This notice is a solicitation for roof repair and replacement services on Building 254 at Pease Air National Guard Base in New Hampshire. The government seeks a contractor to remove and replace three flat roofs totaling 33,250 square feet with an adhered PVC system. Additional work includes demolition, hazardous material abatement, and a 270-day period of performance. The solicitation is set aside entirely for small businesses with average annual receipts less than $45 million. Interested parties should submit bids by February 29, 2024 for public opening on that date at the Portsmouth Armory. A pre-bid conference and site visit will be held on February 8, 2024 at the building. The National Guard provided information on definitizing equitable adjustments but had no agency-specific policies or three-year data available.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Copyright© 2021 GZA GeoEnvironmental, Inc.
An Equal Opportunity Employer M/F/V/H
Via Email
November 17, 2021 File No. 04.0191339.00
Ms. Kerry Peiser, PLA Landscape Architect/Project Manager Oak Point Associates 85 Middle Street Portsmouth, New Hampshire 03801
Re: Limited Asbestos and Lead Sampling Report Building 254 New Hampshire Air National Guard Portsmouth, New Hampshire
Dear Ms. Peiser:
GZA GeoEnvironmental, Inc. (GZA) conducted limited asbestos and lead sampling at Building 254 located at the New Hampshire Air National Guard facility in Portsmouth, New Hampshire. As outlined in our proposal dated September 28, 2021, our scope of services was limited to the collection of bulk samples of suspect asbestos-containing materials (ACM) associated with the building roof systems, submission of the samples to an accredited laboratory, and reporting of the analytical results. As requested, GZA also collected and submitted samples of suspect flashing material for the presence of lead content. Our work is subject to the Limitations contained herein.
The limited suspect asbestos and lead sampling was conducted at the site on October 21 and October 22, 2021 by Mr. Andrew Pomeroy, a United States Environmental Protection Agency (USEPA)-accredited Asbestos Inspector (Certificate Number 21-3541- 106-262357). A copy of Mr. Pomeroy’s asbestos inspector certificate is attached as Appendix A.
The limited asbestos sampling was performed in general accordance with the sample collection protocols established in USEPA regulation 40 CFR 763, the Asbestos Hazard Emergency Response Act. A total of 80 bulk samples were collected from 29 homogeneous areas of suspect ACM. Bulk samples were submitted under chain of custody to Aerobiology Laboratory Associates, Inc. (formally ProScience Analytical Services, Inc.) of Woburn, Massachusetts for analysis by polarized light microscopy with dispersion staining techniques per EPA methodology (40 CFR 763, Subpart E).
The percentage of asbestos, where applicable, was determined by microscopical visual estimation. The laboratory was instructed to analyze samples from each homogeneous area until the first sample containing asbestos was identified. Analytical laboratory certification is provided in Appendix B.
November 17, 2021 Oak Point Associates
04.0191339.00 Page | 2
Based on the results of laboratory analysis, asbestos was not detected in any of the samples submitted for analysis. A summary of suspect ACM samples collected during the limited sampling is included in Table 1. The laboratory analytical reports are attached in Appendix B. We recommend you maintain a copy of this report for your records and provide a copy to the contractor that is performing the roof renovation work.
During the limited lead sampling GZA collected five (5) bulk samples of suspect flashing material and submitted them to Aerobiology for lead content analysis per USEPA method SW846-7000B/3051. Based on the laboratory analysis, lead was detected in one sample above the reporting limit. Sample Pb-02 containing perimeter flashing collected from Roof #2 was analyzed to contain a lead concentration of 18% by weight. A summary of the flashing samples collected during the limited sampling event is included in Table 2, and the laboratory analytical report is attached in Appendix B.
1.0 LIMITATIONS
Limited asbestos and lead sampling was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, and findings expressed in this report are based on conditions observed during the limited sampling event. This letter report has been prepared on behalf of and exclusively for use and reliance by the Client. This report is not a bidding document. Contractors or consultants reviewing this limited sampling report must draw their own conclusions regarding further investigation or remediation deemed necessary. Suspect materials made accessible during demolition/renovation activities must be assumed to be asbestos-containing and handled as such, until testing proves otherwise. Specifically, GZA does not and cannot represent that the Site contains no asbestos or lead-containing materials beyond that observed by GZA during the limited sampling event. GZA does not warrant the work of regulatory agencies, laboratories, or other third parties supplying information, which may have been used in the preparation of this report. No warranty, express or implied is made.
GZA appreciates the opportunity to provide this service to Oak Point Associates. If you have any questions regarding this report, please contact us at (603) 623-3600.
Very truly yours, GZA GEOENVIRONMENTAL, INC.
David G. Oliver, CMC Randy J. Meuse Senior Consultant Consultant/Reviewer
Jeffrey D. Rowell, P.E.
Principal
DGO/JDR/RJM:jaf p:\04jobs\0191300s\04.0191339.00 nhang\report\final 04.0191339.00 limited asbestos survey report 111721.docx
Attachments: Table 1 – ACM Bulk Sampling Log and Results Table 2 – Lead Bulk Sampling Log and Results Appendix A – Certifications
Appendix B – Asbestos and Lead Laboratory Analytical Reports
Table 1 – ACM Bulk Sampling Log and Results
TABLE 1
SUSPECT ACM SAMPLE INVENTORY
OAK POINT ASSOCIATES
PEASE NHANG
Building 254 Portsmouth, New Hampshire
04.0191339.00
SAMPLE NUMBER MATERIAL DESCRIPTION MATERIAL LOCATION
ANALYTICAL
RESULTS
102121B-01 3" Fiberglass insulation board backer paper, grey Exterior, Roof #1, north, center roof field NAD 102121B-01C 3" Fiberglass insulation board backer paper, grey Exterior, Roof #1, south, west roof field NAD 102121B-01E 3" Fiberglass insulation board backer paper, grey Exterior, Roof#1, south, east roof field NAD 102121B-02 Roof membrane, black Exterior, Roof #1, north, center roof field NAD 102121B-02C Roof membrane, black Exterior, Roof #1, south, west roof field NAD 102121B-02E Roof membrane, black Exterior, Roof#1, south, east roof field NAD 102121B-03 Penetration flashing compound, dark grey Exterior, Roof #1, southeast HVAC unit NAD 102121B-03B Penetration flashing compound, dark grey Exterior, Roof #1, east center HVAC unit NAD 102121B-03C Penetration flashing compound, dark grey Exterior, Roof #1, southwest HVAC duct NAD 102121B-04 Edge flashing compound, black Exterior, Roof #1, southwest corner, edge NAD 102121B-04B Edge flashing compound, black Exterior, Roof #1, northwest corner, edge NAD 102121B-04C Edge flashing compound, black Exterior, Roof #1, northeast corner, edge NAD 102121B-05 Seam sealant, black Exterior, Roof #1, southeast roof field NAD 102121B-05B Seam sealant, black Exterior, Roof #1, north, center roof field NAD 102121B-05C Seam sealant, black Exterior, Roof #1, southwest roof field NAD 102121B-101 Roof membrane, black Exterior, Roof #2, northeast roof field NAD 102121B-101C Roof membrane, black Exterior, Roof #2, west roof field NAD 102121B-101D Roof membrane, black Exterior, Roof #2, south roof field NAD 102121B-102 3" Fiberglass insulation board paper, grey Exterior, Roof #2, northeast roof field NAD 102121B-102C 3" Fiberglass insulation board paper, grey Exterior, Roof #2, west roof field NAD 102121B-102D 3" Fiberglass insulation board paper, grey Exterior, Roof #2, south roof field NAD 102121B-103 Edge flashing compound, black Exterior, Roof #2, southeast, center edge NAD 102121B-103B Edge flashing compound, black Exterior, Roof #2, northeast, corner, edge NAD 102121B-103C Edge flashing compound, black Exterior, Roof #2, southwest, edge NAD 102121B-104 Seam sealant, black Exterior, Roof #2, northeast roof field NAD 102121B-104B Seam sealant, black Exterior, Roof #2, southeast roof field NAD 102121B-105 Penetration flashing compound, black Exterior, Roof #2, northwest HVAC unit NAD 102121B-105B Penetration flashing compound, black Exterior, Roof #2, north center HVAC unit NAD 102121B-105C Penetration flashing compound, black Exterior, Roof #2, east, center, exhaust duct NAD 102121B-201 Roof membrane, black Exterior, Roof #3, northwest roof field NAD 102121B-201B Roof membrane, black Exterior, Roof #3, southwest roof field NAD 102121B-201C Roof membrane, black Exterior, Roof #3, northeast roof field NAD 102121B-202 3" Fiberglass insulation board backer paper, grey Exterior, Roof #3, northwest roof field NAD 102121B-202B 3" Fiberglass insulation board backer paper, grey Exterior, Roof #3, southwest roof field NAD 102121B-202C 3" Fiberglass insulation board backer paper, grey Exterior, Roof #3, northeast roof field NAD 102121B-203 Seam sealant, black Exterior, Roof #3, northeast roof field NAD 102121B-203B Seam sealant, black Exterior, Roof #3, northwest roof field NAD 102121B-204 Penetration flashing compound, black Exterior, Roof #3, south center exhaust vent NAD 102121B-204B Penetration flashing compound, black Exterior, Roof #3, west HVAC unit NAD 102121B-205 Edge flashing compound, black Exterior, Roof #3, northwest corner, edge NAD 102121B-205B Edge flashing compound, black Exterior, Roof #3, southeast corner, edge NAD 102121B-206 Building caulk, grey Exterior, Roof #3, east parapet wall, associated with beige metal panels
NAD
102121B-206B Building caulk, grey Exterior, Roof #3, north parapet wall, associated with beige metal panels
NAD
102121B-301B Roof membrane, black Exterior, Roof #4, south center roof field NAD 102121B-301C Roof membrane, black Exterior, Roof #4, east roof field NAD 102121B-301D Roof membrane, black Exterior, Roof #4, north center roof field NAD 102121B-302 Gypsum board, grey Exterior, Roof #4, southwest roof field NAD 102121B-302B Gypsum board, grey Exterior, Roof #4, south center roof field NAD 102121B-302C Gypsum board, grey Exterior, Roof #4, east roof field NAD 102121B-302D Gypsum board, grey Exterior, Roof #4, north center roof field NAD 102121B-303 Gypsum board tape, grey Exterior, Roof #4, southwest roof field NAD 102121B-303B Gypsum board tape, grey Exterior, Roof #4, south center roof field NAD 102121B-303C Gypsum board tape, grey Exterior, Roof #4, east roof field NAD
P:\04Jobs\0191300s\04.0191339.00 NHANG\Report\Tables\ Table 1 ACM_Bulk Sampling Log_04.0191339.00.xls Page 1 of 2 GZA GeoEnvironmental, Inc.
TABLE 1
SUSPECT ACM SAMPLE INVENTORY
OAK POINT ASSOCIATES
PEASE NHANG
Building 254 Portsmouth, New Hampshire
04.0191339.00
SAMPLE NUMBER MATERIAL DESCRIPTION MATERIAL LOCATION
ANALYTICAL
RESULTS
102121B-303D Gypsum board tape, grey Exterior, Roof #4, north center roof field NAD 102121B-304B 3" Fiberglass insulation board backer paper, grey Exterior, Roof #4, south center roof field NAD 102121B-304C 3" Fiberglass insulation board backer paper, grey Exterior, Roof #4, east roof field NAD 102121B-304D 3" Fiberglass insulation board backer paper, grey Exterior, Roof #4, north center roof field NAD 102121B-305 Edge flashing compound, black Exterior, Roof #4, northwest corner, edge NAD 102121B-305B Edge flashing compound, black Exterior, Roof #4, southwest corner, edge NAD 102121B-305C Edge flashing compound, black Exterior, Roof #4, west center edge NAD 102121B-306 Seam sealant, black Exterior, Roof #4, west center roof field NAD 102121B-306B Seam sealant, black Exterior, Roof #4, east center roof field NAD 102121B-307 Penetration flashing compound, black Exterior, Roof #4, northeast corner exhaust vent NAD 102121B-307B Penetration flashing compound, black Exterior, Roof #4, northeast HVAC unit NAD 102121B-307C Penetration flashing compound, black Exterior, Roof #4, south center exhaust vent NAD 102121B-401 Roof membrane, black and white Exterior, Roof #5, south center roof field NAD 102121B-401B Roof membrane, black and white Exterior, Roof #5, northeast roof field NAD 102121B-401C Roof membrane, black and white Exterior, Roof #5, northwest roof field NAD 102121B-402 Adhesive, light grey Exterior, Roof #5, south center roof field NAD 102121B-402B Adhesive, light grey Exterior, Roof #5, northeast roof field NAD 102121B-402C Adhesive, light grey Exterior, Roof #5, northwest roof field NAD 102121B-403 2" Fiberglass insulation board backer paper, grey Exterior, Roof #5, south center roof field NAD 102121B-403B 2" Fiberglass insulation board backer paper, grey Exterior, Roof #5, northeast roof field NAD 102121B-403C 2" Fiberglass insulation board backer paper, grey Exterior, Roof #5, northwest roof field NAD 102121B-406 Edge flashing compound, grey Exterior, Roof #5, northwest corner, edge NAD 102121B-406B Edge flashing compound, grey Exterior, Roof #5, southeast corner, edge NAD 102121B-407 Penetration flashing compound, grey Exterior, Roof #5, south HVAC unit NAD 102121B-407B Penetration flashing compound, grey Exterior, Roof #5, north HVAC unit NAD 102121B-408 Seam sealant, brown Exterior, Roof #5, east center roof field NAD 102121B-408B Seam sealant, brown Exterior, Roof #5, west center roof field NAD
P:\04Jobs\0191300s\04.0191339.00 NHANG\Report\Tables\ Table 1 ACM_Bulk Sampling Log_04.0191339.00.xls Page 2 of 2 GZA GeoEnvironmental, Inc.
Proactive by Design
Table 2 – Lead Bulk Sampling Log and Results
TABLE 2
LEAD BULK SAMPLE SUMMARY
OAK POINT ASSOCIATES
PEASE NHANG
Building 254 Portsmouth, New Hampshire
04.0191339.00
SAMPLE NUMBER MATERIAL DESCRIPTION MATERIAL LOCATION
LEAD CONTENT
(% by weight)
102221 Pb-01 Metal Flashing Exterior, Roof #1, East HVAC penetration flashing <RL 40 LF
102221 Pb-02 Metal Flashing Exterior, Roof #2, north perimeter flashing 18 300 LF 102221 Pb-03 Metal Flashing Exterior, Roof #3, north-center penetration flashing <RL 30 LF
102221 Pb-04 Metal Flashing Exterior, Roof #4, east perimeter flashing, Roof #2 and Roof #4 perimeter with hanger building
<RL 120 LF
102221 Pb-05 Metal Flashing Exterior, Roof #5, southeast corner perimeter flashing <RL 200 LF
NOTES:
1. LF = Linear Feet
3. Analysis conducted for lead via NIOSH Method SW846-7000B/3051
ESTIMATED QUANTITY
2. RL = Reporting Limit
P:\04Jobs\0191300s\04.0191339.00 NHANG\Report\Tables\ Table 2_ Lead_Bulk Sampling Log.xls\ Sheet1 Page 1 of 1 GZA GeoEnvironmental, Inc.
Appendix A – Certifications
AIHA Laboratory Accreditation Programs, LLC acknowledges that
ProScience Analytical Services, Inc.
22 Cummings Park, Woburn, MA 01801-2122
Laboratory ID: LAP-102754 along with all premises from which key activities are performed, as listed above, has fulfilled the requirements of the AIHA Laboratory Accreditation Programs (AIHA-LAP), LLC accreditation to the ISO/IEC 17025:2017 international standard, General Requirements for the Competence of Testing and Calibration Laboratories in the following:
LABORATORY ACCREDITATION PROGRAMS
INDUSTRIAL HYGIENE Accreditation Expires: July 01, 2022
ENVIRONMENTAL LEAD Accreditation Expires: July 01, 2022
ENVIRONMENTAL MICROBIOLOGY Accreditation Expires:
FOOD Accreditation Expires:
UNIQUE SCOPES Accreditation Expires:
Specific Field(s) of Testing (FoT)/Method(s) within each Accreditation Program for which the above named laboratory maintains accreditation is outlined on the attached Scope of Accreditation. Continued accreditation is contingent upon successful on-going compliance with ISO/IEC 17025:2017 and AIHA-LAP, LLC requirements. This certificate is not valid without the attached Scope of Accreditation. Please review the AIHA-LAP, LLC website (www.aihaaccreditedlabs.org) for the most current Scope.
Michael Breu Chairperson, Analytical Accreditation Board
Revision 18: 03/27/2020
Cheryl O Morton Managing Director, AIHA Laboratory Accreditation Programs, LLC
Date Issued: 06/30/2020
Effective: 11/21/2019 Revision: 9
SCOPE OF ACCREDITATION
ProScience Analytical Services, Inc. Laboratory ID: LAP-102754
22 Cummings Park, Woburn, MA 01801-2122 Issue Date: 06/30/2020
The laboratory is approved for those specific field(s) of testing/methods listed in the table below. Clients are urged to verify the laboratory's current accreditation status for the particular field(s) of testing/Methods, since these can change due to proficiency status, suspension and/or withdrawal of accreditation.
Industrial Hygiene Laboratory Accreditation Program (IHLAP)
Initial Accreditation Date: 06/01/2016
IHLAP Scope Category Field of Testing (FOT) Technology sub-type/Detector
Published Reference Method/Title of
In-house Method
Component, parameter or characteristic tested
Asbestos/Fiber Microscopy Core
Phase Contrast Microscopy (PCM)
- NIOSH 7400 Asbestos/Fibers
A complete listing of currently accredited IHLAP laboratories is available on the AIHA-LAP, LLC website at: http:// www.aihaaccreditedlabs.org
Revision: 8
SCOPE OF ACCREDITATION
ProScience Analytical Services, Inc. Laboratory ID: LAP-102754
22 Cummings Park, Woburn, MA 01801-2122 Issue Date: 06/30/2020
The laboratory is approved for those specific field(s) of testing/methods listed in the table below. Clients are urged to verify the laboratory's current accreditation status for the particular field(s) of testing/Methods, since these can change due to proficiency status, suspension and/or withdrawal of accreditation.
The EPA recognizes the AIHA-LAP, LLC ELLAP program as meeting the requirements of the National Lead Laboratory Accreditation Program (NLLAP) established under Title X of the Residential Lead-Based Paint Hazard Reduction Act of 1992 and includes paint, soil and dust wipe analysis. Air and composited wipes analyses are not included as part of the
NLLAP.
Environmental Lead Laboratory Accreditation Program (ELLAP)
Initial Accreditation Date: 11/01/1999
Component, parameter or characteristic tested
Technology sub-type/Detector Method Method Description
(for internal methods only)
EPA SW-846 7000B N/A
AA
NIOSH 7082 Modified N/A
EPA SW-846 6010B N/A
Airborne Dust
ICP
NIOSH 7082 Modified N/A
EPA SW-846 3051 N/A
AA
EPA SW-846 7000B N/A
EPA SW-846 3051 N/A
Paint
ICP
EPA SW-846 6010B N/A
EPA SW-846 3051 N/A
AA
EPA SW-846 7000B N/A
EPA SW-846 3051 N/A
Settled Dust by Wipe
ICP
EPA SW-846 6010B N/A
EPA SW-846 3051 N/A
AA
EPA SW-846 7000B N/A
EPA SW-846 3051 N/A
Soil
ICP
EPA SW-846 6010B N/A
Revision: 8
A complete listing of currently accredited ELLAP laboratories is available on the AIHA-LAP, LLC website at: http:// www.aihaaccreditedlabs.org
Analyte Code Analyte Name Effective Date Expiration Date Matrix Category Accr. Type Method Code: 10155609 Method Ref: SW-846 6010B Revision: UPDATE III Date: 1996
1010 ARSENIC 04/29/2010 04/28/2022 SC MET NE
1015 BARIUM 04/29/2010 04/28/2022 SC MET NE
1030 CADMIUM 04/29/2010 04/28/2022 SC MET NE
1040 CHROMIUM 04/29/2010 04/28/2022 SC MET NE
1070 IRON 02/20/2013 04/28/2022 SC MET NE
1075 LEAD 04/29/2010 04/28/2022 SC MET NE
1140 SELENIUM 03/10/2011 04/28/2022 SC MET NE
1150 SILVER 04/29/2010 04/28/2022 SC MET NE
Method Code: NH0334 Method Ref: SW-846 7471B / 7474 MODIFIED Revision: Date:
1095 MERCURY 06/28/2021 04/28/2022 SC MET NE
Method Code: 10118806 Method Ref: SW-846 1311 Revision: UPDATE I Date: 1992
1466 TOXICITY CHARACTERISTIC LEACHING PROCEDURE (TCLP) 04/29/2013 04/28/2022 SC PRE NE Method Code: 10134006 Method Ref: SW-846 3015A Revision: UPDATE IV Date: 2007
1428 MICROWAVE EXTRACTION 04/27/2016 04/28/2022 SC PRE NE
1430 MICROWAVE-ASSISTED ACID DIGESTION OF TCLP EXTRACTS 04/27/2016 04/28/2022 SC PRE NE
Method Code: 10135601 Method Ref: SW-846 3050B Revision: UPDATE III Date: 1996
1400 ACID DIGESTION OF SOLIDS 04/27/2016 04/28/2022 SC PRE NE
Method Code: NH0212 Method Ref: SW-846 3051A MODIFIED Revision: Date: 1998
1426 MICROWAVE DIGESTION OF SOLIDS 04/27/2016 04/28/2022 SC PRE NE
Matrix Legend: AE=Air; BT=Tissue; D=Drinking Water; N=Non-Potable Water; SC=Solid and Chemical Materials
Category Legend: MIC=Microbiology; MET=Metals; NMI=Non-Metal Inorganics; PRE=Preparation; VOC=Volatile Organic Compounds; SBN=SVOC-BNA; SHE=SVOC-Herbicides;
SNO=SVOC-NOS; SPC=SVOC-PCB; SPE=SVOC-Pesticides; RAD=Radiochemistry; WET=Wet, PFC=Perfluorinated compound
Accreditation Legend: NE=NELAP; NH=NH State Certification; CE=State Certification; IN=Interim (NELAP); WI=Withdrawn; AP=Applied; RE=Revoked; SU=Suspended
Bill Hall NH ELAP Program Manager Issue Date: 07/08/2021
PROSCIENC 7/8/2021
This analyte list supersedes all previously issued analyte lists. Method accreditation does not imply acceptance for NHDES compliance testing.
Laboratory is required to use EPA-approved methods required by regulation. Continuing accreditation status is dependent on successful ongoing participation in the program. Customers may verify the laboratory's current accreditation status by calling (603) 271-2998 or by visiting the NH ELAP website (https://www.des.nh.gov/water/drinking-water/new-hampshire-environmental-laboratory-accreditation-program).
NEW HAMPSHIRE ENVIRONMENTAL LABORATORY ACCREDITATION PROGRAM
29 Hazen Drive, PO Box 95, Concord, NH 03302 (603) 271-2998
PRIMARY ACCREDITATION ANALYTE LIST
PROSCIENCE ANALYTICAL SERVICES INC
22 CUMMINGS PARK
WOBURN MA 01801
ANALYTE LIST NUMBER: 299021-A
781-935-3212 Lab ID: 2990
� � �� � !" � #$ � % &' ( ) � *$ ! ' + $ , -' ,. + $ ( / 0 $ 1 ' ($ ' ( / 2 � � ( � 3 ! $ !' + 4 (' 5 ($ 6
� � 8 � � �9 � � :
� � � � : � ; < : = > ? @ A B C � B A ? @D7
� � � � � � � � � � � � E � � � � � � � � � � � � � F � � � � � �� G� � � : � ;H : � � >H : � I > � � � � � E � � � � � � � J � � � � B A A K L D
| � | � � � � � | � |
| � | � � � � | � � � |
. . / 0 1 1 2 3 4 5 6 7 8 9: ; < 0 8 3 = > ? @ A B @ A C . A . .> 5 D ? 2 1 E E / ; 8 1 2 E 86 F ; 3 E G H B A C I J K C J . A . L 7 M G H B A C I J . C N B K HO 1 7 2 P G 7 2 1 E E D Q ; 8 1 2 E 8 R S 8 ; 5 Q 2 E 3 Q E D 3 E TF T T S G U U V V V D S 8 ; 5 Q 2 E 3 Q E D 3 E T � W X Y Z � [ � Y \ \ ] Z ^ _ ` Y a a � b c d e [ f � g h i a � j f [ � � � � j f k l m n o b f � j d p q � f r � c � � f r � s � f � j p d b � f d � b � �Y t i � t f � t d b u h v w o b t h v � f d � b g � p a v � t� W X Y Z m [ � Y l Z Z X ` \ x m X � � l y q � f r � c � � j f r � s � f � j p d b � f d � b � � Y t i � t f � t d b u h v w u h d v c d b � q � f � j d � v t � W X Y Z z { | g | [ � Y } t ~ o b f � j d p � j � b t p d t t d � b [ v � � f j � b q d � j � t � � a � Y b � v � f d � � v q � f r � c t \ q � b c � f � j � � b c� � b p � b c � f � j � \ � b c q � b c � f � j � g � � f d � b f � s � f � j p d b � ^ � p a v � f d � b � � ` � t a � b t � Y � f d � b t ~ � t � � h b c d b] Z ^ _ ` n � � j f k l m n g h i a � j f [ n Y a a � b c d e Y |
Andrew J. Pomeroy
This is to certify that has completed requisite training, and has passed an examination for reaccreditation as:
Asbestos Inspector Refresher pursuant to Title II of the Toxic Substance Control Act, 15 U.S.C. 2646
Course Location
Zoom Video Conference
Institute for Environmental Education 16 Upton Drive Wilmington, MA 01887
Course Dates
January 20, 2021
Certificate Number
21-3541-106-262357
January 20, 2021
Examination Date
January 20, 2022
Expiration Date Training Director
Appendix B – Asbestos and Lead Laboratory Analytical Reports
GZA GeoEnvironmental, Inc.
| 1.0 LIMITATIONS |
| Table 1 ACM_Bulk Sampling Log_04.0191339.00.pdf |
| Sheet1 |
| Table 2_ Lead_Bulk Sampling Log.pdf |
| Sheet1 |