This document is a detailed Description of Requirement for a DFEJ Commercial Diesel Generator Set with specific technical specifications. The generator is a 450kW Standby 60Hz model designed for U.S. EPA stationary emergency applications, featuring comprehensive technical characteristics including a 350kW-Standby Rating, green steel enclosure, 12-lead alternator, 250-gallon fuel tank, and UL/IEC compliant circuit breakers. Key specifications include a steel sound-attenuated Level 1 enclosure, wind rating of 150 MPH, English language controls, external battery charger, coolant heater for temperatures below 40F, and a 2-year base warranty. Additional technical details cover voltage (2774/80, 3 Phase, Delta 3 Wire), emission certifications (EPA Tier 2, NSPS CI Stationary Emergency Listing), control features, and environmental adaptations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Description of Requirement
Provide the Description of all of the salient physical, functional or performance characteristics that the item must meet to be acceptable for award: (be as detailed as possible)
Item Description:
Salient characteristics - defined and sample **double-click icon
Salient Characteristics
Salient characteristics means those qualities of an item that are essential to ensure that the intended use of the item can be satisfactorily realized. The term sets forth those salient physical, functional, or other characteristics of the referenced product that an equal product must have in order to meet the recipient’s needs. They cannot unduly restrict competition.
Detailed product specifications should be avoided if at all possible. When it is impractical or uneconomical to make a clear and accurate description of the technical requirements, a referenced make or model number may be used as a means to define other salient characteristics of a procurement. Specific features that must be met by offerors shall be clearly stated.
Distinguishing characteristics of the product can include:
• Reference to an existing make/model number
• Including descriptive literature such as illustrations, drawings, or a clear reference to previously furnished descriptive data or information
• Any specifications, dimensions, color
Example
We have a requirement to purchase bandages. Our baseline is the Band-Aid brand bandage. Salient characteristics are:
• Flexible, sterile adhesive bandages
• Safety center pads
• Individually wrapped
• Between 1-3/4 inches wide and 3 inches long
Using these salient characteristics would allow for offers of numerous bandages other than Band-Aid.
1093598390N File Attachment Salient characteristics.pdf
Enter Text: DFEJ Commercial Diesel Generator Set, 450kW Standby 60Hz U.S. EPA, Stationary Emergency Application
• 450 KW DFEJ, Diesel Genset, 60Hz, 350kW-Standby Rating
• Duty Rating - Standby Power (ESP)
• Emission Certification, EPA, Tier 2, NSPS CI Stationary Emergency Listing - UL 2200
• Voltage - 277/480, 3 Phase, Delta 3 Wire
• Alternator - 60Hz, 12 Lead, Limited Range, 125/105C
• Steel Sound Attenuated Level 1 Enclosure, with Exhaust System
• Enclosure Color - Green, Steel
• Wind Rating - 150 MPH, Steel Housing
• Fuel Tank - Sub Base, 250 Gallon, UL142 Compliant (Compliance - Fuel Tank, Michigan Listing, ULC - S601 - 07)
• Alarm - No
• Fuel Water Separator
• Spill/Fill Box – No
• Vent Extension - Fuel Tank, 5 Inch Diameter
• Control Mounting - Left Facing
• Power Command 2.3 Controller
• LCD Control Display
• Stop Switch - Emergency, Externally Mounted
• Signals - Auxiliary, 8 Inputs/8 Outputs
• Control Display Language - English
• Circuit Breaker or Entrance Box or Terminal Box - Right Only
• Circuit Breaker or Entrance Box or Terminal Box, Left - None
• Circuit Breaker - 600A, Right Circuit Breaker on Right side, 3 - Pole, UL 600, IEC 690, 100%
• Circuit Breaker or Entrance Box or Terminal Box, Left - None
• Bottom Entry, Right
• Engine Exhaust Connection - None
• Engine Air Cleaner - Normal Duty
• External Battery Charger - 12 Amp, Regulated
• Engine Cooling - Radiator, 40C Ambient
• Shutdown - Low Coolant Level
• Coolant Heater - 208/240/480 Volts AC, Below 40F Ambient Temperature
• Genset Warranty - 2 Years Base
• Literature - English
• Packing - None, Base Mounted Housing