B6 Pre-Award RFI (cao20250903).pdf

PDF 60 KB Posted

Attached to
LTUY242043 Repair Building 28 Sprinkler Pipes
Solicitation number
W50S8K25RA004
Issued by

About this file

This document is a Request for Information (RFI) for a fire sprinkler pipe repair project at Building 28, with the specific RFI number W50S8K25RA004, LTUY242043. The RFI addresses two key technical questions about pipe specifications: first, confirming the pipe schedule type, and second, determining pipe material for repairs. The government response clarifies that the Statement of Work (SOW) has been updated to specify black steel Schedule 40 pipe, and explicitly states that galvanized pipe will not be considered for this project. The RFI suggests ongoing technical clarification and specification refinement for the sprinkler pipe repair work prior to the formal solicitation.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RFI # RFI Government Response

Scope of Work item #4 identifies the pipe as being black steel schedule 20. Common schedules for fire sprinkler pipes are schedules 10, 40, and 80. Please confirm type of pipe required. The SOW has been updated to Schedule 40.

Repairs to the fire sprinkler have been previously made on the lower level. Pipe used for this repair was Schule 10 or 40 galvanized. Is galvanized pipe a consideration for this repair? Galvanized pipe will not be considered for this project.

Pre-Award RFI - W50S8K25RA004, LTUY242043 Repair Building 28 Sprinkler Pipes

File details come from the government source that posted it. Updated .