DWG_(SMYU_19-1049).pdf
PDF 1 MB Posted
- Attached to
- SMYU 19-1049 Reapir AF Tech B320
- Solicitation number
- W90VN619R0023
View the file
Other files
| File | Type | Posted |
|---|---|---|
| W90VN619R0023_repair_AF_tech_B320.pdf | ||
| Bidding_Schedule__(SMYU_19-1049).xls | XLS spreadsheet | |
| W90VN619R0023_repair_AF_tech_B320.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D1
D2
D3
D5
D6D4
D8
D7D9
16 17 18
19 19
19 19
21DOOR NO.
SOW NO.
23’
23’
20’20’
9’
SMYU 19-1049
REPAIR AF TECH APPLICATONS CENTER, B320
DWG NO. A-01
REMOVE AC IN/OUTDOOR
UNIT W/
REMOVE HOT AIR BLOWER
REMOVE THROUGH THE WALL AC
REPLACE WALL EXHAUST FAN
W/ NEW
REPLACE PIPE INSULATION OF
WATER HEATER W/ NEW
REPLACE WATER CLOSET W/ NEW
REPLACE LAVATORY W/ NEW
DRAWING NO.
M‐01
NEW FLOOR STANDING HEAT
PUMP
NEW EXTERIOR WALL MTD
HEAT PUMP ‐1
T8‐1 T8‐2
T6
WALL MOUNTED WIRED TEMP CONTROLLER
AND ON/OFF SWITCHES
NEW EXTERIOR WALL MTD
HEAT PUMP ‐2
WALL MOUNTED WIRED ERV CONTROLLER
AND ON/OFF SWITCH
NOTE
*THE LOCATION FOR TEMP CONTROLLERS SHALL BE
COORDINATED WITH THE USER.
NEW ENERGY RECOVERY
VENTILATOR7
LEGEND
T
VC
VC
ES
ES EMERGENCY HVAC SHUT OFF SWITCH FOR
ERV AND EXTERIOR WALL MTD HEAT PUMP
DRAWING NO.
M‐02
4‐NEW PENDANT SPRINKER HEAD
(SAME TYPE AS EXISTING), ESCUTCHEON
AND BRANCH PIPING
DRAWING NO.
M‐03
B320 LIGHT PLAN
LED LIGHTING
TYPE RF-8 DIMMABLE
RF8 W/EM
LED LIGHTING
1'X4' SUR. MTD
DIMMABLE
SAME AS ABOVE
BUT WITH EM
MIRROR LIGHT
(LED)
LED RECESSED
MTD 6", 15W
S
TOGGLE S/W
DIMMER S/W
S
S
S
SDM
S D
M
S
SDM
S D
M
S D
M
S
LED WALL PACK
20W
B320 POWER PLAN
S
EF
DUPLEX RECEPTACLE
2P-3W-20A-125VAC
GROUND TYPE
SINGLE RECEPTACLE
2P-3W-20A-250VAC
GROUND TYPE
MANUAL MOTOR STARTER
(UNDER ARCH ITEM)
SAFETY SWITCH
PANELBOARD
EXH FAN (UNDER MECH)
EXISTING
EXISTING
SAFETY SWITCH
JUNCTION BOX
FOR POWER SOURCE
OF VENTILATOR
NEW PANELBOARD
SAFETY SWITCH
JUNCTION BOX
FOR ROLL-UP DOOR
B320 COMM PLAN
RAC
DUAL CAT.6 MODULAR
JACK 8-PIN(RJ45)
W/DOUBLE GANG BOX
AND PLATE
LUG FOR "TEL/DATA"
COMM RACK
WALL MTD
RAC
TO COMM MH
PANELBOARD SCHEDULE
HOT WATER HEATER
NEW PANELBOARD "P" LOAD SCHEDULE
TOTAL DEMAND LOAD ; 14,111 (VA)
FIRE ALARM PNL14
COMM S/W
SPARE16
HEAT PUMP-19
VENTILATOR
FDB PANEL (OUTSIDE)
LOAD DESCRIPTION
LIGHTS
RECEPTACLE
NO.
CKT
4#2 & 1#6(G)
DEMAND FACTOR ; 85 (%)
MTD TYPE, NEMA 1 ENCL.
3PHASE ,4WIRE, 120/208V,
60HZ, SN & GND, FLUSH
WIRE SIZE
#12
10801080
6451289
360 30
PHASE LOAD
TOTAL
LOAD
A
B C
SIZE
10K100
AFP
AT
AIC
CIRCUIT BREAKER
CONNECTION
CA B
DIAGRAM
GN
SPARE17
SPARE18
(RM101) 49W x 9 17w x 2
(EXT 103) 17W x 4
LIGHTS
(RM104) 49W x 11
(RM 105)
(RM101) 5 x 180
RECEPTACLE
(RM103) 6 x 180
RECEPTACLE
(RM104) 5 x 180
RECEPTACLE
2 x 360
720 360360RECEPTACLE
2 x 360
HEAT PUMP-2 1289 645 645
HEAT PUMP-3 1289 645 645
335 335
2000 1000 1000
TOTAL
17,639 5,591 5,679 6,368
MAIN 3P-100AF-50AT MAIN CIRCUIT BREAKER
2 #10
#121 20
17 18
AutoCAD SHX Text
GND
AutoCAD SHX Text S/N
1395512486U Typewritten Text B320
1395512486U Line
1395512486U Callout New duct/innerduct need to be installed between B320 and MH 318; 50 feet
1395512486U Callout 12 Strands FO cable from ITN B355
| DWG (elec) Comm OSP plan for B320.pdf |
| Slide Number 1 |
| Slide Number 2 |
| DWG (SMYU 19-1049) Elec Sketch (updated).pdf |
| Elec E1 Lighting |
| Sheets and Views |
| Model |
| Elec E2 Power |
| Sheets and Views |
| Model |
| Elec E3 Comm |
| Sheets and Views |
| Model |
| Elec E4 Panelboard Schedule |
| Sheets and Views |
| Model |
File details come from the government source that posted it.