Amended Attachment 1- Technical Specification Sheet.pdf
PDF 227 KB Posted
- Attached to
- Hydrazine Detection System
- Solicitation number
- W50S6S24Q0022
About this file
This document is an Amended Technical Specification Sheet for a Hydrazine Detection System solicitation, W50S6S24Q0022, issued by the Department of the Army Arizona Army National Guard.
The solicitation is for the procurement of Drager X-am 5100 and Drager X-zone 5800 gas detection systems or equivalents. The required specifications include dimensions, weight, ambient operating conditions, alarms, battery life, and charging times. The solicitation is 100% set-aside for small businesses under NAICS code 334519. Quotes are due by the date and time listed in SAM.gov and should be sent via email to the specified addresses. Vendors must submit a completed vendor information table along with their quote. Any questions must be submitted by the stated deadline, with responses to be posted via an amendment.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 1- Technical Specification Sheet.pdf | ||
| RFQ W50S6S24Q0022 - Hydrazine Detection System.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W50S6S24Q0022
Hydrazine Detection System
MFG: Drager or equal
Model: Drager X-am 5100 & Drager X-zone 5800 or equal
Part number- 8326839 (Drager X-am 5100) , 8329040 (Drager X-zone 5800) or equal Conforming to the below specifications:
CLIN 0001(Drager X-am 5100) or equal
• Dimensions (W x H x D)- 48 x 130 x 61 mm; 1.89 x 5.12 x 2.4 inches
• Weight- 220 – 250 g; 7.8 – 8.8 oz.
• Ambient conditions Temperature - 20 to + 50 °C; - 4 to + 122 °F
• Pressure 700 to 1300 mbar; 20.7 to 38.4 inch Hg
• Relative humidity 10 to 90 % RH
• Alarms Visual 360°
• Audible Multi-tone > 90 dB at 30 cm; 1 ft.
• Vibration
• Ingress Protection IP 54
• Operating times
• ~150 h (alkaline battery), ~150 h (NiMH rechargeable battery), or
• ~180 h (NiMH high capacity rechargeable battery)
• Charging times < 4 h
• Data logger Retrievable using an infrared interface
• > 1000 h at a recording interval of 1 value per minute
• CE mark Electromagnetic compatibility
• Guideline 2004/108/EC
• Explosion protection – Guideline 94/9/EC
• The Drager X-am 5100 or Equal must include compatible power pack and charging set.
CLIN 0002 (Drager X-zone 5800) or equal
• Dimensions (W x H x D)- 490 x 300 x 300 mm (20 x 12 x 12 in)
• Weight- 10 kg (22 lbs.) (24 Ah battery)
• Ambient condition
• Temperature max. +50 °C (+122 °F), depending on sensors used
• Pressure 700 to 1,300 hPa
• Humidity 10 to 95 % r.h.
• Ambient conditions
Amended Technical Specifications
• Temperature as low as -50 °C (-58 °F), depending on sensors used
• Ingress Protection- IP67
Alarm
• Visual 360° LED (illuminated ring)
• Audible 360°; >108 dB in a distance of 1 m (3 ft), 120 dB in a distance of 30 cm (1 ft)
• Configurable alarm patterns, frequencies and volumes
Life signal
• Green status display (360°),
• illuminated ring (LED)
Operating time
• Approx. 120 h (24 Ah battery)
• Depending on sensor equipment / configuration of the life signal, Extended run time is possible with optional Power Supply Ex
Charging time
• Approx. 14 h
• Flexible power supply: External 100 – 240 V charger (worldwide) or inductive wireless charger
Pump operation.
• Maximum hose length: 45 m (150 ft); 30 m (98 ft) for Zone 0
Alarm output.
• Potential-free alarm contact for intrinsically safe circuits (6-pole); <20 V to 0.25 A (0.15
A constant current); Resisting load.
Radio transmission
• Worldwide license-free ISM frequencies
• Digital radio, robust and interference-free transmission up to 100 m (328 ft)
RF approvals
• 915 MHz (USA, Canada)
Approvals
• ATEX I M1 Ex ia I Ma, II 1G Ex ia IIC T4 Ga
• IECEx Ex ia I Ma, Ex ia IIC T4 Ga
• CSA (Canada and US) [Ex ia Ga] IIC, [AEx ia Ga] IIC
• The Drager X-Zone 5800 or Equal must include the following accessories
1. Power Supply 2.400A 15V
2. Power Cord USA 3 m
3. Power Supply Ex 110V (w/o power cord)
4. X-zone 5x00 alarm-attenuation ring
5. Grease 3g
6. Spare set pin block (X-zone 5500)
7. Spare part gas inlet filter 5100 holder
8. USB DIRA with USB cable (interface with USB-Cable fore infrared data transfer for all portable X-am series instruments).
All items are brand name or equal. Refer to FAR 52.211-6 for additional or equal requirements.
ADDED: All purchased equipment should include manufacturer technical support for equipment and software set up and operations telephonically to the customer at no additional cost. Vendors must identify any additional fee for technical support with their quote.
File details come from the government source that posted it. Updated .