317446_DWG-ELEC.pdf

PDF 4 MB Posted

Attached to
Repair Building S-1832, Camp Casey, Korea (MATOC Only)
Solicitation number
W90VN824R0062
Issued by

About this file

This document is a set of engineering drawings and specifications for a contract to repair Building S-1832 at Camp Casey, Korea. The key details are:

The scope of work includes structural, architectural, mechanical, and electrical repairs and upgrades. Structural work involves replacing existing columns with steel columns. Architectural work includes replacing deteriorated flooring, walls, ceilings, roofing, doors, windows, and other interior and exterior building components. Mechanical work consists of installing new HVAC, plumbing, and ventilation systems. Electrical work entails replacing lighting, power distribution equipment, the fire alarm/mass notification system, and the telecommunication system. The contract is a MATOC (Multiple Award Task Order Contract) opportunity issued by the Army Contracting Command. No award date or pricing details are provided in the document.

View the file

Other files

File Type Posted
317446_DWG-MECH.pdf PDF
W90VN824R0062.pdf PDF
317446_DWG-ARCH (1).pdf PDF
317446_DWG-STRC.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL NOTES

1.

2.MOUNTING HEIGHTS ABOVE FLOOR SHALL BE AS FOLLOW UNLESS OTHERWISE

NOTED ON THE DRAWING.

LIGHTING FIXTURE SEE LIGHTING FIXTURE SCHEDULE

PANELBOARD SEE SPECIFICATION

SAFETY SWITCH 1524mm TO CENTER OF THE ENCL

350mm TO CENTER OF THE ENCL

MOTOR CONTROLLER 1524mm TO CENTER OF THE ENCL

3.

4.

6.THE SOIL RESISTANCE TO GROUND FOR THE ELECTRICAL AND COMMMUNICATION

SYSTEMS SHALL BE 25 OHMS OR LESS. THE SOIL RESISTANCE TEST SHALL BE

7.

5.

CONDUCTED BY THE CONTRACTOR TO OBTAIN THE REQUIRED SOIL RESISTANCE.

INDICATEDS 2 #12AWG IN 16C

INDICATEDS 3 #12AWG IN 16C

INDICATEDS 4 #12AWG IN 16C

A GREATER NUMBER OF WIRES ARE INDICATED AS FOLLOWS;

1219mm TO CENTER OF THE ENCLWALL SWTICH

CONDUIT UNLESS OTHERWISE INDICATED.

ALL EQUIPMENT CONTROL WIRING SHALL BE #14 AWG. "TW" IN 16C

AND LOCATION OF THE F/A ANTENNA WITH THE CENTRAL FIRE DEPARTMENT

THE CONTRACTOR SHALL SUBMIT THE SHOP DRAWING FOR THE MOUNTING

TO TRANSMIT THE ALARM RADIO SIGNAL WAVE WITHOUT ANY OBSTRUCTION.

DETAIL OF THE F/A ANTENNA, AND COORDINATE THE MOUNTING HEIGHT

F/A EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.

THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

SCOPE OF WORKS

LEGEND, GENERAL NOTES AND

E-1

12.

13.

14.

10.

11.

8.

9.

15.

SINGLE POLE TOGGLE SWITCH, 15A-125V

L E G E N D

FLEXIBLE CONDUIT W/CONNECTORS

LIGHTING

WIRING

POWER

INTERIOR

S

SYMBOL DESCRIPTION

DESCRIPTION

DESCRIPTION

J JUNCTION BOX

SYMBOL

SYMBOL

F FAN MOTOR (UNDER MECH. ITEM)

SAFETY SWITCH

C CONTROL CIRCUIT

3-WAY SWITCH, 15A-125V

AND GOVERNMENT INSTALLED

GOVERNMENT FURNISHED

GFGI

WEATHERPROOFWP

LA LIGHTNING ARRESTER

EXPLOSIONPROOFEP

DISTRIBUTIONDIST

GROUND FAULT PROTECTIONGFP

A AMPERE

AC ALTERNATING CURRENT

AF/AT AMPERE FRAME/AMPERE TRIP

AWG AMERICAN WIRE GAUGE

BC BARE COPPER

BLDG BUILDING

BRKR BREAKER

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CONN CONNECTION

CT CURRENT TRANSFORMER

DET(S) DETAIL(S)

DIAG DIAGRAM

DISC DISCONNECT

DWG(S) DRAWING(S)

EA EACH

EM EMERGENCY

ENCL ENCLOSURE

EXST EXISTING

F/A FIRE ALARM

FL FLOOR

FLUOR FLUORESCENT

FXTR FIXTURE

GEN GENERATOR

GND GROUND

HP HORSE POWER

HZ HERTZ

INCAND INCANDESCENT

INSTL INSTALLATION

J-BOX JUNCTION BOX

K KILO

KV KILO VOLT

KVA KILO VOLT AMPERE

LTG LIGHTING

MAG MAGNETIC

MAX MAXIMUM

MIN MINIMUM OR MINUTE

MTG MOUNTING

NO NUMBER

O/H OVER HEAD

PH PHASE

PNLBD PANELBOARD

PRIM PRIMARY

PWR POWER

Q'TY QUANTITY

RCPT RECEPTACLE

REQ'D REQUIRED

SCHED SCHEDULE

SEC SECONDARY

SPEC SPECIFICATION

STD STANDARD

SW SWITCH

TEL TELEPHONE

TYP TYPICAL

U/G UNDERGROUND

V VOLT

VA VOLT AMPERE

W WATT

W/ WITH

XFMR TRANSFORMER

& AND

CABNET TYPE, RATED WATT ON LTG SCHEDULE

LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER

ON LTG SCHEDULE, WET LOCATION

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

FAULT PROTECTED TYPE

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED

PANELBOARD

HOMERUN CIRCUIT TO PANELBOARD

TYPE OF MTG ON LTG SCHEDULE

EXTERIOR LED LIGHTING FIXTURE, RATED WATT &

TYPE

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING

ABBREVIATION

THE COTNRACTOR SHALL SUBMIT A SHOP DRAWING OF HVAC SYSTEM

IN ACCORDANCE WITH SEQUENCE OF OPERATION INDICATED ON THE

MECHANICAL DRAWINGS.

ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG

WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.

THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR

ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.

CATV BEFORE CONSTRUCTION.

CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,

AND GOVERNMENT ACCEPTANCE.

PANELBOARD DOOR, REQUIRED BEFORE FINAL BUILDING INSPECTION

CONTRACTOR SHALL MAKE CIRCUIT CHARTS AND ATTACH THEM TO

FIRE CODE AND SPECIFICATIONS.

OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,

ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS

OR RENOVATION.

CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION

THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING

FIXTURE A MINIMUM DISTANCE OF 458mm.

FIRE ALARM DETECTORS SHALL BE LOCATED TO CLEAR ANY LIGHTING

FMCP

FTR

AUXILIARY

DESCRIPTIONSYMBOL

STROBES

WALL MOUNTED SPEAKER /COMBO. (FA+MNS)VISUAL

BUILDING TRANSMITTER UNIT FOR FIRE ALARM

SYSTEM

L

WP

FAULT PROTECTED TYPE, WEATHER PROOF

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED

TYPE

SINGLE RECEPTACLE, 2P-3W-20A-125V, GROUNDING

L

L

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

W/EMERGENCY BATTERY UNIT

L

W/EMERGENCY UNIT TYPE

QUADPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

L

L

UNITS.

CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER

CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY

16.

THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE

WIDTH OF DUCT EXCAVATION.

AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.

TO THEIR ORIGINAL CONDITION AND OPERATION DURING

ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES

THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING

THE MANUFACTURER AND MODEL OF NEW BUILDING TRANSMITTER EQUIPMENT

IN THE CENTRAL FIRE DEPARTMENT.

THE EQUIPMENT SHOULD BE TESTED WITH THE RECEIVING SYSTEM(D21)

SHALL BE COORDINATED WITH THE CENTRAL FIRE DEPARTMENT.

RECEPTACLE

AND WALL

WIRING CONCEALED OR EXPOSED IN/ON THE CEILING

CEILING OR CONCEALED IN NEW WALL.

ALL WIRING SHALL BE CONCEALED ABOVE CEILING WHEN THE ROOM HAS

SCOPE OF WORK

1.

A. REPAIR/MAINTENANCE ( K )

4.

2.

5.

3.

3S

TYPE WITH PLUG

SINGLE RECEPTACLE, 2P-3W-20A-125/250V, GROUNDING

L

FIRE ALARM & MNSCONTROL PANEL

F

F/M

FIRE ALARM & MNS CIRCUIT

T LAN/TEL LINE

ELECTRICAL

AND ASSOCIATED WIRE & CONDUIT WITH NEW.

OUTLETS W/COVER PLATES, TERMINAL BLOCKS, EQUIPMENT RACK

INCLUDING TELEPHONE TERMINAL BOARD, TELEPHONE/DATA

REPLACE DETERIORATED EXISTING TELECOMMUNICATION SYSTEM

L

L

DS

L

ON LTG SCHEDULE, OUTDOOR TYPE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

7.

CONDUITS FOR MECHANICAL SYSTEMS WITH NEW.

CONTROLLERS, JUNCTION BOXES, CONTROL/POWER WIRES AND

REPLACE DETERIORATED EXISTING SAFETY SWTICHES, MOTOR

6.

ON LTG SCHEDULE, FOR INDIRECT LIGHT

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

ON LTG SCHEDULE, DOWN LIGHT

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

REQUIRED

DIMMING CONTROL SWITCH, 15A-125V, LED, WIRING AS

ANTENNA, SURGE PROTECTOR, AND ASSOCIATED WIRING AND CONDUIT.

SPEAKER (WATTAGE AS REQ'D) DEVICE,FIRE ALARM BUILDING TRANSMITTER,

ANTENNA, VISUAL/SIGNAL STROBES (15 OR 75 CANDELA), MICROPHONE,

PANEL, MANUAL PULL STATION, SMOKE DETECTOR & RELAY MODULE,

ADDRESSABLE FIRE ALARM CONTROL AND MASS NOTIFICATION SYSTEM

REPLACE DETERIORATED FIRE ALARM CONTROL SYSTEM WITH NEW

WITH NEW.

FIXTURES, EXIT LIGHTS, TOGGLE SWITCHES, WIRES AND CONDUITS

REPLACE DETERIORATED EXISTING INTERIOR/ EXTRIOR LIGHTING

INCLUDING PAD MOUNTED TRANSFORMER.

REPLACE EXISTING EXTERIOR POWER DISTIBUTION SYSTEM WITH NEW

ACCESSORIES WITH NEW.

REPLACE EXISTING EXTERIOR UNDERGROUND TELECOMMUNICATION LINE,

& CONDUITS WITH NEW.

PANELBOARDS, RECEPTACLES W/COVER PLATES, ASSOCIATED WIRING

REPLACE EXISTING WATTHOUR METER, CURRENT TRANSFORMERS,

317446

TAK, YS

CP CASEY

REPAIR BLDG S-1832

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-2

1/100

SCALE :

NEW GROUND FL LIGHTING PLAN

ELECTRICAL

NEW GROUND FL LIGHTING PLAN

FEC

W.TOILET

M.TOILET

STORAGE

COMM RM

OFFICE

RECONDITIONING AREA

OFFICE

OPEN ADMIN AREA

J/C

PHYSICAL TRAINING AREA

L L

L L L

L L

L L

L

L

L

L

L

L

LL

L

L L L

L

L L

L L L

L a a a a a a a b b b b b b b b b b b b b b a a a a a a a

S Sa b

L

L

L

L

SS

L

L

LL LLL

S S

LLLLLL

LL L L L L

L

S

L

S

L

S

LL

L

S

L

S

L

S

L

L L

S

L

L

S

L

SS

L L

L

STORAGE

MECH

"P"

P-1

P-1,2

P-3

P-4

"M P

317446

TAK, YS

CP CASEY

S

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-3 m m

308mm

NS-3a & 3b

FIXTURE, 1PH, 120V, 45W, WITH CONVERTER &

ACCESSORIES AS REQUIRED, (NS-5a) & WITH EM UNIT (NS-5b)

OR APPROVED EQUAL.

CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)

FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES,

AS REQUIRED, OR APPROVED EQUAL.

WALL SURFACE MOUNTED LIGHT EMITTING DIODE (LED)

WALL OR CEILING SURFACE MOUNTED LIGHT EMITTING

WITH BATTERY CHARGER, SINGLE FACE (NS-3a) OR

(MAX INPUT) OR 7.22W(MAX INPUT), BATTERY BACK-UP

DIODE(LED) EXIT LIGHT FIXTURE, 1PH, 120V, 4.99W

m m

1220m m

0m m

FIXTURE, 1PH, 120V, 50W, WITH CONVERTER &

ACCESSORIES AS REQUIRED, (NS-6a) & WITH EM UNIT (NS-6b)

CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)

DOUBLE FACE (NS-3b) OR APPROVED EQUAL.

NS-5a & 5b NS-6a & 6b NS-7a & 7b

NS-8

245mm

254mm

CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED)

OR APPROVED EQUAL.

WET LOCATION SHOWER LIGHT TRIM, AS REQUIRED

FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES,

WALL

CEILING SURFACE/PENDANT MOUNTED LIGHT EMITTING DIODE (LED)

FIXTURE, 1PH, 120V, 45W, UL LISTED, WITH CONVERTER AND

ACCESSORIES AS REQUIRED, (NS-7a) & EM UNIT(NS-7b)

ELECTRICAL

LIGHTING FIXTURE DETAILS

WALL OR CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED)

NS-10

FIXTURE SCHEDULE)

(OPTION: DIMMING CONTROL (SEE REMARKS IN LIGHT

LOCATION TYPE, UL LISTED

LIGHTING FIXUTURE 1PH, 120V, 22W LED MODULES, COLOR TEMP. 3000K,

WITH CONVERTER AND ACCESSORIES W/BUILT-IN PHOTOCELL, WET

NS-9

317446

TAK, YS

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-4

REMARKSQ'TY

WATTS

MOUNTING METHOD

TYPE

LAMP

NAMENO

101, ROOM OCE STD DET 40-06-04

LIGHT FIXTURE SCHEDULE

TYPE

LED

NS-6b 50 6

CEILING RECESSED

LIGHT FIXTURE SCHEDULE

ELECTRICAL

NS-6a

NS-6a

NS-6b

W/ "EM" UNIT

W/ "EM" UNIT

M.TOILET

CEILING RECESSED

CEILING SURFACE

NS-6a

50NS-6b

110 145

45 1

NS-7b

NS-7b

NS-5a

NS-10 22 3

- EXIT SIGN

- EXTERIOR LIGHT

1/4.99NS-3

MOUNTED

WALL/CEILING SURFACE

W/ARROW FOR CEILING SURFACE

W/ "EM" UNIT

W/ "EM" UNIT

W/ "EM" UNIT

OPEN ADMIN AREA/

RECONDITIONING AREA

AREA

PHYSICAL TRAINING103 2150

NS-6b 50 7

NS-6a

W/ "EM" UNIT

1 W/ "EM" UNIT

NS-5a

NS-5b

NS-8 WALL MOUNTED ABOVE THE MIRROR TOP

J/C105

1 W/ "EM" UNIT

NS-5a

NS-5b

NS-8 WALL MOUNTED ABOVE THE MIRROR TOP

CEILING RECESSEDW.TOILET

STORAGE 1

NS-5a

NS-5b 45

OFFICE

OFFICE

COMM RM

111 MECH RM

STORAGE

ABOVE THE DOOR TOP

145NS-5b W/ "EM" UNIT

W/ "EM" UNITCEILING SURFACE

CEILING RECESSED

WALL MOUNTED

NS-9

317446

TAK, YS

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

1/100

SCALE :

FEC

W.TOILET

M.TOILET

STORAGE

COMM RM

ELEC RM

OFFICE

PHYSICAL TRAINING AREA

RECONDITIONING AREA

OFFICE

OPEN ADMIN AREA

J/C

EWC

"P"

P-10

STORAGE

P-6

P-7 P-8

P-9

P-11

P-12

P-13

P-15

P-14

P-5

P-16

"M P

EXIST ROLLUP DOOR

NEW GROUND FL POWER PLAN

NEW GROUND FL POWER PLAN

317446

TAK, YS

CP CASEY

E-5

FEC

W.TOILET

M.TOILET

STORAGE

COMM RM

OFFICE

PHYSICAL TRAINING AREA

RECONDITIONING AREA

OFFICE

OPEN ADMIN AREA

J/C

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

HPU

HPU

HPU

HPU

HPU

HPU

HPU

HPU

HPU

EUH

ELEC. UNIT HEATER

EUH

ELEC. UNIT HEATER

OHPU

OHPU

EF

EXHAUST FAN

EF

EXHAUST FAN

EF

EXHAUST FAN

DOMESTIC HOT WATER

RECIRC. PUMP

P

M

ELEC. DOMESTIC HOT WATEREWH

EF

EXHAUST FAN

EF

EXHAUST FAN

EF

EXHAUST FAN

M

B A

D

STORAGE

C

J

P-21

EH

J

P-22 a a a a a

J

MP-5

P-18

MECH RM

a

J

P-20 P-23

P-24

J

J

P-17

J

J P-26

J

M-3 J

M-1 P1-8

M-2

"M" J

M-4

SCALE : 1/100

NEW POWER/CONTROL PLAN FOR MECHANICAL SYSTEM

B

MAGNETIC MOTOR STARTER, 2P-120V

NEMA SIZE "00" W/O.L RELAYS,

PILOT LAMP(GREEN), AND 3-POSITION

SELECTOR SWITCH (H-O-A)

NON-FUSIBLE, NEMA 3R ENCL

NON-FUSIBLE, NEMA 3R ENCL

* ADDITIONAL LEGEND(THIS SHEET ONLY)

FOR OHPU-1

FOR OHPU-2

C

FOR DOA-1

SAFETY SWITCH, 3PST, 240V, 60AA

DEDICATED OUTSIDE AIR SUPPLY UNIT

EUH ELECTRIC UNIT HEATER (FOR MECH ROOM)

ELECTRIC WALL HEATER-1

EH

WALL EXHAUST FAN

SAFETY SWITCH, DPST, 240V, 30A

NON-FUSIBLE, NEMA 1 ENCL

SINGLE RECEPTACLE, 2P-3W-20A-240VAC

GROUNDING TYPE W/PLUG

MP-4

2250WATTS, 208V, 1PH (MECH ITEM)

OHPU

22.6 AMP MCA, 208V, 3PH (MECH ITEM)

OUTDOOR SPLIT SYSTEM HEAT PUMP UNIT-1 (OUTDOOR UNIT)

111.4 AMP MCA, 208V, 3PH (MECH ITEM)

OUTDOOR SPLIT SYSTEM HEAT PUMP UNIT-2 (OUTDOOR UNIT)

OHPU

2.5 AMP, 208V, 1PH (MECH ITEM)

DOAS

X

HPU INDOOR SPLIT SYSTEM HEAT PUMP UNIT(1-3)

40-199WATTS, 208V, 3PH (MECH ITEM)

EUH

1.0KW, 208V, 1PH (MECH ITEM)

2.0KW, 208V, 1PH (MECH ITEM)

12.5A, 120V, 1PH (MECH ITEM)

1/6HP, 115V, 1 PH (MECH ITEM)

WALL EXHAUST FAN

1/6HP, 115V, 1 PH (MECH ITEM)

WALL EXHAUST FAN

1/4HP, 115V, 1 PH (MECH ITEM)

1/4HP, 115V, 1 PH (MECH ITEM)

ROOF EXHAUST FAN

WALL EXHAUST FAN

1/4HP, 115V, 1 PH (MECH ITEM)

EF

EF

EF

EF

EF

P

1/4HP, 115V, 1 PH (MECH ITEM)

EWH

SAC SPLIT AIR CONDITIONING

4.5KW, 208V, 1PH (MECH ITEM)

RECIRC. PUMP

DOMESTIC HOT WATER

ELEC. DOMESTIC HOT WATER HEATER

EH

SAC SPLIT AIR CONDITIONING

"M P

"P"

MP-5

P-19

P-25

DOAS

NEMA 1 ENCL

D

FOR SAC-1

SAFETY SWITCH, DPST, 240V, 30A

NON-FUSIBLE, NEMA 3R ENCL

SAFETY SWITCH, 3PST, 240V, 200A

HPU

HPU

HPU

ELECTRIC UNIT HEATER (FOR STORAGE)

317446

TAK, YS

CP CASEY

REPAIR BLDG S-1832

E-6

MECHANICAL SYSTEM

NEW POWER/CONTROL PLAN FOR

a a

2#8&1#10(G) IN 27C.

3#1/0 & 6(G) IN 53.C

3#8 & 8(G) IN 27.C

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

NOT TO SCALE

EXIST/NEW POWER ONE-LINE DIAGRAM

OUTDOOR

INDOOR

300AT

400AF

100AF

3P

3P

3P 3P

100AF

3P

CONDUCTOR, #3/0(G) IN 21C

NEW GROUNDING

CU BUS, 400A

22,000AIC SYM

G

S/NGND

100AF

321 5

"P"

A B

EXT

OHPU

EXT

-2

OHPU

-1

1WAY: SPARE W/PULL WIRE & CAP

PVC CONDUIT

NEW U/G SEC LINE, 2WAY OF 103dia

100AF

50AT 40AT

NEW CONDUIT COUPLING (TYPICAL)

CONNECTION (TYPICAL)

NEW GROUND ROD, COPPER CLAD

STEEL, 19diax3000LG WITH WELDING

NEW 1#3/0 "BC" IN 27C

OIL-FILLED, SELF-COOLED, LOAD BREAK SW,

NEW PAD MOUNTED,

REPLACE EXISTING PRIM LINE

IN 103dia PVC CONDUIT

W/BUILT-IN PROTECTIVE DEVICES (20A FUSE)

G

G

ARRESTER, 18KV-3EA

25KV, 100A W/25A FUSE-3EA

ADAPTER KIT FOR SINGLE

CONDUCTOR (#1, MAX)

25KV-3EA & 600V-1EA

(UNDER MECH ITEM)

W/BUILT-IN CONTROLLER

OUTDOOR SPLIT SYSTEM HEAT PUMP UNIT-1 (OUTDOOR UNIT)

EXIST O/H PRIM LINE,

3PH, 4W, 11.4KW

RADIAL TYPE TRANSFORMER, METAL ENCL,

3#8 &

IN 27C

"XLP" 25KV & 1-1/C, #2/0, "XLP" 600V

WITH NEW U/G PRIM LINE, 3-1/C, #2/0,

IN 41C

1#8(G)

POWER: 3PH-208V, 111.4 AMP MCA

NEW

NEW #4 "BC"

NEW TERMINATION AND

NEW FUSE CUTOUT SWITCH

NEW LIGHTNING

EXIST CONC POLE

SPARE

40AT

1P

20AT

100AF

3P

225AF

WITH NEW MAIN PANELBOARD "MP"

REPLACE EXISTING MAIN PANELBOARD

1P

20AT

100AF

SPARE

C

2P

20AT

100AF

3P

30AT

100AF

3PH, 11.4KV-120/208V, 60HZ, 112.5KVA

DEDICATED OUTSIDE AIR SUPPLY UNIT

1WAY: 4-350KCMIL

IN 53C

1#6(G) B

NON-FUSIBLE, NEMA 3R ENCL

FOR OHPU-2

C

FOR DOAS-1

SAFETY SWITCH, DPST, 240V, 30A

NON-FUSIBLE, NEMA 1 ENCL

MAGNETIC MOTOR STARTER, 2P-120V

NEMA SIZE "00" W/O.L RELAYS,

PILOT LAMP(GREEN), AND 3-POSITION

SELECTOR SWITCH (H-O-A)

NEMA 1 ENCL FOR WF-1

3 100 22000

TOTAL LOAD 92879

LOAD

TOTAL

PANELBOARD "MP" LOAD SCHEDULE

LOAD DESCRIPTION

NO.

CKT

GND

S/N

DIAGRAM

CONNECTION

CIRCUIT BREAKER

PHASE LOAD

A B PC AT

SIZE

AF AIC

B CA N G

REMARK

MTD TYPE, NEMA 1 ENCL.

3PHASE ,4WIRE, 120/208V,

TOTAL DEMAND LOAD ; 83,069(VA)

31735

MAIN 3P-400AF-300AT CIRCUIT BREAKER

SUPPLY UNIT

DEDICATED OUTSIDE AIR

SPARE

SPARE

31000 1000 1000

29899 31245

4#6&1#8(G)

SPACE

SPACE

PANELBOARD "P"

PANELBOARD "M"

PANELBOARD "C"

24819 8845 6684 9290

2550 275027508050

21252000 21256250

"M"

IN 35C

1#8(G)

"C"

IN 27C

(UNDER MECH ITEM)

W/BUILT-IN CONTROLLER

OUTDOOR SPLIT SYSTEM HEAT PUMP UNIT-1 (OUTDOOR UNIT)

POWER: 3PH-208V, 22.6 AMP MCA

90AT

520 260 260

PUMP UNIT-2 (OUTDOOR UNIT)

OUTDOOR SPLIT SYSTEM HEAT

PUMP UNIT-1 (OUTDOOR UNIT)

OUTDOOR SPLIT SYSTEM HEAT

150AT

A

NON-FUSIBLE, NEMA 3R ENCL

FOR OHPU-1

SAFETY SWITCH, 3PST, 240V, 60A

SAFETY SWITCH, 3PST, 240V, 200A

40104 13368 13368 13368

150225

100 20

SPARE 1000

60HZ, SN & GND, SURFACE

SPACESPACE

SPACE SPACE

SPACESPACE

SPACESPACE

-SPACE

SPACE

-SPACE

SPACE

-SPACE

SPACE

SPARE

2.5 AMP, 220V, 1PH (MECH ITEM)

DOAS

4-350kcmil & #2(G)IN 103C.

4#3 & 4#6& 4#8 & 3#1/0 &

4-350kcmil IN 103C.

1#8(G) 1#8(G)

EXT

WHM

AUX FOR FUTURE USE & CT (300:5A)x3EA, NEMA 3R ENCL.

WIRE MODBUS RTU AND MODBUS ASCII SUPPORT,80KB MEMORY,

OR APPROVED EQUAL,3P-4W-120/208, 0.5CL RS485,2 AND 4

NEW SMART WATT HOUR METER(TARIFF METER)-TYPE MODEL:PM820-SC

317446

TAK, YS

CP CASEY

REPAIR BLDG S-1832

PANELBOARD "MP" LOAD SCHEDULE

EXIST/NEW POWER ONE-LINE DIAGRAM &

E-7

4#3&1#8(G)

4#8&1#8(G)

3#8&1#8(G)

3#1/0&1#6(G)

4#8 & 1#10(G)

1 100 10000 2#12&1#12(G)

TOTAL LOAD 2550 2750

LOAD

TOTAL

PANELBOARD "M" LOAD SCHEDULE

LOAD DESCRIPTION

NO.

CKT

GND

S/N

DIAGRAM

CONNECTION

CIRCUIT BREAKER

PHASE LOAD

A B PC AT

SIZE

AF AIC

B CA N G

REMARK

MAIN 3P-100AF-50AT CIRCUIT BREAKER

MTD TYPE, NEMA 1 ENCL.

3PHASE ,4WIRE, 120/208V,

20300

WATER HEATER

ELECTRIC DOMESTIC HOT

ELECTRIC UNIT HEATER

22502250

60HZ, SN & GND, SURFACE

SPARE 1000

SPACE

SPACE

SPACE

SPACE

SPACE

TOTAL LOAD 21252000 2125

LOAD

TOTAL

PANELBOARD "C" LOAD SCHEDULE

LOAD DESCRIPTION

NO.

CKT

GND

S/N

DIAGRAM

CONNECTION

3PHASE ,4WIRE, 120/208V,

MTD TYPE, NEMA 1 ENCL.

CIRCUIT BREAKER

1000 1000 1

PHASE LOAD

A B PC

20100 10000

AT

SIZE

AF AIC

B CA N G

REMARK

2#12&1#12(G)

TVSS

RCPT FOR TTB 1000

MAIN 3P-100AF-40AT CIRCUIT BREAKER

4#10&1#10(G)

TOTAL DEMAND LOAD ; 5,250 (VA)

SPLIT TYPE A/C UNIT 2250 1125 1125

4#4 & 1#8(G)

1000SPARE

SPARE

SPACE

SPACE

SPACE ----

2#10&1#10(G)

TVSS

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

COMM RACK

5 1000 1000 SPACE

SPACE

SPACE

-SPACE

SPACE

SPACE - - - - - - - -

DOMESTIC HOT WATER

RECIRCULATION PUMP

EXHAUST FAN-1 250 250

1 100 10000 2#12&1#12(G)

TOTAL LOAD 24819

LOAD

TOTAL

LOAD DESCRIPTION

NO.

CKT

GND

S/N

DIAGRAM

CONNECTION

CIRCUIT BREAKER

PHASE LOAD

A B PC AT

SIZE

AF AIC

B CA N G

REMARK

MTD TYPE, NEMA 1 ENCL.

3PHASE ,4WIRE, 120/208V,

700 20

9 10

20 21

839 839

TOTAL DEMAND LOAD ; 19,511(VA)

60HZ, SN & GND, FLUSH

4#2 & 1#8(G)

RCPTS 180VA x4EA

LIGHTS LED 50W x14EA, 22W x2EA

RCPTS 180VA x5EA

ELECTRIC WATER COOLER

LOCKING DEVICE

W/

2#12&1#12(G)

LIGHTS LED 50W x14EA

LED 45Wx2EA, 4.99Wx1EA

LIGHTS LED 50W x4EA, 22W x1EA

LED 45Wx8EA, 18Wx5EA

LIGHTS LED 50W x18EA, 22W x1EA

LED 4.99Wx1EA

RCPTS 360VA x1EA, 180VAx1EA

RCPTS 360VA x2EA

RCPTS 180VA x4EA

RCPTS 180VA x2EA

RCPTS 180VA x4EA

RCPTS 180VA x5EA

RCPTS 180VA x4EA

RCPTS 180VA x5EA

ROLLUP DOOR

& OUTDOOR UNIT-1, 2(2EA), 3(3EA)

SINGLE TYPE HEAT PUMP INDOOR

ELETRIC WALL HEATER-1

ELETRIC WALL HEATER-1

EXHAUST FAN-2

EXHAUST FAN-3

EXHAUST FAN-5

EXHAUST FAN-5

EXHAUST FAN-4

ELECTRIC UNIT HEATER-1

27 FMCP

28 SPARE

SPARE29

& OUTDOOR UNIT-3X6EA

SINGLE TYPE HEAT PUMP INDOOR

250 250

359 358

597 597

10001000

PANELBOARD "P" LOAD SCHEDULE

SPACESPACE

SPACE

SPACESPACE

SPACE

SPARE

SPARE 1000

31 SPARE 1000 -

8845 6684 9290

MAIN 3P-100AF-90AT CIRCUIT BREAKER

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

SPARE

500 500

1000 1000

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

40 2#8&1#10(G)

SPACE

SPACE

SPACE

SPACE

SPACE

TOTAL DEMAND LOAD ; 7,050(VA)

60HZ, SN & GND, FLUSH

317446

TAK, YS

CP CASEY

REPAIR BLDG S-1832

"C" LOAD SCHEDULE

NEW PANELBOARD "P", "M" &

E-8

FEC

W.TOILET

M.TOILET

STORAGE

COMM RM

ELEC RM

OFFICE

PHYSICAL TRAINING AREA RECONDITIONING AREA

OFFICE

103 102

OPEN ADMIN AREA

J/C

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

F

W P

M F

FMCPFTR

W P

F M

AMBER STROBE SHALL BE DE-RATED AS REQUIRED)

+ MNS-AMBER STROBE W/WORDS "ALERT")

WITH COMBO.(FA-CLEAR STROBE W/WORD "FIRE"

WALL MOUNTED SPEAKER (WATTAGE AS REQ'D)

"WP" TYPE, WALL MOUNTED TYPE,

MASS NOTIFICATION SPEAKER

(WATTAGE AS REQ'D)

WP

ADDRESSABLE MANUAL PULL STATIONF

M F

VISUAL SIGNAL STROBES (15 or 75 CANDELA MINIMUM, FMCP

24VDC, BUILT-IN ADDRESSABLE POINTS MODULES AS REQ'D,

(AS REQ'D) & MICROPHONE. NEMA 1 ENCL

DIGITAL VOICE PANEL W/AMPLIFIER & BACK UP AMPLIFIER

BATTERY CHAREGER, POWER MODULES PANEL (AS REQ'D) AND

SYNCHRONIZATION CONTROL MODULE, POWER SUPPLY,

PROGRAMMABLE MODULE & RELAYS, LCD ANNUNCIATOR,

FIRE ALARM/MASS NOTIFICATION CONTROL PANEL (FMCP),

COMBINED ADDRESSABLE

DIGITAL VOICE MODULE, MICROPHONE, BATTERY,

ADDRESSABLE SMOKE

DETECTOR

FTR

(PROGRAM OF D-21 MONACO

BT-XM AT LEAST 16 ZONES)

W/BATTERY & BATTERY

CHARGER, NEMA 1 ENCL

LEGEND

NEW FIRE ALARM BUILDING TRANSMITTER

DETECTOR

ADDRESSABLE HEAT

STORAGE

1/100

SCALE :

NEW FIRE ALARM AND MASS NOTIFICATION SYSTEM PLAN

317446

TAK, YS

CP CASEY

REPAIR BLDG S-1832

E-9

NOTIFICATION SYSTEM PLAN

NEW FIRE ALARM AND MASS

F

F

F

F

F

F

F

F

F

F F F F F F

F

F

F

F

F

F

F

F/M

F /M

F /M

F/MF/MF/M

F /M

F /M

F/M F/M

F/M F/M

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

NOTES:

NFPA 72, 2013 EDITION.

PRERECORDED MESSAGES ARE IN ENGLISH AND HANGUL AT

CONTRACTOR SUBMITS SHOP DRAWINGS.

THE VOLTAGE DROP AND POWER SUPPLY CALCULATION

SHALL BE PROVIDED BY THE CONTRACTOR WHEN THE

4.

(3-FEET) FROM HVAC, HOT & COLD WATER PIPING.

ALSO CONDUITS SHALL BE RUN AWAY AT LEAST 900mmTHE FIRE ALARM SYSTEM IS CONCEPTUAL. THE

MANUFACTURER'S EQUIPMENT LISTING.

SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION

MANUFACTURER'S LISTED INSTALLATION

2.

CONTRACTOR SHALL COMPLETE DESIGN AND INSTALL

13.

12.

11.

9.

SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH

AND THE MASS MESSAGE NEEDS TO HAVE PRE ALERT

PATTERN IS REQUIRED FOR FIRE ALARM EVACUATION

VOICE EVACUATION SYSTEM IN LIEU OF TEMPORAL

ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED

ELECTRICAL AND MECHANICAL SYSTEM EQUIPMENT

COORDINATE THE EXACT DEVICE LOCATIONS WITH

SWITCHES AND NON-ADDRESSABLE INITIATION

ALL TAMPER SWITCHES, FLOW SWITCHES, PRESSURE

PROHIBITED FOR ALL IDC, NAC AND SLC.

ALL CLASS "B" EXCEPTIONS IN NFPA 72, 23.4.2.2 ARE8.

7. CLASS "B" RACEWAY OF FA SYSTEM SHALL BE

SEPARATED BY A MINIMUM OF 1220mm HORIZONTAL

10. COAXIAL CABLE SHALL BE ONE PIECE BETWEEN

3.

5.

6. THE POWER CIRCUIT NUMBER DEDICATED TO FIRE

ALARM CIRCUIT AND ROOM LOCATION OF PANEL

LETTER "FIRE ALARM CIRCUIT" ON THE DEDICATED

FIRE ALARM CIRCUIT SHALL BE IDENTIFIED BY A RED

THE FIRE ALARM/MASS NOTIFICATION SYSTEM

CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING

FIRE ALARM INTELLIGIBILITY/AUDIBILITY CALCULATION,

WIRE SIZE, CONDUIT SIZE, NO. OF WIRES FOR THE FIRE

POWER CIRCUIT BREAKER AND/OR DISCONNECT SWITCH.

SHALL BE INDICATED ON THE FIRE ALARM/MASS

BUILDING TRANSMITTER AND ANTENNA.

AND 305mm VERTICALLY.

DEVICES SHALL BE PROVIDED WITH CLASS "B"

THE SYSTEM FOR READY TO USE. THE NUMBER OF

DEVICES SHOWN IS THE MINIMUM REQUIRED AND THE

FINAL QUANTITY SHALL BE IN ACCORDANCE WITH THE

DEVICE LOCATIONS IN ACCORDANCE WITH THE

AND BUILDING ARCHITECTURAL FEATURES.

OR FM APPROVED.

SPECIFICATION SECTION 28.31.76.00.31 (FA) AND

HAVE PRE ALERT TEMPORAL PATTERN MIN 2 CYCLES

PROVIDE ADDITIONAL RELAYS AS REQUIRED.14.

18.

19.

20.

PER UFC 4-021-01.

17. THE MASS NOTIFICATION SYSTEM IS CONCEPTUAL. THE

NUMBER OF DEVICES SHOWN IS THE MINIMUM REQUIRED

AND THE FINAL QUANTITY SHALL BE IN ACCORDANCE

MANUFACTURER'S EQUIPMENT LISTING.

SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION

THE MASS NOTIFICATION SYSTEM SHALL BE ENSURED THAT

LEAST FOR THE FOLLOWING ITEMS.

FOR ABBREVIATION, LEGEND, AND GENERAL NOTES

STROBES FOR MASS NOTIFICATION SHALL BE MARKED

STROBES FOR FIRE ALARM SHALL BE MARKED "FIRE"

"ALERT" IN RED LETTER AND W/AMBER LENS.

SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH

1.

AND W/CLEAR LENS.

15.

CONTINUOUS 3-10 SECOND TONE, NFPA 72, 24.4.1.2.2

& 24.4.1.8.2.

THE MASS SYSTEM ACTIVATION MUST OVERRIDE THE FIRE

ALARM NOTIFICATION APPLIANCES THE MASS SYSTEM

ON THE PANEL BY SWITCH.

THIS SEQUENCE IS REQUIRED FOR BOTH PRE-RECORDED

MASS MESSAGE IS REQUIRED TO BE ANNOUNCED

IMMEDIATELY UNTIL SHUTDOWN MANUALLY.

SPECIFICATION SECTION 28.31.76.00.31 (MNS)

THE CONTRACTOR SHALL PROVIDE THE REQUIRED

TESTING TO ACHIEVE A MINIMUM CIS SCORE 0.8 AS

16.

DEVICE LOCATIONS IN ACCORDANCE WITH THE

MANUFACTURER'S LISTED INSTALLATION

AND NFPA 72, 2013 EDITION.

APPLIANCES UNTIL MASS ALERT IS CANCELED MANUALLY

ACTIVATION MUST OVERRIDE THE FIRE ALARM NOTIFICATION

MESSAGES AND MANUAL MICROPHONE INITIATED MESSAGES.

ARE IDENTICAL TO FIRE ALARM VISUAL APPLIANCES.

23.

MASS VISUAL APPLIANCE LOCATION REQUIREMENTS

AS SHOP DRAWING SUBMITTALS.

CONTRACT DRAWINGS SHALL NOT BE SUBMITTED

ARMY AND AIR FORCE PROJECTS.

WITH ANY FIRE ALARM VISUAL APPLIANCES ON

MASS VISUAL APPLIANCES SHALL NOT BE COMBINED24.

25.

22. FIRE ALARM SYMBOLS FROM NEPA 170 SHALL BE

AND ALL VISUAL APPLIANCES WITHIN THE SAME ROOM

ALL AUDIBLE APPLIANCES WITHIN THE BUILDING21.

SHALL BE SYNCHRONIZED.

VOICE EVACUATION SPEAKERS, NEPA 72.

AUDIBLE APPLIANCES SHALL PROVIDE THE STANDARD

TEMPORAL PATTERN UNLESS NFPA 101 REQUIRES

USED.

26. SHOW WEATHERPROOF EXTERIOR SPEAKERS AT ALL

EXTERIOR DOORS OR EXTERIOR GATHERING AREAS.

SHALL BE UL LISTED OFF-THE-SHELF-EQUIPMENT AND

ALL BACK-UP AMPLIFIERS WIRING AND ARRANGEMENT27.

SHALL BE TESTED TO THE STANDARDS OF UL OR RM AS

REQUIRED BY UFC 4-21-01, PARAGRAPH 4-4.3.

BOTH KOREAN AND ENGLISH.

THE MAN SHALL HAVE PRERECORDED MASSAGES IN28.

APPLICABLE CODE, SPECIFICATIONS AND

REQUIREMENTS AND WIRE COUNT.

ALARM AND DETECTION SYSTEM.

NOTIFICATION CONTROL PANEL COVER.

MODULES.

SYSTEM. VOICE EVACUATION MESSAGE NEEDS TO

REQUIRED.

WITH THE APPLICABLE CODE, SPECIFICATIONS AND

REQUIREMENTS AND WIRE COUNT.

OF 20% SPARE ADDRESSES FOR FUTURE USE.

FIRE ALARM SYSTEM OF EACH SLC TO HAVE A MINIMUM29.

SEE SHEET NO. E-1.

2) INTRUDER/HOSTILE PERSON SIGHTED WITHIN/AROUND THE BUILDING

1) BOMB THREAT OR ACTUAL BOMB WITHIN/AROUND THE BUILDING

3) OCCUPANTS DIRECTED TO TAKE COVER WITHIN THE BUILDING

6) "ALL CLEAR" MESSAGE

TEST8)

THE BUILDING

CARBON MONOXIDE GAS DETECTION MESSAGE WITHIN/AROUND 7)

THE LOCAL AREA

5) EMERGENCY WEATHER CONDITIONS APPROPRIATE FOR

NORMAL MAIN ENTRANCE/EXIT

4) EVACUATION OF THE BUILDING USING EXITS OTHER THAN THE

FIRE ALARM/MASS NOTIFICATION

CONTROL PANEL (FMCP)

FTR

16#14 IN 21C(FOR SIGNAL)

2#12 IN 16C(FOR POWER)

#6 "BC" IN 21C

GROUND CONDUCTOR

COAXIAL CABLE

W/CONNECTORS IN 16C

OMNI-DIRECTION TYPE

FIRE ALARM ANTENNA

W/MOUNTING BRACKET

GROUND ROD, COPPER CLAD

WITH WELDING CONNECTION

STEEL, 19mmdia x 3000mmLG

SG

G ~

G

CONTROL PANEL & BOOSTER PANEL)

(INSTALLED BESIDE FIRE ALARM

(RATED AS REQ'D) (TYPICAL)

SURGE PROTECTOR

2#12 & 1#12(G) IN 16C

GROUND ROD, COPPER CLAD

GROUNDING SYSTEM #6, "BC" IN 21C

CONN TO BLDG ELECTRODE

STEEL, 19mmdiax3000mmLG

WITH WELDING CONNECTION AND

ENCLOSURE

LIGHTNING ARRESTER

W/WEATHER-PROOF

ADDRESSABLE MANUAL

PULL STATION (TYPICAL)

WALL MOUNTED "WP" TYPE,

NOTIFICATION SPEAKER

FIRE ALARM/MASS

(WATTAGE AS REQ'D) (TYPICAL)

ADDRESSABLE SMOKE

DETECTOR

NOT TO SCALE

ELECTRICAL

W/WORDS "FIRE" + MNS-AMBER STROBE

W/WORDS "ALERT") VISUAL SIGNAL STROBES

AS REQ'D)/COMBO. (FA-CLEAR STROBE

WALL MOUNTED SPEAKER (WATTAGE

SHALL BE DE-RATED AS REQUIRED) (TYPICAL)

(15 or 75 CANDELA MINIMUM, AMBER STROBE

SURFACE MOUNTED BUILDING

TRANSMITTER W/BATTERY &

BATTERY CHARGER, RELAY

FROM MNS NEMA 1 ENCL

BOARD W/CONTROLWIRING

BATTERY CHARGER, POWER MODULE PANEL(AS REQ'D)

SYNCHRONIZATION CONTROL MODULE, DIGITAL VOICE

FIRE ALARM/MASS NOTIFICATION CONTROL PANEL,

24VDC, BUILT-IN ADDRESSABLE POINTS MODULES

AS REQUIRED, PROGRAMMABLE MODULE & RELAYS,

POWER MODULE AS REQ.D LCD ANNUNCIATOR,

MODULE, POWER SUPPLY, MICROPHONE, BATTERY,

AND AMPLIFIER(AS REQ'D), NEMA 1 ENCL

SEMI FLUSH MOUNTED COMBINED ADDRESSABLE

NEW FIRE ALARM/MASS NOTIFICATION SYSTEM DIAGRAM

SYSTEM DIAGRAM

NEW FIRE ALARM/MASS NOTIFICATION

F M

WP

EXT106 103 103 111107

101 102110

111103103102107106

ADDRESSABLE HEAT

TO FIRE ALARM CIRCUITS "P-27"

106101107108

DETECTOR (TYPICAL)

103102104

F

F

103102107 103 103

103103

F M

WP

EXT111109

317446

TAK, YS

CP CASEY

E-10

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

1/100

SCALE :

LEGEND

LAN

W/ RACK MOUNTED 6-SINGLE

REAR RECEPTACLE, ON-OFF

SWITCH & CORD, 2P-3W-20A-125V

(24"(W)x78"(H)x30"(D)

POWER SURGE PROTECTION

EQUIPMENT RACK

(TYP)

DUAL MODULAR JACKS, 1-TEL/1-DATA OUTLET, CAT6

ROOM

MECH

FEC

W.TOILET

M.TOILET

STORAGE

COMM RM

ELEC RM

OFFICE

PHYSICAL TRAINING AREA

RECONDITIONING AREA

OFFICE

OPEN ADMIN AREA

J/C

T T B

LAN

T T B

W/ RACK MOUNTED 6-SINGLE

REAR RECEPTACLE, ON-OFF

SWITCH & CORD, 2P-3W-20A-125V

(24"(W)x78"(H)x30"(D)

POWER SURGE PROTECTION

EQUIPMENT RACK

(TYP)

QUAD MODULAR JACKS, 1-TEL/1-DATA OUTLET, CAT6 Q

Q Q

Q

NEW GROUND FL LAN/TEL PLAN

317446

TAK, YS

CP CASEY

REPAIR BLDG S-1832

NEW GROUND FL LAN/TEL PLAN

E-11

4-CAT6, LAN CABLE IN 27diaC

2-CAT6, LAN CABLE IN 27diaC

EQUIPMENT RACK (1-DATA & 1-TEL) (TYPICAL)

TO BE TERMINATED AT PATCH PANELS IN

6-AWG#24, CAT6, LAN CABLE IN 27mm dia C.

EQUIPMENT RACK (2-DATA & 2-TEL) (TYPICAL)

TO BE TERMINATED AT PATCH PANELS IN

4-AWG#24, CAT6, LAN CABLE IN 27mm dia C.

EQUIPMENT RACK (1-DATA & 1-TEL) (TYPICAL)

TO BE TERMINATED AT PATCH PANELS IN

2-AWG#24, CAT6, LAN CABLE IN 27mm dia C.

EXOTHERMIC WELDING, LISTED COMPRESSION TWO-

1. THE CONNECTIONS OF THE BONDING CONDUCTOR FOR

TELECOMMUNITIONS TO THE TMGB SHALL UTILIZE

HOLE LUGS, SUITABLE AND EQUIVALENT TWO-HOLE

1#6 "BC" IN 21C

CONN TO MAIN PANELBOARD

NOT TO SCALE

STAMP FACING OUT" TO ENSURE THAT THEY CAN BE

3. TEST RESULTS WILL BE PROVIDED IAW THE MOST RECENT

REVISION OF THE ANSI/TIA/EIA-568.

4. LABEL ALL DROPS IAW TIA/EIA-606-A.

5. LABEL ALL GROUNDS IAW I3A.

LUGS ARE PREFERRED.

FIELD VERIFIED.

TO TELEPHONE PATCH PANEL

TGB

CONN TO TMGB

1#6 "BC" IN 27C

(100mm x 450mmLG x 6.4mmTHK)

GROUND BUS BAR(TGB)

TMGB

G

(TYPICAL)

CABLE SUPPORT

G

110TYPE TERMINAL BLOCK

(TYPICAL)

CROSS CONNECTION CORD AS REQ'D

PLUS 25% SPARES TO BE FURNISHED BY THE

1#6 "BC" IN 16C

G

FOR TELEPHONE

1-48PORT PATCH PANEL

AS REQ'D

PROVIDE PATCH CORDS

HUB(N.I.C)

1-48PORT PATCH PANEL

W/ RACK MOUNTED 6-SINGLE

REAR RECEPTACLE, ON-OFF

SWITCH & CORD, 2P-3W-20A-125V

GROUND BUS BAR(TGB)

TELECOMMUNICATION

TELECOMMUNICATION MAIN

PTB

CONTRACTOR

RECEPTACLES

(1-25PAIR)

ENTRANCE TERMINAL BLOCK

110 TYPE PROTECTED

G

2. "PLYWOOD WILL BE INSTALLED WITH FIRE RATED

NOTE.

SHALL BE COORDINATED WITH BASE SIGNAL COMPANY.

SYSTEM AND WIRING FOR GOVERNMENT APPROVAL. TELECOMMUNCATION WORK

6. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR DETAILED TELECOMMUNICATION

PATCH PANEL W/"SC" CONNECTOR

1-12 STRAND FIBER OPTIC

QUAD-PLEX RECEPTACLE

2P-3W-125V-20A GND TYPE

WITH DEDICATED CIRCUIT

(24"(W)x78"(H)x30"(D)

POWER SURGE PROTECTION

1-25 PAIR, #24AWG TEL CABLE IN 103C.

2,800(W)x2,400(H) FIRE RATED PLTWOOD

TELEPHONE TERMINAL BOARD ("TTB"),

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-12

ELECTRICAL

(100PAIR) FOR TEL

(TYPICAL)

NEW LAN/TEL SYSTEM DIAGRAM

G

TO BE TERMINATED AT FIBER OPTIC PATCH PANEL

LENGTH AS REQUIRED

CABLE TRAY 300mm(W)x(150(H)

G

G

G

"MDP" GROUNDING BUS BAR

FOR DATA

(TYPICAL)

NEW LAN/TEL SYSTEM DIAGRAM

TO EACH DATA OUTLET AS REQ'D VIA CABLE TRAY / 103dia CONDUIT

TO EACH TEL OUTLET AS REQ'D VIA CABLE TRAY / 103dia CONDUIT

1-12 CORE, FIBER OPTIC CABLE IN 103C.

C-1

EQUIPMENT RACK FOR NIPRNET

COMM RM

C-2

317446

TAK, YS

W/ GUY WIRE (SEE CABLE RISER SET DETAIL ON E-7)

NEW HIGH VOLTAGE CABLE RISER SET (TYPE-B)

E

E

1/300

SCALE :

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

P4B-7-2

U /G

U /G

P4B-7-1

U /G

P4B-7

P4-28

S

P4B-7-3

EXIST U/G PRIMARY LINE (TYPICAL)

W/BUILT-IN PROTECTIVE DEVICES (20A FUSE)

OIL-FILLED, SELF-COOLED, LOAD BREAK SW,

TRANSFORMER, METAL ENCL, RADIAL TYPE

REPLACE WITH NEW PAD MOUNTED

3PH, 11.4KV-120/208V, 60HZ, 112.5KVA

REPLACE WITH

ARRESTERS ON EXIST PRIMARY POLE

TERMINATION KITS, FUSEMCUTOUT SWITCHES, LIGHTNING

PRIMARY LINE CABLE RISER SET INCLUDING CROSS ARM,

EXIST PRIMARY POLE/ PROVIDE NEW UNDERGROUND

EXIST PAD MOUNTED TR.

EXIST PAD MTD SWITCHGEAR

P

P

P

P

U /G

U /G

S

NEW U/G SEC LINE,

P

P

P

P

P

P

P

P

O/H

O/H

O/H

O /H

O /H

O /H

O /H

O /H

EXIST ELEC MANHOLE (TYP.)

EXIST O/H PRIMARY LINE (TYPICAL)

EXIST/NEW EXTERIOR POWER LINE DISTRIBUTION PLAN

3m0

SCALE: 1:300

6m 12m

DISTRIBUTION PLAN

EXIST/NEW EXTERIOR POWER LINE

NEW PANELBOARD "MP"

4-AWG#350kcmil & #2(G) IN 103dia C.

W H

M

NEW WATTHOUR METER W/CT"S

317446

TAK, YS

CP CASEY

REPAIR BLDG S-1832

E-13

RESTORE GROUND CONDITION AS IT IS.

1-WAY: 103dia PVC C. (EMPTY W/PULLING WIRE ) 1-WAY: 3-#2/0 (24KV) & 1-2/0(600V) IN 103dia PVC C.

NEW 2WAY UNDER GROUND DUCT CONCRETE ENCASED

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

24 1

B L E

A C

H E

R S

S O C C E R

IE

L D

B L E

A C

H E R S

5 17

B

901-1800

20,900-24

SCALE : 1/400

1:400

6 12 18 24M

1-WAY: 1-25 PAIR AWG#24 TEL CABLE W/4x3" FABRIC DUCT IN 103C.

NEW 2-WAY UNDERGROUND CONCRETE ENCASED CABLE DUCT

1-WAY: 1-12 CORE SM FIBER OPTIC CABLE 4x3" FABRIC DUCT IN 103C.

1-WAY: 1-12 CORE SM FIBER OPTIC CABLE 4x3" FABRIC DUCT IN 103C.

1-WAY: 1-25 PAIR AWG#24 TEL CABLE W/4x3" FABRIC DUCT IN 103C.

SEE NEW LAN/TEL SYSTEM DIAGRAM

P

EXIST COMMUNICATION MANHOLE/

NEW SPLICE KIT FOR 25 PAIR TELEPHONE CABLE

COMM RM

C

C

U /G

U /G

U /G

NEW 2-WAY TELECOMMUNICATION CABLE

NEW PULL BOX "WP"

MH1757

C

C

C

FROM MHA1-12 TO MH1757

NEW 1-12 CORE SM FIBER OPTIC CABLE IN EXIST U/G 103C. DUCT

EXIST/NEW EXTERIOR TELECOMMUNICATION LINE DISTRUIBUTION PLAN-1

LINE DISTRUIBUTION PLAN-1

EXIST/NEW EXTERIOR TELECOMMUNICATION

317446

TAK, YS

CP CASEY

REPAIR BLDG S-1832

E-14

MATCH LINE,SEE DWG SHT NO E-15

FOR ABBREVIATION, LEGEND, AND GENERAL NOTES

NOTES

CONTRACTOR SHALL PROVIDE ADEQUATE SUPPORTS

SEE SHEET NO. E-1.

1.

2.

3.

THE CONTRACTOR SHALL VERIFY EXISTING4.

UNDERGROUND TELECOMM LINE'S ACTUAL

CONDITION PRIOR TO WORK.

NEW SINGLE MODE FIBER OPTIC CABLE

AND TELEPHONE CABLE SHALL BE INSTALLED

TO FIX NEW TELECOM CABLES.

COORDINATED WITH BASE SIGNAL COMPANY.

AND TYPE OF SPLICE KITS SHALL BE

ON THE EXISTING MANHOLES,

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

MH20

MHA1-9

B

1:400

6 12 18 24M

EXIST COMMUNICATION MANHOLE

(TYPICAL)

C

C

U/G

U/G

U/G

U /G

U /G

U /G

U /G

FROM MHA1-12 TO MH1757

NEW 1-12 CORE SM FIBER OPTIC CABLE IN EXIST U/G 103C. DUCT

C

C

C

C

C

C

C

C

SCALE : 1/400

EXIST/NEW EXTERIOR TELECOMMUNICATION LINE DISTRUIBUTION PLAN-2

LINE DISTRUIBUTION PLAN-2

EXIST/NEW EXTERIOR TELECOMMUNICATION

317446

TAK, YS

CP CASEY

REPAIR BLDG S-1832

E-15

MATCH LINE,SEE DWG SHT NO E-14

M A

T C

H L

IN

E ,S

E E D

W G S

H T N

O E -1

FOR ABBREVIATION, LEGEND, AND GENERAL NOTES

NOTES

CONTRACTOR SHALL PROVIDE ADEQUATE SUPPORTS

SEE SHEET NO. E-1.

1.

2.

3.

THE CONTRACTOR SHALL VERIFY EXISTING4.

UNDERGROUND TELECOMM LINE'S ACTUAL

CONDITION PRIOR TO WORK.

NEW SINGLE MODE FIBER OPTIC CABLE

AND TELEPHONE CABLE SHALL BE INSTALLED

TO FIX NEW TELECOM CABLES.

COORDINATED WITH BASE SIGNAL COMPANY.

MH22

A1-10

MH

MHA1-11

MHA1-12

503'

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

1:400

6 12 18 24M

C

EXIST COMMUNICATION MANHOLE

C

C

(TYPICAL)

EXIST COMMUNICATION MANHOLE/

NEW SPLICE KIT FOR 1-12 CORE SM FIBER OPTIC CABLE

C

U /G

U /G

U /G

U/G

U/G

U/G

FROM MHA1-12 TO MH1757

NEW 1-12 CORE SM FIBER OPTIC CABLE IN EXIST U/G 103C. DUCT

C

C

C

C

C

C

SCALE : 1/400

EXIST/NEW EXTERIOR TELECOMMUNICATION LINE DISTRUIBUTION PLAN-3

LINE DISTRUIBUTION PLAN-3

EXIST/NEW EXTERIOR TELECOMMUNICATION

317446

TAK, YS

CP CASEY

REPAIR BLDG S-1832

E-16

M A

T C

H L

IN

E ,S

E E D

W G S

H T N

O E -1

FOR ABBREVIATION, LEGEND, AND GENERAL NOTES

NOTES

CONTRACTOR SHALL PROVIDE ADEQUATE SUPPORTS

SEE SHEET NO. E-1.

1.

2.

3.

THE CONTRACTOR SHALL VERIFY EXISTING4.

UNDERGROUND TELECOMM LINE'S ACTUAL

CONDITION PRIOR TO WORK.

NEW SINGLE MODE FIBER OPTIC CABLE

AND TELEPHONE CABLE SHALL BE INSTALLED

TO FIX NEW TELECOM CABLES.

COORDINATED WITH BASE SIGNAL COMPANY.