About this file
This document is a Description of Supplies for two Uninterrupted Power System (UPS) units. The required UPS units must meet specific technical specifications, including a runtime greater than 2 minutes, transformer-less design with internal battery, and precise input/output electrical characteristics. Key input specifications include 3-phase wiring, 208/120 VAC, 83 AMPS, 60 HZ, and 30 kVA, while output specifications are similar with 24 KW. Physical requirements mandate the units weigh under 1200 lbs.
The procurement involves purchasing two UPS units to provide immediate backup power for multiple machines, ensuring no data loss during power interruptions. The delivery schedule is 6-8 weeks after order, with shipping to 11 Hap Arnold Blvd, Coolbaugh Township, PA 18466, specifically to the loading bay at building 1E. The units will be issued as one piece of equipment per unit, and will come with the manufacturer's standard warranty. The intended use is to trigger instantly during power loss, protecting connected equipment from abrupt shutdowns.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Draft Statement of Work UPS.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Description of Supplies: Uninterrupted Power System
Functions to be performed:
Purchase two Uninterrupted Power Units (UPS)
The UPS units must meet the following specifications:
Minimum Requirements
• Runtime greater than 2 minutes
Exact Requirements
• Transformer less with Internal MBS With Internal Battery
• Input:
o Wire: 3Ø 3+N+G o VAC: 208/120 o AMPS: 83 o HZ:60 o kVA: 30 o KW: 26.7 o Neutral sized for 200% Current o Short Circuit Current Rating: 35KA minimum 4% Impedance from a 65KVA Source
• DE input:
o Volts: 331-240 o AMPS: 110 o MAX @240 VDC
• Output:
o Wire: 3Ø 3+N+G o VAC: 208/120 o AMPS: 83 o HZ: 60 o kVA: 30 o KW: 24
Essential Physical Characteristics:
Under 1200 lbs.
Principles of Operation:
Intended Use, including equipment with which the item is to be used:
The UPS (uninterrupted power systems) provides backup power to multiple machines; the UPS units trigger immediately when power is lost. This ensures that the machines attached to it will lose no data due to being abruptly shut down.
Unit of Issue (e.g., each, roll, can, or lot):
One piece of equipment
Quantity Requested:
2 Units
Delivery Schedule (e.g. Number of Days After Receipt of Order):
Once the part is ordered the manufacturer will have the delivery completed within 6-8 weeks.
Ship to Address:
11 Hap Arnold Blvd, Coolbaugh Township, PA 18466
Special packing or marking information:
Ship to loading bay at building 1E
Warranty requirement:
Per manufacturers’ typical warranty
Description of Supplies: Uninterrupted Power System
File details come from the government source that posted it. Updated .