Date: RFI No. RFI QUESTION GOVERNMENT RESPONSE

3/16/2023 1 Does section 1.3.1.1 (unescorted access) apply to all subcontract employees for the project?

Yes

3/16/2023 2 Will a site superintendent with a DBIDS badge (1.3.2) be able to escort all subcontract employees in lieu of all subs receiving a Triple I?

One person with a DBIDS badge is allowed to escort 5 people and up to 2 vehicles.

3/16/2023 3 If awarded contract, how will our subs and us receive the AT Level 1 training? Will it be an online course, or will the base provide a day of training for us?

They can go to the following website:

https://jko.jten.mil/courses/AT-level1/launch.html

3/21/2023 4 What is the footage for the conduit and cable run to the transformer that is not placed yet?

Use 30ft for bidding purposes

3/21/2023 5 Are we to reuse the existing exhaust fan after removal? Yes

3/21/2023 6 What is the desired location for the new Unit(s) The east side of the building is where we would like them placed.

3/21/2023 7 will sheetrock stop at flange of structural steel or continue to the outside skin of the building sheetrock will continue to the insulation/outside skin. Metal studs must be anchored to the steel to support the sheetrock.

3/21/2023 8 Are we to tie into the existing sidewalk? Yes, use doweling instructions similar to tying into the building.

3/21/2023 9 How are we to terminate the downspouts on the south side of the building?

install Flumes with grates in the sidewalk. See Sidewalk Flume details.

3/21/2023 10 Will there need to be duct detectors on the HVAC unit(s)? Yes, the unit(s) shall have duct detectors on them.

3/21/2023 11 Do you want a parts and labor warranty for the package unit(s).

Yes, provide a 5 year parts and labor warranty from the date of shipment.

3/21/2023 12 Do you want to unsulate the underside of the new ridge cap?

Yes

Pre-Quote RFI Log for B408 Conditioned Space