This document is a Project Description for the installation of industrial fans in a hangar facility at the Texas Air National Guard's Ellington Field JRB. The project requires the contractor to provide and install three 24-foot diameter fans and one 6-foot pivot fan in the AMXS hangar, as well as two 16-foot fans in the fire department building. The fans must meet specific electrical, size, structural, and performance requirements, including a minimum 10-year warranty. This requirement is considered a supply purchase with services incidental, to be overseen by the Ellington Field Maintenance Squadron. The related federal contract opportunity, Solicitation Number W50S77-24-Q-0006, is issued by the Department of the Army Texas Army National Guard for the Hangar Fans requirement.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1. Combo W50S77-24-Q-0006 - Amendment 1.pdf | ||
| Questions and Answers - Hangar fans.pdf | ||
| 1. Combo W50S77-24-Q-0006.pdf | ||
| 2. Hangar Pictures.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Description
For
Hangar Fan Project
Texas Air National Guard
Ellington Field JRB, Texas
Prepared July 5, 2023
1. The 147th Aircraft Maintenance Squadron (AMXS) requires four total (Three- 24’, One -6’ pivot) industrial Fans for the AMXS hangar, building 1382. Three 18’ existing fans will be removed and the new 24’ will be installed in the same location. Two additional 16’ overhead fans will be installed in the fire department building (CLIN 0004). No removal required for the two 16’ fans.
This requirement is considered a supply purchase with services incidental.
2. Applicable Documents. See attachment 1 for hangar second floor dimensions and layout.
3. Requirements. The Industrial fan contractor, overseen by Ellington Field’s Maintenance Squadron, will provide all required manpower, equipment and consumables required to complete the tasks.
3.1 Requirements
3.1 Electrical. New fans must be voltage appropriate and compatible with current infrastructure.
Upon award, CES will approve of all electrical before installation.
3.2 Size Requirements. Bldg 1382 -Three of the Industrial fans shall be 24 ft in diameter, with an airfoil clearance of 2 feet on all sides and 6 feet below ceiling. One of the fans shall be a Pivot/directional fan with a 6 ft diameter. Fire department – two 16 ft fans will be installed with enough clearance for trucks and equipment.
3.3 Structural Requirements. Industrial fans shall be constructed with aluminum airfoils with winglets, safety restraints a sealed gearbox and a IP56 rating for the entire fan. A multi-Point safety system to include double safety cable system with grade 8 hardware, hub clips, fire relay, guy wires and airfoil restraint system. Pivot fan shall be constructed with aluminum airfoils with airfoil retainers, safety cables and guy wires.
3.4 Warranty. Industrial fans shall have a minimum of 10-year warranty on all mechanical and electrical components.
3.5 Performance. The pivot fan shall be able to provide up to 120 feet of airflow at 300 RPM with a max operating temp of 131 degrees Fahrenheit. The three 24’ industrial fans shall operate at a max speed of 62 RPM with a max operating temp of 122 degrees Fahrenheit. The two additional 16’ industrial fans shall operate at 96 RPMs with a max operating temperature of 122 degrees Fahrenheit.
Bldg 1382 blueprint – Attachment 1