This solicitation is for AM #6 to EIE443 Turbine Generator Repair at the Central Heat & Power Plant (CHPP) at Eielson Air Force Base in Alaska. The Department of the Army Corps of Engineers Engineering District Alaska is seeking responses for repairs to turbine generators including replacement of rotor and stator windings, replacement of exciter rotor and stator, replacement of generator bearings, and performance of on-site operational tests. Responses are due by June 15, 2021. The award date is expected to be July 15, 2021. The contract will be a firm-fixed price award for a one-year base period with four one-year option periods. This is an unrestricted procurement open to small and large businesses.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
PROJECT TITLE: EIE443 Repair CHPP Turbine Generator, Eielson AFB, Alaska
a. This amendment provides changes to the solicitation as indicated on page 2 of this document.
b. PROPOSAL DUE DATE HAS NOT CHANGED. Submit proposals in accordance w ith Section 00 21 00, paragraph 1.13, Proposal Submittals.
POC for this amendment is Angela Padua, 907-753-5714.
1. CONTRACT ID CODE PAGE OF PAGES
1 2
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W911KB21R0012
X 9B. DATED (SEE ITEM 11)
25-Nov-2020
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO.
5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
21-Dec-2020
CODE
U.S. ARMY ENGINEER DISTRICT, AK
CEPOA-CT (W911KB)
PO BOX 6898
JBER AK 99506-0898
W911KB 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
W911KB21R0012
SUMMARY OF CHANGES
a. The following drawings are submitted for the superseded documents/sections:
• Drawing G-002 (Drawing Index revised to add sheet CIW-123A)
• Drawing DI604B (Revision to piping near PRV-001)
• Drawing DS501 (Clarification added to drawing regarding pipe support detail numbering)
• Drawing DS502 (Clarification added to drawing regarding pipe support detail
“sheet numbers”)
• Drawing CIW-141 (Revision to piping isometric)
b. The following drawings are added:
• Drawing CIW-123A (Adds missing isometric following CIW-123)
c. The following revised documents/sections are submitted for the superseded documents/sections:
• RFP Specifications, Section 26 05 19.1010, Attachment “Cable Schedule” (electronic pages 1163 through 1201 of 2048 pages)
• RFP Specifications, Appendix B “Mechanical Lists”, ML003, Pipeline Schedule (electronic pages 1987 through 2004 of 2048 pages)
• RFP Specifications, Appendix B “Mechanical Lists”, ML004, Valve Schedule (electronic pages 2005 through 2035 of 2048 pages)
d. The following sections are deleted:
• NONE
e. The following documents are added:
• RFP Specification Package, Appendix C, adding 12-month historical steam extraction data (highest hourly flow rate in K-Lbs, and monthly flow totals in M- Lbs)
• RFP Specification Package, Appendix C, adding as-built drawing “ftqw_06203_008_041_Floor_drains” to show existing locations of turbine basement drains
f. The following revisions are incorporated:
• NONE
g. Other:
• NONE
(End of Summary of Changes)
ALL OTHER TERMS AND CONDITIONS SHALL REMAIN THE SAME.
J4COEBJT
Text Box EIE443 Amendment R0003
EIE443, Amendment R0003
S O
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
S T
A N
L E
Y C
O N
S U
L T
A N
T S
IN
C
S
O U
T H C
H E
S T
E R S
T R
E E
T S
U
IT
E
C E
N T
E N
N
IA
L
C O
L O
R A
D O w w w .s ta n le y c o n s u lt a n ts .c o m
A L
A S
K A D
IS
T R
IC
T
W
K B -1
-D -0
N O
V E
M B
E R
A N
S I
D
W
K B
R
E
IE
L S
O N A
IR
F
O R
C E B
A S
E
A L
A S
K A
R E
P A
IR
C
E N
T R
A L H
E A
T P
O W
E R P
L A
N T T
U R
B
IN
E G
E N
E R
A T
O R
E
IE
DESIGN COMPLETE
®of Engineers
US Army Corps
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
GOVERNMENT APPROVAL PER PARAGRAPH 1.10 OF SECTION 01 33 00.
ACTIVITIES ASSOCIATED WITH THE SUBMITTAL PRIOR TO RECEIPT OF
CONTRACTOR SHALL NOT PROCEED WITH FABRICATION OR ERECTION
WITH SPECIFICATION SECTION 01 33 00 - SUBMITTAL PROCEDURES.
REVIEW AND VERIFICATION OF DESIGN TO THE GOVERNMENT IN ACCORDANCE
CONTRACTOR SHALL SUBMIT FINAL EQUIPMENT VENDOR DRAWINGS FOR
IN THE PROJECT “BASIS OF DESIGN” AS IDENTIFIED IN THE SPECIFICATIONS.
CONTRACT DOCUMENTS WERE PREPARED BASED ON INFORMATION CONTAINED
DS: AEC_Screen.dscript.dscriptPD: AEC_pdf.pltcfg11:54:37 AM 11/20/2020
EIE443DS501.dgn
B
D A
H L
P R
O C
E S
S
DS501
R T
U R
N E
R
R T
U R
N E
R
J S
O L
A N
P
IP
E S
U P
P O
R T D
E T
A
IL
S
Highlight
Highlight
Highlight
Highlight
Highlight
Highlight
Highlight
Highlight
Highlight
Highlight
Rectangle
J4COEBJT
Text Box These "Support Details" are contained within Contract Drawing Sheets DS501 through DS506 (see Support Schedule on DS601 and DS602)
J4COEBJT
Text Box
DS502
J4COEBJT
Text Box
DS504, DS505
J4COEBJT
Text Box
DS504
J4COEBJT
Text Box
DS503
J4COEBJT
Text Box
DS505, DS506
J4COEBJT
Text Box
DS502
J4COEBJT
Text Box
DS503
J4COEBJT
Callout To clarify, this is:
"M700, SHEET 1"
J4COEBJT
S O
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
S T
A N
L E
Y C
O N
S U
L T
A N
T S
IN
C
S
O U
T H C
H E
S T
E R S
T R
E E
T S
U
IT
E
C E
N T
E N
N
IA
L
C O
L O
R A
D O w w w .s ta n le y c o n s u lt a n ts .c o m
A L
A S
K A D
IS
T R
IC
T
W
K B -1
-D -0
N O
V E
M B
E R
N
S I
D
W
K B
R
E
IE
L S
O N A
IR
F
O R
C E B
A S
E
A L
A S
K A
R E
P A
IR
C
E N
T R
A L H
E A
T P
O W
E R P
L A
N T T
U R
B
IN
E G
E N
E R
A T
O R
E
IE
DESIGN COMPLETE
®of Engineers
US Army Corps
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
GOVERNMENT APPROVAL PER PARAGRAPH 1.10 OF SECTION 01 33 00.
ACTIVITIES ASSOCIATED WITH THE SUBMITTAL PRIOR TO RECEIPT OF
CONTRACTOR SHALL NOT PROCEED WITH FABRICATION OR ERECTION
WITH SPECIFICATION SECTION 01 33 00 - SUBMITTAL PROCEDURES.
REVIEW AND VERIFICATION OF DESIGN TO THE GOVERNMENT IN ACCORDANCE
CONTRACTOR SHALL SUBMIT FINAL EQUIPMENT VENDOR DRAWINGS FOR
IN THE PROJECT “BASIS OF DESIGN” AS IDENTIFIED IN THE SPECIFICATIONS.
CONTRACT DOCUMENTS WERE PREPARED BASED ON INFORMATION CONTAINED
DS: AEC_Screen.dscript.dscriptPD: AEC_pdf.pltcfg11:55:51 AM 11/20/2020
EIE443DS502.dgn
D A
H L
P R
O C
E S
S
DS502
R T
U R
N E
R
R T
U R
N E
R
J S
O L
A N
P
IP
E S
U P
P O
R T D
E T
A
IL
S
Rectangle
J4COEBJT
Callout To clarify, this is:
"M701, SHEET 2"
J4COEBJT
EIE443, Amendment R0003
CABLE SCHEDULE (Last Iss Date: ) Rev:1
Constraints: NONE
12/17/2020 < EAFB, EIE443 CHPP TURBINE GENERATOR > Job Number: 27751
12/17/2020
FROM TAG TO TAG
FROM DESCRIPTION TO DESCRIPTION
CABLE NUMBER CABLE TYPE ROUTING
SEGR CODE PLANT SYSTEM FROM DWG TO DWG CABLE LAYING METHOD
WORK PACKAGE START UP SYSTEM FROM WIRING DWG TO WIRING DWG LEN CABLE NOTE REV
00-CIW-C-058 9/C #12 00-CIW-CPL-001 EAST WELL PANEL 1000FT FIELD ROUTE CONDUIT 0
C COOLING WATER CONTROL PANEL
EI100
EI821, EI822 EI821, EI822
00-CIW-C-059 9/C #12 00-CIW-CPL-001 WEST WELL PANEL 1000FT FIELD ROUTE CONDUIT 0
EI821, EI822 EI821, EI822
00-CIW-C-060 9/C #12 00-CIW-CPL-001 NORTH WELL PANEL 800FT FIELD ROUTE CONDUIT 0
EI821, EI823 EI821, EI823
00-CIW-C-061 9/C #12 00-CIW-CPL-001 SOUTH WELL PANEL 1000FT FIELD ROUTE CONDUIT 0
EI821, EI823 EI821, EI823
00-CIW-L-100 3/C #12 AWG 00-CIW-LTG-PNL 00-CIW-NPL-100 50FT 120VAC PWR CONN., FIELD ROUTE CONDUIT 0
L COOLING POND PUMP HOUSE COOLING WATER NETWORK PANEL
LIGHTING PANEL
EP107 EI107
00-CIW-M-500 3/C (15KV) #2 O-T-CIRC-14 00-CIW-XFMR-001 100FT CONNECTION TO OVERHEAD CIRCUIT #14, FIELD ROUTE 1
M AWG W/G OVERHEAD TRANSMISSION TAP 7200/480VAC 3PH TRANSFORMER CONDUIT
FROM CIRCUIT #14
E-605 E-605
12/17/2020 < EAFB, EIE443 CHPP TURBINE GENERATOR > Job Number: 27751
12/17/2020
FROM TAG TO TAG
FROM DESCRIPTION TO DESCRIPTION
CABLE NUMBER CABLE TYPE ROUTING
SEGR CODE PLANT SYSTEM FROM DWG TO DWG CABLE LAYING METHOD
WORK PACKAGE START UP SYSTEM FROM WIRING DWG TO WIRING DWG LEN CABLE NOTE REV
00-CIW-M-501 3/C (15KV) #2 O-T-CIRC-2 00-CIW-XFMR-002 60FT CONNECTION TO OVERHEAD CIRCUIT #2, FIELD ROUTE 1
M AWG W/G OVERHEAD TRANSMISSION TAP 7200/480VAC 3PH 300KVA CONDUIT
FROM CIRCUIT #2 TRANSFORMER
00-CIW-M-701 3/C (2KV) #350 00-CIW-VFD-001A 00-CIW-MTR-001A 100FT PWR CONN., FIELD ROUTE CONDUIT 0
M KCMIL W/GND VFD CIRCULATING WATER PUMP A VFD CIRCULATING WATER PUMP MOTOR
EI107 DI604
00-CIW-M-703 3/C (2KV) #350 00-CIW-VFD-001B 00-CIW-MTR-001B 100FT PWR CONN., FIELD ROUTE CONDUIT 0
M KCMIL W/GND VFD CIRCULATING WATER PUMP B VFD CIRCULATING WATER PUMP MOTOR
00-CIW-M-705 3/C (2KV) #350 00-CIW-VFD-001C 00-CIW-MTR-001C 100FT PWR CONN., FIELD ROUTE CONDUIT 0
M KCMIL W/GND VFD CIRCULATING WATER PUMP C VFD CIRCULATING WATER PUMP MOTOR
C
00-CIW-P-501 3/C #500 KCMIL 00-CIW-XFMR-001 00-CIW-PNL-002 150FT PWR CONN., FIELD ROUTE CONDUIT 0
P W/GND 7200/480VAC 3PH TRANSFORMER 480V ELECTRICAL DISTRIBUTION
PANEL
00-CIW-P-502 3/C #500 KCMIL 00-CIW-XFMR-001 00-CIW-PNL-002 150FT PWR CONN., FIELD ROUTE CONDUIT 0
P W/GND 7200/480VAC 3PH TRANSFORMER 480V ELECTRICAL DISTRIBUTION
12/17/2020 < EAFB, EIE443 CHPP TURBINE GENERATOR > Job Number: 27751
12/17/2020
FROM TAG TO TAG
FROM DESCRIPTION TO DESCRIPTION
CABLE NUMBER CABLE TYPE ROUTING
SEGR CODE PLANT SYSTEM FROM DWG TO DWG CABLE LAYING METHOD
WORK PACKAGE START UP SYSTEM FROM WIRING DWG TO WIRING DWG LEN CABLE NOTE REV
00-CIW-P-503 3-1/C #4/0, #4 00-CIW-XFMR-002 00-CIW-PNL-001 165FT DUCT A1 1
P G 7200/480VAC 3PH 300KVA 480V ELECTRICAL DISCTIBUTION
TRANSFORMER PANEL
00-CIW-P-504 3-1/C #4/0, #4 00-CIW-XFMR-002 00-CIW-PNL-001 165FT DUCT A2 1
P G 7200/480VAC 3PH 300KVA 480V ELECTRICAL DISCTIBUTION
TRANSFORMER PANEL
00-CIW-P-700 3/C #500 KCMIL 00-CIW-PNL-001 00-CIW-VFD-001A 30FT PWR CONN., FIELD ROUTE CONDUIT 0
P W/GND 480V ELECTRICAL DISCTIBUTION CIRCULATING WATER PUMP A VFD
E-605 EI107
00-CIW-P-702 3/C #500 KCMIL 00-CIW-PNL-002 00-CIW-VFD-001B 30FT PWR CONN., FIELD ROUTE CONDUIT 0
P W/GND 480V ELECTRICAL DISTRIBUTION CIRCULATING WATER PUMP B VFD
00-CIW-P-704 3/C #500 KCMIL 00-CIW-PNL-002 00-CIW-VFD-001C 30FT PWR CONN., FIELD ROUTE CONDUIT 0
P W/GND 480V ELECTRICAL DISTRIBUTION CIRCULATING WATER PUMP C VFD
00-CIW-P-706 3/C #500 KCMIL 00-CIW-PNL-002 00-CIW-SKD-101 720FT PWR CONN., FIELD ROUTE CONDUIT 0
P W/GND 480V ELECTRICAL DISTRIBUTION SPRAY POND EVAPORATOR SYSTEM
PANEL (PROV. ELEC. TP)
E-605 DI604
12/17/2020 < EAFB, EIE443 CHPP TURBINE GENERATOR > Job Number: 27751
12/17/2020
FROM TAG TO TAG
FROM DESCRIPTION TO DESCRIPTION
CABLE NUMBER CABLE TYPE ROUTING
SEGR CODE PLANT SYSTEM FROM DWG TO DWG CABLE LAYING METHOD
WORK PACKAGE START UP SYSTEM FROM WIRING DWG TO WIRING DWG LEN CABLE NOTE REV
00-COM-T-003 FIBER 6 SM 00-CIW-NPL-100 00-CIW-CPL-100 750FT COMMUNICATIONS, FIELD ROUTE CONDUIT 0
T COOLING WATER NETWORK PANEL COOLING POND AUGMENTATION
SYSTEM CONTROL PANEL
EI107 EP108
EI605 EI606
00-COM-T-004 CAT 6 ETHERNET 00-CIW-NPL-100 POND HOUSE NPL (EXIST) 50FT COMMUNICATIONS, FIELD ROUTE CONDUIT 0
T COOLING WATER NETWORK PANEL
EI107
EI605 EI606
00-COM-T-005 CAT 6 ETHERNET 00-CIW-VFD-001A 00-CIW-NPL-100 50FT FIELD ROUTE CONDUIT 0
T CIRCULATING WATER PUMP A VFD COOLING WATER NETWORK PANEL
EI107 EI107
00-COM-T-006 CAT 6 ETHERNET 00-CIW-VFD-001B 00-CIW-NPL-100 50FT FIELD ROUTE CONDUIT 0
T CIRCULATING WATER PUMP B VFD COOLING WATER NETWORK PANEL
00-COM-T-007 CAT 6 ETHERNET 00-CIW-VFD-001C 00-CIW-NPL-100 50FT FIELD ROUTE CONDUIT 0
T CIRCULATING WATER PUMP C VFD COOLING WATER NETWORK PANEL
00-COM-T-008 CAT 6 ETHERNET 00-CIW-VFD-110 00-CIW-CPL-100 30FT FIELD ROUTE CONDUIT 0
T FLOATING EVAPORATION UNIT 1 COOLING POND AUGMENTATION
PUMP VFD SYSTEM CONTROL PANEL
EI108 EP108
EI606 EI606
12/17/2020 < EAFB, EIE443 CHPP TURBINE GENERATOR > Job Number: 27751
12/17/2020
FROM TAG TO TAG
FROM DESCRIPTION TO DESCRIPTION
CABLE NUMBER CABLE TYPE ROUTING
SEGR CODE PLANT SYSTEM FROM DWG TO DWG CABLE LAYING METHOD
WORK PACKAGE START UP SYSTEM FROM WIRING DWG TO WIRING DWG LEN CABLE NOTE REV
00-COM-T-009 CAT 6 ETHERNET 00-CIW-VFD-111A 00-CIW-CPL-100 30FT FIELD ROUTE CONDUIT 0
T FLOATING EVAPORATION UNIT 1 COOLING POND AUGMENTATION
FAN A VFD SYSTEM CONTROL PANEL
EI108 EP108
EI606 EI606
00-COM-T-010 CAT 6 ETHERNET 00-CIW-VFD-111B 00-CIW-CPL-100 30FT FIELD ROUTE CONDUIT 0
T FLOATING EVAPORATION UNIT 1 COOLING POND AUGMENTATION
FAN B VFD SYSTEM CONTROL PANEL
EI108 EP108
EI606 EI606
00-COM-T-011 CAT 6 ETHERNET 00-CIW-VFD-111C 00-CIW-CPL-100 30FT FIELD ROUTE CONDUIT 0
T FLOATING EVAPORATION UNIT 1 COOLING POND AUGMENTATION
FAN C VFD SYSTEM CONTROL PANEL
EI108 EP108
EI606 EI606
00-COM-T-012 CAT 6 ETHERNET 00-CIW-VFD-111D 00-CIW-CPL-100 30FT FIELD ROUTE CONDUIT 0
T FLOATING EVAPORATION UNIT 1 COOLING POND AUGMENTATION
FAN D VFD SYSTEM CONTROL PANEL
EI108 EP108
EI606 EI606
00-COM-T-013 CAT 6 ETHERNET 00-CIW-VFD-120 00-CIW-CPL-100 30FT FIELD ROUTE CONDUIT 0
T FLOATING EVAPORATION UNIT 2 COOLING POND AUGMENTATION
PUMP VFD SYSTEM CONTROL PANEL
EI108 EP108
EI606 EI606
00-COM-T-014 CAT 6 ETHERNET 00-CIW-VFD-121A 00-CIW-CPL-100 30FT FIELD ROUTE CONDUIT 0
T FLOATING EVAPORATION UNIT 2 COOLING POND AUGMENTATION
FAN A VFD SYSTEM CONTROL PANEL
EI108 EP108
12/17/2020 < EAFB, EIE443 CHPP TURBINE GENERATOR > Job Number: 27751
12/17/2020
FROM TAG TO TAG
FROM DESCRIPTION TO DESCRIPTION
CABLE NUMBER CABLE TYPE ROUTING
SEGR CODE PLANT SYSTEM FROM DWG TO DWG CABLE LAYING METHOD
WORK PACKAGE START UP SYSTEM FROM WIRING DWG TO WIRING DWG LEN CABLE NOTE REV
00-COM-T-015 CAT 6 ETHERNET 00-CIW-VFD-121B 00-CIW-CPL-100 30FT FIELD ROUTE CONDUIT 0
T FLOATING EVAPORATION UNIT 2 COOLING POND AUGMENTATION
FAN B VFD SYSTEM CONTROL PANEL
EI108 EP108
EI606 EI606
00-COM-T-016 CAT 6 ETHERNET 00-CIW-VFD-121C 00-CIW-CPL-100 30FT FIELD ROUTE CONDUIT 0
T FLOATING EVAPORATION UNIT 2 COOLING POND AUGMENTATION
FAN C VFD SYSTEM CONTROL PANEL
EI108 EP108
EI606 EI606
00-COM-T-017 CAT 6 ETHERNET 00-CIW-VFD-121D 00-CIW-CPL-100 30FT FIELD ROUTE CONDUIT 0
T FLOATING EVAPORATION UNIT 2 COOLING POND AUGMENTATION
FAN D VFD SYSTEM CONTROL PANEL
EI108 EP108
EI606 EI606
00-COM-T-018 CAT 6 ETHERNET 00-CIW-VFD-130 00-CIW-CPL-100 30FT FIELD ROUTE CONDUIT 0
T FLOATING EVAPORATION UNIT 3 COOLING POND AUGMENTATION
PUMP VFD SYSTEM CONTROL PANEL
EI108 EP108
EI606 EI606
00-COM-T-019 CAT 6 ETHERNET 00-CIW-VFD-131A 00-CIW-CPL-100 30FT FIELD ROUTE CONDUIT 0
T FLOATING EVAPORATION UNIT 3 COOLING POND AUGMENTATION
FAN A VFD SYSTEM CONTROL PANEL
EI108 EP108
EI606 EI606
00-COM-T-020 CAT 6 ETHERNET 00-CIW-VFD-131B 00-CIW-CPL-100 30FT FIELD ROUTE CONDUIT 0
T FLOATING EVAPORATION UNIT 3 COOLING POND AUGMENTATION
FAN B VFD SYSTEM CONTROL PANEL
EI108 EP108
12/17/2020 < EAFB, EIE443 CHPP TURBINE GENERATOR > Job Number: 27751
12/17/2020
FROM TAG TO TAG
FROM DESCRIPTION TO DESCRIPTION
CABLE NUMBER CABLE TYPE ROUTING
SEGR CODE PLANT SYSTEM FROM DWG TO DWG CABLE LAYING METHOD
WORK PACKAGE START UP SYSTEM FROM WIRING DWG TO WIRING DWG LEN CABLE NOTE REV
00-COM-T-021 CAT 6 ETHERNET 00-CIW-VFD-131C 00-CIW-CPL-100 30FT FIELD ROUTE CONDUIT 0
T FLOATING EVAPORATION UNIT 3 COOLING POND AUGMENTATION
FAN C VFD SYSTEM CONTROL PANEL
EI108 EP108
EI606 EI606
00-COM-T-022 CAT 6 ETHERNET 00-CIW-VFD-131D 00-CIW-CPL-100 30FT FIELD ROUTE CONDUIT 0
T FLOATING EVAPORATION UNIT 3 COOLING POND AUGMENTATION
FAN D VFD SYSTEM CONTROL PANEL
EI108 EP108
EI606 EI606
00-COM-T-023 2TSP #24, RS485 SECTION 105 TURBINE #3 AVR (EXIST) 250FT FIELD ROUTE CONDUIT 0
T MASTER CONTROL CUBICLE MODBUS RS-485 NETWORK FOR GOVERNORS AND AVR'S
EP103
EI603 EI603
00-COM-T-024 1TSP #18 TX SECTION 107 SECTION 104 100FT FIELD ROUTE CONDUIT 0
T GENERATOR 6 CONTROL CUBICLE MASTER CONTROL CUBICLE LONWORKS NETOWRK FOR DSLC'S
EP103 EP103
EI604 EI604
06-CIW-I-013 1TSP #16 06-BOP-CPL-001 06-CIW-FIT-001 100FT FIELD ROUTE CONDUIT, TC-001/2, FIELD ROUTE 0
I STG 6 BALANCE OF PLANT STG 6 CIRCULATING WATER FLOW CONDUIT
CONTROL PANEL XMTR
EP102 EI101C
EI802 EI802
06-CIW-I-014 1TSP #16 06-BOP-CPL-001 06-CIW-FIT-010 150FT FIELD ROUTE CONDUIT, TC-001/2, TC-002/2, FIELD 0
I STG 6 BALANCE OF PLANT UNIT 6 POTABLE WATER FLOW ROUTE CONDUIT
CONTROL PANEL XMTR
EP102 EI101C
EI813 EI813
12/17/2020 < EAFB, EIE443 CHPP TURBINE GENERATOR > Job Number: 27751
12/17/2020
FROM TAG TO TAG
FROM DESCRIPTION TO DESCRIPTION
CABLE NUMBER CABLE TYPE ROUTING
SEGR CODE PLANT SYSTEM FROM DWG TO DWG CABLE LAYING METHOD
WORK PACKAGE START UP SYSTEM FROM WIRING DWG TO WIRING DWG LEN CABLE NOTE REV
06-CIW-I-026 1TSP #16 06-BOP-CPL-001 06-CIW-TIT-005 100FT FIELD ROUTE CONDUIT, TC-001/2, TC-002/2, FIELD 0
I STG 6 BALANCE OF PLANT TURBINE 6 COND COOLING WATER ROUTE CONDUIT
CONTROL PANEL INLET HEADER TEMP XMTR
EP102 EI101C
EI813 EI813
06-CIW-I-027 1TSP #16 06-BOP-CPL-001 06-CIW-TIT-023 100FT FIELD ROUTE CONDUIT, TC-001/2, TC-002/2, FIELD 0
I STG 6 BALANCE OF PLANT TURBINE 6 COND COOLING WATER ROUTE CONDUIT
CONTROL PANEL OUTLET HEADER TEMP XMTR
EP102 EI101C
EI813 EI813
06-CIW-L-001 2/C #12 AWG 06-BOP-CPL-001 06-CIW-FIT-010 150FT FIELD ROUTE CONDUIT 0
L W/GND STG 6 BALANCE OF PLANT UNIT 6 POTABLE WATER FLOW
CONTROL PANEL XMTR
EP102 EI101C
EI813 EI813
06-CIW-L-002 2/C #12 AWG 06-BOP-CPL-001 06-CIW-FIC-090 150FT FIELD ROUTE CONDUIT 0
L W/GND STG 6 BALANCE OF PLANT STG 6 CIRC WATER FILTRATION
CONTROL PANEL UNIT CONTROLLER
EP102 EI101C
EI806 EI806
06-CND-C-004 7/C #14 06-BOP-CPL-001 MCC-A 100FT FIELD ROUTE CONDUIT 0
C STG 6 BALANCE OF PLANT 480VAC MCC, 3PH, 3W, 800A MCC BUCKET A15, 06-CND-PMP-601A DISCRETE INPUT
CONTROL PANEL (EXIST) SIGNALS
EP102 EP102, E-604
EI806 E-616, EI806
06-CND-C-005 7/C #14 06-BOP-CPL-001 MCC-A 100FT FIELD ROUTE CONDUIT 0
C STG 6 BALANCE OF PLANT 480VAC MCC, 3PH, 3W, 800A MCC BUCKET A14, 06-CND-PMP-604A DISCRETE INPUT
CONTROL PANEL (EXIST) SIGNALS
EP102 EP102, E-604
EI806 E-616, EI806
12/17/2020 < EAFB, EIE443 CHPP TURBINE GENERATOR > Job Number: 27751
12/17/2020
FROM TAG TO TAG
FROM DESCRIPTION TO DESCRIPTION
CABLE NUMBER CABLE TYPE ROUTING
SEGR CODE PLANT SYSTEM FROM DWG TO DWG CABLE LAYING METHOD
WORK PACKAGE START UP SYSTEM FROM WIRING DWG TO WIRING DWG LEN CABLE NOTE REV
06-CND-C-009 5/C #14 06-BOP-CPL-001 MCC-A 100FT FIELD ROUTE CONDUIT 0
C STG 6 BALANCE OF PLANT 480VAC MCC, 3PH, 3W, 800A MCC BUCKET A15, 06-CND-PMP-601A DISCRETE OUTPUT
CONTROL PANEL (EXIST) SIGNALS
EP102 EP102, E-604
EI809 E-616, EI809
06-CND-C-010 5/C #14 06-BOP-CPL-001 MCC-A 100FT FIELD ROUTE CONDUIT 0
C STG 6 BALANCE OF PLANT 480VAC MCC, 3PH, 3W, 800A MCC BUCKET A14, 06-CND-PMP-604A DISCRETE OUTPUT
CONTROL PANEL (EXIST) SIGNALS
EP102 EP102, E-604
EI809 E-616, EI809
06-CND-C-014 5/C #14 06-BOP-CPL-001 06-CND-VB-635 100FT FIELD ROUTE CONDUIT, TC-001/3, TC-002/3, FIELD 0
C STG 6 BALANCE OF PLANT TURBINE 6 CONDENSER VACUUM ROUTE CONDUIT
CONTROL PANEL BREAKER VALVE DISCRETE INPUT SIGNALS
EP102 EI101B
EI816 EI816
06-CND-C-015 7/C #14 06-BOP-CPL-001 MCC-H 100FT FIELD ROUTE CONDUIT 0
C STG 6 BALANCE OF PLANT 480VAC MCC, 3PH, 3W, 800A MCC BUCKET H9, 06-CND-PMP-601B DISCRETE INPUT
CONTROL PANEL (EXIST) SIGNALS
EP102 EP102, E-604
EI817 E-616, EI817
06-CND-C-016 7/C #14 06-BOP-CPL-001 MCC-H 100FT FIELD ROUTE CONDUIT 0
C STG 6 BALANCE OF PLANT 480VAC MCC, 3PH, 3W, 800A MCC BUCKET H10, 06-CND-PMP-604B DISCRETE INPUT
CONTROL PANEL (EXIST) SIGNALS
EP102 EP102, E-604
EI817 E-616, EI817
06-CND-C-020 3/C #14 06-BOP-CPL-001 06-CND-VB-635 100FT FIELD ROUTE CONDUIT, TC-001/3, TC-002/3, FIELD 0
C STG 6 BALANCE OF PLANT TURBINE 6 CONDENSER VACUUM ROUTE CONDUIT
CONTROL PANEL BREAKER VALVE DISCRETE OUTPUT SIGNALS
EP102 EI101B
EI819 EI819
12/17/2020 < EAFB, EIE443 CHPP TURBINE GENERATOR > Job Number: 27751
12/17/2020
FROM TAG TO TAG
FROM DESCRIPTION TO DESCRIPTION
CABLE NUMBER CABLE TYPE ROUTING
SEGR CODE PLANT SYSTEM FROM DWG TO DWG CABLE LAYING METHOD
WORK PACKAGE START UP SYSTEM FROM WIRING DWG TO WIRING DWG LEN CABLE NOTE REV
06-CND-C-021 5/C #14 06-BOP-CPL-001 MCC-H 100FT FIELD ROUTE CONDUIT 0
C STG 6 BALANCE OF PLANT 480VAC MCC, 3PH, 3W, 800A MCC BUCKET H9, 06-CND-PMP-601B DISCRETE OUTPUT
CONTROL PANEL (EXIST) SIGNALS
EP102 EP102, E-604
EI819 E-616, EI819
06-CND-C-022 5/C #14 06-BOP-CPL-001 MCC-H 100FT FIELD ROUTE CONDUIT 0
C STG 6 BALANCE OF PLANT 480VAC MCC, 3PH, 3W, 800A MCC BUCKET H10, 06-CND-PMP-604B DISCRETE OUTPUT
CONTROL PANEL (EXIST) SIGNALS
EP102 EP102, E-604
EI819 E-616, EI819
06-CND-I-007 1TSP #16 06-BOP-CPL-001 06-CND-LIT-631A 100FT FIELD ROUTE CONDUIT, TC-001/2, TC-002/2, FIELD 0
I STG 6 BALANCE OF PLANT TURBINE 6 CONDENSER HOTWELL ROUTE CONDUIT
CONTROL PANEL LEVEL A
EP102 EI101B
EI802 EI802
06-CND-I-008 1TSP #16 06-BOP-CPL-001 06-CND-PDIT-610A 50FT FIELD ROUTE CONDUIT, TC-001/2, FIELD ROUTE 0
I STG 6 BALANCE OF PLANT TURBINE 6 COND HOTWELL PUMP CONDUIT
CONTROL PANEL A SUCTION STRNR DIFF PRESS
EP102 EI101B
EI802 EI802
06-CND-I-009 1TSP #16 06-BOP-CPL-001 06-CND-TIT-615 50FT FIELD ROUTE CONDUIT, TC-001/2, TC-002/2, FIELD 0
I STG 6 BALANCE OF PLANT TURBINE 6 CONDENSER HOTWELL ROUTE CONDUIT
CONTROL PANEL PUMPS DISCHARGE TEMP XMTR
EP102 EI101B
EI802 EI802
06-CND-I-010 1TSP #16 06-BOP-CPL-001 06-CND-PIT-616 50FT FIELD ROUTE CONDUIT, TC-001/2, TC-002/2, FIELD 0
I STG 6 BALANCE OF PLANT TURBINE 6 COND HOTWELL PUMPS ROUTE CONDUIT
CONTROL PANEL DISCHARGE PRESSURE
EP102 EI101B
EI802 EI802
12/17/2020 < EAFB, EIE443 CHPP TURBINE GENERATOR > Job Number: 27751
12/17/2020
FROM TAG TO TAG
FROM DESCRIPTION TO DESCRIPTION
CABLE NUMBER CABLE TYPE ROUTING
SEGR CODE PLANT SYSTEM FROM DWG TO DWG CABLE LAYING METHOD
WORK PACKAGE START UP SYSTEM FROM WIRING DWG TO WIRING DWG LEN CABLE NOTE REV
06-CND-I-011 1TSP #16 06-BOP-CPL-001 06-CND-FIT-001 50FT FIELD ROUTE CONDUIT, TC-001/2, FIELD ROUTE 0
I STG 6 BALANCE OF PLANT TURBINE 6 CONDENSER HOTWELL CONDUIT
CONTROL PANEL PUMPS DISCHARGE FLOW XMTR
EP102 EI101B
EI802 EI802
06-CND-I-012 1TSP #16 06-BOP-CPL-001 06-CND-TIT-002 100FT FIELD ROUTE CONDUIT, TC-001/2, TC-002/2, FIELD 0
I STG 6 BALANCE OF PLANT TURBINE 6 SJAE CONDENSATE ROUTE CONDUIT
CONTROL PANEL OUTLET TEMP XMTR
EP102 EI101B
EI802 EI802
06-CND-I-015 1TSP #16 06-BOP-CPL-001 06-CND-FCV-001 50FT FIELD ROUTE CONDUIT, TC-001/2, FIELD ROUTE 0
I STG 6 BALANCE OF PLANT TURBINE 6 CONDENSER HOTWELL CONDUIT
CONTROL PANEL RECIRC FCV
EP102 EI101B
EI804 EI804
06-CND-I-020 1TSP #16 06-BOP-CPL-001 06-CND-PIT-630 100FT FIELD ROUTE CONDUIT, TC-001/2, TC-002/2, FIELD 0
I STG 6 BALANCE OF PLANT TURBINE 6 CONDENSER PRESSURE ROUTE CONDUIT
CONTROL PANEL
EP102 EI101B
EI812 EI812
06-CND-I-021 1TSP #16 06-BOP-CPL-001 06-CND-LIT-631B 100FT FIELD ROUTE CONDUIT, TC-001/2, TC-002/2, FIELD 0
I STG 6 BALANCE OF PLANT TURBINE 6 CONDENSER HOTWELL ROUTE CONDUIT
CONTROL PANEL LEVEL B
EP102 EI101B
EI812 EI812
06-CND-I-022 1TSP #16 06-BOP-CPL-001 06-CND-TIT-633 100FT FIELD ROUTE CONDUIT, TC-001/2, TC-002/2, FIELD 0
I STG 6 BALANCE OF PLANT TURBINE 6 CONDENSER HOTWELL ROUTE CONDUIT
CONTROL PANEL TEMP XMTR
EP102 EI101B
EI812 EI812
12/17/2020 < EAFB, EIE443 CHPP TURBINE GENERATOR > Job Number: 27751
12/17/2020
FROM TAG TO TAG
FROM DESCRIPTION TO DESCRIPTION
CABLE NUMBER CABLE TYPE ROUTING
SEGR CODE PLANT SYSTEM FROM DWG TO DWG CABLE LAYING METHOD
WORK PACKAGE START UP SYSTEM FROM WIRING DWG TO WIRING DWG LEN CABLE NOTE REV
06-CND-I-023 1TSP #16 06-BOP-CPL-001 06-CND-PDIT-610B 50FT FIELD ROUTE CONDUIT, TC-001/2, FIELD ROUTE 0
I STG 6 BALANCE OF PLANT TURBINE 6 COND HOTWELL PUMP CONDUIT
CONTROL PANEL B SUCTION STRNR DIFF PRESS
EP102 EI101B
EI812 EI812
06-CND-I-024 1TSP #16 06-BOP-CPL-001 06-CND-FIT-640 50FT FIELD ROUTE CONDUIT, TC-001/2, FIELD ROUTE 0
I STG 6 BALANCE OF PLANT TURBINE 6 CONDENSATE FLOW CONDUIT
CONTROL PANEL XMTR
EP102 EI101B
EI813 EI813
06-CND-I-025 1TSP #16 06-BOP-CPL-001 06-CND-LIT-603 75FT FIELD ROUTE CONDUIT, TC-001/2, TC-002/2, FIELD 0
I STG 6 BALANCE OF PLANT STG 6 CONDENSATE DRAINS TANK ROUTE CONDUIT
CONTROL PANEL LEVEL XMTR
EP102 EI101B
EI813 EI813
06-CND-I-028 1TSP #16 06-BOP-CPL-001 06-CND-LIT-631C 100FT FIELD ROUTE CONDUIT, TC-001/2, TC-002/2, FIELD 0
I STG 6 BALANCE OF PLANT TURBINE 6 CONDENSER HOTWELL ROUTE CONDUIT
CONTROL PANEL LEVEL C
EP102 EI101B
EI813 EI813
06-CND-I-029 1TSP #16 06-BOP-CPL-001 06-CND-LCV-631 50FT FIELD ROUTE CONDUIT, TC-001/2, FIELD ROUTE 0
I STG 6 BALANCE OF PLANT TURBINE 6 CONDENSER HOTWELL CONDUIT
CONTROL PANEL LCV
EP102 EI101B
EI815 EI815
06-CND-I-053 1TST #16 06-CND-TE-615 06-CND-TIT-615 30FT FIELD ROUTE CONDUIT 0
I TURBINE 6 CONDENSER HOTWELL TURBINE 6 CONDENSER HOTWELL
PUMPS DISCH RTD PUMPS DISCHARGE TEMP XMTR
EI101B EI101B
EI802 EI802
12/17/2020 < EAFB, EIE443 CHPP TURBINE GENERATOR > Job Number: 27751
12/17/2020
FROM TAG TO TAG
FROM DESCRIPTION TO DESCRIPTION
CABLE NUMBER CABLE TYPE ROUTING
SEGR CODE PLANT SYSTEM FROM DWG TO DWG CABLE LAYING METHOD
WORK PACKAGE START UP SYSTEM FROM WIRING DWG TO WIRING DWG LEN CABLE NOTE REV
06-CND-I-054 1TST #16 06-CND-TE-602 06-CND-TIT-002 30FT FIELD ROUTE CONDUIT 0
I SJAE CONDENSATE OUTLET TEMP TURBINE 6 SJAE CONDENSATE
ASSEMBLY OUTLET TEMP XMTR
EI101B EI101B
EI802 EI802
06-COM-T-001 FIBER 2 MM SECTION 105 06-TURB-CPL-001 300FT COMMUNICATIONS, FIELD ROUTE CONDUIT 0
T MASTER CONTROL CUBICLE TURBINE 6 CONTROL PANEL
EP103 EP102
EI601 EI601
06-COM-T-002 FIBER 2 MM SECTION 105 06-BOP-CPL-001 300FT COMMUNICATIONS, FIELD ROUTE CONDUIT 0
T MASTER CONTROL CUBICLE STG 6 BALANCE OF PLANT
CONTROL PANEL
EP103 EP102
EI601 EI601
06-COM-T-025 CAT 6 ETHERNET 06-GEN-CPL-001 06-TURB-CPL-001 30FT FIELD ROUTE CONDUIT 0
T GENERATOR 6 CONTROL PANEL TURBINE 6 CONTROL PANEL
W/AVR (NEW)
EP102 EP102
EI601 EI601
06-HPS-C-001 7/C #14 06-BOP-CPL-001 06-HPS-MOV-001 100FT FIELD ROUTE CONDUIT, TC-001/3, TC-002/3, FIELD 0
C STG 6 BALANCE OF PLANT TURBINE 6 HIGH PRESSURE ROUTE CONDUIT
CONTROL PANEL STEAM SUPPLY ISOL VLV
EP102 EI101
EI805 EI805
06-HPS-C-002 5/C #14 06-BOP-CPL-001 06-HPS-LCV-601 125FT FIELD ROUTE CONDUIT, TC-001/3, TC-002/3, FIELD 0
C STG 6 BALANCE OF PLANT TURBINE 6 HIGH PRESSURE ROUTE CONDUIT
CONTROL PANEL STEAM SUPPLY DRAIN POT LCV
EP102 EI101
EI805 EI805
12/17/2020 < EAFB, EIE443 CHPP TURBINE GENERATOR > Job Number: 27751
12/17/2020
FROM TAG TO TAG
FROM DESCRIPTION TO DESCRIPTION
CABLE NUMBER CABLE TYPE ROUTING
SEGR CODE PLANT SYSTEM FROM DWG TO DWG CABLE LAYING METHOD
WORK PACKAGE START UP SYSTEM FROM WIRING DWG TO WIRING DWG LEN CABLE NOTE REV
06-HPS-C-006 5/C #14 06-BOP-CPL-001 06-HPS-MOV-001 100FT FIELD ROUTE CONDUIT, TC-001/3, TC-002/3, FIELD 0
C STG 6 BALANCE OF PLANT TURBINE 6 HIGH PRESSURE ROUTE CONDUIT
CONTROL PANEL STEAM SUPPLY ISOL VLV
EP102 EI101
EI809 EI809
06-HPS-C-0062 7/C #14 06-HPS-MOV-001 06-HPS-LCS-001 125FT FIELD ROUTE CONDUIT 0
C TURBINE 6 HIGH PRESSURE HIGH PRESS STEAM SUPPLY ISOL
STEAM SUPPLY ISOL VLV VLV LOCAL CNTRL STATION
EI101
EI809 EI809
06-HPS-C-007 3/C #14 06-BOP-CPL-001 06-HPS-LCV-601 30FT FIELD ROUTE CONDUIT, TC-001/3, TC-002/3, FIELD 0
C STG 6 BALANCE OF PLANT TURBINE 6 HIGH PRESSURE ROUTE CONDUIT
CONTROL PANEL STEAM SUPPLY DRAIN POT LCV
EP102 EI101
EI805 EI805
06-HPS-I-001 1TSP #16 06-BOP-CPL-001 06-HPS-LIT-601A 125FT FIELD ROUTE CONDUIT, TC-001/2, TC-002/2, FIELD 0
I STG 6 BALANCE OF PLANT TURBINE 6 HIGH PRESSURE ROUTE CONDUIT
CONTROL PANEL STEAM DRAIN POT LEVEL XMTR A
EP102 EI101
EI802 EI802
06-HPS-I-002 1TSP #16 06-BOP-CPL-001 06-HPS-FIT-002 100FT FIELD ROUTE CONDUIT, TC-001/3, TC-002/3, FIELD 0
I STG 6 BALANCE OF PLANT TURBINE 6 HIGH PRESSURE ROUTE CONDUIT
CONTROL PANEL STEAM SUPPLY FLOW XMTR
EP102 EI102
EI802 EI802
06-HPS-I-016 1TSP #16 06-BOP-CPL-001 06-HPS-LIT-601B 125FT FIELD ROUTE CONDUIT, TC-001/3, TC-002/3, FIELD 0
I STG 6 BALANCE OF PLANT TURBINE 6 HIGH PRESSURE ROUTE CONDUIT
CONTROL PANEL STEAM DRAIN POT LEVEL XMTR B
EP102 EI101
EI812 EI812
12/17/2020 < EAFB, EIE443 CHPP TURBINE GENERATOR > Job Number: 27751
12/17/2020
FROM TAG TO TAG
FROM DESCRIPTION TO DESCRIPTION
CABLE NUMBER CABLE TYPE ROUTING
SEGR CODE PLANT SYSTEM FROM DWG TO DWG CABLE LAYING METHOD
WORK PACKAGE START UP SYSTEM FROM WIRING DWG TO WIRING DWG LEN CABLE NOTE REV
06-HPS-I-058 1TST #16 06-HPS-TE-002 06-HPS-FIT-002 30FT FIELD ROUTE CONDUIT 0
I TURBINE 6 HIGH PRESSURE TURBINE 6 HIGH PRESSURE
STEAM SUPPLY RTD STEAM SUPPLY FLOW XMTR
EI102 EI102
EI802 EI802
06-LOL-C-064 3/C #14 06-LOL-CPL-001 06-TURB-CPL-001 100FT FIELD ROUTE CONDUIT, TC-001/3, TC-002/3, FIELD 0
C OIL PURIFIER SKID CONTROL TURBINE 6 CONTROL PANEL ROUTE CONDUIT
PANEL
EP101 EP102
BY VENDOR BY VENDOR
06-LPS-C-003 7/C #14 06-BOP-CPL-001 06-LPS-MOV-003 30FT FIELD ROUTE CONDUIT, TC-001/3, FIELD ROUTE 0
C STG 6 BALANCE OF PLANT TURB 6 LOW PRESS STEAM CONDUIT
CONTROL PANEL EXTRACT ISOL VLV
EP102 EI101A
EI805 EI805
06-LPS-C-008 5/C #14 06-BOP-CPL-001 06-LPS-MOV-003 30FT FIELD ROUTE CONDUIT, TC-001/3, FIELD ROUTE 0
C STG 6 BALANCE OF PLANT TURB 6 LOW PRESS STEAM CONDUIT
CONTROL PANEL EXTRACT ISOL VLV
EP102 EI101A
EI809 EI809
06-LPS-C-011 5/C #14 06-BOP-CPL-001 06-LPS-LCV-601 75FT FIELD ROUTE CONDUIT, TC-001/3, TC-002/3, FIELD 0
C STG 6 BALANCE OF PLANT TURB 6 LOW PRESS STEAM ROUTE CONDUIT
CONTROL PANEL EXTRACT DRAIN POT LCV
EP102 EI101A
EI816 EI816
06-LPS-C-012 5/C #14 06-BOP-CPL-001 06-LPS-LCV-602 50FT FIELD ROUTE CONDUIT, TC-001/3, FIELD ROUTE 0
C STG 6 BALANCE OF PLANT TURB 6 LOW PRESS STEAM CONDUIT
CONTROL PANEL EXTRACT ISOL VLV DRN POT LCV
EP102 EI101A
EI816 EI816
12/17/2020 < EAFB, EIE443 CHPP TURBINE GENERATOR > Job Number: 27751
12/17/2020
FROM TAG TO TAG
FROM DESCRIPTION TO DESCRIPTION
CABLE NUMBER CABLE TYPE ROUTING
SEGR CODE PLANT SYSTEM FROM DWG TO DWG CABLE LAYING METHOD
WORK PACKAGE START UP SYSTEM FROM WIRING DWG TO WIRING DWG LEN CABLE NOTE REV
06-LPS-C-013 5/C #14 06-BOP-CPL-001 06-LPS-LCV-603 75FT FIELD ROUTE CONDUIT, TC-001/3, FIELD ROUTE 0
C STG 6 BALANCE OF PLANT TURB 6 LOW PRESS STEAM CONDUIT
CONTROL PANEL RECYCLE DRAIN POT LCV
EP102 EI101A
EI816 EI816
06-LPS-C-017 3/C #14 06-BOP-CPL-001 06-LPS-LCV-601 75FT FIELD ROUTE CONDUIT, TC-001/3, TC-002/3, FIELD 0
C STG 6 BALANCE OF PLANT TURB 6 LOW PRESS STEAM ROUTE CONDUIT
CONTROL PANEL EXTRACT DRAIN POT LCV
EP102 EI101A
EI819 EI819
06-LPS-C-018 3/C #14 06-BOP-CPL-001 06-LPS-LCV-602 50FT FIELD ROUTE CONDUIT, TC-001/3, FIELD ROUTE 0
C STG 6 BALANCE OF PLANT TURB 6 LOW PRESS STEAM CONDUIT
CONTROL PANEL EXTRACT ISOL VLV DRN POT LCV
EP102 EI101A
EI819 EI819
06-LPS-C-019 3/C #14 06-BOP-CPL-001 06-LPS-LCV-603 75FT FIELD ROUTE CONDUIT, TC-001/3, FIELD ROUTE 0
C STG 6 BALANCE OF PLANT TURB 6 LOW PRESS STEAM CONDUIT
CONTROL PANEL RECYCLE DRAI