire Protection Systems), latest Edition.

BldgLocationQuantitySizeManufacturerApprox. Coverage (SF)Air Leakage5 Year InternalsHydro ans Inspect FDC
PRE_ACTION FIRE PROTECTION SYSTEMS
38Center Sprinkler Rm.22 1/2 InchFirelock NXT202420242024
110East Side A-6214 InchVictaulic15,000Due 2025Due 2026Due 2026
110West Side E-2514 InchVictaulic4,700Due 2025Due 2026Due 2026
114Room 10414 InchFirelock1,500202420242024
Total5

&"Times New Roman,Bold"APPENDIX G: Pre-Action Systems &"Times New Roman,Regular"Building Locations

Appendix G-2

FrequencyComponentTasks
Base Year, Option Year 1, and Option Year 21. Control Valves (locked or supervised)1. Verify valve position.
2. Waterflow Alarm Devices1. Operate to verify initiation and receipt of alarm. 2. Verify alarm test valve alignment and tamper switch (if supervised).
3. Pre-Action Valve and Trim1. Inspect exterior of valves, gauges, trim alignment. 2. Verify valve pressure and legibility of hydraulic nameplate.
4. Main Drain1. Conduct main drain test to verify supply (valve position).
5. Fire Department Connection1. Verify accessibility and condition. 2. If caps removed or missing, check for obstructions.
6. Valve and Riser Heated Enclosure (if provided)1. Verify operability at beginning of heating season (for constant cold areas annually).
7. Low Temperature Alarm1. Verify initiation and receipt of alarm at beginning of heating season.
8. Initiating Devices: Radiant Energy Detectors1. Test to verify alarm initiation and receipt. 2. Verify no facility change which affects performance.
9. Entire SystemVisually check: 1. Pipe hangers. 2. Heads for obstruction. 3. Piping for leaks. 4. Riser condition. 5. Sprinkler spares.
10. Pre-Action1. Full flow
Option Year 1 (only)1. Control Valves1. Operate valve through entire travel to verify function. 2. Lubricate valve stem.
2. Pre-Action Valve1. Trip valve to verify operation. 2. Verify manual actuators (if provided). 3. Inspect internal condition and clean valve seat before resetting.
3. Low Point Drains1. Drain all low points after pre-action valve trip test and before cold weather (if unheated area).
4. Air supply (if present)1. Test automatic air pressure maintenance device. 2. Test low air supply alarm.
Base Year1. Strainers1. Clean and inspect interior to verify condition.
Every 3 Years2. Dry Side Piping1. 3 year air leakage test.
Every 5 Years1. Internal Piping1. Internal inspection to verify condition of piping.
2. FDC1. Internal inspection to verify condition of FDC, check valve and piping. Hydrostatically test FDC at 150 psi for 2 HRs.

&"Times New Roman,Bold"APPENDIX G: Pre-Action Systems &"Times New Roman,Regular"Pre-Action Systems Inspection, Testing, and Maintenance Tasks