RFI 1 CES Repair Fire Supp Bldg 15.pdf
PDF 114 KB Posted
- Attached to
- 183 CES Repair Fire Suppression Building 15 Federal contract opportunity
- Solicitation number
- W50S7U-24-B-0002
- Issued by
- Department of the Army National Guard
About this file
This document is a Request for Information (RFI) related to Solicitation W50S7U-24-B-0002 for the repair of Fire Suppression Building 15 by the Department of the Army National Guard.
The key details are:
- The solicitation requires a licensed Fire Protection Engineer to provide shop drawings, rather than a NICET Level III designer.
- The project is for the repair of Fire Suppression Building 15.
- The solicitation number is W50S7U-24-B-0002.
- The procuring agency is the Department of the Army National Guard.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Bid Abstract W50S7U-24-B-0002.pdf | ||
| W50S7U-24-B-0002 -0001 CES Repaire Fire Suppression Bldg 15.pdf | ||
| Site Visit Minutes Repair Fire Suppression Bldg 15 - 18 Jun 24.pdf | ||
| SBSA Pre-Bid Slides - CES Repair Fire Suppression Bldg 15.pdf | ||
| Site Visit Sign In - Repair Fire Suppression P-15 18 Jun 24.pdf | ||
| W50S7U-24-B-0002 -CES Repaire Fire Suppression Bldg 15.pdf | ||
| 183d Wing Map - P15 Fire Suppression.pdf | ||
| Building 15 Existing Fire Protection.pdf | ||
| W50S7U-24-B-0002 -CES Repair Fire Suppression Bldg 15.pdf | ||
| P-15 Floor Plan.pdf | ||
| PWS Services DCFT 212001 CES Repair Fire Suppression Bld 15.pdf | ||
| SF 1705.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT DCFT212001
SOLICITATION/IFB # W50S7U-24-B-0002/RFI 1 CES Repair Fire Suppression Building 15
REQUEST FOR INFORMATION (RFI) #1 27 June 2024
Q1. Performance Work Statement Part 1.2 states “The Contractor is also responsible for providing shop drawings that are prepared and signed by a licensed Fire Protection Engineer…”. Is a NICET Level
III designer acceptable in lieu of a Fire Protection Engineer?
A1. NICET Level III designer is not acceptable. Licensed Fire Protection Engineer stamp required per Federal Laws and Regulations.