SOW.docx
DOCX document 56 KB Posted
- Attached to
- Industrial Fans - HVLS with Installation
- Solicitation number
- W50S82-23-Q-0XHM
About this file
This statement of work outlines requirements for installing industrial fans at Building 1070 of the Maryland Air National Guard in Middle River, Maryland. The contractor shall remove existing fans from the hangar ceiling and install four 24-foot fans along with required accessories and electrical work. Specific tasks include disconnecting and removing 12 existing fans, installing the new high-volume low-speed fans centered between sprinkler heads with a minimum 3-foot clearance, running AC power and data communication wiring, installing wall control keypads and emergency shutoff, providing start-up and training, and integrating the fans with the fire alarm system and panels. The contractor must follow all applicable codes and safety standards and provide a one-year warranty on workmanship. The period of performance is 30 days.
The related federal contract opportunity is a solicitation seeking offers for industrial fans with HVLS technology and installation services. The solicitation number is W50S82-23-Q-0XHM and is being issued by the Department of the Army Maryland Army National Guard.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFI.docx | DOCX document | |
| WD.pdf | ||
| Solicitation - HVLS.docx | DOCX document | |
| WF 113 - Installation Access Application.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Headquarters Sidewalk
STATEMENT OF WORK
PROJECT NUMBER: PJMS 232003
MARYLAND AIR NATIONAL GUARD
MARTIN STATE AIRPORT
BALTIMORE, MARYLAND
23 MAY 2023
1. Scope: The contractor shall provide all personnel, equipment, tools, materials, supervision, and quality control necessary as defines in this SOW to install industrial fans (High-Volume Low-speed Fan) at building 1070, located on 175th Maryland Air National Guard, Middle River, Maryland 21220
1.1. Introduction and background:
1.2. Install industrial fans (High-Volume Low-speed Fan (HVLF)) in building 1070 (MXS Hangar). Throughout the year the maintenance hangar becomes either warm or cold. The fans would improve the temperature within the maintenance hangar by circulating the air flow during the year. The hangar has large doors to open during the summer months but with the lack of air flow it stays warm inside and the air is stagnant. During the winter months, with the heat on in the hangar for the members the fans would be utilized to circulate the heat from the heaters that are around 15 feet above the floor. This will provide members with a controlled work environment to lessen either heat or cold weather-related injuries.
1.3. Objectives: The 175th MXS seeks to have install industrial fans (High-Volume Low-speed Fan (HVLF)) in building 1070 (MXS Hangar). The HVLF will help to modernize and provide the maintenance hangar with proper air flow during the cold and warm months.
1.4. Places of Performance: Building 1070, located on 175th Maryland Air National Guard, Middle River, Maryland 21220.
1.5. Contractor Passes: Passes are only issued to personnel who have properly submitted a locally generated WF 113 Wing Installation Access Application (available from the Contracting Office or from the COR) and have been cleared through an approved background investigation by the 175th Security Forces Squadron. The Installation Access Application contains required information necessary to conduct a National Criminal Information Center (NCIC) background check or a Defense Biometric Identification System (DBIDS) check.
Contractors who will be working on the installation need to complete an Antiterrorism Level I training. The training can be found at http://jko.jten.mil/courses/atl1/launch.html. Please ensure contractors are attaching their certificates along with their applications. Contractors who have not completed an Antiterrorism Level I training will not be allowed on the installation.
Contractor Passes are only issued to contractors who will be required to work more than 14-days on the installation in performance of their contract. For contractors requiring less than 14 days of access, an AF FM 75, Visitors Pass, will be issued upon a favorable background investigation.
The contractor shall comply with all applicable installation/facility access and local security policies and procedures, which may be obtained from the Contracting Officer’s Representative (COR). The contractor shall also provide all information required for background checks to meet installation access requirements to be accomplished by the local installation’s Security Forces, Director of Emergency Services or local Security Office. The contractor shall ensure compliance with all personal identity verification requirements as directed by DoD, HAF and/or local policy. Should the Force Protection Condition (FPCON) change, the Government may require changes in contractor security matters or processes.
Contractor and all associated sub-contractors employees shall comply with adjudication standards and procedures using the National Crime Information Center Interstate Identification Index (NCIC-III) and Terrorist Screening Database (TSDB) (AFI 10-245, AFI 31-101 and AFMAN 31-113), applicable installation, facility and area commander installation/facility access and local security policies and procedures (provided by government representative), or, at OCONUS locations, in accordance with status of forces agreements and other theater regulations.
The Defense Forces Commander (DFC) maintains the right to deny contractors access to the installation based on unfavorable information obtained through NCIC or DBIDS.
1.6. Burnt Permits: Unless otherwise specified in other sections of this specification, the use of burning equipment or open flame welding and cutting shall be allowed only as authorized in writing by the local Fire Inspector (Facility 3150). Once approved by the Fire Inspector, a written AF Form 592 – USAF Welding, Cutting, and Brazing Permit will be issued. The permit will be issued by the fire department within one (1) hour of request and must be renewed daily.
1.7. Digging Permits: Are obtained from the Work Control Office (Facility 2100) at (410) 918- 6300. The Contractor is responsible for contacting ‘Miss Utility’ to mark the gas and electrical lines. The Contractor is responsible for hiring a private underground utility locating company to mark the water, sanitary sewer, storm sewer, broadband cable, and communication lines.
1.8. Change Orders: Only the Base Civil Engineer (BCE) or the Contractor may initiate change order requests. Do not proceed with any work until a signed modification or other written authority is received from the Contracting Officer. Only the Contracting Officer may approve a change order.
1.9. Field Changes: No changes in the cost or the scope of the project may be made without processing a change order. Field changes not involving cost or scope may be initiated by the BCE, COR, Contracting Officer or the Contractor.
1.10. Daily Report and Sign-In Register: Each day the Contractor is on site to perform any work, the Superintendent/Foreman shall sign in at the Base Engineering Building (BLD 2100), indicating specific Building/Location and the number of persons who shall be performing work that day.
1.11. Hours of Operations: The hours of operations at Martin State Airport for the Air National Guard are 10 hours per day (0700 – 1700) Tuesday – Friday. Coordinate access to premises with COR, for execution of work. Government facility/installation is closed due to local or national emergencies, administrative closings, or similar Government-directed facility/installation closings.
1.12. Off-Hours Work: Except as otherwise specified, all work shall be performed during regular work hours (indicated above). If the Contractor desires or is required to work on Saturdays, Sundays, Holidays or other hours outside normal work schedule, the Contractor shall be required to seek written approval from the BCE. The Contractor is not entitled to premium time if the request is approved.
1.13. Clean up: The work site is an active civilian and military airport. Site cleanliness, Foreign Object Debris (FOD) control is absolute. The Contractor will clean up all construction debris and refuse and will remove it from the work site and the Base daily at their own expense.
1.14. Safety: The Contractor is responsible for performing all work In Accordance With (IAW) State and Federal OSHA requirements as well as compliance with the most current USACE EM 385-1
1.14 Military Real Property Data – DD Form 1354: The Contractor shall furnish real property data to the Government via the DD Form 1354, Building Information Checklist for the Transfer and Acceptance of Military Real Property, for each new construction and/or renovation project awarded, unless otherwise notified. The cost and unit of measure of each individual asset must be identified separately. If demolition work is within the scope of the project, demolished assets and demolition costs must also be identified. The Contractor is responsible for accuracy of data, current up to the time of completion. The Contractor should contact the Real Property Office at 410-918-6222 with questions pertaining to the DD Form 1354. For construction data assistance, Contractor may contact the 175th Base Civil Engineer’s Office to speak with the COR, or Project Manager assigned to the project.
1.15 Hazardous Materials: If suspected hazardous materials are discovered (other than dip tank solvents already included within the scope of work), do not disturb, contact the COTR.
1.16 Period of Performance (PoP).
30 days is the allotted time frame to complete the project.
| Maintenance 1 Base Year of 12 months and four (4) years 12-month option years. | Comment by SILFIES, CORY L MSgt USAF ANG 175 WG/175 MSG: Are the option years for maintenance services? | Comment by KENNEDY, SHAWN P SMSgt USAF ANG 175 AMXS/MXMTC: I know the group did one for all the fans in on base. So it would be grouped into that one |
| 2. | Scope of Work: | |
| 2.1 | Building 1070 – Phase Hangar: | |
| 2.1.1. | Disconnect and remove 12 fans (household style) from the hangar ceiling. | |
| 2.1.2. | Install Four (4) Twenty-four-foot Fans, 400-480 Volt/3 Phase with Accessories/Static Tube, Mount Kit, etc., or Equivalent items. | |
| 2.1.3. | Contractor will dispose all material to a location offsite | |
| 2.2. | General Information: | |
| 2.2.1. | Lifts shall be provided by the Contractor. Lifts must be OSHA approved, two-man scissor lifts. | |
| 2.2.2 | Angle iron or other steel added by Contractor – to support fans – shall be painted to match existing adjacent elements. | |
| 2.2.3 | Contractor is to ensure that any bridge cranes in or near fan and light fixture installation areas must be locked out during fan and light fixture installation. | |
| 2.2.4 | The Contractor shall insure that any and all Check-In and Close-Out forms required by the manufacturer be completed and returned to the manufacturer for warranty coverage. | |
| 2.2.5 | Testing is to be done in accordance with NETA Specifications. | |
| 2.2.6 | The Contractor shall provide the electrical inspector’ final report in the form of a Submittal to the Contracting Officer. | |
| 2.3. | Fan: | |
| 2.3.1. | Fan installation must be in accordance with the National Electric Code, ANSI/NFPA 70, and all local codes. | |
| 2.3.2 | High-Volume/Low-Speed Fans shall be centered between four adjacent sprinkler heads. | |
| 2.3.3 | The vertical distance from an HVLF fan to sprinkler deflector shall be a minimum of 3 feet. | |
| 2.3.4 | HVLF fans shall be interlocked to shut down immediately upon receiving a water flow signal or from the alarm system in accordance with the requirements of NFPA 72. | |
| 2.3.5 | Contractor shall be responsible for bringing any and all power necessary for full operation of fans. | |
| 2.4. | HVLFs: | |
| 2.4.1. | Install AC power wiring to each fan. | |
| 2.4.2. | Install junction box with appropriate size NEMA twist-lock receptacle within three (3) feet of fan(s) mounting locations. | |
| 2.4.3. | Attach yokes and extension tubes as required. | |
| 2.4.4. | Install wall control keypad to accessible surface. | |
| 2.4.5 | Install CAT-5 data communications cable per NEC between fan(s) and wall control keypads (in EMT conduit). | |
| 2.4.6 | Install airfoils and hub covers, etc. | |
| 2.4.7 | Install emergency shut off near exit. | |
| 2.4.8 | Fan(s) start-up and operational training. | |
| 2.5. | Fan Fire Relays and Fire Alarm Panel: | |
| 2.5.1. | The Contractor to provide switched 20-32 VDC power from the fire control panels, if not already provided by the Government. | |
| 2.5.2. | The Contractor shall install fire alarm cable per NEC Article 760, from each fan VFD to next fan in chain, etc., and once reached last fan in chain, to fire alarm panel | |
| 2.5.3. | Per NEC, the Contractor shall install protective conduit from fire relay locations to ceiling height (where applicable) and free air installation of fire alarm cable at ceiling height. | |
| 2.5.4 | Verify fire relay operation at all sites, using temporary power, prior to final tie-ins. | |
| 2.5.5 | Provide final tie-ins of fire alarm cable at fire control panels and provide all programming and testing in coordination with Base electrician and Fire Department. | |
| 2.5.4. | Quality Assurance (QA): | |
| 2.5.5. | Quality Assurance (QA): The Government will evaluate the contractor’s performance under this contract in accordance with the Quality Assurance Surveillance Plan (QASP). This plan is primarily focused on what the Government will do to ensure that the contractor has performed in accordance with the performance standards. It defines how the performance standards will be applied, the frequency of surveillance, and acceptable quality level(s) or defect rate(s) | |
| 3.0 | Warranty: Provide a 1-year workmanship warranty | |
| 4.0 | Product Information: Provide product information and material to the COR at final walk through: |
--- End of Statement of Work ---image1.jpeg