W5J9JE-16-R-00069_-_Police_Town_Amendment_-_0003_20APR17_PLANS.pdf
PDF 44 MB Posted
- Attached to
- FEMALE POLICE TOWN PHASE I
- Solicitation number
- W5J9JE-16-R-0069
About this file
W5J9JE-16-R-00069 - Police Town Amendment 0003 - 20APR2017 PLANS
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DULANEY.HENRY.A.
1230764693
Digitally signed by
DULANEY.HENRY.A.1230764693
DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USA, cn=DULANEY.HENRY.A.1230764693 Date: 2017.03.13 16:21:14 -05'00'
JOHNSON.BRIAN.RI
CHARD.1256508644
Digitally signed by
JOHNSON.BRIAN.RICHARD.1256508644
DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USA, cn=JOHNSON.BRIAN.RICHARD.1256508644 Date: 2017.03.13 16:23:36 -05'00'
A
M
EN
D M
EN
T
A
PR
BR
J
A
M
EN
D M
EN
T
A
PR
A
M
EN
D M
EN
T
A
PR
B2EDLBRJ
Polygon
B2EDLBRJ
Polygon
3 3
TYPE
LAMP
WATTS
IES
DISTRIBUTION
TYPE
POLE
HEIGHT
(FEET) FIXTURE DESIGN BASIS QTY
F121 150 II 4572mm LithoniaMR1 150MHC SR2 4 F131 150 III 4572mm LithoniaMR1 150MHC SR3 8 F132 150 III 6096mm LithoniaMR1 150MHC SR3 6 F232 250 III 6096mm LithoniaMR2 250MSR3 12 F422 400 II 6096mm LithoniaMR2 400MSR2 9 F432 400 III 6096mm LithoniaMR2 400MSR3 3
1. FEMALE POLICE TOWN EXTERIOR LIGHTING (ROADWAYS, PARKING LOTS, SIDEWALKS).
2. LIGHT FIXTURE SCHEDULE: (ALL LAMPSMETAL HALIDE, PULSE START)
3. POLEMATERIAL: HOT DIPPED GALVANIZED STEEL (SEE DETAILS THIS SHEET)
LIGHTING FIXTURE SCHEDULE
REF.
NO.
BUILDING
NUMBER
SERVICE
PHASE/WIRES
VOLTS
(PEAK TO PEAK)
BUILDING SERVICE
ENTRANCE FULL LOAD
AMPERE RATING TO RECORD
DEMAND
TIME/TYPE METER LOCATION REMARKS
1 100A 3 PHASE / 4WIRE 400VOLTS, 50Hz 1500AMPERES KWH NONE
BUILDING
EXTERIOR 100A
SEE GENERAL SHEET NOTE 1
2 100B 3 PHASE / 4WIRE 400VOLTS, 50Hz 1500AMPERES KWH NONE
BUILDING
EXTERIOR 100B
SEE GENERAL SHEET NOTE 1
3 100C 3 PHASE / 4WIRE 400VOLTS, 50Hz 1500AMPERES KWH NONE
BUILDING
EXTERIOR 100C
SEE GENERAL SHEET NOTE 1
6 102D 3 PHASE / 4WIRE 400VOLTS, 50Hz 60 AMPERES KWH NONE
BUILDING
EXTERIOR 102D
SEE GENERAL SHEET NOTE 2
7 102E 3 PHASE / 4WIRE 400VOLTS, 50Hz 60 AMPERES KWH NONE
BUILDING
EXTERIOR 102E
SEE GENERAL SHEET NOTE 2
8 102F 3 PHASE / 4WIRE 400VOLTS, 50Hz 60 AMPERES KWH NONE
BUILDING
EXTERIOR 102F
SEE GENERAL SHEET NOTE 2
9 102G 3PHASE / 4WIRE 400VOLTS, 50Hz 60 AMPERES KWH NONE
BUILDING
EXTERIOR 102G
SEE GENERAL SHEET NOTE 2
10 102H 3PHASE / 4WIRE 400VOLTS, 50Hz 60 AMPERES KWH NONE
BUILDING
EXTERIOR 102H
SEE GENERAL SHEET NOTE 2
11 102I 3 PHASE / 4WIRE 400VOLTS, 50Hz 60 AMPERES KWH NONE
BUILDING
EXTERIOR 102I
SEE GENERAL SHEET NOTE 2
UTILITY SERVICEMETERS SCHEDULE
REFERENCE
NO.
TRANSFORMER
NUMBER
POWER POLE
NUMBER TRANSFORMER TYPE
BUILDING SERVICE
ENTRANCE RATING (KVA
PHASE WIRES)
TRANSFORMER
SIZE (KVA) SECONDARY SERVICE ENTRANCE SIZE
1 T 100A PP30 2
CONCRETE PAD
MOUNTED
1000 KVA,3 PHASE, 5
WIRE, GROUNDED
1000 KVA, 3
PHASE, (1 EACH)
4 PARALLEL SETS OF 4 X 240MM2 IN 4 PARALLEL
103MMEXPOSEDWEATHER HEAD, RISER, AND
UNDERGROUND RGS CONDUIT
2 T 100B PP30 7
CONCRETE PAD
MOUNTED
1000 KVA,3 PHASE, 5
WIRE, GROUNDED
1000 KVA, 3
PHASE, (1 EACH)
4 PARALLEL SETS OF 4 X 240MM2 IN 4 PARALLEL
103MMEXPOSEDWEATHER HEAD, RISER, AND
UNDERGROUND RGS CONDUIT
3 T 100C PP29
CONCRETE PAD
MOUNTED
1000 KVA,3 PHASE, 5
WIRE, GROUNDED
1000 KVA, 3
PHASE, (1 EACH)
4 PARALLEL SETS OF 4 X 240MM2 IN 4 PARALLEL
103MMEXPOSEDWEATHER HEAD, RISER, AND
UNDERGROUND RGS CONDUIT
6 T 102D PP31 POLE MOUNTED
30 KVA, 3 PHASE, 5WIRE,
GROUNDED
10 KVA, 1 PHASE,
(3 EACH)
4 X 16MM2 IN ONE 103MMRGS EXPOSED RISER
ANDUNDERGROUND CONDUIT
7 T 102E PP30 1 4 POLE MOUNTED
30 KVA, 3 PHASE, 5WIRE,
GROUNDED
10 KVA, 1 PHASE,
(3 EACH)
4 X 16MM2 IN ONE 103MMRGS EXPOSED RISER
ANDUNDERGROUND CONDUIT
8 T 102F PP30 8 3 POLE MOUNTED
30 KVA, 3 PHASE, 5WIRE,
GROUNDED
10 KVA, 1 PHASE,
(3 EACH)
4 X 16MM2 IN ONE 103MMRGS EXPOSED RISER
ANDUNDERGROUND CONDUIT
9 T 102G PP30 11 POLE MOUNTED
30 KVA, 3 PHASE, 5WIRE,
GROUNDED
10 KVA, 1 PHASE,
(3 EACH)
4 X 16MM2 IN ONE 103MMRGS EXPOSED RISER
ANDUNDERGROUND CONDUIT
10 T 102H PP20 4 1 POLE MOUNTED
30 KVA, 3 PHASE, 5WIRE,
GROUNDED
10 KVA, 1 PHASE,
(3 EACH)
4 X 16MM2 IN ONE 103MMRGS EXPOSED RISER
ANDUNDERGROUND CONDUIT
11 T 102I PP20 0 POLE MOUNTED
30 KVA, 3 PHASE, 5WIRE,
GROUNDED
10 KVA, 1 PHASE,
(3 EACH)
4 X 16MM2 IN ONE 103MMRGS EXPOSED RISER
ANDUNDERGROUND CONDUIT
SERVICE TRANSFORMERS SCHEDULE (SEE SHEET GENERAL NOTE 4)
MEDIUM
VOLTAGE
SWITCH
NUMBER
POWER POLE
NUMBER CUTOUT SWITCH TYPE
CUTOUT SWITCH
(AMPERES) FUSE SIZE (AMPERES)
FEEDER SWITCH
LOCATION
S 1
PP1
UTILITY TIE IN IN LINE
S 2 PP24 SOLID CUTOUT (SCOS) 300 NO FUSE IN LINE
S 3 PP23 SOLID CUTOUT (SCOS) 300 NO FUSE IN LINE
S 4 PP20 0 FUSED CUTOUT (FCOS) 100 SIZED BY CONTRACTOR BUILDING 102I
S 5 PP20 4 1 FUSED CUTOUT (FCOS) 100 SIZED BY CONTRACTOR BUILDING 102H
S 6 PP30 11 SOLID CUTOUT (SCOS) 300 NO FUSE IN LINE
S 7 PP25 SOLID CUTOUT (SCOS) 300 NO FUSE IN LINE
S 8 PP29 FUSED CUTOUT (FCOS) 100 SIZED BY CONTRACTOR BUILDING 100C
S 9 PP30 SOLID CUTOUT (SCOS) 300 NO FUSE IN LINE
S 10 PP30 SOLID CUTOUT (SCOS) 300 NO FUSE IN LINE
S 11 PP30 1 SOLID CUTOUT (SCOS) 300 NO FUSE IN LINE
S 12 PP30 1 4 FUSED CUTOUT (FCOS) 100 SIZED BY CONTRACTOR BUILDING 102E
S 13 PP30 2 FUSED CUTOUT (FCOS) 100 SIZED BY CONTRACTOR BUILDING 100A
S 14 PP30 7 FUSED CUTOUT (FCOS) 100 SIZED BY CONTRACTOR BUILDING 100B
S 15 PP30 8 3 FUSED CUTOUT (FCOS) 100 SIZED BY CONTRACTOR BUILDING 102F
S 16 PP30 11 FUSED CUTOUT (FCOS) 100 SIZED BY CONTRACTOR BUILDING 102G
S 17 PP31 FUSED CUTOUT (FCOS) 100 SIZED BY CONTRACTOR BUILDING 102D
COORDINATEDWITH CITY ELECTRIC POWER UTILITY AND PROVIDED BY
CONTRACTOR AND CITY UTILITY AS COORDINATED
20KV, 3 PHASE, POLE MOUNTED CUTOUT SWITCH SCHEDULE
A
M
EN
D M
EN
T
A
PR
A
M
EN
D
PR
3 3 3
M
EN
D
PR
A
M
EN
D M
EN
T
A