This document contains questions and answers regarding an industrial fan installation project at an Army National Guard facility. The project involves installing high-volume low-speed industrial fans on both sides of an aircraft hangar that measures approximately 170 feet in length, 150 feet in width, and 45-50 feet in height. The ceiling structure is sloped to match the steel roof trusses. The answers provide details such as the location of the existing fire alarm panel and electrical panels, as well as specifications regarding available voltage, space in the electrical panel, and clearances for running electrical wiring along the roof trusses. No fixed equipment below the planned fan installation area needs relocation. Proper fan installation must prevent any dark spots in the hangar and potential strobe effects from lights.

The related federal contract opportunity is solicitation number W50S82-23-Q-0XHM for industrial fans requiring high-volume low-speed fans with installation services. The opportunity is issued by the Department of the Army Maryland Army National Guard.

View the file

Other files

File Type Posted
WD.pdf PDF
Solicitation - HVLS.docx DOCX document
WF 113 - Installation Access Application.pdf PDF
SOW.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

August 18, 2023 RFI’s Questions:

1. Location of fire alarm panel in building.

a. Left stairwell near the flightline

2. Current fire alarm company/ contact for programming/wiring into new fan panels.

2. The location of the project doesn’t have any proprietary fire systems

3. Please provide location for new fan panel(s).

3. Location of fan panels will be located on both sides of the hanger. One panel controlling the left side fans and the other one controlling the right-side fans

4. Fan manufacture recommends relocating existing lights to prevent strobe effect.

4. If lights need to be relocated due to the strobe effect. The contractor is to ensure there are no dark spots in the hanger

1. Could you please provide the dimensions of the installation area? Specifically, the length, width, and height.

5. Length (170ft) Width (150ft) Height (45-50ft)

1. Can you describe the ceiling structure? Is it sloped?

6. The roof of the hanger sloped, and the steel trusses are parallel with the ground see photo (Roof Diagram.png)

1. Are there any fixed equipment or objects below the planned fan installation area that cannot be relocated?

7. No

1. What is the available voltage on-site?

8. 480

1. Is there adequate space in the existing panel for the installation?

9. There are two spaces

1. How far is the electrical panel from the intended fan installation location?

10. Varies in length.

1. Is there flexibility to run wires in a direct path, or must they be routed through cable trays or attached to the main beams?

11. Please provide a clean look, along with staying on the trusses as much as possible