Repair Fire Station Foundation Drawing E-501.pdf
PDF 915 KB Posted
- Solicitation number
- W50S8525BA006
About this file
This document is an electrical engineering drawing (E-501) for a transformer pad, underground conduit, and electrical equipment rack installation at Selfridge Air National Guard Base. The detailed technical drawing provides specific specifications for transformer pad construction, including concrete strength (3500 PSI), reinforcing steel requirements, conduit placement, and mounting details. Key technical specifications include a minimum 6-inch tall concrete pad extending 1'-0" beyond the transformer footprint, underground conduit installation requirements for grass and pavement areas, and transformer wall/ceiling mounting instructions with notes emphasizing compliance with National Electrical Code and local building codes. The drawing includes precise measurements for conduit depth, sand fill, compacted backfill, and metallic warning tape placement, along with mounting hardware details such as expansion bolts, threaded rods, and vibration dampeners.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FINISHED FLOOR
42"
18"
POWER RECEPTACLES LOCATED IN
OFFICES AND OTHER FINISHED AREAS
UNLESS NOTED OTHERWISE.
ALL LIGHTING CONTROL
DEVICES UNLESS
NOTED OTHERWISE.
NOTE:
MOUNTING HEIGHT DIMENSION FOR POWER RECEPTACLES ABOVE COUNTER SHALL BE 6" ABOVE
TOP OF COUNTER OR COUNTER BACKSPLASH MEASURED TO THE CENTERLINE OF DEVICE.
CENTERLINE OF
DEVICE
46"
ALL POWER RECEPTACLES
LOCATED IN UNFINISHED AREAS
UNLESS NOTED OTHERWISE.
CENTERLINE OF DEVICE
PROVIDE RISER CLAMPS ON BOTH
SIDES TO PREVENT LATERAL
MOVEMENT
PATCH AROUND HOLE BORING
WITH COMPATIBLE WALL MATERIAL
(DO NOT USE FIRESTOP MATERIAL)
CONDUIT BUSHINGS
(BOTH ENDS)
EMT SIZE AS SHOWN ON PLANS -
MINIMUM 1"
CONDUIT TO BE FILLED WITH
FIRESTOP AFTER WIRE PULLED
STUD WALL (TYPICAL)
MINIMUM 3" EXTENSION
(BOTH SIDES)
FLOOR
DECK OR CONCRETE
STRUCTURE
SUPPORT CONDUIT
PER CODE.
EMT CONDUIT IN CMU OR STUD-
WALL.
LAY-IN, GYP, PLASTER, OR TILE
CEILING
NEW NOTIFICATION APPLIANCE.
PROVIDE BACKBOX IN CMU OR
STUD-WALL AS APPLICABLE.
REFER TO DETAIL X, SHEET
E-5XX FOR MOUNTING HEIGHT.
NOTES
1. CONCRETE: fc ≥ 3500 PSI AT 28 DAYS.
2. REINFORCING STEEL: ASTM A 615-60.
3. 6x6-4.5x4.5 WELDED WIRE FABRIC (WWF): ASTM A 185.
4. SOIL: ≥ 95 PERCENT PROCTOR DENSITY OR 55 PSI PBV.
5. VERIFY FINAL REQUIREMENTS AND DIMENSIONS WITH NEW TRANSFORMERS.
SECTION 'A-A'
6x6-4.5x4.5 WWF PAD
REINFORCEMENT (TYP.
OF 2LAYERS)
PRIMARY AND SECONDARY
CONDUITS SHALL BE CENTERED
IN BOX-OUTS
CABLE DUCT BOX-OUT 1"
CONCRETE OVER LEVELING BED
(BOTH BOX-OUTS)
1-1/2" CHAMFER (BEVEL) TOP
EDGE
SEE ONE-LINE DIAGRAM
90° ELBOWS, 24" RADIUS
1"-2" THICK SAND
LEVELING BED, (NO
ROCK)
GRADE
POLYETHYLENE FILM
ALL CONDUITS SHALL EXTEND 1"
MAXIMUM ABOVE CONCRETE AT
BOTTOM OF BOX-OUT
PLAN VIEW
6 x 6-4.5 x 4.5 WWF PAD
REINFORCEMENT (TYP.
OF 2LAYERS)
SECONDARY
PRIMARY
A A
MINIMUM PAD DIMENSIONS SHALL EXTEND
1'-0" BEYOND FOOTPRINT OF
TRANSFORMER IN ALL DIRECTIONS
MINIMUM 6" TALL CONCRETE PAD
2'-0" MIN. BELOW
FINAL GRADE
CONDUITS-TYPE, QUANTITY AND
SIZE AS SHOWN ON DRAWINGS
4" SAND FILL ABOVE AND
BELOW CONDUITS
COMPACTED BACKFILL W/ 2"
OR SMALLER AGGREGATE
METALLIC WARNING TAPE
12" BELOW FINAL GRADE
ORGANIC TOP SOIL
(GRASS AREA)
MULTIPLE CONDUITS
UNDER GRASS
2'-0" MIN. BELOW
FINAL GRADE
CONDUITS-TYPE, QUANTITY AND
SIZE AS SHOWN ON DRAWINGS
4" SAND FILL ABOVE AND BELOW
CONDUITS
COMPACTED BACKFILL W/ 2"
OR SMALLER AGGREGATE
METALLIC WARNING TAPE
6" BELOW FINAL GRADE
PAVEMENTMULTIPLE CONDUITS
UNDER PAVEMENT
PRECAST CONCRETE
CEILING
5/8" EXPANSION BOLT
5/8" GALVANIZED
THREADED ROD
TRANSFORMER
TRANSFORMER WALL MOUNTING
BRACKET AS RECOMMENDED BY
MANUFACTURER
5/8" ANCHORS THRU WALL
(TYPICAL OF 4 PER XFMR)
TRANSFORMER AND MOUNTING BRACKETS
SHALL BE LOCATED OUTSIDE OF DEDICATED
ELECTRICAL SPACE.
VIBRATION DAMPENERS
(TYPICAL OF 4 PER XFMR)
PRECAST CONCRETE CEILING
5/8" EXPANSION BOLT
5/8" GALVANIZED
THREADED ROD
TRANSFORMER
TRANSFORMER WALL MOUNTING
BRACKET AS RECOMMENDED BY
MANUFACTURER
5/8" ANCHORS THRU WALL
(TYPICAL OF 4 PER XFMR)
1/4" PRIMED STEEL PLATE
ENCLOSED CIRCUIT BREAKER
TRANSFORMER AND MOUNTING BRACKETS
SHALL BE LOCATED OUTSIDE OF DEDICATED
ELECTRICAL SPACE.
VIBRATION DAMPENERS
(TYPICAL OF 4 PER XFMR)
END CAP
FRONT ELEVATION
PIPE 3 STD GALV.
(TYP)
GALV. UNISTRUT
(TYP)
GENERAL NOTES:
1. ALL WORK SHALL CONFORM TO THE NATIONAL ELECTRICAL CODE, STATE BUILDING CODES AND THE LOCAL BUILDING CODES.
ALL COMPONENTS SHALL BE UL LISTED.
2. BOND ALL ELECTRICAL EQUIPMENT TO RACK.
3. TOP OF RACK SHALL BE MAXIMUM 6'-0" ABOVE FIXED GRADE.
4. PROVIDE ALL BOXES, CONDUITS, FITTINGS, SUPPORTS, COVERS, ETC.. FOR A COMPLETE, WEATHERPROOF INSTALLATION.
DEVICES SHALL BE WEATHERPROOF WHILE IN-USE.
INCOMING
FEEDER CONDUIT
T Y
P
RECEPTACLE SCHEDULE
1. NEMA 5-20R (120V); WP/GFCI (2#12, 1#12G IN 1/2"C.)
PROPOSED H-FRAME UTILITY RACK (TYP)
EXPANSION
FITTING
PANEL
TEMP
RLB
GRADE
18" DIAMETER
CONCRETE FOOTING
6 INCHES ABOVE GRADE
TEMP RLB
CKT:1
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright Mead & Hunt, Inc.
This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
14000 Quail Springs Parkway, Suite 500
Oklahoma City, OK 73114 phone: 405-478-5353
/1
/2
:2 :3
P
M C
R e v it L o ca l\
.0
-E
-R z a c h .d a w ie cX
M F
D U
.r v t
S E
L F
R
ID
G E
A N
G B
W
IL
B
U R
W R
IG
H
T B
L V
D
H A
R R
IS
O
N T
W P
M
IC
H
IG
A
N
R E
P A
IR
F
IR
E
S T
A T
IO
N
F O
U N
D A
T
IO
N
E-501
DETAILS
3141700-231224.01
ZMD
ARG
February 20, 2025
ZMD
NO SCALE1
DEVICE MOUNTING HEIGHTS DETAIL
NO SCALE2
NON-RATED WALL PENETRATION
NO SCALE3
NOTIFICATION APPLIANCE
MOUNTING - FLUSH
NO SCALE4
TRANSFORMER PAD DETAIL
NO SCALE5
UNDERGROUND CONDUIT DETAIL-GRASS
NO SCALE7
UNDERGROUND CONDUIT DETAIL-PAVEMENT
NO SCALE8
TRANSFORMER WALL/CEILING MOUNT
NO SCALE9
TRANSFORMER WALL/CEILING MOUNT PROFILE
1/8" = 1'-0"6
ELECTRICAL EQUIPMENT RACK
02/20/25 TYPE B3 FINAL
08/05/25 AMENDMENT 0002
1505591034C Polygon