RFIs - Fiber Installation.pdf
PDF 1 MB Posted
- Attached to
- Fiber Installation
- Solicitation number
- W50S8Z26QA032
About this file
The provided PDF file is not a federal contract opportunity document. The file contains only a generic Adobe Reader error message indicating that the PDF viewer cannot properly display the document contents. No contract-related information, solicitation details, requirements, timelines, pricing terms, agency information, or other substantive procurement data is present in this file. The document appears to be corrupted or improperly formatted and requires a PDF viewer upgrade or file reconstruction to access the actual contents.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 219 Bay Dims.pdf | ||
| I.A.02 PWS and PRS CS Fiber Installation.pdf | ||
| SCA Wage Determination Klamath Falls Oregon.pdf | ||
| Solicitation - W50S8Z26QA032.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Please wait...
If this message is not eventually replaced by the proper contents of the document, your PDF viewer may not be able to display this type of document.
You can upgrade to the latest version of Adobe Reader for Windows®, Mac, or Linux® by visiting http://www.adobe.com/go/reader_download.
For more assistance with Adobe Reader visit http://www.adobe.com/go/acrreader.
Windows is either a registered trademark or a trademark of Microsoft Corporation in the United States and/or other countries. Mac is a trademark of Apple Inc., registered in the United States and other countries. Linux is the registered trademark of Linus Torvalds in the U.S. and other countries.
Request for Information Worksheet Page of RFIW, v1.0 Requirement Information Requirement Description Solicitation Number Contracting Officer Questions and Answers Number Question Answer Increase Rows Decrease Rows
Notes General Notes and Information 2.1 817-852-3254 02 June 2015
136 MSG/MSC
Micah Kruse Contract Execution Checklist 03 June 2015 Yes.
Contractor shall test the fiber after the install using LSPM testing. Contractor shall establish the acceptable power loss requirements in accordance with TIA-568.3. Test results shall be submitted electronically to the COR identifying the strand origin/destination, wavelength, direction, measured loss, allowable loss and pass/fail.
Conduit does not need to be painted to match the wall color.
If additional escorts are required, the government will provide them.
No.
No. It must be posted to SPRS prior to the Contracting Officer awarding the contract.
No. However, payment for the project cannot be accomplished until the contractor submits their invoice in WAWF.
No, but the paperwork should be submitted before work begins.
The Government has determined this to be a service contract applicable to SCA determination and not a construction project that would fall under Davis-Bacon. The SCA codes that could apply to this contract include: 23931, 23932, and 23125.
A completed and signed SF 1449 is required.
OS1. No area should require plenum-rated cable.
TIA 568, TIA-569, TIA-455, UFC 3-580-01.
No Oregon business license requirement. Yes Oregon electrical license is required.
No.
Standard warranty is expected. This would cover workmanship warranty (minimum of 1 year) and component/harware warranty (minimum of 1 year).
No.
No.
Yes
| CurrentPage: |
| PageCount: |
| PRNumber: Fiber Installation |
| PRNumber: W50S8Z26QA032 |
| PRNumber: SMSgt Jason Rice |
| Cell1: 1 |
| Cell1: |
Can floor plans or bldg specs be provided?
| Cell1: 2 |
| Cell1: PWS Section 5.3 requires testing of the installed fiber and connectors in accordance with applicable TIA standards and submission of results to the COR prior to acceptance. Cable Dogs LLC may utilize factory-terminated LC-LC 9/125 single-mode fiber assemblies where practical. |
• Will manufacturer factory performance/test documentation, supplemented by connector end-face inspection, continuity/polarity verification, and operational verification of the installed links, satisfy the field acceptance requirement?
• If additional field testing is required, please clarify the light-loss and performance testing expected for acceptance. Specifically, will light-source/power-meter loss testing be sufficient, or are OTDR traces also required? Please also identify any required pass/fail loss criteria and the preferred format for submitted results.
| Cell1: 3 |
| Cell1: During the site visit, Government representatives advised that surface-mounted conduit/raceway installed for this requirement would not need to be painted to match the existing concrete walls. |
• Please confirm that new conduit and/or surface raceway installed under PWS Sections 5.1 and 5.2 is not required to be painted or otherwise field-finished to match adjacent wall surfaces.
| Cell1: 4 |
| Cell1: PWS Section 1.4.5.2 requires contractor personnel to remain with their designated Government escort while performing services. Certain installation and testing activities may require technicians to work simultaneously at opposite ends of a fiber run. |
• Please confirm whether sufficient escort coverage will be available when contractor personnel must work simultaneously at opposite ends of a fiber run for pulling, termination, testing, or troubleshooting.
| Cell1: 5 |
| Cell1: Does the contractor have to qualify for NAICS 238210? |
| Cell1: 6 |
| Cell1: Does the contractor have to have their NIST SP 800-171 self-assessment score uploaded to SPRS via the Procurement Integrated Enterprise Environment (PIEE) before the bid submission? |
| Cell1: 7 |
| Cell1: Does the contractor need to be registered with Wide Area WorkFlow (WAWF) before the bid submission? |
| Cell1: 8 |
| Cell1: Does the contractor have to complete NCIC-III/TSDB, Antiterrorism AT Level I, and OPSEC 1301 training prior to beginning work at the base? |
| Cell1: 9 |
| Cell1: The wage determination (2015-5581, Rev. 32) is a Service Contract Act determination rather than a Davis-Bacon (construction) wage schedule. Please confirm SCA applies to this effort rather than DBA and identify which SCA occupational classification(s) the government expects fiber/cable installers to be conformed under (e.g., Telecommunications Mechanic I/II, Cable Splicer, or a new conformed classification), since no classification is explicitly designated in the PWS for certified payroll reports. |
| Cell1: 10 |
| Cell1: Please verify the solicitation response needs to be on SF 1449. |
| Cell1: 11 |
| Cell1: What is the exact fiber cable specification required (OS1 vs. OS2, jacket rating (armored?) is any portion of the run through a plenum air-handling space requiring plenum-rated cable)? |
| Cell1: 12 |
| Cell1: What TIA standard(s) specifically govern the fiber testing in paragraph 5.3 (e.g., TIA-568, TIA-455-series for optical loss testing), and what test result format/documentation does the COR require for acceptance? |
| Cell1: 13 |
| Cell1: Is an Oregon business license or Oregon electrical license required for this project? |
| Cell1: 14 |
| Cell1: Is a project performance or payment bond required? |
| Cell1: 15 |
| Cell1: What is the warranty period for the project? |
| Cell1: 16 |
| Cell1: Are there any project plans available showing the fiber routing, room layout, or floor plans for scaling? |
| Cell1: 17 |
| Cell1: Will the pre-bid sign in be posted to Sam.Gov? |
| Cell1: 18 |
| Cell1: Will all questions and answers be posted to Sam.Gov in an addendum? |
| : |